TO:
All Contractors
FROM: LePique & Orne Architects, Inc. DATE: July 24, 2017 RE:
New Base Station No. 18
ADDENDUM No. 6 Base 18 The following Addendum to the Drawings and Specifications modifies and supersedes previously issued documents. Acknowledge receipt of this Addendum on the Bid Form. IMPORTANT: This addendum and all bidding construction documents represent a comprehensive scope of work. It is each contractor’s responsibility to reference all drawings, specifications and addendums to verify their respective scope of work.
General information and Specifications:
1.
Supplementary Conditions, Paragraph 27: B) Clarification, Use this section for temporary fence & gates. A chain link fence will not be required on this project. Plumbing & Architectural Drawings: 1. Clarification: The exterior drain tile as shown that is to be routed to daylight shall be connected to the interior drain tile and ran to the sump pit, for the purpose of this bid.
Electric Drawings:
The attached electric drawings show the added circuit and wiring for the grinder pump, no other changes, please note the correct sheet attached. 1.
End of Addendum No. 6
701 N. Fifth Street
■
Saint Charles, MO 63301
■
(636) 947 -0099
■
Fax (636) 947 -8700
GENERAL NOTES - ELECTRICAL
2
A.
COORDINATE ELECTRIC UTILITY WORK WITH UTILITY ENGINEER PRIOR TO START OF CONSTRUCTION.
B.
REFER TO RISER DIAGRAM DETAIL 5/E0.1 FOR ADDITIONAL INFORMATION.
#
PLAN NOTES - ELECTRICAL
1.
PROPOSED LOCATION OF NEW UTILITY PAD-MOUNTED TRANSFORMER.
2.
PROVIDE ONE (1) 4" CONDUIT FROM EXISTING UTILITY COMPANY POWER POLE TO NEW UTILITY PAD-MOUNTED TRANSFORMER. VERIFY ALL REQUIREMENTS WITH LOCAL UTILITY COMPANY AND INSTALL PER THEIR REQUIREMENTS. COORDINATE CONDUIT ROUTING WITH OTHER UNDERGROUND UTILITIES.
3.
PROVIDE ONE (1) 2" CONDUIT FOR TELEPHONE SERVICE AND ONE (1) 1" CONDUIT FOR CABLE TV. COORDINATE ROUTING WITH OTHER UNDERGROUND UTILITIES.
4.
48 kW EMERGENCY GENERATOR.
5.
FLAGPOLE LIGHT FIXTURE, VERIFY FINAL LOCATION WITH OWNER.
6.
PROVIDE 1" CONDUIT MINIMUM FOR SITE LIGHTING.
7.
GRINDER PUMP, CONNECT PUMP AND COMBINATION AUDIBLE / VISUAL ALARM PER EQUIPMENT SUPPLIER SPECIFICATIONS COMPLETE AND READY FOR OPERATION.
T 3 1
LPA-13 (VIA "SLC")
#10
4
2
"SE"
4
13
1
5
"SC"
6
2
LPA-3 (VIA "SLC")
2
3
#10
(TYP.) "SF"
3 #10
13
GENERAL NOTES - MECHANICAL 4
A.
COORDINATE NEW LOW PRESSURE GAS METER PER THE LOCAL UTILITY COMPANY, MECHANICAL CONTRACTOR AND AUTHORITY HAVING JURISDICTION REQUIREMENTS. CONFIRM GAS SYSTEM REQUIREMENTS WITH THE LOCAL UTILITY COMPANY.
B.
GAS COMPANY IS RESPONSIBLE FOR THE METER AND GAS LINES UP TO METER. CONTRACTOR IS RESPONSIBLE FOR ALL GAS EQUIPMENT AFTER THE METER.
C.
GAS LINE SHOWN IS FOR REFERENCE ONLY. COORDINATE EXACT LOCATION WITH GAS COMPANY.
#
PLAN NOTES - MECHANICAL
1.
GAS MAIN EXTENSION BY LACLEDE GAS COMPANY UP TO THE GAS METER AT THE BUILDING.
2.
