1. GENERAL INFORMATION
DTV_VR2E018E_04--CHAPTER01 2013.07.29
CONTENTS 1. GENERAL INFORMATION 1.
FEATURES OF SYSTEM........................................................... 01-01
1-1. HIGH ENERGY EFFICIENCY..........................................................................01-01 1-2. COMFORT & CONVENIENCE.........................................................................01-05 1-3. DESIGN FLEXIBILITY...................................................................................... 01-07 1-4. EASY INSTALLATION..................................................................................... 01-09 1-5. HIGH RELIABILITY.......................................................................................... 01-11 1-6. EASY MAINTENANCE & SERVICE................................................................01-13
2. MODEL LINE UP........................................................................ 01-15 2-1. OUTDOOR UNIT..............................................................................................01-15 2-2. INDOOR UNIT..................................................................................................01-17 2-3. CONTROLLER.................................................................................................01-19 2-4. ADAPTOR / CONVERTOR / MAINTENANCE TOOL...................................... 01-20 2-5. RB UNIT...........................................................................................................01-21 2-6. BRANCH KIT....................................................................................................01-22 2-7. EV KIT..............................................................................................................01-25 2-8. CASSETTE GRILLE......................................................................................... 01-25 2-9. OTHERS (optional parts)................................................................................ 01-26
GENERAL INFORMATION
GENERAL INFORMATION
111FEATURES OF SYSTEM 11111HIGH ENERGY EFFICIENCY EFFICIENCY IN ACTUAL OPERATION
Top class high COP is realized for all combinations by our unique heat exchanger structure, high efficient DC twin compressor, and other distinctive technologies.
Space saving combination zz (COP) 5 4.39
4.30 3.90
4
4.13
4.34
4.30
3.92
4.07
3.90
4.05
3.91
4.01
3.92
4.01
28
30
32
34
3.90
4.00
3.91
4.00
3.91
3.98
3.92
36
38
40
42
44
46
48
3
2
1
0
8
10
12
14
16
18
20
24*
22
26
(HP)
Energy efficincy combination zz (COP) 5 4.39
4.22
4.39
4.35
4.32
4.30
4.24
4.23
4.18
4.17
4.08
4.13
4.05
For 24 HP Combination
4
Energy efficincy
Space saving 3
2
COP
1
0
12.6 % UP 16
22
24*
26
28
30
32
34
36
38
- (01-01) -
40
42
44
(HP)
GENERAL INFORMATION
Powerful large propeller fan By using CFD*1 technology, a newly designed fan achieves high performance and low noise operation. *1. CFD = Computational Fluid Dynamics
3 phase DC fan motor Efficiency is substantially improved by high efficient motor with sophisticated driver control. In addition, low noise is realized by DC fan motor.
Subcool heat exchanger High heat exchange efficiency is achieved by using an internal projection shape double pipe construction.
Sine-wave DC inverter control High efficiency is realized by adoption of reduced switching loss IPM.
Unique 4-face heat exchanger Heat exchange efficiency is significantly improved by the introduction of a new 4-face heat exchanger that increases effective surface area.
Front intake port In multiple outdoor unit installations, the unique front intake design improves airflow into the Heat Exchanger.
High efficient compressor Large capacity DC inverter compressor
High efficient compressor speed control
Large capacity high efficient DC twin rotary compressor with excellent intermediate capability.
Comfortable space with small changes in room temperature and little energy loss is created by 0.1Hz steps compressor speed control. Capacity
GENERAL INFORMATION
ENERGY EFFICIENCY TECHNOLOGY
0.1Hz
Inverter frequency
- (01-02) -
GENERAL INFORMATION
GENERAL INFORMATION
ENERGY SAVING FUNCTIONS Heat exchanger refrigerant control zz The heat exchanger in the outdoor unit is split into two parts (Top and Bottom). The efficiency of the heat exchanger has been improved by adopting an optimum refrigerant path control where the refrigerant is distributed more into the top heat exchanger as this is where there is a greater air flow intake. High efficient refrigerant flow control Fan
Larger refrigerant flow
Large intake airflow
Small intake airflow
Heat exchanger EEV
Heat exchanger
Distributor
Outdoor unit
Multiple outdoor operation control zz When multiple outdoor units are connected, a sophisticated operation is performed by each compressor. Rather than running one compressor at full load and distributing refrigerant to one heat exchanger, this control method operates all compressors at part load and distributes refrigerant to all of the heat exchangers which allows for the overall system efficiency to be improved.
