INSTALLATION
INSTRUCTIONS
2-STAGE HEAT PUMPS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS T**S
T**S*D
T**R
T**R*D
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned.
Manual : Supersedes: File: Date:
2100-554B 2100-554A Volume III Tab 16 10-12-12
Manual Page
2100-554B 1 of 14
Contents
Installation Instructions Wiring – Low Voltage Wiring ................................... 3 Operating Voltage Range ........................................ 3 Low Voltage Connection .......................................... 3
Wiring Diagram Figure 7 Heat Pump w/CS2000A* ........................ 11
Figures
Tables
Figure 1 Basic HP w/Opt. Elec. Heat .................... 5
Table 1
Diagram to Use w/Unit & Vents ............... 3
Figure 2 Opt. MFAD, CRV & ERV Vent. Pkg. w/ Programmable T-Stat .............................. 6
Table 2
Operating Voltage Range ........................ 3
Table 3
Wall Thermostat ...................................... 3
Figure 3
Heat Pump w/Opt. Economizer ............... 7
Table 4
Humidity Controls .................................... 4
Figure 4 HP w/Dehumidification Sequence & No Vent Pkg. Using T-Stat Comb ................. 8
Table 5
CO2 Controller ......................................... 4
Table 6
Thermostat Wire Size ............................. 4
Figure 5 HP w/Dehumidification Sequence & Opt. MFAD, CRV, & ERV Vent Pkg. Using Elec. T-Stat with Combination Temp. & Humidity Control ........................... 9 Figure 6 Dehum. HP w/Opt. Economizer ............ 10 Figure 7 HP w/CS2000 T**R/T**S HP Connection ............................................. 11 Figure 8 2-Stage HP w/Opt. Elec. Heat w/ ECONWM* Style Economizer ............... 12 Figure 9 2-Stage HP w/Dehum. & Opt. Elec. Heat . w/ECONWM* Style Economizer ........... 13
Manual 2100-554B Page 2 of 14
TABLE 1 DIAGRAM TO USE WITH UNIT AND VENTS
MODEL SERIES
No Vents
ER V MFAD CRV
CRVMWH-3 CHCRV-5
Economiz er "E" Vent Option
CS2000A*
T, W, S ECONWMT
VENT CODE
X
R, M, V, P
C
E
T, W, S
T**S / T**R
1
2
10
3
7
8
T**S*D / T**R*D
4
5
10
6
7
9
WIRING – LOW VOLTAGE WIRING
“W2” terminal is second stage heat (if equipped).
230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240V and 208V taps are:
“O1” terminal is the ventilation input. This terminal energizes any factory installed ventilation option.
TABLE 2
“E” terminal is the emergency heat input. This terminal energizes the emergency heat relay. “W3” terminal is the dehumidification input. This terminal energizes compressor, blower and three-way valve. 1
OPERATING VOLTAGE RANGE TAP
RANGE
240V
253 – 216
208V
220 – 187
NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
An 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in this Manual. See Table above. Low Voltage Connection
These units use a grounded 24-volt AC low voltage circuit.
LOW VOLTAGE CONNECTIONS FOR DDC CONTROL
Fan Only
Energize G
Cooling Mode 1st Stage
Energize Y, G
Cooling Mode 2nd Stage
Energize Y, Y1, G
st
Energize Y, G, B
nd
Heat Pump Heating 2 Stage
Energize Y, Y1, B, G
3rd Stage Heating w/Heat Pump (if employed)
Energize G, W2, Y, B, Y1
Ventilation
Energize G, O1
Emergency Heat
Energize B, W2, E, G
Dehumidification 1
Energize W3
Heat Pump Heating 1 Stage
1 Applies only to Models equipped for dehumidification sequence.
The “R” terminal is the hot terminal and the “C” terminal is grounded. “G” terminal is the fan input.
TABLE 3 WALL THERMOSTAT
“Y” terminal is the compressor input Stage 1. “B” terminal is the reversing valve input. The reversing valve must be energized for heating mode.
