Transcript
REV-2
hydronics 2
O
O
6
design supply support
10 Industrial Parkway
Woburn, MA 01801
Tel. 781-721-0303
www.CapcoSupply.com
Fax 781-721-9119
TABLE OF CONTENTS 2006 HYDRONICS BOOK REV.2 Page# Tekmar 152 Dual Domestic Water Heaters………………………….......... 3 Tekmar 260 Basic…………………………………………………………….. 4 Tekmar 264 Dual Boiler and Pumps…………………………………… ….. 5 Tekmar 360 Basic Radiant Add On…………………………………………. 6 Tekmar 360 Quick Set Up……………………………………………………. 7-9 Tekmar 360 with Taco SR and Thermostats………………………………. 10 Tekmar 360 with Taco ZVC and Thermostats……………………………… 11 Tekmar 363 with Taco ZVC and SR Control……………………………….. 12 Tekmar 374 with Taco ZVC and Thermostats……………………………… 13 Tekmar 374 with Taco ZVC and Thermostats Piping……………………… 14 Tekmar tN4 Adding A Transformer For Additional VA…………………….. 15 Tekmar tN4 Adding A Zone Valve To A 335……………………………….. 16 Basic Snowmelt………………………………………………………………… 17 Tekmar 664 Snowmelt………………………………………………………... 18 501 Control Match……………………………………………………………… 19 Buderus Mixing Station Tekmar 363…………………………………………. 20 Buderus Mixing Station Tekmar 360…………………………………………. 21 Unico Control Box New Style…………………………………………………. 22 UniChiller Piping………………………………………………………………… 23 Roth Tank………………………………………………………………………. 24 Vitotronic 200 & 300 Cheat Sheet……………………………………………. 25 Vitotronic 200 Accessing service levels……………………………………… 26 Vitoronic 200 with Zone Controls……………………………………………… 27 Viessmann Combustion Air Controls…………………………………………. 28 Viessmann Double 41 with Tjernlund UC-1………………………………….. 29 Vitodens Contols………………………………………………………………… 30 Viessmann Vitotronic 100 KW10 DHW……………………………………… 31 Harvey Glycol……………………………………………………………………. 32-33 Water / Glycol Mixture…………………………………………………………… 34 Glycol System Fill Assembly…………………………………………………… 35 Axiom Hydronic System Feeder………………………………………………. 36-37 Pumping Basics…………………………………………………………………. 38-40 Grundfos UPS1558 Pump Chart………………………………………………. 41 Grundfos Pumps………………………………………………………………… 42-44 Viega Pex Pressure Drop Chart………………………………………………. 45-47 FlatPlate Snowmelt Specifications……………………………………………. 48 FlatPlate Swimming Pools and Spas Selection……………………………… 49-50 Viega Diverting Valve…………………………………………………………… 51-52 Tekmar 3-way Mixing Valve Sizing…………………………………………… 53-54 Tekmar 4-way Mixing Valve Sizing …………………………………………… 55-56 Viessmann 3-way & 4-way Mixing Valve Sizing……………………………… 57-58 Caleffi Hydronic Separator……………………………………………………… 59-61 Buderus Quick-Fit Modular Piping System…………………………………… 62-63 Buderus Mixing Station Instructions…………………………………………… 64-65 Taco I Series Radiant Mixing Valve………………………………………….. 66-68 Taco Radiant Mixing Block…………………………………………………….. 69-71 GB 142 Modulation Of A Single Unit………………………………………….. 72 GB 142 Modulation Of Two Units……………………………………………… 73 GB 142 Modulation Of Three Units……………………………………………..74
2 Sensors
Off
On
C-
2
4
Relay 1
3
24 VAC POWER
R+
Power
1
10A
FACTORY INSTALLED TRANSFORMER
6
Sen
ZONE 1
120V AC
JUMPERS
DHW Pump 1
X2 N P ZC H X1 ZR
FUSE 1 AMP
Sen
S2
S1
Com Sen
9
8
7
ZONE 2
ZONE 1
DHW Pump 2
ZONE 2
ZONE 3
ZONE 3
TWO ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
152 No Power
SR 502
Relay 2
5
10A
781-721-0303
DHW 2
DHW Sensor 2
MDF 3/3/2006 THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
DUAL DHW TANKS/ TEKMAR
WWW.CAPCOSUPPLY.COM
ENERGY SUPPLY, INC. FAX 781-721-9119 10 INDUSTRIAL PARKWAY WOBURN MA 01801
POWER ZONE 1 ZONE 2
DHW 1
DHW Sensor 1
24 VAC POWE R
SLAVE
MASTER
FUSE 1 AMP
FACTORY INSTALLED TRANSFORMER
X
END SWITCH
X
RESET
ZC ZR
NORMAL
PLUG IN CARDS
ZONE 2 ZONE 3
ZONE 2 ZONE 3
EXISTING CIRCULATORS
120 VOLT CIRCULATORS
ZONE 1
120 VAC
INPUT
POWER
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 1
SR 503 EXP
OFF
ZONE 3 PRIORITY ON
N
120 VAC
L
6
Power
5
10A
P1
Boil
7
10A
Pmp/Vlv
DHW
KK10
Sw
Out
Com
TK 260 BASIC
Indr
OUTDOOR
BOILER SUPPLY
Boil
MCB 9/23/03 THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
64 CAMBRIDGE ST BURLINGTON MA 01803
260 13 14 15 16 17 18
Do not apply power
UnO Com
X2.1 X2.2 X2.3
Boiler
9 10 11 12
DHW PUMP
N
8
10A
ENERGY SUPPLY, INC. FAX 781-272-0514 WWW.CAPCOSUPPLY.COM
DHW AQUA STAT
Demand
4
Demand
3 DHW
2
Boiler
1
781-272-0020
POWER ZONE 1 ZONE 2 ZONE 3
Ret
Sup
KK10
Dem
Boil
6
X2.1 X2.2 X2.3
Sw
UnO
5
KK10
Out
4
X2.1 X2.2 X2.3
P1
Boil
Boil
Com
3
2
1
264
Dem
Com
7
L
120V AC
N
10
Power
9
P2
Dem
Setp
8
5A
P1
Prim
11
Alarm
C A L E F F I
13
C.A. /
12
5A
1
1
15
Relay
14
5A
P1
2
2
17
Relay
16
5A
3
4
To System
P2
4
21
Relay
20
5A
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL TEKMAR 264 MCB2/14/05 PARKWAY WITH CALEFFI WOBURN MA 01801
3
19
Relay
18
5A
120V (ac)
L
C
Class II Transformer 24V (ac)
N
R
R W T T COM
24 VAC
4 4 6 6 5 N H 3 N/O N/C N/C N/O
120 VAC INPUT
1 ZONE SWITCHING RELAY
SR501
T8400B
POWER T STAT
1 Mixing Demand
2
L
3 Power Pmp
Sys
5
N
6
System Pump & Mixed Pump
N
4
10A
7
1 Opn
Opn
R
9
Com
2
Cls
R
10
781-272-0020
8
Sw
UnO
12 Boil
14 Mix
15
Indoor Sensor
Outdoor Sensor
Mix Sensor
Com
13
Do not apply power
Com
16
Out
17
Indr
18
360
MDF 3/8/2006 THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
Basic Radiant Add
ENERGY SUPPLY, INC. FAX 781-272-0514 WWW.CAPCOSUPPLY.COM
C
11
Cls
3
Powered Output
10 Industrial Parkway Woburn, Ma. 01801
Boiler
10A
360 QUICK SET UP Select “VIEW” from the Menu
DISPLAY OUTDOOR VIEW
ROOM VIEW
MIX VIEW
MIX TARGET VIEW BOIL VIEW
DESCRIPTION Current outdoor air temperature as measured by the outdoor sensor. This is also the default display for the control.. (outdr dsgn off) Current room air temperature as measured by the indoor sensor. (Indoor sensor is present) Current mixed supply water temperature as measured by the mixing sensor. Target mixed supply is the temperature the control is currently trying to maintain at the mixing sensor. Current boiler temperature as measured by the boiler sensor. (Boiler sensor is present)
RANGE -67 to 149 F -55 to 65 C
23 to 113 F -5 to 45 C 14 to 266 F -10 to 130 C 14 to 266 F -10 to 130 C 14 to 266 F -10 to 130 C
Dip switches - Advance 30% enable boiler sensor = supply.
To Select ”adjust” Menu - press item, up, and down buttons at once for 2 seconds.
In the “ADJUST” Menu, changes may be made to the systems operating parameters ROOM ADJUST OCCUPIED
ROOM ADJUST UNOCCUPIED
MIX TARGET ADJUST OUTDOOR DSGN ADJUST
TERMINAL UNIT ADJUST
INDOOR MIX ADJUST
MIX DSGN ADJUST
The desired room air temperature during an occupied (Day) period. (OUTDR DSGN OFF) The desired room air temperature during an unoccupied (Night) period. (OUTDR DSGN OFF) Mixing setpoint temperature (OUTDR DSGN OFF) The design outdoor air temperature used in the heat loss calculation for the heating system. For setpoint operation, set the (OUTDR DSGN to OFF.) The type of terminal units that are being used in the heating system. (OUTDR DSGN OFF)
The design indoor air temperature used in the heat loss calculation for the heating system. (OUTDR DSGN OFF) The design supply water temperature used in the heat loss calculation for the heating system. (OUTDR DSGN OFF)
35 to 100 F 2 to 38 C
35 to 100 F 2 to 38 C
60 to 200 F 16 to 93 C -60 to 32 F OFF -51 to C OFF
1:High Mass Radiant 2:low Mass Radiant 3:Fancoil 4:Fin-tube Convenctor 5:Radiator 6:Baseboard 35 to 100 F 2 to 38 C
70 to 220 F 21 to 104 C
MIX MAX ADJUST
The maximum supply temperature for the mixing system. (OUTDR DSGN OFF)
80 to 210 F 27 to 99 C
ADJUST Menu Continued DISPLAY MOTOR SPEED ADJUST MIX MIN ADJUST
BOIL MIN ADJUST
BOIL DIFF ADJUST
WWSD OCCUPIED ADJUST WWSD UNOCCUPIED ADJUST ADJUST
ESC ADJUST
DESCRIPTION
RANGE
The time that the actuating motor requires to operate from fully closed to fully open. The minimum supply temperature for the mixing system. (OUTDR DSGNOFF) The minimum temperature allowed for the boiler target temperature. (Boiler sensor is present) The differential that the control is to use when it is operating the boiler. (Boiler Sensor DIP switch = Supply and boiler sensor is present) The system’s warm weather shut down during the occupied (Day) period. The system’s warm weather shut down during the Unoccupied (Night) period. The units of measure that all of the temperatures are to be displayed in the control. This item exits the ADJUST menu by pressing either the Ń or Ņ button.
30 to 230 seconds (1 sec. incr.) OFF 35 to 150 F OFF 2 to 65C Off 80 to 180 F Off 27 to 82 C
Ad 2 to 42 F Ad -17 to 6 C
35 to 100 F Off 2 to 38 C Off 35 to 100 F Off 2 to 38 C Off F C
RECOM. SET
2
R
1
C
3
4
MASTER
POWER CONTROL INTERFACE
SLAVE
Heat
2A
1234
FUSE 1 AMP
24 VAC POWER
FACTORY INSTALLED TRANSFORMER
507
C
R
Com
3
5 7
ZONE 2
Heat 1
6
2A
ZR
ZONE 3
P3
120V AC
INPUT
To Existing Boiler
P4
120 VOLT CIRCULATORS
POWER
SR 503 EXP ZONE 1 ZONE 2 ZONE 3
P2
ZONE 3 PRIORITY
3
ON OFF
POWER ZONE 1 ZONE 2 ZONE 3
P1
P2
120V AC
N
4
Power
2
L
W
1
10A
Mixing RH
Erie T201
Demand
Installer / User
Cool
9
2 Stage / Heat - Cool
Heat 2/
8
2A
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 1
S2
JUMPER
X END ZC SWITCH
X
S1
4
NORMAL
120V RELAY
RESET
PLUG IN CARDS
2
1
512
P1
P3
Pmp
Sys
5
N
6
P4
8
Cls
R
C
10 11
Opn
1
2 C
Mix
Com
Out
3 Cls
2
2
H5
H5
03/03/04 JEH THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
360 WITH SR503 AND STATS
WWW.CAPCOSUPPLY.COM
2
Indr
H5
Indoor Sensor
Outdoor Sensor
Boil
Com
Com
ENERGY SUPPLY, INC.