PROVIDE LOW PRESSURE GAS METER PER THE LOCAL UTILITY COMPANY AND AUTHORITY HAVING JURISDICTION REQUIREMENTS. PROPOSED LOAD TO BUILDING: 1,200 CFH PROPOSED DELIVERY PRESSURE: 10"-14" W.G. COORDINATE GAS SYSTEM REQUIREMENTS WITH THE LOCAL UTILITY COMPANY. PROVIDE ALL PIPING, VALVES, ASSOCIATED MATERIALS AND PRESSURE REDUCING VALVES AS REQUIRED TO PROVIDE THE PROPOSED DELIVERY PRESSURE TO THE BUILDING. PAINT ALL GAS PIPING, VALVES AND MATERIALS EXPOSED TO THE ELEMENTS WITH RUST INHIBITING PAINT TO MATCH THE COLOR OF THE BUILDING EXTERIOR. VERIFY COLOR WITH ARCHITECT PRIOR TO PAINTING. VERIFY AVAILABLE GAS SERVICE DELIVERY PRESSURE WITH UTILITY COMPANY PRIOR TO BID.
3.
3/4" GAS TO SERVE GAS GRILL ON PATIO. COORDINATE FINAL LOCATION WITH OWNER.
4.
1" GAS TO SERVE GENERATOR, COORDINATE ROUTING IN FIELD.
5
#10 3
3
2 LP-37
J
13 "SE"
#10
13 "SE"
F
7
"SF" 13
"SF" 13
GENERAL NOTES - PLUMBING
1
N SITE PLAN - MEP SCALE: 1/16" = 1'-0"
A.
PRIOR TO CONSTRUCTION OF OR CONNECTION TO ANY STORM DRAIN, SANITARY SEWER, WATER MAIN, OR ANY OTHER UTILITIES, THE CONTRACTOR SHALL EXCAVATE, VERIFY AND CALCULATE ALL POINTS OF CONNECTION AND ALL UTILITY CROSSING AND INFORM THE OWNER/DEVELOPER OF ANY CONFLICT OR REQUIRED DEVATIONS FROM THE PLAN.
#
PLAN NOTES - PLUMBING
1.
1-1/2" WATER SERVICE.
2.
4" FIRE SERVICE, SEE CIVIL DRAWINGS FOR CONTINUATION.
3.
PROVIDE OIL / SAND INTERCEPTOR, INSTALL PER MANUFACTURER'S INSTRUCTIONS. ROUTE (2) TWO 3" VENTS FROM INTERCEPTOR, SEE P2.0 FOR ADDITIONAL INFORMATION.
4.
PROPOSED FIRE DEPARTMENT SIAMESE CONNECTION.
5.
PROPOSED WATER METER LOCATION.
06-21-2017
PLAN MARK
MOUNTING
MANUFACTURER
A
W/S
METALUX
B
C/R
HALO
C
C/S
METALUX
GROUNDING BUS LOCATED IN MAIN PANEL
TO BUILDING STEEL. TYPE "VS" EXOTHERMIC WELD.
#1/0 #1/0
TYPE "GR" EXOTHERMIC WELD.
PANELBOARD SCHEDULE
LIGHTING FIXTURE SCHEDULE
TO MAIN WATER PIPE. CONNECT AHEAD OF MAIN SHUT OFF VALVE. TYPE "VN" EXOTHERMIC WELD OR LISTED GROUND CLAMP.