Compressor Load level
High efficient operation
Inefficient operation
- (01-03) -
Room temperature set point limitation zz The minimum and maximum temperature range can be set giving further energy saving while considering the comfort of the occupants. Heating
(°C) 30
Cooling
28 26 24 22 20 18 16 14 12 10
Original Set Temp
Set point limitation setting
Auto-off timer zz New wired remote controller is equipped with an OFF timer function that automatically stops operation when a fixed time has elapsed from the start of operation. This prevents waste of energy. Furthermore a new wired remote controller can set up the interval of time in case operation stops.
Set interval time hour (17:00 to 24:00) ON
Auto OFF
Set off time (30 to 240 minutes) 17:00
24:00
OFF
Economy operation zz Economy operation can be set by remote controller. The temperature setting is offset automatically over a certain period of time. Economy operation Control Temperature
Set Temp.
Up
MAX. +2°C
Up
Cooling Set Temperature
Heating Set Temperature
Economy operation
Set Temp.
MAX. - 4°C Economy operation Control Temperature
Down
Down
Down
Down
Economy operation
Capacity save operation zz Operation capacity can be set in 5 steps for rated capability. The power consumption at peak is cut down and the maximum load is suppressed. Setting range
100% 80%
Capacity
Capacity save
Setting level
60% 40% 0% Time
- (01-04) -
GENERAL INFORMATION
GENERAL INFORMATION
OPERATION PERFORMANCE IS EFFICIENTLY CONTROLLED
NEW TOUCH PANEL WIRED REMOTE CONTROLLER
The new wired remote controller has an easy to use LCD touch panel. This new controller has a backlight function and can easily control the air conditioner which provides a better energy saving operation of the air conditioner. Large-sized LCD touch panel screen Setting status display Room temperature display
Multi language support Large ON/OFF button Backlight
- (01-05) -
GENERAL INFORMATION
GENERAL INFORMATION
11111COMFORT & CONVENIENCE
GENERAL INFORMATION
GENERAL INFORMATION
AUTO CHANGEOVER FUNCTION At Auto setting, the cooling/heating mode is automatically switched according to the set temperature and room temperature. 2°C 0.5°C
Set Temp. - 0.5°C - 2°C
time Cooling operation Heating operation
Cooling fan operation Heating fan operation
Automatic cooling/heating operation for each room is possible.
Heating
Dry
Cooling
Room B 18°C
Room A 24°C
Room D OFF
Room C 27°C
Fan
Room E 23°C
PRECISION REFRIGERANT FLOW CONTROL Precision and smooth refrigerant flow control is achieved by using a DC Inverter control in conjunction with individual indoor unit electronic expansion valve control. This allows for a high precision comfortable temperature control within ±0.5°C of set temperature. ±0.5 °C
High
Set temp.
Hot
Hot
Thermal change of the room *Simulation in heating operation. Comfortable operation is achieved due to a small variation of room temperature
Cold
Low
Reach the set temperature quickly
QUIET OPERATION Low noise mode zz Two low noise modes can be selected automatically by quiet priority setting and capacity priority setting depending on the usage environment and outside temperature load. Outdoor unit external input and setting from system controller are possible. Capacity priority setting
Quiet priority setting Air conditioning load factor
Capacity
Air conditioning load factor
Heat load 100%
down
Capacity
Heat load 100%
Operating sound
Alternated automatically
0
0 58dB
Operating sound
0 Quiet priority low noise mode
58dB
time
0
Reset automatically Capacity priority low noise mode
- (01-06) -
time
FLEXIBLE PIPING CONNECTION SUITABLE FOR VARIOUS APPLICATIONS With many piping and RB unit options available, designing a piping system to suit most applications has been made more flexible and easy.