Sw
UnO
FAX 781-272-0514 64 CAMBRIDGE ST BURLINGTON MA 01803
360 12 13 14 15 16 17 18
CA PC O
Opn
R
9
Powered Output
781-272-0020
MIX SENSOR
Boiler
7
10A
M
2
R
1
C
Factory Installed Transformer
3
Heat
2A
4
END SWITCH
N/O
COM
N/C
C
R
FUSE (5 AMP MAX)
2
1
512
T
2
3
4
4
S1
ZONE 1
PH
1
ZONE 1
T
Com
3
T
T
ZVC 403
ZONE 2
7
Heat 1
6
2
3
ZONE 2
Three wire zone valve
3
2
1
1
4
THREE ZONE ZONE VALVE CONTROL
S2
5
2A
T
T
2
3
ZONE 3 4
Four wire zone valve
1 2 3 4
1
Tstat 1 Valve 1 Tstat 2 Valve 2 Tstat 3 Valve 3 Power
120V AC
N
4
Power
3
L
W
2
Mixing RH
1
10A
Demand
9
Erie T201
Cool
2A
Installer / User
Heat 2/
8
ZONE 3
EndSw Motor
507 2 Stage / Heat - Cool
POWER IN
P1
Pmp
Sys
5
7 Boiler
8
2 Com
1
Cls
R
Cls
3
C
10 11
Opn
Opn
R
9
Powered Output
Sw
UnO
Com
Mix
Com
Out
MIX SENSOR
Indoor Sensor
Outdoor Sensor
Boil
Indr
12 13 14 15 16 17 18
360
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL 360 WITH MDF 3/4/2006 PARKWAY SR503 WOBURN MA 01801 AND STATS
N
6
10A
MASTER
Setp/
DHW
Boil
5
Dem
4
SLAVE
Com
Dem
Mix
3
Demand
2
FUSE 1 AMP
24 VAC
Power
L
7
P1
Boil
8
X X E. S. ZC
RESET
DHW
T T ZONE 1
7.5A
T T ZONE 3
ES B
RESET
Var
Cls/
Opn Com C Cls
1 2 3
Opn
NORMAL
T T ZONE 4
Com
2
3
tN2
tN1/
4
T T ZONE 6
ES A
120V AC
7 A
F U S E
Com 1
10K
PH
ON OFF
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
PH
S2
Boil
T T ZONE 3
S3
Out
T T ZONE 4
T T ZONE 5
PH
PH
Taco Zone Valve
ZONE 5 1 2 3 4
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
03/05/06 MDF
WWW.CAPCOSUPPLY.COM BASIC 363
FAX 781-272-0514 10 Industrial Parkway Woburn, Ma. 01801
781-272-0020
E R I E
ZONE 6 1 2 3 4
ENERGY SUPPLY, INC.
ZONE 4 1 2 3 4
T T ZONE 6
CA PC O
ZONE 3 1 2 3 4
ZVC 406 EXP SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T T ZONE 2
S1
Mix
ZONE 2 1 2 3 4
Com
T T ZONE 1
Sw
UnO
ZONE 1 1 2 3 4
ZONE 6 PRIORITY
EXPANSION
1
2
10K
SR 506-EXP
T T ZONE 5
NO COM NC ZONE 6 REL
MODE
363 17 18 19 20 21 22 23 24 25 26
120V
2.4A
SLAVE POWER CONTROLS MASTER
Mix
Pwr
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
T T ZONE 2
Boiler
12 13 14 15 16
7.5A
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 POWER 120 VOLT CIRCULATORS INPUT
NORMAL
ZR
P2
Mix
10 11
7.5A
Pmp/Vlv
9
PLUG-IN CARDS
120V AC
N
6
7.5A
TACO, INC ZVC406-EXP
1
FACTORY INSTALLED TRANSFORMER
FACTORY INSTALLED TRANSFORMER FACTORY INSTALLED TRANSFORMER
POWER IN
Mix
Pwr
3
2
Opn
4
5A
L
N
R
Var2
Cls2
5
2.5A
C
Class II Transformer 24V (ac)
Cls
120V (ac)
Com
Opn
1
3
Cls1
Var1
Opn
2
2
1
1
2.5A
5A
6
3
8
Boil
7
Com
MASTER
Sw
UnO
Cls
SLAVE
2
Com
1
Opn
FUSE 1 AMP
24 VAC
374
S2
Com
10
X X E. S. ZC
RESET
PLUG-IN CARDS
S1
Out
9
Do not apply power
T T ZONE 3
Power
T T ZONE 4
L
14
0
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
T T ZONE 2
P2
Mix1
13
N
P3
Mix2
17
T T ZONE 5
T T ZONE 6 POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
(Low)
Stage 1/
5A
24
(High)
Setp Enbl.
Stage 2/
23
Low/High Fire Boiler
22
Boil Enbl.
21
DHW
20
5A
Pmp/Vlv
19
5A
ZONE 6 PRIORITY ON OFF
N
18
HIGH TEMP
P1
Prim
16
5A
SR 506-EXP
15
5A
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 POWER 120 VOLT CIRCULATORS INPUT
NORMA L
ZR
S4
S3
Mix2
12
T T ZONE 1
Mix1
11
5A
Dem
Mix1
25
Dem
Com
26
Dem
Mix2
27
D H W A Q U A S T A T
Dem
Setp
28
Dem
DHW
29
Dem
Boil
30
Dem
Com
31
ES
RESET
3 A
F U S E
3 A
F U S E
T T ZONE 2
T T ZONE 3
T T ZONE 2
E R I E
ZONE 2 1 2 3 4
T T ZONE 3
E R I E
E R I E
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
THREE ZONE ZONE VALVE CONTROL
ZONE 1 1 2 3 4
MIX 2
MIX 1
ZONE 3 1 2 3 4
ZVC 403
T T ZONE 1
E R I E
ZONE 1 1 2 3 4
THREE ZONE ZONE VALVE CONTROL
ZVC 403
T T ZONE 1
T 8400 B Heat Only
MB 9/15/05
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 POWER
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 POWER
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
374 WIRING
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM
NO COM NC
NO COM NC
10 INDUSTRIAL PARKWAY WOBURN MA 01801
781-721-0303
E S
RESET
POWER IN
FACTORY INSTALLED TRANSFORM ER
FACTORY INSTALLED TRANSFORMER
FACTORY INSTALLED TRANSFORME R
POWER IN
SX40V
P-1 P-3
P-4
Panel Radiators
Tile Floor Radiant
Tekmar 374 Piping
MDF 2/13/2006 THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
10 INDUSTRIAL PARKWAY WOBURN MA 01801
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM
BUDERUS “ QUICK HEADER” JUNCTION MANIFOLD
781-721-0303
P-2
Wood Floor Radiant
C
Wiring instructions for adding a transformer to Zone Manager in the event of the need for more VA (watts of power) from the Transformer.
R
A
B
544
544 To isolate relay, cut jumper
To isolate relay, cut jumper
No Power
G1
tN4
C
Pmp
tN4
A
tNt
3
4
Zn Grp A
1
2
G1
Rc
C
Y1
R
Com
W
Zone A1
5
6
S2
tN4
8
PH
No Power
S1
tN4
C
tNt
7
Zone Valve B
C
R
R
W
Zone A2
9
10
Rh1
tN4
W1
G1
C
tNt
11
12
R
W
Zone A3
13
14
G1
tN4
Rc
Y1
C
R
tNt
15
16
Com
S2
S1
W
Zone A4
17
18
tN4
tN4
C
C
R
Rh1
R
tNt
W1
W
Zone A5
tN4
C
R
tNt
W
Zone A6
19
20
21
22
23
24
25
26
36
37
38
39
40
41
42
43
27
Limited power available, see wiring brochure
28
29 Input Power
L
30
31
335
32
Zone Group N
Pmp A
33
34
Zone A2
Zone A1 N
C
Vlv
35
C
Vlv
Zone A3 C
Vlv
Zone A4 C
Vlv
Zone A5 C
Vlv
Zone A6 C
Vlv
PH
Zone Valve A Wiring for an additional zone valve, beyond the total number allowed on the Zone Manager would be wired like shown above. Thermostat A represents a typical TN4 thermostat wiring schematic while Thermostat B would be an additional zone valve/ thermostat wiring schematic. Notice that for Thermostat B, the W terminal is sent directly to the additional zone valve while the W terminal for Thermostat A comes back to the Zone Manager so that it’s respective zone valve gets fed out of the bottom of the 335. Both Thermostats continue to communicate Via the TN4 and common terminals.
Basic Snowmelt MDF 3/17/2006
WWW.CAPCOSUPPLY.COM
ENERGY SUPPLY, INC.
FAX 781-781-9119
SX40V
Exspansion Tank
Purge Valve
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
10 Industrial Parkway Woburn, Ma. 01801
781-721-0303
SX40V
Use transfer pump to pressurize
Relief Valve piped to drain or pail
Glycol Feed Tank
Set for 50 Lbs.
Set for 12-15 Lbs.
Fill point
M
Snowmelt Manifold
Slab
Tekmar 090 Snow/Ice Sensor
Var
Opn/
4-20 mA
-
2
1
+
3
max
1k
2.4A
Mix
Pwr
4
5A
Cls
5 Blu
8
Mix Supply
Com
Blk /
7
Mix Return
Red
6 Yel
9
2
1
040
no Power
Com
Com
12
tN2
2
Slab
11 tN2
741
Ret
Mix
14 Com
16
Boiler
Sup
Mix
15
C 24V (AC) R
1 5 6 7 2 4 3 Com Opn Cls Opn Cls Aux Aux C limit limit Sw Sw
M
P2
M
13
Polarity Sensitive
Slab1
Brn /
10
664
Boil
17
120V AC
P1
Outdoor
Out
18
20
22
1
Stage
21
24
2
Stage
23
5A
P2
1
Zn
25
5A
Zn
Com
26
5A
2
Zn
P1
27
P1
Sys
28
5A
L
120V AC
N
30
Power
29
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL 664 Snowmelt PARKWAY MDF 3/4/06 with Tekmar 040 WOBURN MA 01801
Demand
Melt/Idle Com
19
5A
120V (ac)
L
C
Class II Transformer 24V (ac)
N
R
4 N/O
4 N/C
6 N/O
COM
24 VAC
6 N/C
R W T T
To Mix Demand
N H 3
120 VAC INPUT
SR501 1 ZONE SWITCHING RELAY
T8400B
5
POWER T STAT
P1 UPS-1558 Opn Com Cls C
1 2 3
P2
MIX SUPPLY
BLUE BLACK BROWN
120V (ac)
L
Boil DHW Mix P1 Pmp/Vlv P2
7.5A
Pwr Opn Cls/ Mix Var
P1 P2
Boiler
12 13 14 15 16
7.5A 2.4A
363
DHW
OUTDOOR
BOILER SUPPLY
MIX SUPPLY
Com 10K tN1/ Com 10K UnO Com Mix Boil Out 2 tN2 1 Sw
17 18 19 20 21 22 23 24 25 26
Do not apply power
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL PARKWAY Buderus Mix MCB 1/27/04 WOBURN MA 01801
N
R
Power N L
6 7 8 9 10 11
7.5A
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
C
Class II Transformer 24V (ac)
1ST FLOOR RADIATORS
2ND FLOOR RADIATORS
Mix Com Boil Setp/ Demand Dem Dem DHW
1 2 3 4 5
7.5A
BOILER SUPPLY
1 2 3 Opn Com Cls
P1
MIX SUPPLY
RADIANT FLOOR OR PANEL RADIATORS
120V (ac)
L
C
N
R
Class II Transformer 24V (ac)
N
N
6
P1
Pmp
Sys
5
7 Boiler
10A
8
Opn
R
9
Cls
R
C
10 11
Powered Output
360
Sw
UnO
Com
Boil
Mix
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
Com
Indr
OUTDOOR
Out
12 13 14 15 16 17 18
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL Buderus Mix MDF 5/25/06 PARKWAY with Tekmar 360 WOBURN MA 01801
BLUE BROWN
Black
Power
4
L
3
Mixing
2
Demand
1
10A
BRN
TO FUSED 230V DISCONNECT NOT OVER 15 AMP FUSE
BRN
GRD. LEAD TO MOTOR BASE
BK
RED
RED
L2
L1
BK
BK
BK
RED
EQUIPMENT GROUND
RED
Unico Control Box
2
4
2
4
2
4
RED 5
6
5
6
5
6
BLU
1
3
HI RELAY
1
3
LO RELAY
YEL
1
3
YEL
BLU
BLU
YEL
YEL
BLU
UNLATCHING RELAY
R B O
Power Rev. Valve (Heating) Rev. Valve (Cooling)
COMMON
Fan
OR
206V
24V
BLU
G
Heating W
Y
C
Common
Compressor
TYPICAL THERMOSTAT
2
3
4
3
4
6
ANTI-FROST CONTROL BYPASS RELAY
1
2
5
7
BRN
BRN
C Common
ANTI-FROST CONTROL
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL UNICO PARKWAY 02/20/04 JEH CONTROL WOBURN MA 01801 BOX 2003
TRANSFORMER
230V
YEL
1
Power
Rev. Valve
Y Compressor
R
O
W Defrost Heat
TYPICAL OUTDOOR SECTION
Chiller Chiller
NOTE TOTAL SYSTEM VOLUME MUST BE 25 GALLONS WITH ONE CHILLER AND 10 ADDITIONAL GALLONS FOR EACH ADDITIONAL CHILLER. BUFFER TANK MUST BE USED IF THESE MINIMUMS ARE NOT MET.
