Transcript
Cassette Type
Compact but Powerful 2Way Cassette is a perfect fit for long and narrow places with limited installation space, thanks to its compact and slim size. The unit operates with air coming out from two sides, providing powerful and fast cooling and heating performance to create a pleasant environment for you.
Compact but Powerful 2Way Cassette Ideal for Long and Narrow Places
Features With its slim and compact size, 2Way Cassette indoor unit is ideal air solution for long and narrow places such as corridor and classroom. This unit saves space up to 30% compared to conventional 4Way cassette as well as blends into the interior design. Indoor units
Small Size, Big Performance 2Way Cassette indoor unit is now 45% smaller than our competitor’s models, making it even easier to incorporate into building design.
45%
Decreased
305mm 600mm
230mm 1,180mm
Conventional
575mm
890mm
2Way Cassette
Twin Cross Flow Fan Cross Flow Fans
2Way Cassette type unit is a perfect fit for long and narrow rectangular spaces. The Twin Cross Flow Fan inside 2Way Cassette will spread cool or warm air even further and wider with less noise.
Standard formula for Easy Installation The dimensions of 2Way Cassette air conditioner allow for easy installation into standard ceiling grids (600Wx600D) in such a way that everything just falls into place.
600mm
650mm
1030mm
600mm
56
2013 SAMSUNG System Air Conditioners
57
2
2 way cassette 2-1. Specifications 1) Technical specifications Model Power Supply Mode*1) Capacity Performance (Nominal)
Power
Cooling*2) Heating*3)
*2) Power Input Cooling (Nominal) Heating*3) *2) Current Input Cooling (Nominal) Heating*3)
Fan
7.1
Btu/h
19,100
24,200
kW
6.3
8.0
Btu/h
21,500
27,300
70
75
W A
70
75
0.38
0.40
Output
W
14
14
Number of unit
EA
2
2
CMM
14 / 13 / 12
15 / 14 / 13
Min / Std / Max
l/s
233.33/216.67/200.00
250.00/233.33/216.67
mmAq
-
-
Pa
-
-
WG
-
-
-
012044-115561-203838-330010
012044-115582-204747-330010 9.52
Ø, mm
6.35
Ø, inch
1/4
3/8
Ø, mm
12.70
15.88
Ø, inch
1/2
5/8
Ø, mm
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
mm2
1.5 / 2.5
1.5 / 2.5
mm2
0.75~1.5
0.75~1.5
Type
-
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
Drain Pipe Power Source Wire
Below 20m / over 20m
Transmission Cable
Sound Pressure
High / Mid / Low*4)
dBA
38 / 37 / 35
41 / 39 / 37
Net Weight
kg
21.00
22.00
Shipping Weight
kg
25.00
26.00
mm
890 x 230 x 575
890 x 230 x 575
mm
1,077 x 299 x 642
1,077 x 299 x 642
-
PC2NUSMEN
PC2NUSMEN
Panel Net Weight
kg
4.00
4.00
Shipping Weight
kg
8.00
8.00
Net Dimensions (W×H×D)
mm
1030 x 25 x 650
1030 x 25 x 650
Shipping Dimensions (W×H×D)
mm
1103 x 151 x 727
1103 x 151 x 727
- / Model
Built-in
Built-in
mm/liter/h
750 / 24
750 / 24
-
Long life filter
Long life filter
Dimensions Net Dimensions (W×H×D) Shipping Dimensions (W×H×D) Panel model
Panel Size
5.6
0.40
Piping Connections Gas Pipe
Sound
HP/HR
kW
Crossflow Fan
Liquid Pipe
Refrigerant
HP/HR
0.38
Option Code
Field Wiring
1, 2, 220-240, 50
-
Crossflow Fan
Air Flow Rate H/M/L (UL) External Pressure
AM071FN2DEH✴✴✴
1, 2, 220-240, 50
-
Type Motor
AM056FN2DEH✴✴✴ Ø, #, V, Hz
Drain pump Additional Drain pump Accessories Air Filter
Max. lifting Height / Displacement
* Specifications may be subject to change without prior notice for product improvement. *1) Mode - HP : Heat Pump, HR : Heat Recovery *2) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m *3) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m *4) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
24
2-2. Capacity tables 1) Cooling
TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Outdoor temperature (ºC, DB)
056
10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
071
20 (ºC, DB) 14 (ºC, WB) TC SHC 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 3.1 3.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9 4.0 4.9
23 (ºC, DB) 16 (ºC, WB) TC SHC 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 3.4 4.6 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8 4.4 5.8