Separation tube
RB Unit (multi type)
RB Unit (single type)
Max.3 or 8 indoor units
Application
Single connection
Group connection
Individual cooling and heating
Simultaneous cooling and heating
Max. 8 indoor unit Single connection Individual cooling and heating
&
Group connection Simultaneous cooling and heating
*1 RB unit less connection Cooling only
●●The RB unit can be freely positioned between the first branch and the indoor unit. ●●The maximum height difference between RB units is 15 m. *1. RB unit is not necessary for cooling only applications.
- (01-07) -
GENERAL INFORMATION
GENERAL INFORMATION
11111DESIGN FLEXIBILITY
Total pipe length
1,000 m
HIGH STATIC PRESSURE OF 80Pa
Large diameter fan and 3 phase DC motor has been utilized allowing an external static pressure of 80Pa. This allows outdoor units to be installed on balconies, etc. on each floor in high rise buildings.
Height difference between outdoor and indoor units
*2
50m max.
Actual pipe length
For the outdoor unit stated
165m max.
below : 40m max.
80 Pa
as standard
Installation Example
Height difference between indoor and indoor units
Pipe length from first separation tube to the farthest indoor unit
15m max.
60m max.
*2. Note : When there is 1 outdoor unit, the maximum is 700m.
HIGH CAPACITY CONNECTION
Various combination from 8HP to 48HP. 55 models of indoor units can be selected ranging from 1.1kW to 25kW in capacity. A maximum of 150% indoor unit connectable capacity.
Connectable indoor unit capacity
50% to 150% Connectable indoor unit number
up to 64
WIDE OPERATING RANGE
Installation in extreme temperature conditions is possible due to an increase in operational range. Cooling : -10°C~46°C Cooling & Heating : -10°C~21°C Heating : -20°C~21°C (°C) 50
Cooling
46°C
40
Cooling & Heating
30
21°C
20
Heating
21°C
10 0 -10 -20
-10°C
-10°C -20°C
- (01-08) -
GENERAL INFORMATION
GENERAL INFORMATION
OVERALL PIPING LENGTH 1,000m
GENERAL INFORMATION
GENERAL INFORMATION
11111EASY INSTALLATION FLEXIBLE INSTALLATION OF RB UNIT
RB unit(single type)
RB unit(multi type)
・Small & slim design saves space ・A drain pipe is not required ・The control box position can be changed to meet the installation conditions
・Small design saves space ・A drain pipe is not required ・Simple installation by connection in series
Height
•2-way connection
198mm
•Up to 2 units can be connected in series.
Installation possible from either side for freedom of the control box
Installation possible on the upper-side for use in narrow space
- (01-09) -
GENERAL INFORMATION
GENERAL INFORMATION
SIMPLE WIRING WORK Installation of the wiring systems is made easier as the communication wiring can be installed continuously between the indoor, outdoor and RB units. Up to maximum
length
RB Unit
3,600m
or
Parallel connection
Serial connection
Note: Automatic address setting can't be used when connected in serial in a multiple refrigerant system.
AUTOMATIC ADDRESS SETTING The address of the indoor unit, RB unit and signal amplifier can be set through the automatic function setting on the outdoor unit PCB. Addresses are automatically distributed from outdoor unit.
Automatic address setting is performed at outdoor unit
1 Signal Amplifier
RB unit
3
3
7
7
2
2 Press the push button switch of outdoor unit.
1
1
4
4
0
0
5
5
6
6
Manual address setting from indoor unit and remote controller is also possible.
EASILY TRANSPORTED Easily craned using lifting belt hooks Design of outdoor unit allows for lifting straps to be used
Can be transported in a small elevator
Easy access By adopting a L-Shape front panel that can be removed, the work space for installation and service has been significantly expanded by this new design. For multiple installations, work is performed easily and efficiently even in a narrow space.