SUPER STOR CB-30
C A L E F F I
Fan Coil
Fan Coil
MCB 04/15/05 THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
CHILLER PIPING
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL PARKWAY WOBURN MA 01801
781-721-0303
Fan Coil
3/8" Compression X ½” NPT male fitting Material List
3/8" Flare x MNPT Ftg’s
½” Black Plug Double Tapped Bushing
½” Black Iron Pipe chase
1.) Qty (3) Oil Firomatic Valves 2.) Qty (4) 3/8" FM x 3/8" Flare Adapters with Qty (4) nuts 3.) Roll of Copper Tubing 3/8" 4.) Qty (1) ½” Black Plug 5.) Qty (1) 2" Double Tapped Bushing 6.) Qty (1) ½” Male x 3/8" Compression fitting for slipping tubing through 7.) Qty (1) ½” Black Iron Pipe x 10' 8.) Qty (2) 3/8" x 4" Black Nipples 9.) Qty (1) Spin & Grin Vacuum Gauge for Garber Oil Filter 10.) Garber Filter
Firomatic Oil Valves 3/8" female with FM x Copper Adapters
Vacuum Gauge and 3/8" Nipples
To Burner
FACTORY INSTALLED TRANSFORMER
POWER SUPPLY 120 VAC
L
N
ES
RESET
L
3 A
F U S E
N
P2 PUMP DHW 3 FLA
G
T T ZONE 2
N L
PH
PH
ZONE 1 1 2 3 4
Two Wire Zone Valve
ZONE 2 1 2 3 4
G PUMP DHW REC. 3 FLA
T T ZONE 3
N
Taco Zone Valve
ZONE 3 1 2 3 4
THREE ZONE ZONE VALVE CONTROL
T T ZONE 1
LOW WATER CUT-OFF
LP1 G
NO COM NC
PUMP SYSTEM #1 3 FLA
G L
SLAVE
PUMP SYSTEM #2 3 FLA
G
MASTER
L
FUSE 1 AMP
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 POWER
N
24 VAC
G
FACTORY INSTALLED TRANSFORMER
N
POWER IN
L I N E
C O M M O N 0 P E N
X X E. S.
ZC
RESET
PLUG-IN CARDS
MIXING VALVE 120 VAC 5W
C L O S E
7133-436 POWER/PUMP MODULE
T T ZONE 3
T T ZONE 4
T T ZONE 6
SR 506-EXP
T T ZONE 5
ON OFF
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL VITRONIC MCB 2/14/05 PARKWAY 200 TACO WOBURN MA 01801 CONTROLS
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 POWER 120 VOLT CIRCULATORS INPUT
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
T T ZONE 2
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ZR
NORMAL
T T ZONE 1
ZONE 6 PRIORITY
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM VIESSMAN 10 INDUSTRIAL PARKWAY COMBUSTION MCB 2/14/05 WOBURN MA 01801 AIR 781-721-0303
G
120 VAC
L1 N M
T1 T2 T3
FAN IN CAN CAS-3
RD
BK WH GN
B K 5 B K 2 B K 1
B K 4 B K 3 G N Y E
B K 1
B K 4 B K 2 G N Y E
B K 3
B K 5
B K 6
41
41
41
RD
41
BK WH GN
PRESSURE SWITCH
120V Field Supplied Relay
IN-FORCER PAI-1G, PAI-2G
M
L1 G N
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
B K 1
G N Y E B K 2 B K 3
B K 4
B K 5
41
41
BK WH GN RD
115V
A B
1
3
4
N
115 VAC
L
MTR
To Combustion Air Or Power Venter
N
COM
J2
UC-1
MOTOR RELAY
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL VIESSMAN MCB 2/14/05 PARKWAY WITH UC-1 WOBURN MA 01801
2
COM
J1
24V
INTERLOCK RELAY NO
XL
DRY
XN
TJERLUND
NO
20
HeatingCircuit Pump
Boiler Pump
20
20
L
20A
20A
40 100
N
L
N
20A L
21 N
X3B
X3A
DHW Pump
POWER PUMP MODULE
A1
X4
120 VAC
10
11
REMOTE WS/RS
9
1 2 3
X3
20
145
1 2 3 4
X5
1 2 3
#5 DHW SENSOR
40 120 VAC
#5 HEADER SENSOR
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL Vitodens PARKWAY MCB 2/14/05 Controls WOBURN MA 01801
MIX OUTPUT SENSOR
2
40
1 2 3
#1 OUTDOOR SENSOR
1 2 3 4
X7
VITRONIC 300 ACTUATOR
1 2 3 4
X6
OPTIONAL MIX PUMP OUTPUT
1 2 3 4
X4
VIT ODE NS C O N TROLS
V I ES M A N N S
21
21
3/21/2006
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
MDF
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM
10 INDUSTRIAL PARKWAY WOBURN MA 01801
781-721-0303
X2
1
2
3
4
5
6
7
8
9
120V (ac)
L N
SR501
R W T T
COM
24 VAC
115 Volt Connection
JUMPER
DHW Pump
4 4 6 6 5 N H 3 N/O N/C N/C N/O
120 VAC INPUT
1 ZONE SWITCHING RELAY
DHW Aquastat
POWER T STAT
HARVEY'S
Part No. 016850
MAXIMUM BURST
PROTECTION!
Nontoxic / Noncorroding
HARVEY HEAT -100 Inhibited Propylene Glycol Fluid
ANTIFREEZE
®
°F. -50° -60° -70° -80° -90° -100°
NET 1 GALLON U.S. (3.785 L)
Nontoxic / Noncorroding
HARVEY HEAT -100 ANTIFREEZE INSTRUCTIONS: TABLE I - (Addition to system based on size of piping) 1. Turn off water supply. Pipe Diameter 1/2" 3/4" 1" 1-1/2" 2" 3" 2. Drain water lines through faucets, petcocks and other outlets. Close all Gallons outlets once system has drained. Harvey Heat -100 1.6 2.8 4.5 10.6 17.4 38.4 3. Refill system with Harvey Heat -100 (undiluted) from this container. Be per 100 ft. pipe sure to add amount according to capacity of piping. See Table I. 4. For boats, trailers or recreational vehicles with pressurized or electric TABLE II - Boat and Trailer Guide pump water systems, follow Table II. Drain all water lines and supply tank Size of Add approximate quantity of completely and refill with Harvey Heat -100. Repressurize water supply Boat/Trailer Harvey Heat -100 to water tank system. Open all faucets one at a time to see if system is full. Close Under 18 ft. 2-3 gal. faucet when yellow color of Harvey Heat -100 begins to flow. 18 ft.-23 ft. 3-4 gal. 5. Protect drains. Be sure to add 1 quart or more of Harvey Heat -100 23 ft. and over 4-5 gal. (undiluted) to traps and toilets to prevent freeze-up and to keep seals soft and pliable. 6. For permanent protection of HVAC and solar heating/cooling systems, Harvey Heat -100 may be left in the system all year. Concentration necessary for freeze protection depends on the system design. Consult with the manufacturer of the individual systems before using Harvey Heat products. Before charging any new or existing systems with Harvey Heat -100, they should be thoroughly cleaned and flushed. 7. Other recommended uses for Harvey Heat -100 include protection of non-drainable fire hydrants; sprinkler systems; coolant in manufacture and processing of beef, wine, milk, and other liquids; in freezing of poultry, fish, and vegetables; and in freezer coil defrosting. 8. To de-winterize water systems–open all faucets, petcocks and other outlets and run fresh water through system until yellow color disappears. Continue to flush several times until only fresh water flows from faucets. Refill supply tank with fresh water. 9. Harvey Heat -100 is recommended to be used undiluted in most cases. However, it is also effective when mixed with water to provide freeze and burst protection. For other than maximum protection, see Table III. 10. Do not use in gasoline or diesel engines.
TABLE III # Parts of # Parts of Freeze Concentration Harvey Heat -100 Water Protection 100% 75% 50%
Undiluted 3 1
0 1 1
-60°F -30°F +3°F
Burst Protection -100°F -80°F -30°F
NOTE: Do not add more than 1 part water for every 1 part Harvey Heat -100 (50% dilution).
INGREDIENTS -
Name CAS No. Propylene Glycol 57-55-6 Water 7732-18-5 Dipotassium Phosphate 7758-11-4 HMIS: 1-1-O
WARNING: KEEP OUT OF THE REACH OF CHILDREN. DO NOT TAKE INTERNALLY. For Emergency First Aid Help Call 1-303-623-5716 Collect Manufactured by William H. Harvey Company, Omaha, NE 68117 Made in U.S.A.
©2005
Part No. 016850
SYSTEM DESIGN - CHAPTER 3 3.6 Water/ Glycol Mixture: Selecting the percentage of Glycol Mixture: Freeze protection is essential to the snow melting system. For typical applications, Viega recommends using 40% Propylene Glycol. Ethylene Glycol is accepted. Use the table to determine the freezing point of the water/ glycol mixture based on % glycol by volume. Note: Automotive antifreeze is not recommended; the silicates in automotive antifreeze can coat and foul heat transfer surfaces and plug the system, reducing energy efficiency. Glycol effects on the system: The material properties change according to the % glycol mixture. Use the table to adjust the flow rate and pressure drop calculated through the tubing (refer to 3.7 and 3.8 for values).
Freezing Point (°F) Glycol Mixture
Ethylene Glycol
Propylene Glycol
30%
3.7
8.4
40%
-12.6
-6.7
50%
-35.0
-30.0
Table 3.6A
Glycol Effects on the System Glycol Mixture
Flow Rate Pressure Drop % Increase Multiplier % Increase Multiplier
Procedure: 1. Use the table to find the % increase multiplier (based on the % glycol mixture).
30%
5% (1.05)
20% (1.20)
40%
8.5% (1.085)
25% (1.25)
2. Multiply the flow rate and pressure drop figures by the multiplier.
50%
12.5% (1.125)
31% (1.31)
Table 3.6B
Example: Glycol mixture: 40% Calculated flow rate: 7 gpm Flow rate multiplier: 8.5% (1.085) Adjusted flow rate calculation: 7 gpm x 1.085 = 7.6 gpm Calculated pressure drop: 20 ft of hd Pressure drop multiplier: 25% (1.25) Adjusted pressure drop calculation: 20 ft of hd x 1.25 = 25 ft of hd
VIEGA NA
877-VIEGA-NA
IM-SNO-09/04
To System
SBN56F Pressure Reducing Valve
Boiler Drain and Fill Point with Cap
SX40V Expansion Tank
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
ENERGY SUPPLY, INC. 781-721-0303 FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL Glycol Fill PARKWAY MCB 2/14/05 System WOBURN MA 01801
GLYCOL
Set to 60 PSI
AIR
0 - 100 PSI Pressure Gauge
Basic Snowmelt/Axiom MDF 5/27/2006
WWW.CAPCOSUPPLY.COM
ENERGY SUPPLY, INC.