26 (ºC, DB) 18 (ºC, WB) TC SHC 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 3.8 5.3 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7 4.9 6.7
28 (ºC, DB) 20 (ºC, WB) TC SHC 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 3.8 5.8 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 5.0 7.4 4.9 7.3 4.9 7.3
2) Heating Model
056
071
30 (ºC, DB) 22 (ºC, WB) TC SHC 3.8 6.3 3.8 6.3 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.8 6.2 3.7 6.1 3.7 6.1 5.1 8.0 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 5.0 7.9 4.9 7.8 4.8 7.7
32 (ºC, DB) 24 (ºC, WB) TC SHC 6.7 3.7 6.7 3.7 6.7 3.7 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.6 3.6 6.5 3.5 6.4 3.4 4.8 8.5 4.8 8.5 4.8 8.5 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.7 8.4 4.6 8.2 4.5 8.1
TC : Total Capacity(kW) Outdoor temperature (ºC) DB -20 -17 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -20 -17 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15
WB -21 -18 -16 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -21 -18 -16 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14
Indoor temperature (ºC, DB) 16.0 TC kW 3.9 4.0 4.2 4.4 4.6 4.9 5.2 5.4 5.7 5.9 6.2 6.5 6.7 6.9 7.1 7.3 4.9 5.1 5.3 5.6 5.9 6.2 6.5 6.9 7.2 7.6 7.9 8.2 8.5 8.7 9.0 9.2
18.0 TC kW 3.8 4.0 4.1 4.3 4.6 4.8 5.1 5.3 5.6 5.9 6.1 6.4 6.5 6.6 6.7 6.8 4.9 5.0 5.2 5.5 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.1 8.2 8.4 8.5 8.6
20.0 TC kW 3.8 3.9 4.0 4.2 4.5 4.8 5.0 5.3 5.5 5.8 6.0 6.3 6.3 6.3 6.3 6.3 4.8 4.9 5.1 5.4 5.7 6.0 6.4 6.7 7.0 7.3 7.7 8.0 8.0 8.0 8.0 8.0
22.0 TC kW 3.7 3.8 3.9 4.2 4.4 4.7 4.9 5.1 5.3 5.6 5.7 5.8 5.8 5.8 5.8 5.8 4.7 4.8 4.9 5.3 5.6 5.9 6.2 6.4 6.7 7.1 7.2 7.4 7.4 7.4 7.4 7.4
24.0 TC kW 3.7 3.8 3.8 4.1 4.4 4.5 4.7 4.9 5.0 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.7 4.8 4.8 5.2 5.6 5.8 6.0 6.2 6.4 6.8 6.8 6.8 6.8 6.8 6.8 6.8
25
Indoor units
Model
Indoor temperature (ºC, WB) 27 (ºC, DB) 19 (ºC, WB) TC SHC 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 3.8 5.6 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1 5.1 7.1
2
2 way cassette 2-3. Dimensional drawing
Unit:mm
Suspension bolts(M8~M10) X 4EA
3
2
1
4
7
5
6
No.
Name
1
Liquid pipe connection Gas pipe connection Drain pipe connection Conduit for power supply & communication wiring Air inlet grille Air outlet louver Fresh air intake
2 3 4 5 6 7
26
Description 5.6kW 7.1kW Ø6.35 Flare Ø9.52 Flare Ø12.70 Flare Ø15.88 Flare VP25 (OD 32, ID 25)
-
2
2 way cassette 2-5. Sound pressure level 1) Operation sound level
Unit : dB(A)
1.5m
Model
High
Low
AM056FN2DEH✴✴✴
38
35
AM071FN2DEH✴✴✴
41
37
Microphone
Note These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed. Operation sound level may differ depending on operation and ambient conditions.
2) NC curves (1) AM056FN2DEH✴✴✴
(2) AM071FN2DEH✴✴✴
45
45 NC 45 NC 40
HIGH
35 30
NC 35
LOW
NC 30
25 NC 25
20
NC 20
15
NC 15
10 5
63
125
250
500
1000
2000
4000
Octave band center frequency(Hz)
28
8000
40
Sound pressure level (dB)
Sound pressure level (dB)
40
NC 45 HIGH
NC 40
35 NC 35
LOW
30 NC 30
25 NC 25
20
NC 20
15
NC 15
10 5
63
125
250
500
1000
2000
4000
Octave band center frequency(Hz)
8000
2-6. Temperature and air flow distribution 1) AM071FN2DEH✴✴✴ (1) Cooling air velocity distribution
Discharge angle : 54°
Ceiling height
3m
2m 0.8m/s
0.8m/s
4m
2m
3m
1m
0.6m/s
0.4m/s
0.4m/s
0.4m/s
1m
1m 0m Floor distance
0.4m/s
2m
4m
Discharge angle : 54° 20
3m
20
25
25
24
Ceiling height
0.2m/s
3m
(2) Cooling temperature distribution
24
21
24
21
24
22
1m
23
23
2m
3m
2m
22
23
4m
Indoor units
0.6m/s 0.2m/s
23
1m
1m 0m Floor distance
2m
3m
(3) Heating air velocity distribution
4m
Discharge angle : 54° 3m 0.2m/s
Ceiling height
0.2m/s 0.8m/s
2m
0.8m/s
0.8m/s
0.8m/s
0.4m/s
0.4m/s
0.2m/s
4m
2m
3m
1m
0.2m/s
1m
1m 0m Floor distance
2m
3m
(4) Heating temperature distribution
4m
Discharge angle : 54° 3m 33
33 0.4m/s
Ceiling height
31
29
31
2m 29
25
25 27
3m
2m
1m
27
23
4m
0.2m/s
23
1m
1m 0m Floor distance
2m
3m
4m
2928 34