Preview only show first 10 pages with watermark. For full document please download

114-92029 Fire Survival Optical Fiber Cable Description

   EMBED


Share

Transcript

Data Sheet – 114-92029 Fire Survival Optical Fiber Cable Gel filled loose tube containing up to 24, 250 µm optical fibers Rodent resistant glass yarns Inner ULSZH jacket Corrugated steel tape Outer ULSZH jacket Description: AMP NETCONNECT Fire Survival Optical Fibre Cable is for installations where signal continuity during a fire is required e.g. tunnels, subways etc. All fibers are contained within a single gel filled loose tube. The construction contains rodent resistant glass yarns, an inner Universal Low Smoke Zero Halogen (ULSZH) jacket, Corrugated Steel Tape Armour (CST) and finally an outer ULSZH jacket. Standards Compliance: IEC 60794 – Optical Fiber Cable Specifications IEC 60331-25 – Circuit integrity optical fiber cables IEC 60332 part 1 and 3C – Tests on optical fiber cables under fire conditions IEC 61034 – Smoke density IEC 60754 – Halogen acid gas emissions ISO 11801 – Generic cabling for customer premises Specification (text in brackets [ ] requires a choice): All cable constructions consist of [two, four, six, eight, twelve, sixteen or twenty-four] primary coated 250µm [singlemode, OM1, OM2, OM3, OM3+ (OM4)] fibers. All fibers are colour coded in accordance with EIA/TIA 598C and contained within a single gel filled loose tube. Rodent resistant glass yarns surround the loose tube, followed by a ULSZH inner jacket, CST armour and finally an outer ULSZH jacket. The cable is tested in accordance with IEC 60331-25: circuit integrity and is able to maintain a signal whilst being subjected to flame temperatures of 750 °C for 90 minutes, and then a subsequent cooling time of 15 minutes. 1 Datasheet 114-92029: Rev B Part Numbers: Part number 2-1716219-y 2-1716218-y 2-1716217-y 2-1716211-y 2-1716220-y 2-1716216-y Cable description 4f uni-tube, CST double ULSZH jkt 6f uni-tube, CST double ULSZH jkt 8f uni-tube, CST double ULSZH jkt 12f uni-tube, CST double ULSZH jkt 16f uni-tube, CST double ULSZH jkt 24f uni-tube, CST double ULSZH jkt Jacket colour Black Black Black Black Black Black Fibre Types: Fibre Type 9/125 50/125 50/125 50/125 50/125 62.5/125 62.5/125 Fibre Classification OS2 OM2 OM2+ OM3 OM3+ (OM4) OM1 OM1+ Suffix (y) Bandwidth OFL 4 7 6 3 2 5 9 n/a 500/500 600/1200 1500/500 3500/500 (EMB 4700/500) 200/600 250/800 Physical Properties (IEC 60794-1-2): Tensile Strength (short term) Compressive Strength Impact Torsion Temperature Range Water Penetration 700N 3000N 10Nm 5 cycles Operation: -20 to +70C Installation: -5 to +50C Storage: -20 to +70C No water at free end (inner cable only) Mechanical Properties: Nominal Diameter Nominal Cable Weight Minimum Bending Radius 12.7mm 216 kg/km Static: 180mm Dynamic: 255mm Cable Print: Cables will be marked with the following print: AMP NETCONNECT F.O. CABLE 2-xxxxxxx-y INT/EXT FIRE SURVIVAL [fibre count x fibre type] [fibre classification] [batch number] [metre mark] e.g. AMP NETCONNECT F.O. CABLE 2-1716219-3 INT/EXT FIRE SURVIVAL 4 X 50/125 OM3 [batch number] [metre mark] Shipping and Packaging: The cable will be shipped on a wooden reel. The cable shipping and billing tolerances are -0 to +10% Specifications subject to change without notice. Revised 11/2009 2 AMP NETCONNECT Regional Headquarters: North America Latin America Europe Mid East & Africa Asia Pacific Harrisburg, PA, USA Ph: +1-800-553-0938 Fx: +1-717-986-7406 Buenos Aires, Argentina Ph: +54-11-4733-2200 Fx: +54-11-4733-2282 Kessel-Lo, Belgium Ph: +32-16-35-1011 Fx: +32-16-35-2188 Cergy-Pontoise, France Ph: +33-1-3420-2122 Fx: +33-1-3420-2268 Hong Kong, China Ph: +852-2735-1628 Fx: +852-2735-1625 Sydney, Australia Ph: +61-2-9407-2600 Fx: +61-2-9407-2519 AMP NETCONNECT in Europe, Mid East, Africa and India: Austria - Vienna Ph: +43-1-90560-1204 Fx: +43-1-90560-1270 Denmark - Glostrup Ph: +45-70-15-52-00 Fx: +45-43-44-14-14 Greece/Cyprus-Athens Ph: +30-1-9370-396 Fx: +30-1-9370-655 Lithuania –Vilnius Ph: +370-5-2131-402 Fx: +370-5-2131-403 Romania - Bucharest Ph: +40-1-311-3479 Fx: +40-1-312-0574 Belgium - Kessel-Lo Ph: +32-16-35-1011 Fx: +32-16-35-2188 Finland - Helsinki Ph: +358-95-12-34-20 Fx: +358-95-12-34-250 Hungary - Budapest Ph: +36-1-289-1007 Fx: +36-1-289-1010 Russia - Moscow Ph: +7-095-926-55-06 Fx: +7-095-926-55-05 Bulgaria - Sofia Ph: +359-2-971-2152 Fx: +359-2-971-2153 France-Cergy-Pontoise Ph: +33-1-3420-2122 Fx: +33-1-3420-2268 India –Bangalore Ph: +91-80-2841-2433 Fx: +91-80-2841-2155 Netherlands - Den Bosch Ph: +31-73-6246-246 Fx: +31-73-6246-958 Norway - Nesbru Ph: +47-66-77-88-99 Fx: +47-66-77-88-55 Czech Rep.-Slov.Kurim Ph: +420-541-162-112 Fx: +420-541-162-132 Switzerland - Steinach Ph: +41-71-447-0-447 Fx: +41-71-447-0-423 Germany - Langen Ph: +49-6103-709-1547 Fx: +49-6103-709-1219 Italy - Collegno (Torino) Ph: +39-011-4012-111 Fx: +39-011-4012-268 Poland - Warsaw Ph: +48-22-4576-700 Fx: +48-22-4576-720 SwedenUpplandsVäsby Ph: +46-8-5072-5000 Fx: +46-8-5072-5001 Turkey - Istanbul Ph: +90-212-281-8181 Fx: +90-212-281-8184 Ukraine - Kiev Ph: +380-44-206-2265 Fx: +380-44-206-2264 UK - Stanmore, Middx Ph: +44-208-420-8140 Fx: +44-208-954-7467 Spain - Barcelona Ph: +34-93-291-0330 Fx: +34-93-291-0608 3