FAX 781-781-9119
Purge Valve
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
10 Industrial Parkway Woburn, Ma. 01801
781-721-0303
Exspansion Tank
SX40V
Fill point
M
Glycol Feed Tank
Axiom MF-100 Glycol Feeder
3 Way Valve with Actuator
Relief Valve piped to drain or pail
Snowmelt Manifold
GAS VALVE
AQUASTAT
PRESSURE GUAGE
AIR SEPERATOR
SX40V
BASIC HYDRONICS
MCB 4/12/05
ENERGY SUPPLY, INC. FAX 781-721-9119 WWW.CAPCOSUPPLY.COM 10 INDUSTRIAL PARKWAY WOBURN MA 01801
781-721-0303
HEAT EMITTER
THIS IS ONLY A CONCEPT DRAWING. ALL CONDITIONS AND NECESSARY COMPONENTS MUST BE FIELD VERIFIED AND ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
EXPANSION TANK
PRESSURE REDUCING VALVE
BACKFLOW PREVENTER
BALL VALVE
SPRING CHECK VALVE
PUMP
FLANGED BALL VALVE
Pu m ping A w a y1 The Point of No Pressure Change The point where the expansion tank connects to a closed hydronic system is called the Point of No Pressure Change. The Point of No Pressure Change is the location in the system where the circulator cannot have any affect on the pressure. The Correct Position of the Circulator The position of the circulator in a hydronic heating system is critical. For any number of reasons, in the middle 1940’s boiler manufacturers began to deliver their assembled packages with the circulator mounted on the return side of the boiler. This delivery practice found its way into installation practices, and before long most contractors were putting the circulator on the return side of the boiler as a standard practice. Installing the circulator on the return side of the boiler, pumping towards the Point of No Pressure Change, can create problems with the system. When systems are assembled in this manner, the circulator cannot raise the pressure any higher than it already is, i.e. whatever the tank precharge pressure is. The circulator has to move water, however, and it does this by decreasing its inlet pressure below the pressure at the Point of No Pressure Change. This practice can lead to the following problems: 1. Air can enter the system, usually in commercial applications, if the pump drops the inlet pressure below zero. 2. If you do not “Pump Away” from Point of No Pressure Change, it becomes difficult to remove air from the system. The lower pressure on the inlet side of the circulator can allow air that has been absorbed into the water to be released into the system. If you install the circulator immediately after the expansion tank and “Pump Away” from the Point of No Pressure Change, the circulator adds whatever head it develops to the static pressure that already exists in the pre charged system. Pumping towards the Point of No Pressure Change creates system operating problems which are eliminated if you “Pump Away”. All wet rotor circulators in production today are capable of handling high temperature water produced by the boiler when the pump is positioned to “Pump Away.”
1
F ro m P u m pin g A w a y (a n d o t h e r r e a lly c o ol pipin g o p tio n s for h y dro ni c s y s t e m s) b y D a n H olo h a n, a v a il a bl e a t w w w .h e a tin g h e lp. c o m
Ho w to Sele ct a Pump Follow This Path to Select the Proper Pump:
1. Calculate BTUh – BTUh is the heat output capability of the heat source over time. a) Given in specification, or b) Heat Loss Calculation 2. Determine GPM a) Formula: Solve for GPM by using the equation: GPM = BTUh / (500 x ¨T) b) Shortcut for Calculating GPM: For systems with a ¨T of 20 degrees F, divided output boiler BTU’s by 10,000 3. Select Pipe – This step ensures the velocity through the piping network is under four feet/second. Excess velocity could cause noise and/or premature erosion of the piping system. Most hydronic engineers use .05 ft head per linear foot of pipe as “rule of thumb” to size pipe. 4. Determine the System Piping Friction Head – Head is calculated by multiplying the equivalent length of the circuit of pipe, including the valves and fittings, by the friction loss values located in the pressure drop charts for various piping materials, ie copper, pex, and steel.
5. Apply System Curve – Overlay the system curve template on a preliminary pump curve selection to pick the “Operating Point”. The specified duty point and the actual operating point will often occur at different flow and heat performance rates found on manufacturers pump charts. 6. Select Pump – From manufacturer’s pump charts.
GRUNDFOS PLUMBING & HVAC PRODUCTS
PRODUCT LINE (UP,UPS,TP,LM/LP) PERFORMANCE CURVES Series UPS-Performance Range
Series UP-Performance Range Closed Systems 60 Hz
Series TP Performance Range
Open Systems 60 Hz
Series LM/LP Performance Range
Series Comfort Performance Range
NOTE: Performance curves and technical information listed as a range only and subject to change without notice. Consult a Grundfos product submittal data sheet for exact pump specifications.
Products At-A-Glance
CAPACITY IN U.S. GPM
TOTAL HEAD IN FEET
HP
TEMP. RANGE*
MAX. WORKING PRESS.
Series UP Circulators
0 - 46
0 - 37
1/25 - 1/6
32°F - 230°F
145 PSI
Series VersaFlo UPS-Pumps
9 - 270
1 - 62
1/3 - 3
14°F - 230°F
145 PSI
Series VersaFlo TP-Pumps
8 - 300
3.5 - 67.5
1/3 - 3
5°F - 288°F
145 PSI
Series L Pumps
30 - 600
8 - 180
3/4 - 20
5°F - 250°F
175 PSI
**The UP15 has a minimum water temperature range down to 36°F.
BEING RESPONSIBLE IS OUR FOUNDATION THINKING AHEAD MAKES IT POSSIBLE INNOVATION IS THE ESSENCE
GRUNDFOS PUMPS FOR HOT WATER RECIRCULATION SYSTEM COMPONENTS
WHY INSTALL A HOT WATER RECIRCULATION SYSTEM?
Typical Hot Water Recirculation System
• Hot Water on Demand Convenience Hot water recirculation systems are routinely installed in hotels and other commercial buildings. Guests and building occupants not only appreciate instant hot water but have come to expect it. Residential customers can enjoy the convenience of instant hot water with proper system design and quality components.
• Water Conservation Water conservation is an important part of all of our lives. Not only do we pay for the water coming in, but we also pay for it when it goes down the drain to our sewage systems. With hot water recirculation, the waste of valuable water becomes minimal.
• Energy Savings When hot water sits for a long period of time in a pipe, it cools down. This water is then drained and wasted while waiting for hot water from the water heater. Every time the water sits for longer periods of time, allowing this water to cool, the energy that was used to heat that water is wasted. With the Grundfos hot water recirculation pump, in conjunction with insulated piping, system timer, and AquaStat heat sensor, the waste of energy is minimized.
Hot Water Recirculation Accessories
AquaStat Heat Sensing Unit
Models Available for Hot Water Recirculation Standard Models UP15-10B5 UP15-10B7 UP15-18B5 UP15-18B7 UP15-42B5 UP15-42B7 UP15-10BUC5 UP15-10BUC7
UP15-18BUC5 UP15-18BUC7 UP15-42BUC5 UP15-42BUC7 UP15-18SU UP15-42SU UP25-64SU Line Cord Models UP15-10B5/LC
www.hotwaterrecirc.com
L-PH-SL-001 Rev. 9/01 PRINTED IN USA
Grundfos Pumps Corporation 17100 W.118th Terrace Olathe, Kansas 66061 Telephone: (913) 227-3400 Fax: (913)227-3500 www.grundfos.com
Grundfos Canada, Inc. 2941 Brighton Rd. Oakville, Ontario L6H 6C9 Telephone: (905) 829-9533 Fax: (905)829-9512
UP15-10B7/LC UP15-18B5/LC UP15-18B7/LC UP15-42B5/LC UP15-42B7/LC UP15-10BUC5/LC UP15-10BUC7/LC UP15-18SU/LC
Timer and Line Cord Models UP15-10B5/TLC UP15-10B7/TLC UP15-18B5/TLC UP15-18B7/TLC UP15-42B5/TLC UP15-42B7/TLC UP15-10BUC5/TLC UP15-10BUC7/TLC UP15-18SU/TLC
Timer Comfort Models UP10-16B5/LC UP10-16B5/TLC UP10-16B5/ATLC UP10-16BN5/LC UP10-16BN5/TLC UP10-16BN5/ATLC UP10-16BU/LC UP10-16BU/TLC UP10-16BU/ATLC
Available from:
Performance curves and technical information listed as a range only and subject to change without notice. Consult a Grundfos product submittal data sheet for exact pump specifications. VersaFlo® and Brute II® is a registered trademark of Grundfos Pumps Corporation.
Bombas Grundfos de Mexico, S.A. de C.V. Boulevard TLC #15, Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. Mexico Telephone: 52-8-144-4000 Fax: 52-8-144-4010
TI UVUQ4",U!W!75,67X,Y6%YZ%6Q![7U $89/:;<=,>?>@/A>,>B<8;C,D/,C/>.0E/C,F<;;<=.E0 >@1EC19C,G;8AD.E0,/E0.E//9.E0,
[email protected]/I,:<;;<=, ;
,@<,C/@/9A.E/,A.E.A8A,@8D.E0,>.J/,1EC 9/K8.9/C,LM@89/,G9/>>89/>I, $9/>>89/,C9
,H1E,D/,/>@.A1@/C,F9,19/,/MG9/>>/C,.E,/K8.N1;/E@ ;/E0@B,<,1CC,@B/,N1;8/>,F<9,@B/,9/;/N1E@ L@@.E0>,@<,@B/,;/E0@B,>89/,C9 D/;<=,<9,>89/,C9,@1$/M,@8D.E0P,9/F/9,@<,@B/,G9/>>89/,C9.J/P,1EC,@8D.E0,;/E0@BP,@B/,G9/>>89/ C9.;?,C/@/9A.E/CI
-./01,'#233#-!456#76,,
!"#$%&' *$+)
,'-".
()) /012"3415
()) /-2&%615
78&90)2
\)2
+I]
'I+
^I\
(I(
')(
+I+
'I^
^I]
(I(
\)]
^I*
'I3
^IT
(I\
'
3I]
(I(
2I^
(I2
'#')]
''I*
]I2
'\I*
+I+
'#')(
'\I*
+I*
'^I*
^I'
!"#$$%"#&'($$#$&)*&!%"#+'(,&-..)*/$ 0#12"#$$#3 )* #4%)56'#*.&7##.&(7&!89&.%:)*/;<
!"#$%'()*+,
49# *I' *I( *I\ *I] *I+ *I^ *I3 *I2 *IT 'I* 'I+ (I* (I+ \I* \I+ ]I* ]I+ +I* ^I* 3I* 2I* TI* '*I* ''I* '(I* '\I* ']I* '+I* '^I* '3I* '2I* 'TI* (*I* ('I* ((I* (\I* (]I* (+I* (^I* (3I* (2I* (TI* \*I* \'I* \(I* \\I* \]I* \+I* \^I* \3I* \2I* \TI* ]*I*
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
-./01,'#233#-!456#76,,
CFC@D :2);;32) ?'".< =2"9 *9))8 *I**** *I*\ *I**** *I*+ *I**** *I*2 *I**** *I'' *I***' *I'\ *I***' *I'^ *I***' *I'2 *I***' *I(' *I***' *I(] *I***( *I(^ *I***] *I]* *I***^ *I+\ *I***T *I^^ *I**'( *I3T *I**'^ *IT( *I**(* 'I*+ *I**(+ 'I'T *I**\* 'I\( *I**]( 'I+2 *I**+] 'I2+ *I**^T (I'' *I**2+ (I\3 *I*'*( (I^] *I*'(' (IT* *I*']' \I'^ *I*'^( \I]\ *I*'2] \I^T *I*(*2 \IT+ *I*(\\ ]I(( *I*(^* ]I]2 *I*(23 ]I3+ *I*\'^ +I*' *I*\]^ +I(3 *I*\33 +I+] *I*]*T +I2* *I*]]( ^I*^ *I*]3^ ^I\\ *I*+'( ^I+T *I*+]2 ^I2+ *I*+2^ 3I'( *I*^(+ 3I\2 *I*^^+ 3I^+ *I*3*+ 3IT' *I*3]3 2I'3 *I*3T* 2I]] *I*2\] 2I3* *I*23T 2IT^ *I*T(+ TI(\ *I*T3( TI]T *I'*(* TI3+ *I'*^T '*I*( *I'''T '*I(2 *I''3* '*I++ !"#$%'()*+,
SELECTIONS
SNOW MELT
FlatPlate heat exchangers are very cost effective in Snow Melt applications and provide high output, fast response and separation of the fluids. Used for Boiler water to Glycol heat transfer, and in some applications, zone isolation, the FP Series provides an easy solution to Snow Melt systems. Typical Snow Melt systems are Boiler Water to Glycol 10% to 40% (typical) depending upon location and weather conditions, with the heat exchanger providing isolation of the glycol from the boiler water, providing an oxygen barrier to the boiler and protecting other components in the boiler system. To Select a Heat Exchanger for a Snow Melt application: Step 1
Step 2
Step 3
P1 Bypass/ Balancing Valve
180°F
Check the total GPM required. If the GPM requirement of the snow melt system is greater than the GPM listed in the selection table, select a larger model to match the GPM and pressure drop needs, or install a Bypass balancing valve. This will allow full flow and optimum pressure drop for the pump. This applies to the GPM (s) on both Boiler and Glycol sides.
