ENGINEERING SPECIFICATIONS RH-12-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 12 Reversing (Heating AND Cooling) 208/230-1-60VAC
Liquid to Air Geothermal Heat Pumps
Maritime Geothermal Ltd. P.O. Box 2555 Petitcodiac, N.B. E4Z 6H4 Ph. (506) 756-8135
Email:
[email protected] Web: www.nordicghp.com Document Number: 001694SPC-02 DATE: 24-July-2015
MODEL NOMENCLATURE RH—12—HAC—P—1L—C—SDELF—xx Series: RH = Horizontal Liquid to Air
Revision: 01, 02 etc.
Nominal Size: 12 = 1 Ton
Fan Discharge: F= Field Configurable
Functions: H = Heating AC = Active Cooling
Fan Return: L= Left Hand Return R= Right Hand Return Fan Motor: E = ECM (Variable Speed)
Refrigerant: P = R410a
Fan Type: D = Direct Drive
Voltage Code: 1 = 208/230-1-60
Air Coil: S = Standard
Compressor Stages: L = 1 Stage rotary
Outdoor Loop Exchanger: C = Copper
The models and revisions covered by this document are listed in the table below.
MODEL
REVISION
RH-12-HAC-P-1L-C-SDELF
02
RH-12-HAC-P-1L-C-SDERF
02
Maritime Geothermal Ltd. has a continuous improvement policy and reserves the right to modify specification data at any time without prior notice . 24-July-2015
Page 2
001694SPC-02
NORDIC® DESIGN FEATURES LIST The heat pump described in this specification document comes with the following features:
CSA certified for safety (CSA 22.2 No 236-05). 20ga satin galvanized case with reinforcing channel stiffeners and corner posts. Corner brackets for hanger applications. Acoustically insulated cabinet (1/2” thick) ECM fan motor with removable blower for changing blower motor Field configurable fan outlet, side or end. Air filter accessible from either end of rack. ABS condensate drip tray. Condensate drain with 3/4” PVC FPT connection. Condensate overflow protection. Multi-circuit high efficiency air-coil. Refrigeration service ports located inside unit (1/4” Schrader) Insulated copper coaxial heat exchangers and piping 1/2” brass FPT fittings for Outdoor Loop connections. High efficiency single stage rotary compressor Double grommet compressor isolation for reduced noise and vibration. Suction line accumulator Liquid line filter-dryer Liquid line sight glass Balanced port Thermostatic Expansion Valve with internal bleed 4-way reversing valve High and low pressure safety controls Control board with random start, anti-short cycle timer, 3 re-start attempts and permanent lockout mode. Electrical box layout and schematic diagrams Installation and service manual
OPTIONAL EQUIPMENT The following is a list of optional equipment that may be ordered with the heat pump:
Programmable thermostat. Circulator pump module with loop / unit isolation valves (230VAC) for ground loop applications. Various adapters for unit and loop connections to pump module. Electric plenum heater
24-July-2015
Page 3
001694SPC-02
NORDIC® DESIGN FEATURES Heavy duty cabinet, satin galvanized with powder coated doors for premium appearance
Cabinet completely insulated with 1/2” acoustic insulation. Multi-circuit high efficiency air coil.
Condensate drain with 3/4” PVC FPT connection.
Fault monitoring board with random start, lock -out indicator and antishort cycle timer.
ABS condensate drip tray.
Bi-flow filter dryer.
Corner hangers for concealed ceiling applications.
Balanced port TXV with external equalization port.
1/2” Brass FPT fittings for Outdoor Loop connections. Field replaceable variable speed ECM fan motor with ball bearings and resilient mounting bracket.
Field configurable fan outlet: SIDE or END Suction line accumulator.
Dual mount compressor for reduced noise and vibration.
Sight glass.
High efficiency LG® rotary compressor.
24-July-2015
Page 4
High & Low 4-way refrigerant reversing access ports. valve.
Insulated High Efficiency Turbotec® coaxial heat exchanger. Resistant to accidental freezing.
