THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
SECTION 077100
ROOF SPECIALTIES
PART 1 - GENERAL 1.1
RELATED DOCUMENTS:
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. SUMMARY:
A.
This Section includes the following: 1. 2.
A.
Related Sections include the following: 1.
1.2
Fascia systems. Coping systems.
Division 07 Section "Sheet Metal Flashing and Trim" for shop- and field-fabricated metal flashing and counterflashing, scuppers, gutters and downspouts, trim and fascia units, roof expansion-joint covers, and miscellaneous sheet metal accessories.
SUBMITTALS: A.
Product Data: For each type of product specified. Include details of construction relative to materials, dimensions of individual components, profiles, and finishes.
B.
Shop Drawings: Indicate layout, joining, profiles, accessories, anchorage, flashing connections, and relationship to supporting structure and to adjoining roof and wall construction.
C.
Samples for Initial Selection: Manufacturer's sample finishes showing the full range of colors and textures available for units with factory-applied color finishes.
D.
Samples for Verification: For copings, and roof-edge flashings made from 12-inch (300-mm) lengths of full-size components including fasteners, cover joints, accessories, and attachments.
E.
Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for copings and roof-edge flashings.
1.3
PERFORMANCE REQUIREMENTS: A.
General: Provide manufactured roof specialties capable of withstanding wind loads, structural movement, thermally induced movement, and exposure to weather without failing.
October 12, 2012 N09003.01
Roof Specialties 077100 - 1
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
B.
Edge securement for low-slope roofs. Low-slope membrane roof systems metal edge securement, except gutters, installed in accordance with Massachusetts State Building Code Section 1504, shall be designed in accordance with ANSI/SPRI ES-1, except the basic wind speed shall be as follows: 1.
C.
Cladding components shall be designed and anchored to resist wind-induced overturning, uplift and sliding in accordance with Massachusetts Building Code Paragraph 1609.1.3. 1.
1.4
Wind Speed: 90 mph.
Wind Speed: 90 mph.
QUALITY ASSURANCE: A.
Mockups: Build mockups to verify selections made under sample submittals and to demonstrate aesthetic effects and set quality standards for fabrication and installation. 1.
2.
3.
B.
Preinstallation Conference: Conduct conference at Project site. 1.
2. 3.
1.5
Build mockup of typical roof edge, including fascia, gutter and downspout, approximately 10 feet(3.0 m) long, including supporting construction, seams, attachments, underlayment, and accessories. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing. Approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
Meet with Owner, Architect, Owner's insurer if applicable, Installer, and installers whose work interfaces with or affects roof specialties including installers of roofing materials and accessories. Examine substrate conditions for compliance with requirements, including flatness and attachment to structural members. Review special roof details, roof drainage, and condition of other construction that will affect roof specialties.
DELIVERY, STORAGE, AND HANDLING: A.
Do not store roof specialties in contact with other materials that might cause staining, denting, or other surface damage. Store roof specialties away from uncured concrete and masonry.
B.
Protect strippable protective covering on roof specialties from exposure to sunlight and high humidity, except to extent necessary for the period of roof specialties installation.
October 12, 2012 N09003.01
Roof Specialties 077100 - 2
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
1.6
WARRANTY: A.
Special Warranty on Painted Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace roof specialties that show evidence of deterioration of factory-applied finishes within specified warranty period. 1.
Fluoropolymer Finish: Deterioration includes, but is not limited to, the following: a. b. c.
2.
Color fading more than 5 Hunter units when tested according to ASTM D 2244. Chalking in excess of a No. 8 rating when tested according to ASTM D 4214. Cracking, checking, peeling, or failure of paint to adhere to bare metal.
Finish Warranty Period: 20 years from date of Substantial Completion.
PART 2 - PRODUCTS 2.1
MANUFACTURERS: A.
Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1.
Formed-Aluminum Roof Edge Flashings/Copings: a. b. c. d. e. f. g. h. i. j.
2.
2.2
ABC Seamless, Inc. Architectural Products Co. ATAS International, Inc. Cheney Flashing Company. Hickman: W.P. Hickman Co. Merchant and Evans, Inc. Metal-Era, Inc .MM Systems Corp. Petersen Aluminum Corp. Southern Aluminum Finishing Co.
Products manufactured by Metal-Era are specified. Items designated establish minimum requirements for design and performance of equipment required by this Section.
METALS: A.
Aluminum Extrusions: ASTM B 221, 6063-T5 alloy and temper, or as recommended by manufacturer for use intended and as required for proper application of finish indicated.
October 12, 2012 N09003.01
Roof Specialties 077100 - 3
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
B.
Aluminum Sheet: ASTM B 209, alloy and temper recommended by aluminum producer and finisher for use intended and finish indicated, and with not less than the strength and durability of alloy and temper designated below: 1.
2.3
Alloy 3003-H14, with a minimum thickness of 0.040 inch, unless otherwise indicated, for aluminum sheet with mill finish.
CONCEALED METALS: A.
2.4
Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, G90 (Z275) coating designation. ROOF-EDGE FLASHINGS:
A.
Roof-Edge Fascia: Manufactured, two-piece, roof-edge fascia consisting of snap-on metal fascia cover in section lengths not exceeding 12 feet (3.6 m) and a continuous formed- or extrudedaluminum anchor bar with integral drip-edge cleat to engage fascia cover. Provide matching corner units. 1. 2. 3. 4.
Basis-of-Design Product: Subject to compliance with requirements, provide Model #AF-85, Metal-Era, tel: 604-689-0188, or one of the listed manufacturers. Height: 8 inches. Extruded aluminum in thickness indicated, but not less than 0.060 inch. Fascia Cover: Fabricated from the following exposed metal: a. b.