Part Number
Predominate Features
8403-060 (1120-445)
3 stage Cool; 3 stage Heat Programmable/Non-Programmable Electronic HP or Conventional Auto or Manual changeover Dehumidification Output
“R” terminal is the 24 VAC hot. “C” terminal is the 24 VAC grounded. “Y1” terminal is the compressor input Stage 2. “L” terminal is compressor lockout output. This terminal is activated on a high or low pressure trip by the electronic heat pump control. This is a 24 VAC output.
Manual 2100-554B Page 3 of 14
TABLE 4 HUMIDITY CONTROLS Part Number
8403-038 (H600A1014)
Predominate Features
SPDT switching, pilot duty 50VA @ 24V Humidity range 20-80% RH
8403-047 Electronic dehumidistat SPST closes-on-rise (H200-10-21-10) Humidity range 10-90% with adjustable stops
TABLE 5 CO2 CONTROLLER Part Number
Predominate Features
Normally Open SPST relay closes-on-rise 24V with automatic background calibration 8403-056 Default setting is 800ppm, adjustable to (C7232A1008) 1000 or 1200, on-off differential is 100ppm 0-2000ppm range, with display
8403-067
Normally Open SPST relay closes-on-rise 24V dual wave length sensor. Default setting 950ppm, adjustable to 0-2000ppm Default off setting 1000ppm, adjustable to 0-200 ppm can be calibrated
TABLE 6 THERMOSTAT WIRE SIZE
Transformer VA
55
Manual 2100-554B Page 4 of 14
FLA
Wire Gauge
Maximum Distance In Feet
2.3
20 gauge 18 gauge 16 gauge 14 gauge 12 gauge
45 60 100 160 250
FIGURE 1 BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT NO ECONOMIZER or VENTILATION PACKAGES
Thermostat Bard part #8403-060
C
G
R
Y2
Y1 O/B
24V Low Voltage Terminal Block
C
G
R
Y1
Y
MIS-2965
B
W2
Y O/D W1/E
W1 W2 W3
E
L
A
L
DH O1
Unit
Factory Installed Jumper
Manual 2100-554B Page 5 of 14
FIGURE 2 HEAT PUMP WITH OPTIONAL MFAD, CRV & ERV VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT
Low Voltage Wiring Diagram Thermostat Bard part #8403-060
C
G
R
Y1
Y2 W1/E W2 O/B
L
Y O/D
1
2
3
4
5
Electronic Programmable
A
Optional CO2 Controllers Bard part #8403-067
6
(C7232A1008) Bard part #8403-056
BLK RED YEL ORG GRN BRN Not Used
Not Used
2 24V Low Voltage Terminal Block
C
G
R
Y
Y1
E
Orange Black Black
B
L
W1 W3 DH
O1
Unit
1
Red 3
W2
CRV ERV
Brown/White Ventilation Packages Red MFAD 1 Factory Jumper Installed
MIS-2966 A
Manual 2100-554B Page 6 of 14
2 Do not connect "A" from tstat #8403-060 if optional CO2 controller is used. Connect orange wire to "G" only if 3 optional CO controller is used. 2
FIGURE 3 HEAT PUMP WITH OPTIONAL ECONOMIZER
Low Voltage Wiring Diagram
Thermostat Bard part #8403-060
C
R
O/B
24V Low Voltage Terminal Block
C
R
B
W1
W1/E
W2
L
G
E
W2
L
G
W3
Y
A
Y2
Y1 YO/D
Y1 DH O1 W3
Unit Pink
Yellow
F
Y1
Black
E
Orange
1 Blue
Black
Y2
Purple
2
3
MIS-2967 A
Economizer Wiring Harness 1 Factory Jumper Installed.
Must be configured for economizer with YO/D output to 2 be active as first stage cooling. 3 These wires are used in special control applications only.
Manual 2100-554B Page 7 of 14
FIGURE 4 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE AND NO VENTILATION PACKAGE USING THERMOSTAT #8403-060 COMBINATION TEMPERATURE & HUMIDITY CONTROLLER
Low Voltage Wiring Diagram Thermostat Bard part #8403-060
C
G
R
Y2
Y1 W1/E
C
G
R
Y1
Y
1
W2 YO/D O/B
L
A
L
O1
MIS-2968 A
24V Low Voltage Terminal Block
E
W1 W2 W3
B
DH
Factory Installed Jumper
1
Manual 2100-554B Page 8 of 14
Must be configured for "no economizer" to make YO/D output active for humidity control.