#6
UFER
2000
120
23
WHITE
POLES:
2PSN
SLD606830WHUNVJB
760
120
13
WHITE
FEEDER:
SEE RISER DIAGRAM
4SNLED-LD4-27SL-LW-UNV-L830-CD1-U
2732
120
25
WHITE
C/B
VOLTAGE:
D
C/S
LITHONIA
UN2-96T8-120-GEB
8550
120
118
WHITE
F
C/R
METALUX
22CZ-LD4-24-UNV-L830-CD1-U
2220
120
23
WHITE
G
W/R
GM LIGHTING
STLS-LT-W
LED
120
2
WHITE
1
20/1
H
C/R
METALUX
24CZ-LD4-40-UNV-L830-CD1-U
3941
120
34
WHITE
3
20/1
5
20/1
E0.1
1080 1080
42
C L A S S
LOAD DESCRIPTION
LOAD DESCRIPTION
C L A S S
R
REC - BEDROOM #1
REC - KITCHEN
R
R
REC - BEDROOM #2
REC - MICROWAVE
R
R
REC - BEDROOM #3
REC - FRIDGE
R
R
REC - BEDROOM #4
REC - FRIDGE
R
R
REC - RRs, CORRIDOR
REC - FRIDGE
R
R
REC - RR, CORRIDOR
REC - DINING, EXTERIOR
R
R
REC - STORAGE
REC - DISHWASHER
R
R
REC - GARAGE
REC - DISPOSAL
R
R
REC - GARAGE SHORELINE
REC - HOOD
R
R
REC - GARAGE DOOR
REC - CLOSET
R
R
REC - GARAGE DOOR
REC - CLOSET
R
R
REC - GARAGE, EXTERIOR
REC - LIVING AREA
R
R
REC - WORKOUT ROOM
REC - LIVING AREA
R
R
REC - BSMT RR, LAUNDRY
REC - LIVING AREA
R
H
F-1
F.A.C.P.
R
A2
CU-1
PAGING SYSTEM
R
A2
--
LTG - GARAGE
L
L
LTG - LIVING, DINING AREA
LTG - BEDROOMS, CORR, RRs
L
R
GRINDER PUMP
LTG - BASEMENT
L
20/1
SB
W/S
LUMARK
XTOR6BRL-W-BZ-PC1
6133
120
58
BRONZE
9
20/1
SC
UNIV
GREENLEE
(175W MH)
120
175
BLACK
11
20/1
SD
C/R
HALO
H750ICAT-ML5612835-692SC
1570
120
18
SPEC-CLEAR
13
20/1
SE
G/PL
LEOTEK
AR13-10M-MV-NW-3-DB-530
7380
120
65
DARK BRONZE
2
15
20/1
SF
G/PL
LEOTEK
AR13-10M-MV-NW-2-DB-530
7380
120
65
DARK BRONZE
2
17
20/1^
19
20/1
21
20/1
23
20/1
25
20/1
27
20/1
29
20/1
31
60/2
33
-
ORDERING NOTES:
35
20/1
1. PROVIDE FINISH TO MATCH EXTERIOR COLOR OF BUILDING; VERIFY FINISH WITH OWNER. 2. PROVIDE 20'-0" SQUARE STRAIGHT STEEL POLE.
37
20/1
39
20/1
R
SPARE
LPA
SF
ABBREVIATIONS:
41
20/1
R
SPARE
LPA
SF
W/S
SURE-LITES
UNIV
XR
SURE-LITES
UNIV
SURE-LITES
LEM2
-
LPXH7
120 120
-
SRP-25-BK
-
-
WHITE
-
120
WHITE
-
WHITE
1
GENERAL NOTES: A. ORDERING INFORMATION: THE ELECTRICAL CONTRACTOR SHALL REVIEW THE CONSTRUCTION DRAWINGS, BRANCH CIRCUIT VOLTAGE AND SUBMITTED LIGHTING FIXTURE SHOP DRAWINGS. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING THE CORRECT VOLTAGE FOR LIGHTING FIXTURES - NO EXCEPTIONS. INCORRECTLY SUBMITTED SHOP DRAWINGS AND FIXTURE ORDERS WITH THE INCORRECT FIXTURE VOLTAGE WILL NOT BE CAUSE FOR CONSTRUCTION DELAYS OR ADDITIONAL COSTS.
2
900 720 900 720 1000 1000 900 900 720 1000 3000 3000
TOTALS
750 250
10470
10330
#12 GA. SAFETY WIRE TIED TO SAFETY WIRE SUPPORT HOLES & FASTENED TO BLDG. STRUCTURE. MINIMUM (1) SAFETY WIRE AT CENTER OF FIXTURE FOR LIGHT FIXTURES LESS THAN 10 LBS. MINIMUM (2) SAFETY WIRES PLACED AT DIAGONAL CORNERS FOR LIGHT FIXTURES WEIGHING 10 LBS. OR MORE BUT LESS THAN 56 LBS.