Flexible piping connection Transporting by forklift Transport with forklift is possible.
Piping and wiring are available to the front, left and right, and bottom.
- (01-10) -
Expansion of work space
GENERAL INFORMATION
GENERAL INFORMATION
11111HIGH RELIABILITY OUTDOOR UNIT ROTATIONAL OPERATION
The compressor starting order is rotated so that the running time is shared. Rotation
DC 1
DC 2
DC 3
DC 1
DC 2
Rotation
DC D C 3
Rotation
DC 1
DC 2
DC 3
Note: Rotational operation is alternated by the start / stop timing of the compressor.
- (01-11) -
GENERAL INFORMATION
GENERAL INFORMATION
BACKUP OPERATION If one compressor fails, backup operation will be performed by the remaining compressors*. *:Note: Backup operation may not be possible depending on the trouble state.
ADVANCED REFRIGERANT CONTROL Innovative compressor control logic has been introduced in order to balance the refrigerant mass flow rate of each outdoor unit by controlling the inverter speed. ON
ON
ON
ON
ON
OFF
DC 1
DC 2
DC 3
DC 1
DC 2
DC 3
Slave 1
Slave 2
Slave 1
Slave 2
Master
Load level
Balance operation condition
Master
Unbalance operation condition
LIQUID BACK FLOW PROTECTION By adopting a large sized accumulator, the refrigerant which is not completely vapourised stays inside of the accumulator to ensure no liquid refrigerant is fed back into the compressor. Completely vapourised refrigerant
from Evapolator
Compressor Large sized Accumulator Liquid refrigerant (stays inside of accumulator)
ADOPTION OF BLUE FIN HEAT EXCHANGER Corrosion resistant of the heat exchanger has been improved by the introduction of blue fin treatment to the outdoor unit’s heat exchanger. Blue fin heat exchanger Cobalt Blue protection Standard chromate protection Aluminium base material Hydrophilic coating
- (01-12) -
OPERATION AND ERROR STATUS CAN BE CHECKED EASILY VIA THE WIRED REMOTE CONTROLLER. Address, setting status, and error status can be checked.
Setting status
Wired Remote Controller (Touch panel)
Indoor unit address
Error status / Error history
- (01-13) -
GENERAL INFORMATION
GENERAL INFORMATION
11111EASY MAINTENANCE & SERVICE
Inspection and replacement of the main parts is easier due to the innovative construction of the outdoor unit. Operation and Error checking can be done easily via an LED operational display. Consolidated electrical components make maintenace easy.
Easy-to-read 7-segment LED display which explains operational and trouble status
Movable PCB panel that allows for easier maintenance work behind the PCB. Maintenance of electrical components, valves, and co compressor parts from the front is possible.
Maintenance can be performed from the side.
Split front panel allows for maintenance from top or bottom of the outdoor unit
The control box cover can be temporarily fixed for maintenance.
Easy to maintenance in a narrow space
Parts can be replaced easily even at narrow space in the ceiling.
Expansion of work space
RB unit
Ceiling
SERVICE TOOL Our service tool can be connected anywhere on the VRF wiring network. This program allows for easy maintenance and troubleshooting by allowing the user to analyse all operational data of the VRF system Outdoor unit
Service Tool UTY-ASGX
Transmission line
Software
USB adaptor RB unit
Indoor unit
- (01-14) -
(Field supplied)
Easy to carry out with USB adaptor
GENERAL INFORMATION
GENERAL INFORMATION
DESIGN FOR EASY SERVICE AND MAINTENANCE
●●Extensive line up from 8HP to 48HP in 2HP increments. ●●Space saving combination and Energy efficiency combination available, which can be selected to suit any air conditioning needs.
LINE UP (SINGLE) Cooling HP capacity (kW)
Model name
8
22.4
AJA72GALH
10
28.0
AJA90GALH
12
33.5
AJ108GALH
14
40.0
AJ126GALH
16
45.0
AJ144GALH
Chassis
SPACE SAVING COMBINATION
●●Combinations other than the followings are prohibited.