Unit
FIGURE 5 HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION PACKAGING USING ELECTRONIC THERMOSTAT WITH COMBINATION TEMPERATURE & HUMIDITY CONTROL WITH OPTIONAL CO2 CONTROLLER
2 Thermostat Bard part #8403-060
Low Voltage Wiring Diagram C
G
R
Y2
Y1 O/B W2 YO/D
A W1/E
L
3 1
2
3
4
5
Optional CO2 Controllers Bard part #8403-067
6
(C7232A1008) Bard part #8403-056
BLK RED YEL ORG GRN BRN Not Used
24V Low Voltage Terminal Block
C
G
R
Y1
Y
B
W2 W3 W1
DH
Not Used
O1
E
L
Unit
1
Red 3
Orange Black Black
MIS-2969 A
CRV ERV
Brown/White Ventilation Packages MFAD Red
1 Factory Jumper Installed Must be configured for "no economizer" to make YO/D 2 output active for humidity control. Do not connect "A" from thermostat if optional CO 3 controller is used. Connect orange wire to "G" only2 when optinal CO 2 controller is used.
Manual 2100-554B Page 9 of 14
FIGURE 6 DEHUMIDIFICATION HEAT PUMP WITH OPTIONAL ECONOMIZER
HUMIDITY CONTROLLER CONNECTIONS USED ONLY FOR OPTIONAL DEHUMIDIFICATION CIRCUIT THAT MUST BE FACTORY INSTALLED IN HEAT PUMP YELLOW 8403-038 H600A1014 HUMIDITY CONTROLLER BLUE
RED
Low Voltage Wiring Diagram
6
5
4
8403-047 H200-10-21-10 DEHUMIDSTAT
3
2 C
R
O/B
24V Low Voltage Terminal Block
C
R
B
W1
W1/E
W2
L
G
E
W2
L
G
A
Y
Y2
Y1 YO/D
Y1 DH O1 W3
Unit Pink
Yellow
F
Y1
Black
E
Orange
1 Blue
Black
Y2
Purple
Thermostat Bard part #8403-060
3
MIS-2970 A
Economizer Wiring Harness 1 Factory Jumper Installed.
Must be configured for economizer with YO/D output to 2 be active as first stage cooling. 3 These wires are used in special control applications only.
Manual 2100-554B Page 10 of 14
FIGURE 7 HP WITH CS2000 T**S/T**R HEAT PUMP CONNECTION DIAGRAM
DO NOT CONNECT "L" UNTIL AFTER 8403-060 CONTROLLER IS CONFIGURED TO CS2000 = YES YELLOW TEMPERATURE/HUMIDITY CONTROLLER BARD P/N 8403-060
R
G
C
Y1
W2
Y2 O/B
L
W1/E
8403-038 H600A1014 HUMIDITY CONTROLLER
YO/D
BLUE
RED 6
5
4
3
1 IF OPTIONAL VENT PACKAGE IS INSTALLED, THE "G" WIRE MUST BE CONNECTED TO ASSURE CONTINUOUS BLOWER DURING OCCUPIED PERIODS WHEN VENT SYSTEM IS "ON". THE "G" WIRE MUST ALSO BE CONNECTED FOR PRE-PURGE OPERATION (SEE STEP 2, FUNCTION SWITCH SETTINGS). BARD VENTILATION PACKAGE (OPTIONAL) NOTE: IF FACTORY INSTALLED DISCONNECT AND TAPE RED AND ORANGE WIRES R
01
C
R
G
Y
Y1
W1 W2
B
L
E
W3
HUMIDITY CONTROLLER CONNECTIONS USED ONLY FOR OPTIONAL DEHUMIDIFICATION CIRCUIT THAT MUST BE FACTORY INSTALLED IN HEAT PUMP
WERV OR CRV
NC C VENT
BR/W
OPTIONAL LIGHTING CONTROL
NO C
NC
PWR
C
NC
HVAC FAN
FACTORY JUMPER - SEE SEARCH TIME DETAIL ON PAGE 3
AREA OCCUP. REM + NO C NC -
+
-
+
PWR PRECOND DOOR
NO C NC HVAC
LIGHTING CONTROL RELAY NORMALLY CLOSED CONTACTS
MANUAL SWITCH FIELD SUPPLIED
LIGHTS
UNIT 24V TERMINALS
1 BK
O
2
8403-047 H200-10-21-10 DEHUMIDSTAT
MAN. OVERIDE (24 HRS)
REMOTE MOTION DETECTOR (OPTIONAL) NORMALLY OPEN CONTACTS
CS2000A2 ENERGY MONITOR
1
JUMPER IS FACTORY INSTALLED.