001694SPC-02
DIMENSIONS - LEFT RETURN
24-July-2015
Page 5
001694SPC-02
DIMENSIONS - RIGHT RETURN
24-July-2015
Page 6
001694SPC-02
ELECTRICAL BOX LAYOUT
Legend 13. 14. 15. 16.
compressor contactor run capacitor 40VA control transformer thermostat terminal strip
17. ground lug 18. condensate overflow safety control 19. control board
ELECTRICAL SPECIFICATIONS Heat Pump Electrical Information Voltage Identifier 1
V-ø-Hz
MIN
MAX
RLA
LRA
RLA
Circ. Pump Max. A
208/230-1-60
187
253
5.5
26
2.8
1.5
Power Supply
Compressor
Fan
Amps
Max. Fuse / Breaker Amps
Minimum Wire Size ga
11.4
15
#14-2
FLA
MCA
Amps 10.0
MISCELLANEOUS INFORMATION Unit Weight Lbs.
kg
Refrigerant Type
172
78
R410a
Refrigerant Charge
Nominal Airflow
Lbs.
kg
CFM
L/s
2.0
0.91
400
189
MINIMUM AND MAXIMUM OPERATING TEMPERATURES* Loop
Outdoor
Indoor (Duct)
Parameter
Mode
(°F)
(°C)
Note
Minimum ELT
Heating / Cooling
41
5
Ground water system.
Minimum ELT
Heating / Cooling
23
-5
Ground loop system. Adequate freeze protection required.
Maximum ELT
Heating
80
27
Maximum ELT
Cooling
110
43
Minimum EAT
Heating / Cooling
60
16
Maximum EAT
Heating
80
27
Reduce air flow if necessary during heating startup.
* Values in this table are for rated liquid and airflow values. 24-July-2015
Page 7
001694SPC-02
ELECTRICAL DIAGRAMS (208/230-1-60)
24-July-2015
Page 8
001694SPC-02
REFRIGERATION CIRCUIT DIAGRAMS
24-July-2015
Page 9
001694SPC-02
REFRIGERATION CIRCUIT DIAGRAMS (continued)
24-July-2015
Page 10
001694SPC-02
STANDARD CAPACITY RATINGS The tables below depict the results of standard capacity rating tests according to C13256-1 standards. C13256-1 is identical to ISO13256-1.
Standard Capacity Ratings - Ground Loop Heating*
60Hz
EAT 68°F (20°C) Model 12
ELT 32°F (0°C)
Liquid Flow USG 3.0
L/s 0.189
Pressure Drop PSI 3.5
kPA 24.1
Airflow CFM 400
L/s 189
Input Energy Watts 920
Capacity BTU/Hr 11,800
kW 3.5
COPH W/W 3.75
* 15% NaCl by Weight Ground Loop Fluid
Standard Capacity Ratings - Ground Water Heating EAT 68°F (20°C) Model 12
ELT 50°F (10°C)
Liquid Flow USG 3.0
60Hz
L/s 0.189
Pressure Drop PSI 3.2
kPA 22.1
Airflow CFM 400
L/s 189
Input Energy Watts 945
Capacity BTU/Hr 13,500
kW 4.0
Standard Capacity Ratings - Ground Loop Cooling* EAT 80.6°F (27°C) Model
12
W/W 4.18
60Hz ELT 77°F (25°C)
Liquid Flow USG 3.0
COPH
L/s 0.189
Pressure Drop PSI 3.3
kPA 22.7
Airflow CFM 400
L/s 189
Input Energy Watts 740
Capacity BTU/Hr 12,800
kW 3.8
COPH W/W 5.07
* 15% NaCl by Weight Ground Loop Fluid
Standard Capacity Ratings - Ground Water Cooling EAT 80.6°F (27°C) Model
12
24-July-2015
ELT 59°F (15°C)