Cooling HP capacity Set model name (kW) 8 22.4 AJA72GALH
Unit1 (Model name)
Unit2 (Model name)
Unit3 (Model name)
AJA72GALH
-
-
Maximum connectable indoor unit 15
10
28.0
AJA90GALH
AJA90GALH
-
-
16
12
33.5
AJ108GALH
AJ108GALH
-
-
17
14
40.0
AJ126GALH
AJ126GALH
-
-
21
16
45.0
AJ144GALH
AJ144GALH
-
-
24
18
50.4
AJ162GALH
AJA90GALH
AJA72GALH
-
27
20
56.0
AJ180GALH
AJA90GALH
AJA90GALH
-
30
22
61.5
AJ198GALH
AJ108GALH
AJA90GALH
-
32
24
67.0
AJ216GALH
AJ108GALH
AJ108GALH
-
35
26
73.0
AJ234GALH
AJ144GALH
AJA90GALH
-
39
28
78.5
AJ252GALH
AJ144GALH
AJ108GALH
-
42
30
85.0
AJ270GALH
AJ144GALH
AJ126GALH
-
45
32
90.0
AJ288GALH
AJ144GALH
AJ144GALH
-
48
34
95.0
AJ306GALH
AJ108GALH
AJ108GALH
AJA90GALH
50
36
100.5
AJ324GALH
AJ108GALH
AJ108GALH
AJ108GALH
53
38
106.5
AJ342GALH
AJ144GALH
AJ108GALH
AJA90GALH
57
40
112.0
AJ360GALH
AJ144GALH
AJ108GALH
AJ108GALH
60
42
118.0
AJ378GALH
AJ144GALH
AJ144GALH
AJA90GALH
63
44
123.5
AJ396GALH
AJ144GALH
AJ144GALH
AJ108GALH
64
46
130.0
AJ414GALH
AJ144GALH
AJ144GALH
AJ126GALH
64
48
135.0
AJ432GALH
AJ144GALH
AJ144GALH
AJ144GALH
64
- (01-15) -
GENERAL INFORMATION
GENERAL INFORMATION
222MODEL LINE UP 22222OUTDOOR UNIT
GENERAL INFORMATION
GENERAL INFORMATION
ENERGY EFFICIENCY COMBINATION
●●Combinations other than the followings are prohibited.
Cooling HP capacity Set model name (kW) 16 44.8 AJ144GALHH
Unit1 (Model name)
Unit2 (Model name)
Unit3 (Model name)
AJA72GALH
AJA72GALH
-
Maximum connectable indoor unit 24
22
62.4
AJ198GALHH
AJ126GALH
AJA72GALH
-
33
24
67.2
AJ216GALHH
AJA72GALH
AJA72GALH
AJA72GALH
36
26
72.8
AJ234GALHH
AJA90GALH
AJA72GALH
AJA72GALH
39
28
78.4
AJ252GALHH
AJA90GALH
AJA90GALH
AJA72GALH
42
30
84.0
AJ270GALHH
AJA90GALH
AJA90GALH
AJA90GALH
45
32
90.4
AJ288GALHH
AJ126GALH
AJA90GALH
AJA72GALH
48
34
96.0
AJ306GALHH
AJ126GALH
AJA90GALH
AJA90GALH
51
36
102.4
AJ324GALHH
AJ126GALH
AJ126GALH
AJA72GALH
54
38
108.0
AJ342GALHH
AJ126GALH
AJ126GALH
AJA90GALH
57
40
113.0
AJ360GALHH
AJ144GALH
AJ126GALH
AJA90GALH
60
42
120.0
AJ378GALHH
AJ126GALH
AJ126GALH
AJ126GALH
64
44
125.0
AJ396GALHH
AJ144GALH
AJ126GALH
AJ126GALH
64
MODEL DESIGNATION 1
A
2
J
Type AJ : Outdoor unit
3
Y Destination H: GENERAL Y: FUJITSU
4
A
5
9 Model code (kW) A72 : (22.4) A90 : (28.0) 108 : (33.5) 126 : (40.0) 144 : (45.0)
6
7
0
G Function G:H eat Recovery
- (01-16) -
8
A
9
L
10
H
Model change code Series name AL H : VRFII
11
Set name H : Energy Efficiency Combination Blank : Space Saving Combination
GENERAL INFORMATION
GENERAL INFORMATION
22222INDOOR UNIT LINE UP (1/2) Various combinations of types and capacity 55 models, ranging from 1.1kW to 25.0kW. Capacity kW
Model code
1.1
04
2.2
07
2.8
09
3.6
12
4.5
14
5.6
18
7.1
24
9.0
30
11.2
36
12.5