5. 6. 2.5
Formed Aluminum: 0.040 inch (1.02 mm) thick. Finish: Two-coat fluoropolymer.
Corners: Factory mitered and continuously welded. Splice Plates: Concealed, of same material, finish, and shape as fascia cover.
COPINGS: A.
Copings: Manufactured coping system consisting of decorative formed-metal coping cap with continuous galvanized steel anchor/support in section lengths not exceeding 12 feet (3.6 m), concealed anchorage; corner units, end cap units, and concealed splice plates with same finish as coping caps. 1.
Coping-Cap Material: a. b. c. d.
2. October 12, 2012 N09003.01
1- to 16-inches Wide: Formed aluminum, 0.050 inch (1.27 mm) thick, or as required to meet performance requirements. 16-inches to 24-inches Wide: Formed aluminum, 0.063 inch (1.60 mm) thick, or as required to meet performance requirements. 24-inches + Wide: Formed aluminum, 0.080 inch (2.032 mm) thick, or as required to meet performance requirements. Finish: Two-coat fluoropolymer.
Height: Reference Drawings. Roof Specialties 077100 - 4
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
3. 4. 5. 6. B.
2.6
Corners: Factory mitered, welded and finished. Coping-Cap Attachment Method: Snap-on, fabricated from coping-cap material. Snap-on-Coping Anchor Plates: Concealed, 20 ga. galvanized-steel sheet, 12 inches (300 mm) wide, with integral stainless steel spring cleats. Anchor Bar: Aluminum, 12-inches wide, 4'-0" o.c.
Basis-of-Design Product: Anchor-Tite Coping (tapered); Metal-Era, tel: 604-689-0188, or one of the listed manufacturers. ACCESSORIES:
A.
General: Provide manufacturer's standard accessories designed and manufactured to match and fit roof edge treatment system indicated.
B.
Concealed Fasteners: Same metal as item fastened or other noncorrosive metal as recommended by manufacturer.
C.
Asphalt Mastic: SSPC-Paint 12, solvent-type asphalt mastic, nominally free of sulfur and containing no asbestos fibers, compounded for 15-mil dry film thickness per coat.
D.
Mastic Sealant: Polyisobutylene; nonhardening, nonskinning, nondrying, nonmigrating sealant.
E.
Foam-Rubber Seal: Manufacturer's standard foam.
F.
Adhesives: Type recommended by manufacturer for substrate and project conditions, and formulated to withstand minimum 60-lbf/sq. ft. wind-uplift force.
2.7
FINISHES, GENERAL: A.
Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations relative to applying and designating finishes.
B.
Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipment.
C.
Finish manufactured roof specialties after fabrication and assembly if products are not fabricated from prefinished metals.
D.
Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are unacceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
2.8
ALUMINUM FINISHES: A.
Finish designations prefixed by AA conform to the system established by the Aluminum Association for designating aluminum finishes.
October 12, 2012 N09003.01
Roof Specialties 077100 - 5
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
B.
High-Performance Organic Coating Finish: AA-C12C42R1x (Chemical Finish: cleaned with inhibited chemicals; Chemical Finish: acid-chromate-fluoride-phosphate conversion coating; Organic Coating: as specified below). Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating or resin manufacturer's written instructions. 1.
Fluoropolymer 2-Coat Coating System: Manufacturer's standard 2-coat, thermocured system composed of specially formulated inhibitive primer and fluoropolymer color topcoat containing not less than 70 percent polyvinylidene fluoride resin by weight; complying with AAMA 1402, Test Method 7. a.
Color and Gloss: Match Architect’s sample.
PART 3 - EXECUTION 3.1
EXAMINATION: A.
3.2
Examine walls, roof edges, and parapets for suitable conditions for roof edge system installation. Do not proceed with installation until unsatisfactory conditions have been corrected. PREPARATION:
A.
Promptly remove protective film, if any, from exposed surfaces of finished metals. Strip with care to avoid damage to finish.
B.
Prepare concrete, concrete masonry block, and similar surfaces to receive roof edge system specified. Install blocking, cleats, water dams, and other anchoring and attachment accessories and devices required.
3.3
INSTALLATION: A.
General: Comply with manufacturer's written installation instructions. Coordinate with installation of roof deck and other substrates to receive work of this Section and with vapor retarders, roofing insulation, roofing membrane, flashing, and wall construction, as required to ensure that each element of the Work performs properly and that combined elements are waterproof and weathertight. Anchor products securely to structural substrates to withstand lateral and thermal stresses and inward and outward loading pressures.
B.
Isolation: Where metal surfaces of units contact dissimilar metal or corrosive substrates, including wood, apply bituminous coating on concealed metal surfaces or provide other permanent separation as recommended by aluminum producer.
C.
Expansion Provisions: Install running lengths to allow controlled expansion for movement of metal components in relation not only to one another but also to adjoining dissimilar materials, including flashing and roofing membrane materials, in a manner sufficient to prevent water leakage, deformation, or damage.
October 12, 2012 N09003.01
Roof Specialties 077100 - 6
THE ALLAN P. & MARIAN SUTHERLAND KIRBY CENTER FOR THE CREATIVE ARTS WYOMING SEMINARY
3.4
ROOF-EDGE FLASHING INSTALLATION: A.
Install cleats, cants, and other anchoring and attachment accessories and devices with concealed fasteners.
B.
Anchor roof edgings with manufacturer's required devices, fasteners, and fastener spacing to meet performance requirements.
3.5
CLEANING AND PROTECTING: A.
Clean exposed metal surfaces according to manufacturer's written instructions. Touch up damaged metal coatings.
B.
Protection: Provide protective measures as required to ensure work of this Section will be without damage or deterioration at the time of Substantial Completion.
END OF SECTION 077100
October 12, 2012 N09003.01
Roof Specialties 077100 - 7