HOUSING + 12"
VOLTAGE:
E
R TU
FIX
SEISMIC RESTRAINT CLIP MINIMUM (4) PER LIGHT FIXTURE, SECURELY AND POSITIVELY ATTACHED TO CEILING GRID, TYPICAL
EMBEDING. COORDINATE WITH GENERATOR SHOP DRAWINGS. #5 REBAR, AT 12" O.C. EA WAY, PLACED IN CENTER OF 8" SLAB
ANCHORS 8"
GRADE
SWAY BRACED GRID CEILING
NOTES: 1. SUPPORT WIRES FOR FIXTURES WEIGHING LESS THAN 56 LBS. MAY BE INSTALLED SLACK. ALL OTHER SUPPORT WIRES SHALL BE INSTALLED TAUT WITH A MINIMUM OF 3 TIGHT TURNS AROUND ITSELF. 2. LIGHT FIXTURES WEIGHING 56 LBS. OR MORE SHALL BE INDEPENDENTLY SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE, BY APPROVED HANGERS.
36"
EXCEPTION: LIGHT FIXTURES THAT ARE NOT COMPONENTS OF A STANDBY OR EMERGENCY LIGHTING SYSTEM AND WEIGH LESS THAN 20 POUNDS AND ARE POWERED USING FLEXIBLE CABLE CONNECTIONS NOT LESS THAN 3 FT. LONG CONNECTED TO THE FIXTURES, ARE NOT REQUIRED TO HAVE THE ADDITIONAL SUPPORT WIRE(S) DESCRIBED ABOVE. SUCH FIXTURES ARE REQUIRED TO BE POSITIVELY ATTACHED TO THE CEILING GRID AS DESCRIBED ABOVE.
2 1 12"
GENERATOR CONCRETE PAD DETAIL
3 E0.1
NO SCALE
LPA
DESIGNATION/I.D:
LIGHT FIXTURE SAFETY WIRE SUPPORT HOLE, TYPICAL
3 32"
120 / 240
STANDARD
TOTAL SPACE REQUIRED:
2PSN
FEEDER:
SEE RISER DIAGRAM
C/B
1
20/1
3
20/1
5
20/1
7
20/1
9
20/1
11
20/1
13
20/1
15
POWER SOURCE:
3
C
100
MAIN SWITCH:
2
20/1
4
20/1
6
20/1
8
20/1
10
20/1
12
20/1
14
20/1
16
20/1
18
20/1
20
20/1
22
20/1
24
20/1
26
20/1
28
20/1
30
20/1
32
20/1
34
20/1
36
20/1
38
100/2
40
-
42
1200 1000 1000 1000 1080 1200 500 500 360 360 900 540 900 180 180 1925 950 750 6290 6280 13360
0
CALC. DEMAND LOAD AMPERE:
TOTALS
157A
M.L.O.