Liquid Flow USG 3.0
60Hz
L/s 0.189
Pressure Drop PSI 3.1
kPA 21.4
Airflow CFM 400
Page 11
L/s 189
Input Energy Watts 600
Capacity BTU/Hr 13,600
kW 3.9
COPH W/W 6.64
001694SPC-02
CAPACITY RATINGS Heating Mode RH-12-HAC-P-1L Source Data (Outdoor Loop)
Nominal 1 ton Power Consumption
ELT
Evap. Temp
Flow
LLT
Delta T
HAB
Compressor
Fan*
°F °C
°F °C
USGPM L/s
°F °C
°F °C
BTU/Hr Watts
Watts Amps
Watts
Watts
29.0
20
3.0
23.1
5.9
8,397
104
916
-1.7
-6.7
0.189
-4.9
3.3
2,460
35.0
25
3.0
28.8
6.2
8,862
1.7
-3.9
0.189
-1.8
3.5
2,597
41.0
30
3.0
34.5
6.5
9,314
5.0
-1.1
0.189
1.4
3.6
2,729
47.0
35
3.0
40.1
6.9
9,794
8.3
1.7
0.189
4.5
3.8
2,870
51.0
40
3.0
44.0
7.0
10,523
10.6
4.4
0.189
6.7
3.9
3,083
57.0
45
3.0
49.3
7.7
11,528
13.9
7.2
0.189
9.6
4.3
3,378
63.0
50
3.0
54.7
8.3
12,506
17.2
10.0
0.189
12.6
4.6
3,664
69.0
55
3.0
60.1
8.9
13,309
20.6
12.8
0.189
15.6
4.9
3,899
812
3.7
824
3.7
EAT
Cond. Temp.
Flow
LAT
Delta T
Net Output
W/W
°F °C
°F °C
CFM L/min
°F °C
°F °C
BTU/Hr Watts
3.69
68
102
400
96.8
28.8
11,523
20.0
38.9
189
36.0
16.0
3,376
Effective COPh
104
928
3.80
834
3.8
104
938
3.91
835
3.8
104
939
4.06
843
3.9
104
947
4.26
859
3.9
104
963
4.51
875
4.0
104
979
4.74
887
4.1
104
991
R410a 60 Hz Sink Data (Indoor Loop)
4.94
68
104
400
98.1
30.1
12,029
20.0
40.0
189
36.7
16.7
3,525
68
106
400
99.3
31.3
12,514
20.0
41.1
189
37.4
17.4
3,666
68
108
400
100.5
32.5
12,997
20.0
42.2
189
38.1
18.1
3,808
68
110
400
102.4
34.4
13,754
20.0
43.3
189
39.1
19.1
4,030
68
112
400
105.0
37.0
14,815
20.0
44.4
189
40.6
20.6
4,341
68
114
400
107.6
39.6
15,847
20.0
45.6
189
42.0
22.0
4,643
68
116
400
109.7
41.7
16,689
20.0
46.7
189
43.2
23.2
4,890
* @ 24.9Pa (0.10inH2o) Ext. Static
Compressor: GKS120KAB
Cooling Mode RH-12-HAC-P-1L Source Data (Indoor Loop) EAT
Evap. Airflow Temp
LAT Delta T Latent Sensible
°F °C
°F °C
CFM L/s
°F °C
°F °C
BTU/Hr BTU/Hr Watts Watts
80.6
44
400
57.0
23.6 4,433
9,421
Power Consumption HAB BTU/Hr Watts
13,854
27.0
6.7
189
13.9
13.1 1,299
2,760
4,059
80.6
44
400
57.4
23.2 4,367
9,281
13,648
27.0
6.8
189
14.1
12.9 1,280
2,719
3,999
80.6
44
400
57.7
22.9 4,308
9,154
13,462
27.0
6.9
189
14.3
12.7 1,262
2,682
3,944
80.6
45
400
58.1
22.5 4,242
9,014
13,256
27.0
7.0
189
14.5
12.5 1,243
2,641
3,884
80.6
45
400
58.4
22.2 4,178
8,877
13,055
27.0
7.1
189
14.7
12.3 1,224
2,601
3,825
80.6
45
400
58.8
21.8 4,104
8,722
12,826
27.0
7.2
189
14.9
12.1 1,203
2,555
3,758
80.6
45
400
59.2
21.4 4,021
8,546
12,567
27.0
7.3
189
15.1
11.9 1,178
2,504
3,682
80.6
45
400
59.6
21.0 3,945
8,383
12,328
27.0
7.4
189
15.4
11.6 1,156
2,456
3,612
Compressor
ELT
Cond. Temp.
