Facility Planning Data Sheet 1100B Series 50 ‐ 80 kVA UPS (208‐WYE IN/208 WYE OUT)
ELECTRICAL DATA UPS RATING (KVA) 50 60 70 80 NOTES
1100B UPS MAIN INPUT DATA 1100B UPS BYPASS INPUT DATA VOLTAGE/FREQUENCY UPS INPUT BATTERY SYSTEM VOLTAGE/FREQUENCY UPS BYPASS (VAC/HZ) POWER MAXIMUM (VAC/HZ) (KVA) (KVA @ 0.99 CHARGING POWER (KW) PF) 208/60 55 3.45 208/60 50 208/60 66 4.32 208/60 60 208/60 77 4.90 208/60 70 208/60 88 5.76 208/60 80 1,2,3 4 5 6,7,8
1100B UPS OUTPUT DATA VOLTAGE/FREQUENCY UPS OUTPUT (VAC/HZ) (KVA)
208Y‐120/60 208Y‐120/60 208Y‐120/60 208Y‐120/60 9,10,11,12
1100B UPS BATTERY SYSTEM DATA FULL LOAD POWER BATTERY DISCHARGE (KW) FINAL VOLTAGE (VDC)
50 60 70 80
49 59 68 78 5
240 240 240 240
MECHANICAL DATA PHYSICAL DATA DIMENSIONS (W X D X H) INCHES
UPS RATING (KVA) 50 60 70 80 NOTES
FLOOR LOADING POINT LOADING DISTRIBUTED FLOOR LOADING (LBS/FT2) (LBS/FT2)
WEIGHT (LBS)
31.5 X 27.0 X 67.3 31.5 X 27.0 X 67.3 31.5 X 27.0 X 67.3 31.5 X 27.0 X 67.3 14
675 719 763 807
114 122 129 137
1100B UPS THERMAL DATA (UPS MODULE ONLY) HEAT REJECTION COOLING FAN AIR FLOW (KBTU/HR) (CFM) 100% 75% 50% 13.00 8.67 5.69 1,300 15.60 10.41 6.83 1,500 18.20 12.14 7.97 1,800 20.80 13.88 9.11 2,000 13 14,15
14,580 15,531 16,481 17,432
NOTES 1. Acceptable voltage range is 208 WYE VAC +15%, ‐30%. Three phase; four wire. UPS units have top or bottom entry.
12. Maximum load crest factor: 2.5.
2. UPS Reflected input current harmonics (THDi): 4% at 100% load; 7% at 50% load.
13. The specified heat losses are only for the UPS module. Peripheral equipment must be considered separately.
3. UPS main input frequency: 60Hz ± 10%.
14. Maintain clearances per the UPS installation drawing. These UPS have rear exhaust. Minimum rear clearance: 8 inches.
4. UPS input power factor: 0.98 at 100% load; 0.98 at 50% load. The UPS input power factor is independent of
15. Minimum top clearance is 16 inches.
the UPS output (load) power factor.
.
5. DC system load is non‐continuous and is based on lead acid battery systems. Consult the factory when using a non‐lead acid battery stored energy system.
.
6. Actual bypass voltage is determined by the voltage source and is not conditioned by the UPS. Three‐phase; four‐wire. 7. A neutral is required for UPS operation. 8. Bypass voltage frequency deviation limit 60Hz ± 5%, required for tracking. 9. UPS inverter output voltage regulation: 208Y 120 VAC ±1% balanced load, ±2% unbalanced load. Three‐phase, four‐wire. 10. UPS output voltage manual adjustment: ±3%. 11. UPS output total harmonic voltage distortion (THDv): 2% at 100% linear load and 5% at 100% non‐linear load.
QUESTIONS OR NEED TECHNICAL SUPPORT?
CONTACT MEPPI AT 724‐772‐2555
In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any modification(s) to the following specifications for which MEPPI has not approved or authorized such modifications. Further, MEPPI shall not be liable for any special, incidental, indirect, punitive or consequential damages arising out of or in connection with the use of such specifications.
U‐ENS00050 Rev2 07/02/2014 Page 1 of 1