Preview only show first 10 pages with watermark. For full document please download

Cassettes Op Een Bus

   EMBED


Share

Transcript

Group Control Wiring Diagram Indoor Unit 2 Indoor Unit 1 Brown(GND) Cassette/Duct Indoor Unit 16 Yellow (Signal) Main PCB #1 RED Terminal Housing Block(Local supply) Main PCB #2 Main PCB #16 Lead wire Wire of remote controller Jet Cool Temp On/Off Timer Cancel E_Heater Fan Fan Speed Operation Program Week Holiday Set Select Select Wiring method Air clean Room Temp Auto Swing Hour MIN SET/CLR RESET Wired Remote Controller Components 1. Remove “R02K(12KΩ)”on the Main PCB (Solder side) --See next page 2 .Make resister OP7 open on the PCB in Wired Remote Controller 3. Disconnect the wire of remote controller in indoor unit 1 4. Set up the terminal block 5. Connect the wire of remote controller with terminal, and assemble the housing between main pcb and terminal 6. Connect indoor unit 1& unit 2 with Lead wire(double insulated) 7. Another indoor units(3~16) are also connected like above method 1.Terminal Block,Housing,Lead wire : Local Sourcing 2.But if you want Terminal block and Housing, LG Can provide these optionally. Remove “R02K(12KΩ)” on the Main PCB (Solder side) Micom chip Slide s/w for two thermister Slide s/w for Ceiling height OP7 IC02M Micom chip R02K Remote Control Board Main PCB Board Old Version OP7 OP7 Slide Switch (2002.5.30)