For Example: For a snow melt system requiring a 122,000 BTUH, from the Table, Model FP5x12-16 (3/4" MPT) would be selected. If the GPM requirement is greater than 8.6 use the next larger model to match the pump requirement.
Snow Melt Loop
100°F 150°F
Boiler
Snow Melt Heat Exchanger
Piping Note: A boiler side bypass valve is recommended, but not required. A 3 Way Tempering valve or motorized control valve on the snow melt side is required.
Determine the Total BTUH required (from guidance from your Radiant Tube supplier) for the Snow Melt system. Select the appropriate FP Model from the table, based on the Total BTUH required. If the Boiler water temperature is 180˚F or higher, or steam, use the Table shown. If the Boiler water temperature is less than 180˚F Contact your local FlatPlate Representative.
130°F
Controls: . A 3 Way Tempering Valve is required to allow for adjustment of the snow melt side, and to limit the temperature of the glycol. For radiant tubing in sand maximum glycol temperature is 140˚F. In asphalt and concrete, maximum temperature is typically 150˚F. Recommended set point 130˚F for the glycol snow melt side. Start-up: Adjust the 3 Way tempering valve to 130˚F or the desired set point.
For Snow Melt Application 100˚F In-130˚F Out (40% P.G.) Connected to Boiler 180˚F Supply - 150˚F Return Model FP5X12L-6 (3/4" MPT) FP5X12L-6 (3/4" MPT) FP5X12L-6 (3/4" MPT) FP5X12L-8 (3/4" MPT) FP5X12L-8 (3/4" MPT) FP5X12-10 (3/4" MPT) FP5X12-10 (3/4" MPT) FP5X12-12 (3/4" MPT) FP5X12-14 (3/4" MPT) FP5X12-16 (3/4" MPT) FP5X12-20 (1" MPT) FP5X12-24 (1" MPT) FP5X12-24 (1" MPT) FP5X12-30 (1" MPT) FP5X12-36 (1" MPT) FP5X12-36 (1" MPT) FP5X12-40 (1-1/4" MPT) FP5X12-50 (1-1/4" MPT) FP5X12-50 (1-1/4" MPT) FP5X12-60 (1-1/4" MPT) FP5X12-70 (1-1/4" MPT) FP10X20-30 (1-1/2" MPT) FP10X20-30 (1-1/2" MPT) FP10X20-36 (1-1/2" MPT) FP10X20-40 (1-1/2" MPT) FP10X20-50 (2" MPT) FP10X20-60 (2" MPT) FP10X20-60 (2" MPT) FP10X20-70 (2" MPT)
BTUH 20,000 30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 125,000 150,000 175,000 200,000 225,000 250,000 275,000 300,000 350,000 400,000 450,000 500,000 400,000 450,000 500,000 600,000 700,000 800,000 900,000 1,000,000
Side A Boiler GPM PD (psi) 1.3 0.2 2.0 0.6 2.7 1.0 3.4 0.7 4.1 1.0 4.8 1.2 5.5 1.6 6.2 2.9 6.8 2.6 8.6 2.9 10.3 2.6 12.0 2.4 13.7 3.1 15.5 2.5 17.2 2.2 18.9 2.6 20.6 2.6 24.1 2.4 27.5 3.0 31.0 2.9 34.4 2.8 27.5 3.1 31.0 3.8 32.8 3.0 41.3 3.7 48.2 3.3 55.1 3.0 62.0 3.8 68.8 3.5
1. Larger models available. Contact your local FlatPlate representative. 2. For 200˚F Boiler Water, use the above chart. For 160˚F Boiler Water, multiply model number by 1.66. 3. For Steam use the above chart, substituting MP Model #.
Side B Snow Melt Circuit GPM PD (psi) 1.4 0.1 2.1 0.3 2.8 0.6 3.6 0.5 4.3 0.7 5.0 0.8 5.7 1.2 6.4 2.9 7.2 2.7 9.0 3.1 10.8 2.9 12.6 2.8 14.4 3.6 16.2 3.1 18.0 2.7 19.8 3.2 21.6 3.2 25.2 3.0 28.8 3.8 32.4 3.6 36.1 3.6 28.8 3.7 32.4 4.6 35.6 3.9 43.3 4.6 50.5 4.2 57.7 3.9 64.9 4.8 72.2 4.5
SELECTIONS – SWIMMING POOLS & SPAS Selecting a FlatPlate Heat Exchanger for Swimming Pool Applications is quick and easy, based on the Total Pool Capacity (gallons), Heat Loss of the pool and the Heat Up Rate desired. FlatPlate’s MP Marine Series is designed for Swimming Pool applications where chemically treated water and biological elements are present. Note: MP Series Heat Exchangers use a special Marine Stainless Alloy and MUST be used in pool environments. Materials such as 316 Stainless steel will corrode and fail due to chlorine, and other chemical and biological elements typical in pool water.
Swimming Pools To select a Heat Exchanger for Boiler to Pool Water Heating: Step 1 Select the Heat Up Rate Desired Pool Use Periodic Use Only (weekends, holidays) Extended Use (summer season) Step 2
Heat Up Rate 2˚F/hour 1˚F/hour
Determine Pool Capacity Rectangular Pools Capacity (gallons) = _____Length (ft) x _____Width (ft) x _____Average Depth (ft) x 7.5 gallons/cu ft Circular Pools 2 Capacity (gallons) = _____Diameter (ft) x _____Avg Depth (ft) x .785 x 7.5 gallons/cu ft 1˚F/Hr Heat up Rate
Pool Capacity (Gallons) 1,000 2,000 4,000 6,000 8,000 10,000 12,000 15,000 20,000 25,000 30,000 35,000 40,000 45,000 50,000 60,000 70,000 80,000 90,000 100,000 125,000 150,000 175,000 200,000 1. 2. 3. 4. 5. 6.
2˚F/Hr Heat up Rate
Boiler Output Required (BTUH)
Boiler Side Minimum GPM
FlatPlate Model
Boiler Output Required (BTUH)
Boiler Pump Minimum GPM
8,345 16,690 33,380 50,070 66,760 83,450 100,140 125,175 166,900 208,625 250,350 292,075 333,800 375,525 417,250 500,700 584,150 667,600 751,050 834,500 1,043,125 1,251,750 1,460,375 1,669,000
2 2 2 3 4 6 7 8 11 14 17 18 19 21 24 29 33 38 43 48 60 72 83 95
MP5x12-4 (1" MPT) MP5x12-4 (1" MPT) MP5x12-6 (1" MPT) MP5x12-6 (1" MPT) MP5x12-8 (1" MPT) MP5x12-8 (1" MPT) MP5x12-10 (1" MPT) MP5x12-10 (1" MPT) MP5x12-16 (1" MPT) MP5x12-16 (1" MPT) MP5x12-20 (1-1/4" MPT) MP5x12-20 (1-1/4" MPT) MP5x12-24 (1-1/4" MPT) MP5x12-30 (1-1/4" MPT) MP5x12-30 (1-1/4" MPT) MP5x12-40 (1-1/4" MPT) MP5x12-40 (1-1/4" MPT) MP5x12-50 (1-1/4" MPT) MP5x12-50 (1-1/4" MPT) MP5x12-60 (1-1/4" MPT) MP5x12-70 (1-1/4" MPT) MP5x12-80 (1-1/4" MPT) MP5x12-100 (1-1/4" MPT) MP5x12-110 (1-1/4" MPT)
16,690 33,380 66,760 100,140 133,520 166,900 200,280 250,350 333,800 417,250 500,700 584,150 667,600 751,050 834,500 1,001,400 1,168,300 1,335,200 1,502,100 1,669,000 2,086,250 2,503,500 2,920,750 3,338,000
2 2 4 7 9 11 13 17 22 28 33 36 38 43 48 57 67 76 86 95 119 143 167 191
Typical Design Conditions: 180˚F Boiler Water to HX, 80˚F Pool Water. For 160˚F Boiler Water, multiply product model by 1.5 to select larger required model. (ie, FP5x12-16 at 180˚F, use FP5x12-24 at 160˚F). For 200˚F Boiler Water and Steam, use model number shown for 180˚F. Multipy minimum Boiler gpm by .60. Bypass/Balancing valve on Pool side of HXREQUIRED to allow for full pool pump flow from 30 to 100 gpm or more. Pool side Pressure drop for all models ranges for typical flow with bypass/balancing valve 4.0 psi or higher. Boiler side Pressure drop for all models ranges 4.0 psi to 4.5 psi for the above Minimum Flow rates.
FlatPlate Model MP5x12-4 (1" MPT) MP5x12-6 (1" MPT) MP5x12-8 (1" MPT) MP5x12-10 (1" MPT) MP5x12-10 (1" MPT) MP5x12-16 (1" MPT) MP5x12-16 (1" MPT) MP5x12-20 (1-1/4" MPT) MP5x12-24 (1-1/4" MPT) MP5x12-30 (1-1/4" MPT) MP5x12-40 (1-1/4" MPT) MP5x12-40 (1-1/4" MPT) MP5x12-50 (1-1/4" MPT) MP5x12-50 (1-1/4" MPT) MP5x12-60 (1-1/4" MPT) MP5x12-70 (1-1/4" MPT) MP5x12-80 (1-1/4" MPT) MP5x12-90 (1-1/4" MPT) MP5x12-100 (1-1/4" MPT) MP5x12-110 (1-1/4" MPT) (2) MP5x12-70 (1-1/4" MPT) (2) MP5x12-80 (1-1/4" MPT) (2) MP5x12-100 (1-1/4" MPT) (2) MP5x12-110 (1-1/4" MPT)
SELECTIONS – SWIMMING POOLS & SPAS Step 3
Step 4
Select the Heat Exchanger and Boiler Output Required From the Selection table, based on the Pool Capacity (gallons) select the appropriate heat exchanger and boiler capacity based on the Heat Up Rate.
For Example: For a 15x30 ft pool, averaging 5.5 ft deep, the pool capacity is 24,475 gallons. Using the Selection table, a 1˚F/hr heat up rate, requires 208,625 BTUH and a MP5x12-16 heat exchanger. Check for Heat Loss to surroundings Heat Loss (BTUH) = 12 x _____Pool Surface Area (sq ft) x _____(Desired Pool Temp(˚F) – _____Coldest Ambient Temp During Use (˚F)) Use this calculation to verify that the Boiler output exceeds the heat loss to surroundings.
Chemical Feed 90°F
Swimming Pool Bypass/ Balancing Valve
Bypass/ Balancing Valve
Filter
S1 80°F
180°F P2 150°F P1
Boiler
Piping: Pools and Spas always have high water flow rates, from 30 th 50 gpm for a typical residential pool, to higher gpms for commercial applications. Because the MP Series is a high efficiency heat exchanger and does not require the full pool gpm flow, a BYPASS balancing valve is required to bypass 50% to 80% of the pool water. This bypass/balancing valve should be adjusted and permanently set at start-up. Chemical feeds MUST be down stream from the heat exchanger, and a check valve should also be installed to prevent back-flow of chemicals into the heat exchanger when the pump is not in operation. Controls: Temperature control of the pool should be based on a return water temperature stat, controlling (on/off) the boiler and boiler pump. Temperature control of the 90-100˚F feed to the pool should be controlled by permanent adjustment of the bypass valve.