2
LIGHTING CONTROL CIRCUIT IS OPTIONAL AND FIELD SUPPLIED. LIGHTING CONTROL RELAY REQUIRES NORMALLY CLOSED CONTACTS AND MUST BE SIZED ACCORDING TO CONTROLLED LOAD.
RECOMMENDED SWITCH SETTINGS SHOWN BELOW FUNCTION SWITCHES LEARN PRE P MODE RATE SEARCH-TIME N/C STAGE AUX DEMAND 2 DEMAND 1
TEMPERATURE SWITCHES
90 84 81 78 68 65 62 58 54 48 4093-154
Manual 2100-554B Page 11 of 14
FIGURE 8 2-STAGE HEAT PUMP WITH OPTIONAL ELECTRIC HEAT WITH ECONWM STYLE ECONOMIZER
Low Voltage Wiring Diagram
C
R
B
Red
W1
W2
L
G
E
W2
L
G
Brown/white Orange
3
Y2
Y1
A
Y1 YO/D
Y
DH O1 W3
1
Purple
24V Low Voltage Terminal Block
W1/E
Pink
O/B
Yellow/red
R
Yellow
C
Blue
Thermostat part #8403-060
Black
2
Economizer Wiring Harness 1
Must be energized to enable minimum position. NOTE: Economizer Control Default Setting is 10V (100%). Depending upon application may require setting to lower value.
2
Must be configured for heat pump and economizer to enable YO/D output to be active as 1st-stage cooling
3
Factory Jumper Installed. MIS-2982 A
Manual 2100-554B Page 12 of 14
FIGURE 9 2-STAGE HEAT PUMP WITH DEHUMIDIFICATION & OPTIONAL ELECTRIC HEAT WITH ECONWM STYLE ECONOMIZER
Low Voltage Wiring Diagram
C
R
B
Red
W1
W2
L
G
E
W2
L
G
Y1
Y
DH O1 W3
Brown/white Orange
3
A YO/D
1
Y2
Y1
Purple
24V Low Voltage Terminal Block
W1/E
Pink
O/B
Yellow/red
R
Yellow
C
Blue
Thermostat part #8403-060
Black
2
Economizer Wiring Harness 1
Must be energized to enable minimum position. NOTE: Economizer Control Default Setting is 10V (100%). Depending upon application may require setting to lower value.
2
Must be configured for heat pump to enable YO/D output to be active dehumidification output
3
Factory Jumper Installed. MIS-2999
Manual 2100-554B Page 13 of 14
FIGURE 10 2-STAGE HEAT PUMP WITH CHCRV-5 OR CRVMWH-3 VENT OPTION PACKAGE WITH PROGRAMMABLE THERMOSTAT
Low Voltage Wiring Diagram
4 Thermostat Bard part #8403-060
C
G
R
Y1
Y2 W1/E W2 O/B
L
Y O/D
A
3 1
2
3
4
5
Electronic Programmable Optional CO2 Controllers Bard part #8403-067
6
(C7232A1008) Bard part #8403-056
BLK RED YEL ORG GRN BRN Not Used
Not Used
2 24V Low Voltage Terminal Block
C
G
Black
R
Y
Y1
E
W2
Purple Yellow Red CHCRV-5 OR CRVMWH-3 Ventilation Package
MIS-3135
B
W1 W3 DH
L
O1
Unit
1 Orange
1 Factory Jumper Installed 2 Do not connect "A" from tstat #8403-060 if optional CO2 controller is used. 3 Wire only needed for dehumidification units Must be configured to programmable and fan 4 set to programmed for the "A" output to function during scheduled occupied periods
Manual 2100-554B Page 14 of 14