45
14.0
54
18.0
60
22.4
72
25.0
90
Compact Cassette
Cassette
Compact Cassette AUXB04GALH AUXB07GALH AUXB09GALH AUXB12GALH AUXB14GALH AUXB18GALH AUXB24GALH
Slim Duct/Slim Concealed Floor
ARXD04GALH ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH
Low Static Pressure Duct/ Concealed Floor
Slim Duct/ Slim Concealed Floor
Cassette AUXD18GALH AUXD24GALH AUXA30GALH AUXA36GALH AUXA45GALH AUXA54GALH
Medium Static Pressure Duct
Low Static Pressure Duct/ Concealed Floor
ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH
Medium Static Pressure Duct ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH
ARXD18GALH ARXD24GALH
- (01-17) -
GENERAL INFORMATION
GENERAL INFORMATION
LINE UP (2/2) Various combinations of types and capacity 55 models, ranging from 1.1kW to 25.0kW. Capacity kW 1.1
High Static Pressure Floor / Ceiling Duct
Model code 04
2.2
07
2.8
09
3.6
12
4.5
14
5.6
18
7.1
24
9.0
30
11.2
36
12.5
45
14.0
54
18.0
60
22.4
72
25.0
90
High Static Pressure Duct
ARXC36GATH ARXC45GATH ARXC60GATH
Floor / Ceiling
Wall Mounted
ASE04GACH ASE07GACH ASE09GACH ASE12GACH ASE14GACH
MODEL DESIGNATION
Type AU: Cassette AR: Duct AB: Floor/Ceiling or Ceiling AS: Wall Mounted
ABA30GATH ABA36GATH ABA45GATH ABA54GATH
Wall Mounted (EEV external)
ASA04GACH ASA07GACH ASA09GACH ASA12GACH ASA14GACH ASA18GACH ASA24GACH ASA30GACH
A
Ceiling
ABA12GATH ABA14GATH ABA18GATH ABA24GATH
ARXC72GATH ARXC90GATH
1
Wall Mounted Wall Mounted (EEV external)
Ceiling
2
U
3
X
Destination H: GENERAL Y: FUJITSU X:Neutral brand
4
B
Model A: Standard B: Compact (AU) B: Low Static Pressure (AR) C: High Static Pressure (AR) D: Slim (AU) (AR) E: EEV external (AS)
EV kit
5
1
6
2
Model code (kW) 04 (1.1) 07 (2.2) 09 (2.8) 12 (3.6) 14 (4.5) 18 (5.6) 24 (7.1) 30 (9.0) 36 (11.2) 45 (12.5) 54 (14.0) 60 (18.0) 72 (22.4) 90 (25.0) - (01-18) -
7
G Function G : Inverter (R410A)
8
A
9
L
Model change code AC AL AT BL
10
H Series name H : VRF II
GENERAL INFORMATION
GENERAL INFORMATION
22222CONTROLLER LINE UP
Type
Model
System Controller
UTY-APGX
Option: UTY-PEGX
System Controller Lite
UTY-ALGX
Option: UTY-PLGXA1, UTY-PLGXR1, UTY-PLGXE1
Touch Panel Controller
UTY-DTG
Central Remote Controller
UTY-DCG
Group Remote Controller
UTY-CGG
Wired Remote Controller (Touch panel)
UTY-RNR
Wired Remote Controller
UTY-RNK
Simple Remote Controller (With operation mode)
UTY-RSK
Simple Remote Controller (Without operation mode)
UTY-RHK
Wireless Remote Controller
UTY-LNH
CENTRAL CONTROL
Touch Panel Controller
System Controller
Central Remote Controller
Group Remote Controller
UTY-CGG UTY-APGX / UTY-ALGX
Network Convertor (UTY-VGGXZ1) is necessary to connect Group Remote Controller to VRF network system.