Spas To select a MP Series Heat Exchanger for a Spa:
Startup: Start up the system, and adjust the pool side bypass valve so that the pool heats up no faster then 2˚F/hr, initially. After the pool reaches approximately 78-80˚F, and the boiler water is entering at 180˚F, adjust the pool side bypass/balancing valve to obtain 90˚F to 100˚F water to the pool. Then adjust the boiler bypass/balancing valve so that approximately 150˚F water is being returned to the boiler.
Step 1
Determine the Capacity (gallons) of the Spa or Hot Tub. (See Step 2 in Pool calculations)
Step 2
From the Spa selection table, based on the Spa Capacity (gallons) select the appropriate heat exchanger and boiler capacity based on the Heat Up Rate. Note: A spa is typically operated at 100˚F to 105˚F, requires a faster heat up rate, and due to aeration, has a higher loss to ambient surroundings. The above table is based on 3F/hr plus ambient losses due to aeration. 2˚F/Hr Heat up Rate, plus Aeration Spa Capacity Gallons 750 1,000 1,500 2,000 4,000 6,000 8,000 1. 2. 3. 4. 5.
Boiler Output Required (BTUH) 31,300 41,725 62,588 83,450 166,900 250,350 333,800
Boiler Side Minimum GPM 2 3 4 6 11 17 22
FlatPlate Model MP5x12-6 (1" MPT) MP5x12-8 (1" MPT) MP5x12-10 (1" MPT) MP5x12-16 (1" MPT) MP5x12-20 (1-1/4" MPT) MP5x12-30 (1-1/4" MPT) MP5x12-40 (1-1/4" MPT)
Typical Design Conditions: 180˚F Boiler Water to HX, 105˚F Spa Water. For 160˚F Boiler Water, multiply product model by 1.5 to select larger required model. (ie, FP5x12-16 at 180˚F, use FP5x12-24 at 160˚F). For 200˚F Boiler Water and Steam, use model number shown for 180˚F. Bypass/Balancing valve on SPA side of HX REQUIRED to allow for full spa pump flow of 20 to 60 gpm. Use individual HX’s for each SPA.
Diverting Valve Product Instructions Applications
Operation
Viega NA three way diverting valves can be used for temperature control in many heating and snowmelting applications.
Viega NA diverting valves have one entry port and two exit ports (see diagram below). Depending upon the position of the valve stem, flow is diverted from one exit port to the other.
Features • Includes solder tailpieces (1-1/4” and 1-1/2” models use same valve body with different tailpieces) • Pre-installed high limit kit • Compatible with most Viega NA actuators (Three Position 18 003, Two Position 18 005, and nonelectric models 16 101 thru 16 105)
Specifications Materials: Bronze valve body Brass and corrosion-resistant steel internal components EPDM rubber seals Actuator threads:
Dimensions
M30 x 1.0
Max working temp.:
242°F (120°C) Max working pressure: 145 psi (10 bar) Max differential pressure (tight shut-off on both end positions of valve discs) 3/4” 10.9 psi (75 kPa) 1” 7.3 psi (50 kPa) 1-1/4” 2.9 psi (20 kPa) 1-1/2” 2.9 psi (20 kPa)
Solder tailpieces
Siz e
Stock C ode
3/4"
20 001
1"
L H H1 (inches) (inches) (inches) 3.15
3.94
20 002
3.54
4.06
1.97
1-1/4" 20 003
4.53
4.65
2.52
1-1/2"
4.53
4.65
2.52
20 041
Siz e
D2 (inches)
L2 (inches)
3/4"
0.875
0.91
1"
1.125
1.18
1-1/4"
1.375
1.57
1-1/2"
1.625
1.26
VIEGA NORTH AMERICA • Building Tomorrow’s Plumbing & Heating Technology ... Today 3 Alfred Circle • Bedford, MA 01730 • Ph: 877-VIEGA-NA • Fax: 781-275-5398 • E-Mail: [email protected] • www.viega.com
PI-20001-02/04
1.85
Diverting Valve Product Instructions Piping a Diverting Valve with a Circulator Installed in Boiler
Floorheating
Install spring check valve on bypass as shown!
Supply Return
Diverting Valve
Diverting valves may also be used to control small snow melting systems as shown at right. For further details, refer to instructions with Viega NA Snow Melt controls.
Non-Electric Fixed Water Temp. Control
SNOWMELT SYSTEM SUPPLY
Diverting Valve
HEAT EXCHANGER
BOILER
SNOWMELT SYSTEM RETURN
50
1-1/4” and 1-1/2” models share the same valve body, so the pressure drop for these models is the same. Valve size
cv
3/4” 1” 1-1/4” 1-1/2”
5.3 7.6 11.1 11.1
1/
4"
&
1-
1/
1" 1-
Pressure Drop (feet of head)
Pressure drop values for Viega NA diverting valves may be determined from the chart at right (cv values are listed below).
2"
3/
4"
Pressure Drop
10
5
1
0.5
0.1 1
2
3
4
5 6 7 8 9 10
20
30
40 50
Flow Rate (gpm) VIEGA NORTH AMERICA • Building Tomorrow’s Plumbing & Heating Technology ... Today 3 Alfred Circle • Bedford, MA 01730 • Ph: 877-VIEGA-NA • Fax: 781-275-5398 • E-Mail: [email protected] • www.viega.com
PI-20001-02/04
- Data Brochure
D 710
3-Way Mixing Valves 710 - 714
05/05
The 3-Way Brass Mixing Valves 710, 711, 712, 713, and 714 are used to mix supply water from a heat source with water returning from a system. They are designed for use in either closed loop or open loop hydronic systems. All valves have standard female NPT threads. The valve provides a maximum leak through rate of 1% to allow for water expansion during temperature changes. The valve position can be manually set using the handle. An Actuating Motor 741 can be used to automatically operate the valve.
Sequence of Operation When the flap is in the fully closed position, 100% of the heating system return water is supplied to the system. When the valve flap is in the fully open position, 100% of the boiler supply water enters the heating system. Mixing of the water takes place when the valve flap is in an intermediate position.
Installation Check the contents of the package. If any of the items listed below are missing or damaged, please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or local tekmar representative. Types 710 - 714 include • One Mixing Valve & One Data Brochure D 710
return
from boiler
supply
supply
from boiler
supply
from boiler
return
• Factory postion • No changes required
• Rotate handle 1/4 turn • Flip face plate over
from boiler
supply
return
return
• Rotate handle 1/2 turn • Flip face plate over
• Rotate handle 1/4 turn
Replacement Parts
0
5 7 9 1 3
brass screw
10
The Mixing Valve Handle Kit M3047 contains a replacement manual valve handle, a brass screw, a “C” clip, and a position indicator plate. “C” clip handle
indicator plate
© 2005
D 710 - 05/05
Technical Data 3-Way Mixing Valves 710 - 714 Brass Literature Maximum Operating Pressure Operating Temperature Range Valve Body and Vane Shaft Seal Main Seal
— — — — — —
Acceptable Fluid Media
D 710 146 psi (10 bar) -20 to 248°F (-28 to 120°C) CW 617N - EN 12165 Brass Viton “O” ring EPDM Perioxide “O” ring
— Chilled and hot water with antifreeze and anticorrosive compounds (max 60%), glycol, ethyl alcohol glycol, propylene dichloride alcohol, mono ethyl alcohol, ethyl methyl alcohol, glycerine. Not for use with media based on mineral oil components or chlorinated pool water.
W Type
Pipe Size
CV Value
Dimension H
Dimension W
Packaged Weight
710 711 712 713 714
3/4” 1” 1-1/4” 1-1/2” 2”
7 14 21 32 51
1-1/2” (38 mm) 1-1/2” (38 mm) 1-5/8” (41 mm) 2-3/16” (56 mm) 2-5/16” (60 mm)
3” (76 mm) 3” (76 mm) 3-1/4” (82 mm) 4-3/8” (111 mm) 4-5/8” (119 mm)
1.9 lbs (860 g) 1.6 lbs (730 g) 1.8 lbs (800 g) 6.7 lbs (3020 g) 5.6 lbs (2520 g)
710
3
4
Valve Performance 712, 713, 714
m3/h 1.5
1
711
1
0.6 0.4
0.5
m of head
2
Normal Operating Range
0
3
6
9
712
3
0.8 1
psi
ft of head
3
12
15
713
0
0
2
4
6
8 10 12 US Gal/min
14
16
18
20
1
714
0.8 2 1
1
Normal Operating Range
0.6 0.4
0.5
0.2
0.2 0
m3/h
18
m of head
1.5
2
1
psi
Valve Performance 710, 711 0
ft of head
H
0
0
0
0 0
10
20
30 40 50 US Gal/min
60
70
80
Limited Warranty and Product Return Procedure Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract. The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers. Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NONVIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW. Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2005 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
All specifications are subject to change without notice. Printed in Canada. D 710 - 05/05.
- Data Brochure
D 720
4-Way Mixing Valves 720 - 724
05/05
The 4-Way Brass Mixing Valves 720, 721, 722, 723, and 724 are used to mix supply water from a heat source with water returning from a system. They are designed for use in either closed loop or open loop hydronic systems. All valves have standard female NPT threads. The valve provides a maximum leak through rate of 1% to allow for water expansion during temperature changes. The valve position can be manually set using the handle. An Actuating Motor 741 can be used to automatically operate the valve.
Sequence of Operation When the flap is in the fully closed position, 100% of the boiler supply water is returned to the boiler and 100% of the heating system return water is supplied to the system. When the valve flap is in the fully open position, 100% of the boiler supply water enters the heating system and 100% of the heating system return water returns to the boiler. Mixing of the water takes place when the valve flap is in an intermediate position.
Valve in closed position
Valve 50% position
Valve fully open
Installation STEP ONE ------------- GETTING READY ----------------------------------------------------------------------------------------------------Check the contents of the package. If any of the items listed below are missing or damaged, please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or local tekmar representative. Types 720 - 724 include
• One Mixing Valve & One Data Brochure D 720
STEP TWO ------------- MOUNTING ------------------------------------------------------------------------------------------------------------Clockwise to Open
Counter Clockwise to Open
to system
0
from system
from boiler
from system
to boiler
5 3 1 97
0
As delivered, no changes required.
10
5 7 9 1 3
to system
Valve Closed
10
Valve Closed
from boiler
Remove the “C” clip from the shaft. Turn over the indicator plate in order to reverse the scale. Re-install the indicator plate, “C” clip and handle. (components shown below)
to boiler
Replacement Parts
0
5 7 9 1 3
brass screw
10
The Mixing Valve Handle Kit M3047 contains a replacement manual valve handle, a brass screw, a “C” clip, and a position indicator plate. “C” clip handle
indicator plate © 2005
D 720 - 05/05
Technical Data 4-Way Mixing Valves 720 - 724 Brass Literature Maximum Operating Pressure Operating Temperature Range Valve Body and Vane Shaft Seal Main Seal
— — — — — —
Acceptable Fluid Media
D 720 146 psi (10 bar) -20 to 248°F (-28 to 120°C) CW 617N - EN 12165 Brass Viton “O” ring EPDM Perioxide “O” ring
— Chilled and hot water with antifreeze and anticorrosive compounds (max 60%), glycol, ethyl alcohol glycol, propylene dichloride alcohol, mono ethyl alcohol, ethyl methyl alcohol, glycerine. Not for use with media based on mineral oil components or chlorinated pool water.