Flow
LLT
Watts
EER COPc
°F °C
°F °C
USGPM L/s
°F °C
27.8
51
70
3.0
382
2.2
116
498
451
2.4
116
567
8.15 24.1 7.06
514
2.6
116
630
21.4 6.26
550
2.7
116
666
578
2.8
116
694
19.9 5.83 18.8 5.51
626
2.9
116
742
17.3 5.07
671
3.1
116
787
715
3.3
116
831
16.0 4.68 14.8 4.35
10.6 21.1 56
75
13.3 23.9 61
80
16.1 26.7 66
85
18.9 29.4 72
90
22.2 32.2 77
95
25.0 35.0 82
100
27.8 37.8 87
105
30.6 40.6
5.8
4,574
5.8
4,550
6.0
4,519
6.0
4,500
92.7 10.7 15,253
0.189 33.7 3.0
4,566
87.8 10.8 15,358
0.189 31.0 3.0
5.8
82.8 10.8 15,425
0.189 28.2 3.0
4,557
76.4 10.4 15,530
0.189 24.6 3.0
5.8
71.4 10.4 15,612
0.189 21.9 3.0
BTU/Hr Watts
66.4 10.4 15,583
0.189 19.1 3.0
°F °C
61.4 10.4 15,554
0.189 16.3 3.0
Delta Rejection T
5.9
4,469
97.6 10.6 15,164
0.189 36.5
5.9
4,443
* @ 24.9Pa (0.10inH2o) Ext. Static
Compressor: GKS120KAB
24-July-2015
Efficiency
Fan* Effective
Watts Amps Watts
R410a 60 Hz Sink Data (Outdoor Loop)
Page 12
001694SPC-02
LIMITED WARRANTY MARITIME GEOTHERMAL LTD. warrants that its commercial geothermal heat pumps shall be free from defects in materials and workmanship for a period of ONE (1) YEAR after the date of installation or for a period of ONE (1) YEAR AND SIXTY (60) DAYS after the date of shipment, whichever occurs first. This warranty covers all internal components of the heat pump. MARITIME GEOTHERMAL LTD. shall, at its option, repair or replace any part covered by this warranty. Defective parts shall be returned to MARITIME GEOTHERMAL LTD., transportation charges prepaid. Replacement or repaired parts and components are warranted only for the remaining portion of the original warranty period. This warranty is subject to the following conditions: 1. The geothermal heat pump must be properly installed and maintained in accordance with MARITIME GEOTHERMAL LTD. guidelines. 2. The installer must complete the Startup Record and return it to MARITIME GEOTHERMAL LTD. within 21 days of unit installation. 3. For new construction, it is the responsibility of the building or general contractor to supply temporary heat to the structure prior to occupancy. Geothermal heat pumps are designed to provide heat only to the completely finished and insulated structure. Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty. 4. It is the customer's responsibility to supply the proper quantity and quality of water or properly sized ground loop with adequate freeze protection.
If a geothermal heat pump manufactured by MARITIME GEOTHERMAL LTD. fails to conform to this warranty, MARITIME GEOTHERMAL LTD.'s sole and exclusive liability shall be, at its option, to repair or replace any part or component which is returned by the customer during the applicable warranty period set forth above, provided that (1) MARITIME GEOTHERMAL LTD. is promptly notified in writing upon discovery by the customer that such part or component fails to conform to this warranty; (2) the customer returns such part or component to MARITIME GEOTHERMAL LTD., transportation charges prepaid, within (30) thirty days of failure, and (3) MARITIME GEOTHERMAL LTD.'s examination of such component discloses to its satisfaction that such part or component fails to conform to this warranty and the alleged defects were not caused by accident, misuse, neglect, alteration, improper installation, repair or improper testing. MARITIME GEOTHERMAL LTD. will not be responsible for any consequential damages or labour costs incurred. In additional, MARITIME GEOTHERMAL LTD. will not be responsible for the cost of replacement parts purchased from a third party.