UTY-DCG
UTY-DTG
INDIVIDUAL CONTROL Wired Remote Controller (Touch panel)
SET TEMP.
UTY-RNR
Simple Remote Controller (With operation mode)
(Without operation mode)
UTY-RSK
UTY-RHK
START/STOP
UTY-RNK
MODEL DESIGNATION 1
U
2
T Series name UTY : Control unit
Wireless Remote Controller
3
Y
4
-
5
R
6
N
UTY-LNH
7
K
Type APG: System Controller ALG: System Controller Lite DTG: Touch Panel Controller DCG: Central Remote Controller CGG: Group Remote Controller RNR, RNK: Wired Remote Controller RSK: Simple Remote Controller (with operation mode) RHK: Simple Remote Controller (without operation mode) LNH: Wireless Remote Controller - (01-19) -
8
Y Destination G: GENERAL Y: FUJITSU X:Neutral brand
Network Convertor
Model : UTY-VGGXZ1
Split type systems can be controlled from a central controller via the convertor.
Network Convertor for LONWORKS® Model : UTY-VLGX For connection between VRF
network system and a LONWORKS ® open network for management of small to medium-sized BMS.
Group remote controller can be controlled up to two refrigerant systems via the convertor.
BACnet® Gateway
Model : UTY-ABGX
The central control of maximum 1600 indoor units can be realized by connecting the VRF network system to the BACnet®, a global standard for open network.
Signal Amplifier
Model : UTY-VSGXZ1
External Switch Controller
Service Tool
Model : UTY-ASGX
Model : UTY-TEKX
Air conditioner switching can be controlled by connecting other external sensor switches.
If the total length of transmission line exceeds 500m, or the number of units exceeds 64, a Signal Amplifier will be necessary.
Web Monitoring Tool
Extensive monitoring and analysis functions for installation and maintenance. Operation status and error history can be grasped promptly and adequately.
- (01-20) -
Model : UTY-AMGX
Trouble free operation at all times by web monitoring system. The operation status of the VRF network system within the building can be monitored in real time over the Internet.
GENERAL INFORMATION
GENERAL INFORMATION
22222ADAPTOR / CONVERTOR / MAINTENANCE TOOL
GENERAL INFORMATION
GENERAL INFORMATION
22222RB UNIT
Single type
Single type
Multi type
Model :UTP-RX01AH
Single type
Model :UTP-RX01CH
Model :UTP-RX04BH
- (01-21) -
Model :UTP-RX01BH
GENERAL INFORMATION
GENERAL INFORMATION
22222BRANCH KIT 2222222OUTDOOR UNIT BRANCH KIT Outdoor Unit Branch Kit
Model :UTP-DX567A Discharge Gas Pipe
Liquid Pipe
Suction Gas Pipe
2222222SEPARATION TUBE Separation Tube (for 2 pipes)
Model :UTR-BP567X
Liquid Pipe
Gas Pipe
Separation Tube (for 2 pipes)
Model :UTP-AX567A
Liquid Pipe
Gas Pipe
Separation Tube (for 3 pipes) Liquid Pipe
Model :UTP-BX567A Discharge Gas Pipe
- (01-22) -
Suction Gas Pipe
Liquid Pipe
Liquid Pipe
Gas Pipe
Gas Pipe
Separation Tube (for 2 pipes) Separation Tube (for 2 pipes) Model :UTP-AX090A Model :UTP-AX180A Liquid Pipe
Liquid Pipe