W Type
Pipe Size
CV Value
Dimension H
Dimension W
Packaged Weight
720 721 722 723 724
3/4” 1” 1-1/4” 1-1/2” 2”
7 14 21 32 51
3” (76 mm) 3” (76 mm) 3-1/4” (82 mm) 4-3/8” (111 mm) 4-5/8” (119 mm)
3” (76 mm) 3” (76 mm) 3-1/4” (82 mm) 4-3/8” (111 mm) 4-5/8” (119 mm)
2.2 lbs (980 g) 1.8 lbs (800 g) 2.2 lbs (980 g) 7.3 lbs (3320 g) 5.8 lbs (2640 g)
1.5
2
1
720
3
4
Valve Performance 722, 723, 724
m3/h 1.5
1
721
1
0.4
0.5
ft of head
0.6
m of head
2
Normal Operating Range
0
3
6
9
722
3
0.8 1
psi
ft of head
3
12
15
723
0
0
2
4
6
8 10 12 US Gal/min
14
16
18
20
1
724
0.8 2 1
1
Normal Operating Range
0.6 0.4
0.5
0.2
0.2 0
m3/h
18
m of head
Valve Performance 720, 721 0
psi
0
H
10
57 9 1 3
0
0
0
0 0
10
20
30 40 50 US Gal/min
60
70
80
Limited Warranty and Product Return Procedure Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract. The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers. Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NONVIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW. Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2005 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
All specifications are subject to change without notice. Printed in Canada. D 720 - 05/05.
4.2 Sizing the 3-Way Mixing Valve
4.2 Sizing the 3-Way Mixing Valve USGPM
Flow resistance through valve in mbar
Fig. 19 Sizing chart for 3-way mixing valve The selection of the size of the mixing valve can be done using the above diagram. The best mixing ratio and velocity conditions with the 3-way mixing valve are achieved when the selected mixing valve is within the shaded section. Selecting the mixing valve in the following way will ensure the best mixing effect for the system supply and the system return:
1. In the right-hand side of the diagram, select the amount of Btu/h / kW available for the heating system or the heating loop. 2. Draw a straight line up through the temperature drop available through the system (diagonal lines). 3. Select the temperature differential where the vertical line crosses the diagonal line. Follow a line to the left into the shaded area (the shaded area is between 4” and 8” w.c. / 10 and 25 mbar). The line crossed indicates the proper size mixing valve. 4. Extend a vertical line downwards and read the exact pressure drop through the valve; add this pressure drop to the pump head.
5167 158
5. By extending the horizontal line to the left of the diagram, the USGPM / m3/h of water flow can be read.
Example The dashed line in the above diagram shows a boiler with 170,600 Btu/h / 50 kW output. The heating system has a temperature differential between boiler supply and return of 36°F / 20°C and the selected mixing valve is 1¼”. The required pumping rate is 9 USGPM / 2.1 m3/h.
3.2 Sizing the 4-Way Mixing Valve
3.2 Sizing the 4-Way Mixing Valve USGPM
Flow resistance through valve in mbar
Fig. 5 Sizing chart for 4-way mixing valve
Selecting the mixing valve in the following way will ensure the best mixing effect for the system supply and the system return:
1. In the right-hand side of the diagram, select the amount of Btu/h / kW available for the heating system or the heating loop. 2. Draw a straight line up through the temperature drop available through the system (diagonal lines). 3. Select the temperature differential where the vertical line crosses the diagonal line. Follow a line to the left into the shaded area (the shaded area is between 4” and 8” w.c. / 10 and 25 mbar). The line crossed indicates the proper size mixing valve.
Example The dashed line in the above diagram shows a boiler with 170,600 Btu/h / 50 kW output. The heating system has a temperature differential between boiler supply and return of 36°F / 20°C and the selected mixing valve is 1¼”. The required pumping rate is 9 USGPM / 2.1 m3/h.
4. Extend a vertical line downwards and read the exact pressure drop through the valve; add this pressure drop to the pump head. 5. By extending the horizontal line to the left of the diagram, the USGPM / m3/h of water flow can be read.
5167 158
The selection of the size of the mixing valve can be done using the above diagram. The best mixing ratio and velocity conditions with the 4-way mixing valve are achieved when the selected mixing valve is within the shaded section.
Hydro Separator
CALEFFI
series 548
cert. n° 0003
ISO 9001
01076/03 NA
Function This device consists of several different functional components, each of which meets specific requirements, typical of the circuits used in heating and air-conditioning systems. ·
Hydronic separator To keep connected hydronic circuits totally independent from each other.
·
Dirt remover To permit the separation and collection of any impurities present in the circuits. Provided with a valved connection with discharge piping.
·
Automatic air vent valve For automatic venting of any air contained in the circuits. Provided with a valved connection for maintenance purposes.
Product range Series 548 Threaded hydronic separator Series 548 Flanged hydronic separator Series 548 Flanged hydronic separator with insulation
sizes 1”, 1 1/4”, and 1 1/2” F with union sizes 2", 2 1/2", 3" and 4" ANSI Flange sizes 2", 2 1/2", 3" and 4" ANSI Flange
Technical specification series ➫ Materials Separator body: Air vent body: Shut-off and drain valve body: Air vent seal: Air vent float: Performance Max. operating pressure: Temperature range: Medium: Max. percentage glycol: Connections Separator: Front (thermometer pocket): Air vent relief: Drain valve:
548 threaded
548 flanged
Epoxy resin painted steel Brass Brass EPDM PP
Epoxy resin painted steel Brass Brass, chrome plated VITON Stainless steel
150 psi (10 bar) 32-230°F (0÷110°C) Water, non hazardous glycol solutions 50%
150 psi (10 bar) 32-230°F (0÷110°C) Water, non hazardous glycol solutions 50%
1”, 1 1/4”, 1 1/2” F with union 1/2” F hose connector
2", 2 1/2", 3" and 4" with flanged ANSI 150 CLASS 3/8” F 1 1/4” F
Technical characteristics of insulation (supplied on flanged models only)
Operating principle
Internal part - Material: rigid closed cell expanded polyurethane foam - Thickness: 2.3/8" (60 mm) - Density: 3 lb/ft3 (45 kg/m3) - Thermal conductivity (ISO 2581): 0.16 BTU/in (0.023 W/mK) - Temperature range: 32-220°F (0÷105°C) External cover - Material: - Thickness: - Fire resistance (DIN 4102):
embossed aluminium 7.0-mil (0,7 mm) Class 1
Head covers - Heat moulded material:
PS
Dimensions
When a single system contains a primary production circuit, with its own pump, and a secondary user circuit, with one or more distribution pumps, operating conditions may arise in the system whereby the pumps interact, creating abnormal variations in circuit flow rates and pressures. The hydronic separator creates a zone with a low pressure loss, which enables the primary and secondary circuits connected to it to be hydronically independent of each other; the flow in one circuit does not create a flow in the other if the pressure loss in the common section is negligible. In this case, the flow rate in the respective circuits depends exclusively on the flow rate characteristics of the pumps, preventing reciprocal influence caused by connection in series. Therefore, using a device with these characteristics means that the flow in the secondary circuit only circulates when the relevant pump is on, permitting the system to meet the specific load requirements at that time. When the secondary pump is off, there is no circulation in the secondary circuit; the whole flow rate produced by the primary pump is by-passed through the separator.
A
A
E
E
With the hydronic separator, it is thus possible to have a production circuit with a constant flow rate and a distribution circuit with a variable flow rate; these operating conditions are typical of modern heating and air-conditioning systems.
Hydro Separator
Hydro Separator
Series 548
Series 548
Tmax 220°F Pmax 150 psi
Tmax 230°F Pmax 150 psi
Tmax 220°F Pmax 150 psi
Gp
Gs
D
C
A
A
C
D
Tmax 230°F Pmax 150 psi
B
1” 0.5
Primary
secondary circuit
F
Code A B C D E Weight (lb) 548006A 1" 8 7/8” 7 5/8” 6 5/8” 8” 7.5 548007A 1 1/4” 9 3/4” 8 7/8” 9 1/2” 8 1/2” 8.3 548008A 1 1/2” 11 1/8” 9 1/4” 10 1/4” 8 7/8” 12.5 Size Volume (gal)
primariy circuit
B
1 1/4” 0.7
1 1/2” 1.3
Code A B 548050/2A 2” 1 1/4" 548060/2A 2 1/2” 1 1/4" 548080/2A 3” 1 1/4" 548100/2A 4” 1 1/4" DN 50 4
Secondary
Gp
Gs
Gprimary = Gsecondary
DN 65 4
C 13” 13” 18” 18”
D E F 9 1/2" 15 1/2” 14” 9 1/2" 15 1/2” 14” 15" 17" 18” 15" 17" 18” DN 80 8
Weight (lb)
73 79 108 117
DN 100 8
Primary
Three possible hydronic balance situations are shown below.
Secondary
Gp
Gs
Gprimary > Gsecondary
Primary
Secondary
Gp
Gs
Gprimary < Gsecondary
Constructional details
Insulation The flanged separators are available complete with a hot pre-formed insulation shell. The presence of the outer aluminium cover also makes the separator completely sealed, even preventing water vapour entering from outside. For these reasons, this type of insulation can also be used in chilled water circuits, as it prevents the formation of condensate on the surface of the valve body.
Isolating the air vent valve In flanged separators, the air vent is isolated manually, using a shut-off ball valve. In threaded separators, however, the air vent body is automatically isolated by the built-in valve, which closes when the air vent body is removed.
Dirt removing element A vital function of the hydronic separator is carried out by the dirt removing element inside the device. This makes is possible to separate and collect any impurities which may be present in the system.
Hydronic characteristics The hydronic separator should be sized according to the maximum flow rate value at the inlet. The selected design value must be the greatest between the primary circuit and the secondary circuit.
These impurities are removed by means of the drain valve, which can be connected to a discharge pipe.
THREADED
Size gpm m3/h
1” 11 2,5
1 1/4” 18 4
FLANGED
1 1/2” 26 6
2” 40 9
2 1/2” 80 18
3” 124 28
4” 247 56
Quick-Fit
TM
Modular Piping System
Simplifies and Speeds Any Boiler Installation
■ ■ ■ ■ ■ ■
Quick-Mix Mixing Station for Radiant Flooring Applications Quick-Pump Station for High-Temperature Zones Quick-Header Manifold for Multi-Temp Heating Systems Saves Time and Money on Any Boiler Installation Eliminates Incorrect Valve or Motor Installations Ensures a Clean, Finished and Professional Installation www.buderus.net
Quick-Fit
TM
Modular Piping System
The Quick-Fit System takes only minutes to connect and includes all the piping, valves, circulating and control elements to feed both radiant floor heating zones and conventional high-temperature heating zones. The Quick-Fit System can be used to connect virtually any piping arrangement.
Quick-Mix Station
The Quick-Mix Station is a fully assembled radiant heat mixing station that conveniently combines a motorized mixing valve, circulator pump, shutoff valves, a check valve and temperature gauges in a compact, attractive foam-insulated unit. It includes everything needed to automatically adjust water temperature for radiant floor heating. The mixing valve is controlled by a Buderus Logamatic 2107 control which considers both inside and outside temperatures for maximum efficiency and economy.
Quick-Header Manifold
Quick-Header Manifolds allow you to combine multiple stations in order to customize any application. Available in a 2-station or 3-station configuration, they simplify installation, requiring only a supply to and return from the header. Quick-Header manifolds are made of heavy-gauge welded steel and have durable insulated covers. Union connections make mounting Quick-Mix and Quick-Pump stations to the Quick-Header manifold fast and easy.
Quick-Pump Station
The Quick-Pump Station simplifies installation and piping of high-temperature heating applications such as fin-tube baseboard, panel radiators or hydo-air systems. An optional larger pump is available.
TC62 Outdoor Reset Control
The optional TC62 Outdoor Reset Control Motor can be added to the Quick-Mix Stations to configure systems that require multiple mixed water temperatures. The unit’s digital display shows water temperature and adjustments. The TC62 has programmable heating curve and automatic warm weather shutdown. Sensor wiring is quick and easy using plug-in cables. The unit also accepts input from optional room sensors.
Specifications Fittings Pipe Systems Insulated Shell Valve Handles Ball Seats
Dimensions Height Depth Inlet/Outlet
Hot-pressed brass, Ms5 Precision Pipes Precision Pipes Epp with patented snap seam Heat-resistant plastic O-ring seal: EPDM elastomers Flat seals: AFM 34 or EPDM PTFE Model: Grundfos UPS25-58 Optional: Grundfos UP26-99 Voltage: 115 Vac/60Hz 13¼” 7¾” 51/8”
Width 11½” Connection 1¼“ NPT Female
444-99-006 12/04 © Buderus Hydronic Systems 2004
50 Wentworth Ave Londonderry, NH 03053 Phone: 603-552-1100 Fax: 603-421-2719
Hydronic Accessories
i Series Mixing Valve Taco iSeries Mixing Valves are a breakthrough in precision, cost effective temperature control for heating systems. Available in 2-way mixing or 3-way injection configurations, iSeries valves provide either outdoor reset control or fixed water supply temperature. Additionally, iSeries valves protect the boiler against flue gas condensation. A microprocessor-based control is built into the valve actuator, to which all wiring connections are made. All-in-one iSeries Mixing Valves deliver optimum zone-by-zone temperature control, with built-in boiler protection.