MAIN RATING AIC
10k
NOTES:
30
"LP" PANEL
LOAD DESCRIPTION
LOAD DESCRIPTION
C L A S S
R
GEN - BATTERY CHARGER
WASHER
R
L
LTG - EXTERIOR
DRYER
R
L
EXTERIOR SIGNAGE
--
R
M1
EF-B
SP-1
R
H
IUH-1
WH-1
R
R
HW RECIRC PUMP
GEN - BLOCK HEATER
R
L
LTG - SITE POLES
SPARE
20/1
R
SPARE
17
20/1
R
19
20/1
21
C/B
C K T #
20/1
2
30/2
4
-
6
20/1
8
20/1
10
20/1
12
R
20/1
14
SPARE
R
20/1
16
SPARE
SPARE
R
20/1
18
R
SPARE
SPARE
R
20/1
20
20/1
R
SPARE
SPARE
R
20/1
22
23
20/1
R
SPARE
SPARE
R
20/1
24
25
20/1
R
SPARE
SPARE
R
20/1
26
27
20/1
R
SPARE
SPARE
R
20/1
28
29
20/1
R
SPARE
SPARE
R
20/1
30
TOTALS
1000 500 1000 1610 600 180 500
3100
CONNECTED LOAD: (VOLT-AMPERE)
2290
0
LOAD (WATTS)
1000 2500 2500 180 180 1500
3680 NOTES:
* PROVIDE LOCK ON DEVICE ** 10,000 A.I.C. RATING UNLESS OTHERWISE SPECIFIED
13,250VA
4180
0
CALC. DEMAND LOAD AMPERE:
TOTALS
57A
CLASS: M1=SINGLE PH MOTOR, M3=3PH MOTOR, M2=2PH MOTOR, L=LIGHTING, R=RECEPTACLE, A1=1PH A/C LOAD, A2=2PH A/C LOAD, A3=3PH A/C LOAD, H=HEATING, K=KITCHEN; XF=TRANSFORMER-PANEL; SF=SUB-FEED
RECESSED LIGHTING FIXTURE SUPPORT DETAIL NO SCALE
4
5
HOT
20/1
1080
MOUNTING: SURFACE
C L A S S
LOAD (WATTS)
"SLC"
ET
CIRCUIT BREAKER **
BUS SIZE (AMPS):
POLES:
C K T #
LUGS:
TYPE OF PANEL:
/1PH-3W
# "TC"
C K T #
CLASS: M1=SINGLE PH MOTOR, M3=3PH MOTOR, M2=2PH MOTOR, L=LIGHTING, R=RECEPTACLE, A1=1PH A/C LOAD, A2=2PH A/C LOAD, A3=3PH A/C LOAD, H=HEATING, K=KITCHEN; XF=TRANSFORMER-PANEL; SF=SUB-FEED
LI
3
* PROVIDE LOCK ON DEVICE ** 10,000 A.I.C. RATING UNLESS OTHERWISE SPECIFIED ^ GROUND FAULT BREAKER
C/B
LOAD (WATTS)
14815
48,975VA
10k
PANELBOARD SCHEDULE
T GH
HOUSING + 12"
0 NOTES:
STRUCTURE
HILTI CC27 CLIP (OR EQUAL)
MAIN RATING AIC
"ATS"
7
720
M.L.O.
NOTES:
BRONZE
RDB-175MH-120-SPV-BLR
1080
MAIN SWITCH:
26
NO SCALE
E0.1
POWER SOURCE:
1080
CONNECTED LOAD: (VOLT-AMPERE)
6" MIN.
TOTAL SPACE REQUIRED:
STANDARD
LOAD (WATTS)
200
120
GROUNDING ELECTRODE SYSTEM
2
LUGS:
MOUNTING: SURFACE
2710
C/AC CEILING AIR-CRAFT CABLE, C/CV CEILING COVE, C/P CEILING PENDANT, C/R CEILING RECESSED, C/S CEILING SURFACE, C/SP CEILING SUSPENDED, C/TK TRACK MOUNTED, F/S FLOOR SURFACE, G/P GRADE PAD, G/PL GRADE POLE, R/S ROOF SURFACE, TBD TO BE DETERMINED, U/C UNDER COUNTER, UNIV. UNIVERSAL, W/R WALL RECESSED, W/S WALL SURFACE
1
120 / 240
CIRCUIT BREAKER **
XTOR3B-W-BZ-PC1
X
5. ALL GROUNDING AND BONDING SHALL BE INSTALLED IN ACCORDANCE WITH ARTICLE 250 OF NFPA 70 THE "NATIONAL ELECTRICAL CODE".
BUS SIZE (AMPS):
2BCLED-LD4-20SL-F-UNV-L830-CD1-U
NOTES
LUMARK
NOTE: 1. EXOTHERMIC WELD DESIGNATION INDICATED ABOVE ARE ERICO "CADWELD". ALL CONNECTIONS SHALL BE EXOTHERMIC WELD OR UL LISTED MECHANICAL CONNECTIONS.