Gas Pipe
Gas Pipe
Separation Tube (for 3 pipes) Separation Tube (for 3 pipes) Model :UTP-BX090A Model :UTP-BX180A Liquid Pipe
Liquid Pipe
Discharge Gas Pipe
Discharge Gas Pipe
Suction Gas Pipe
Suction Gas Pipe
- (01-23) -
GENERAL INFORMATION
GENERAL INFORMATION
Separation Tube (for 2 pipes) Separation Tube (for 2 pipes) Model :UTR-BP090X Model :UTR-BP180X
GENERAL INFORMATION
GENERAL INFORMATION
2222222HEADER Model : UTR-H0906L Model : UTR-H1806L
Header Model : UTR-H0908L
Model : UTR-H1808L
Liquid Pipe
Liquid Pipe
Liquid Pipe
Liquid Pipe
Gas Pipe
Gas Pipe
Gas Pipe
Gas Pipe
Header Model : UTP-J0908A
Model : UTP-J0906A
Model : UTP-J1806A
Liquid Pipe
Liquid Pipe
Liquid Pipe
Discharge Gas Pipe
Discharge Gas Pipe
Discharge Gas Pipe
Discharge Gas Pipe
Suction Gas Pipe
Suction Gas Pipe
Suction Gas Pipe
Suction Gas Pipe
- (01-24) -
Model : UTP-J1808A Liquid Pipe
GENERAL INFORMATION
GENERAL INFORMATION
22222 EV KIT EV Kit
Models : UTR-EV09XB UTR-EV14XB
For Wall Mounted type (EEV external type)
22222CASSETTE GRILLE Cassette grille
Models : UTG-UFYC-W UTG-UFGC-W
Cassette grille
For Compact Cassette type
Models : UTG-UGYA-W UTG-UGGA-W
For Cassette type
- (01-25) -
GENERAL INFORMATION
GENERAL INFORMATION
22222OTHERS (optional parts) Flange (Square)
Model : UTD-SF045T
For Medium Static Pressure Duct type 205 x 1,063 ; L=40 (mm)
Long-life Filter
Flange (Round)
Model : UTD-RF204
For Medium Static Pressure Duct type ø195 (ø205) ; L=85 (mm)
Model : UTD-LF25NA
Long-life Filter
For Medium Static Pressure Duct type
Model : UTD-LF60KA
For High Static Pressure Duct type For ARXC36 For ARXC45 For ARXC60 x 2 pcs
Drain Pump Unit
x 2 pcs
Models : UTZ-PX1BBA *1 UTZ-PX1NBA *2
Drain Pump Unit
*1 For Low Static Pressure Duct/Concealed Floor type *2 For Medium Static Pressure Duct type
Air outlet shutter plate
Model : UTR-DPB24T
For Ceiling type
Model : UTR-YDZB
Air outlet shutter plate
For Compact Cassette type
For Cassette type
- (01-26) -
Model : UTR-YDZC
Model : UTG-BGYA-W
GENERAL INFORMATION
Wide panel
Model : UTG-AGYA-W Indoor unit 950mm Panel 600mm
242mm
GENERAL INFORMATION
Panel spacer
Panel spacer Panel 600mm
IR Receiver Unit
Model: UTB-YWC
IR Receiver Unit
For all Duct type
Remote Sensor Unit
Models : UTY-LRHYB1 UTY-LRHGB1
For Cassette type
Model : UTY-XSZX Thermo-sensor for sensing the temperature of arbitrary place in the room
Fresh air intake kit
Model : UTZ-VXAA
Fresh air intake kit
For Compact Cassette type
For Cassette type
Insulation Kit for High Humidity Models : UTZ-KXGA *1 UTZ-KXGB *2 UTZ-KXGC *3
Auto louver grille kit
Insulation Kit
*1 For Cassette type (30-54 models) *2 For Cassette type (18-24 models) *3 For Compact Cassette type
Model : UTZ-VXGA
Models : UTD-GXSA-W *1 UTD-GXSB-W *2 UTD-GXSC-W *3
*1 For Slim Duct (07-14 models) *2 For Slim Duct (18 model) *3 For Slim Duct (24 model) - (01-27) -