H YDRONIC C OMPONENTS & S YSTEMS
©Taco Catalog # 100-19 Supersedes: New
Effective Date: 11/01/03 Printed in USA
Submittal Data # 101-089 Supersedes: New
Submittal Data Information i Series Mixing Valves
Effective: 11/01/03
Outdoor Reset Application
iSeries Features
Use the Taco Outdoor Reset iSeries Mixing Valves instead of a conventional injection system. With a full featured outdoor reset control built right into the actuator there is no need for an externally mounted reset control or expensive control valve. The iSeries valves can also be set up to do zone-by-zone outdoor reset, providing optimal comfort control for every zone.
• 2-Way Injection or 3-Way Mixing • Operates Off Constant Power or Relay End Switch • Ball Valve Design, High Cv • Manual Operation Button • Solid State Microprocessor Design • Compact Design • Easy, One-handed Actuator Removal • 125 PSI Shutoff Pressure • Plug-in Low Voltage Connections • Multi-Status LED Indicator Light • Fail Safe Mode • Sensors Included
The direct drive actuator modulates a 2-way or 3-way valve that injects different rates of hot water, supplying virtually any water temperature to the heating system. Working off an adjustable reset ratio, the valve’s maximum and minimum system supply temperatures can be adjusted to support all types of jobs, including staple-up radiant floors that require a higher starting temperature. The iSeries valves include an adjustable boiler protection function which prevents low water temperatures from returning to the boiler. With a multi-status LED indicator light, plug-in wiring connections and an easy to remove actuator, the installation could not be easier.
Additional Outdoor Reset Features
Outdoor Sensor
• Selectable Maximum Supply Temperature (110°F, 130°F, 150°F, or Off) • Selectable Minimum Supply Temperature (85°F, when max. supply temp. is set to 150°F or Off) • Adjustable Minimum Boiler Return Temperature (120°F, 135°F, or Off) • Warm Weather Shutdown (70°F or Off) • Adjustable Heating Curve (0.2-2.2 Reset Ratio)
Supply Sensor
Outdoor Sensor
Supply Sensor
A
iSeries-R
iSeries-R
Supply Sensor
Boiler Sensor
B
iSeries-R
Outdoor Sensor
C
Boiler Sensor
A B
C
Boiler Sensor
Multiple Temperature System
Additional Setpoint Features
See applications brochure for additional schematics.
• Adjustable Setpoint Dial (80°F to 180°F) • Selectable 15°F Setback • Optional Boiler Protection (Set at 135°F)
Setpoint Application
• Maximum Operating Pressure: 300 psi, (2,100 kPa) • Fluid Temperature Range: 20°F to 240°F (-7°C to 115°C) @ 135°F (57°C) ambient • Ambient Conditions: Indoor Use Only, -22°F to 185°F (-30°C to 85°C), < 90% Non-Condensing • Service: Closed Systems, Hot and Chilled Water, up to 50% Glycol • Seat Leakage: Drop-Tight Close Off • Power Supply: 24 VAC ±10% 50/60 HZ • Electrical Rating: 24 VAC, 60 HZ, 0.16 Amps. Do not exceed number of valves per transformer rating. Example: Do not use more than 12 valves per 40VA transformer • Sensors: NTC Thermistor, 10 k Ω @ 77°F (25°C ±0.2°C) β=3892
High Temperature Zones Low Temperature Zones C
Supply Sensor
B A
iSeries-S
Specifications
Use the Taco Setpoint iSeries Mixing Valves instead of a thermostatic mixing valve for precise dial-in temperature control to a heating system. The direct drive actuator modulates a 2-way or 3-way valve to inject different rates of hot water into the cooler system return water. In combination with the optional boiler protection sensor, the iSeries valves provide the unique benefit of optimal temperature control with boiler protection. The setpoint temperature is adjustable from 80°F to 180°F using a dial located on top of the actuator. A 15°F setback of the supply water can be initiated for additional unoccupied or nighttime setback control. An external multi-status LED indicator light, plug-in wiring connections and an easy to remove actuator makes installation and diagnostics a snap.
Return Sensor
See applications brochure for additional schematics.
Dimensions
iSeries Ordering 1
i
Actuator Type: R Outdoor Reset S Setpoint
iSeries Size: 1/2" 050 3/4" 075 1" 100
Connection: Sweat C Thread T
Ball Type: 2 2-way 3 3-way
C
Valve Size
A
1/2”
3”
2-3/8” 3-9/16” 4-9/16” 2-9/16” 3-1/8” 1-9/16”
3/4”
3”
2-3/8”
1”
3”
2-3/8” 3-11/16”
B
2-Way
3-3/4”
3-Way
E
F
G
4-7/8”
2-5/8”
3-1/8” 1-9/16”
5”
2-5/8”
3-1/8” 1-9/16”
H YDRONIC C OMPONENTS & S YSTEMS
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360 Taco (Canada) Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3 / (905) 564-9422 / Fax (905) 564-9436 www.taco-hvac.com
iValve, 3-Way Mixing Working with SR502/503 Switching Relay with DHW Priority T DHW Aquastat Power Input Outdoor Sensor
H
Z ONE1
SR 503
N
24 Volt
24 VAC POWER INPUT
N
P
ZC
Z ONE2
Z ONE3
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
FUSE 1 AMP
Transformer
SENSOR COMMON
T
A
24 VAC POWER
BACK OF iVALVE-R MIXING VALVE ACTUATOR
BOILER POWER SUPPLY GREEN OUTDOOR
Thermostats
H
X1
X2 ZR
Z ONE1
Z ONE2
Z ONE3
C R
SENSOR ERROR RED
DHW Circ.
Supply Sensor
iSeries-R
C C
B B A A
Boiler Sensor
iValve, 4-Way Mixing Working with Zone Valve Control BACK OF iVALVE-R MIXING VALVE ACTUATOR
24 Volt
Motor
M
End Switch
SENSOR ERROR RED
M
T T ZONE 1 FUSE (5 AMP MAX)
Transformer
C R
POWER IN
Power H Input N
24 VAC SENSOR COMMON POWER INPUT
E ND SWITCH
N/O COM N/C
T
Thermostats
T T ZONE 2
T T ZONE 3
ZVC 403 THREE ZONE ZONE VALVE CONTROL ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
End Switch
BOILER POWER SUPPLY GREEN OUTDOOR
Factory Installed Transformer
T
Motor
Outdoor Sensor
Supply Sensor
iSeries-R
Boiler Sensor
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard
7ATER #IRCULATION 0UMPS #IRCULATORS
2ADIANT -IXING "LOCK 4HE 4ACO 2ADIANT -IXING "LOCK REPRESENTS A BREAKTHROUGH IN THE DESIGN CONTROL AND INSTALLATION OF RADIANT SYSTEMS 4HE PATENT PENDING DESIGN COMBINES A VARIABLE SPEED INJECTION MIXING CONTROL INJECTION CIRCULATOR SYSTEM CIRCULATOR AND AIR ELIMINATION INTO A SINGLE UNIT %XTREMELY VERSATILE THE 2ADIANT -IXING "LOCK CAN BE SET UP AS AN OUTDOOR RESET CONTROL A SETPOINT CONTROL OR A DELTA 4 LIMITING CONTROL !LL THIS WITH NO SPECIAL PIPING NO BALANCING VALVE NO CLOSELY SPACED TEES NO EXTERNAL CONTROLS NO COMPLEX WIRING JUST FOUR PIPE CONNECTIONS AND YOUR INSTALLATION IS COMPLETE 7ELCOME TO THE NEW AGE OF 2ADIANT
-ANIFOLD 2EADY
4ACO #ATALOG 3UPERSEDES .%7
%FFECTIVE 0RINTED IN THE 53!
3UBMITTAL $ATA 3UPERSEDES .EW
3UBMITTAL $ATA )NFORMATION 2ADIANT -IXING "LOCK &EATURES
s !LL IN /NE )NJECTION 0IPING 0UMPING !IR %LIMINATION #ONTROL 0ACKAGE s /NLY 0IPE #ONNECTIONS 2EQUIRED s 0LUG IN ,OW 6OLTAGE #ONNECTIONS s 3OLID 3TATE -ICROPROCESSOR $ESIGN s 'REATLY $ECREASES )NSTALLATION 4IME s 3UBSTANTIAL 3PACE 3AVINGS s ,INE #ORD )NCLUDED (ARD 7IRE /PTION s "RONZE #ASING FOR /PEN OR #LOSED 3YSTEMS s 2EPLACEABLE #ARTRIDGE $ESIGN s -AINTENANCE &REE 7ET 2OTOR #IRCULATORS s /PERATION -ODES /UTDOOR 2ESET 3ETPOINT OR $ELTA 4 WITH ,IMIT s 0OWERED OR 5NPOWERED $EMAND 3IGNAL s )NTEGRAL #HECK 6ALVE s -AIN 3YSTEM 0UMP #ONTACT s 0UMP /PERATION #ONTROL /VERRIDE 3WITCH s !UTOMATIC 0UMP %XERCISE s !DJUSTABLE 2ESET 2ATIO s 7ARM 7EATHER 3HUTDOWN s "OILER #ONTROL OR %NABLE 3ETTING s "OILER 0ROTECTION s ,ARGE ,#$ $ISPLAY s #ª OR &ª s /UTDOOR AND 3TRAP ON 3ENSORS INCLUDED
%FFECTIVE
!PPLICATION
4HE 4ACO 2ADIANT -IXING "LOCK 2-" IS A COMPLETE INJECTION MIXING SYSTEM )NTEGRAL TO THE UNIT IS A VARIABLE SPEED INJECTION CIRCULATOR CONSTANT SPEED SYSTEM CIRCULATOR AIR ELIMINATION AND THE ELECTRONICS TO DRIVE IT ALL 7ITH ONLY FOUR PIPING CONNECTIONS NEEDED THE 2-" GREATLY REDUCES THE TIME AND SPACE REQUIRED FOR INSTALLATION SEE &IG ! 4HE 2-" CAN BE SET UP TO OPERATE AS AN OUTDOOR RESET CONTROL A SETPOINT CONTROL OR A DELTA 4 LIMITING CONTROL CREATING FLEXIBILITY NEVER SEEN BEFORE IN A SINGLE UNIT &IG !
"
!
/PERATION !
"
#
$
(OT WATER FROM THE BOILER LOOP ENTERS THE 2-" AT THE "OILER 3UPPLY PORT ! 4HE COOLER RETURN WATER FROM THE RADIANT LOOPS ENTERS AT THE 3YSTEM 2ETURN PORT " )N THE MIDDLE OF THESE TWO PORTS ANY AIR IN THE SYSTEM IS PURGED THROUGH THE INTEGRAL 4ACO (Y 6ENT 4HE INJECTION CIRCULATOR VARIES IN SPEED TO BLEND THE TWO TEMPERATURES INJECTING THE EXCESS REQUIRED TEMPERATURE BACK THROUGH THE "OILER 2ETURN PORT # 4HE CONSTANT SPEED SYSTEM CIRCULATOR DELIVERS THE REQUIRED BLENDED WATER TEMPERATURE TO THE RADIANT LOOP THROUGH THE 2ADIANT 3UPPLY PORT $
3IZING AND 0IPING
4HE 2ADIANT -IXING "LOCK CAN HANDLE RADIANT LOAD DEMANDS OF UP TO "45S 9OUR CURRENT METHOD OF ZONING THE RADIANT LOOPS MANIFOLDS ZONE VALVES ETC DOES NOT CHANGE WITH THE INSTALLATION OF THE 2-" -ULTIPLE 2ADIANT -IXING "LOCKS CAN BE USED TO SEPARATE THE DISTINCTIVE TEMPERATURE REQUIREMENTS BETWEEN MANIFOLDS .O SPECIAL PIPING JUST CONNECTIONS AND YOUR INSTALLATION IS COMPLETE
0ERFORMANCE $ATA &LOW