4. GROUND RODS ARE TO BE LOCATED AT SERVICE ENTRANCE WITH SIZE AS NOTED.
/1PH-3W
FINISH
C K T #
EM
3. ALL WIRING SHALL BE COPPER AND TYPE THHN/THWN GREEN INSULATION WHERE REQUIRED..
TYPE OF PANEL:
INPUT WATTS
W/S
FOUNDATION CONTRACTOR SHALL STUB-UP RE-BAR FROM FOUNDATION FOR USE BY THE E.C. TYPE "VS" CONNECTION OR APPROVED CONNECTOR. E.C. SHALL COORDINATE WITH FOUNDATION CONTRACTOR.
2. ALL GROUND BUS CONNECTIONS TO BE MADE WITH 2-HOLE COMPRESSION TYPE CONNECTORS. BUS SHALL BE INSULATED FROM ITS SUPPORT AND SHALL MAINTAIN A 2" SPACING FROM WALL.
LP
VOLTAGE
SA
#4
COPPER CLAD GROUND ROD TYPICAL, 5/8"x10'.
DESIGNATION/I.D:
LUMENS (LAMPS)
MODEL NO.
PLAN NOTES - RISER DIAGRAM 1.
PROVIDE 4" SCHEDULE 40 PVC CONDUIT FOR UTILITY COMPANY'S PRIMARY CABLES FROM EXISTING UNDERGROUND POWER TO UTILITY TRANSFORMER AS DIRECTED BY UTILITY CO. REPRESENTATIVE. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION.
2.
3 #3/0 & 1 #6 GRD, 2"C.
3.
AMEREN APPROVED NEMA 3R METERING ENCLOSURE. REFER TO AMEREN ELECTRIC SERVICE MANUAL FOR SPECIFICATIONS.
4.
200A/2PSN FUSIBLE SWITCH, 200A FUSES, NEMA 1 ENCLOSURE AND GROUNDING KIT.
TERMINAL (TYP.)
120V NEUTRAL "PC"
PROVIDE LOCK-ON DEVICE FOR C.B.
(SPARE) UTILITY XFMR
M
FROM PANEL - SEE PLANS FOR CIRCUITS TO LOADS - SEE PLANS FOR CIRCUITS ("PC" - ON, "TC" - OFF)
GENERATOR
3
5.
GRADE 1
"PC" - PHOTOCONTROL: INTERMATIC #K4121C.
LAUNDRY 003
2
"TC" - TIME CLOCK: INTERMATIC #ET-1725 WITH TWO SPST LOADS * PROGRAM TIME CLOCK PER OWNER'S DIRECTIONS
5 "ATS"
"SLC" - SITE LIGHTING CONTACTOR: ASCO #918-4-20-31, 47L, C 4 POLES, 20 AMPS, MECHANICALLY-HELD, 120 VOLT/2-WIRE CONTROL, NEMA 1 ENCLOSURE
2 4
"LP" 6
4 E0.1
LIGHTING CONTROL DIAGRAM NO SCALE
2-POLE WITH SOLID NEUTRAL IN NEMA 1 ENCLOSURE. KOHLER #: RDT-CFNA-0200 OR EQUAL.
11
5 E0.1
RISER DIAGRAM NO SCALE
BASEMENT
2
"LPA" 7
2
1 E0.1
9 10
8
6.
PANELBOARD "LP": 200A M.L.O.
7.
3 #3 & 1 #8 GRD, 1-1/4"C.
8.
PANELBOARD "LPA": 100A M.L.O.
9.
PROVIDE AND ROUTE 3 #3/0 & 1 #6 GRD, 2"C FROM "ATS" TO GENERATOR.
10. ROUTE CONTROL WIRING FROM GENERATOR TO "ATS". 11. GENERATOR SPEC: KOHLER MODEL # 48RCL WITH ALERNATOR "4Q7BX". 48 KW, 120/240V, 1PH, 3W WEATHERPROOF HOUSING, NATURAL GAS FUEL. INTEGRAL BATTERY, BATTERY CHARGER, MUFFLER, 200 AMP C/B. MOUNT GENERATOR/TANK ON CONCRETE PER DETAIL 2/E0.1. COORDINATE EXACT SIZE OF PAD WITH GENERATOR HOUSING APPROVED SUBMITTALS.
06-21-2017