MiniMate EX
Liebert
Keeping Business in Business
LPN: SLE MMX TDM E.2 HPN: 272033 (17/8/99)
ENVIRONMENTAL CONTROL
Technical Data Manual
Table of Contents System nomenclature Introduction Standard features - all models Optional features - all models Technical data - MMX04E Technical data - MMX05E Technical data - MMX06E Technical data - MMX08E Technical data - MMX10E Technical data - MMX14E Technical data - all models Electrical data - all models Sound data - all models Dimensional data - MMX04/05/06E Dimensional data - MMX08/10/14E Dimensional data - MMC04/05/06 Dimensional data - MMC08/10/14 Typical installation schematics Refrigerant connections
1 2 3 7 9 10 11 12 13 14 15 16 18 19 21 23 24 25 27
MiniMate EX - Technical Data Manual
System nomenclature The nomenclature for MiniMate EX system is as follows:
MMX
04
E
Freecooling: E = With Freecooling
Model size: Capacity in kW (Nominal)
Liebert MiniMate EX
Six models are available. All models are of the split type, comprising of an Evaporator unit with a freecooling module and a Condensing unit. Each Evaporator unit is matched to a Condensing unit as outlined below:
Evaporator Unit
MMX04E
MMX05E
MMX06E
MMX08E
MMX10E
MMX14E
Condensing Unit
MMC04
MMC05
MMC06
MMC08
MMC10
MMC14
SLE MMX TDM E.2 (08/99)
1
MiniMate EX - Technical Data Manual
Introduction Precision environment control may be defined as the simultaneous control of air temperature, humidity, distribution and cleanliness on a continual, around-the-clock basis. Conventional building or ‘ comfort’ systems, as they are called, are not designed for this 24-hour, year-round usage, they lack the ability to provide the precision and reliability or ‘close control’ that is so critical to many applications. All Liebert MiniMate EX units are built in accordance with European directives 98/37/CE (89/392/CEE; 91/368/CEE; 93/68/CEE), 89/336/CEE; 73/23/CEE. The Liebert Air Conditioning Quality System is approved by LRQA in accordance with the standards UNI EN ISO 9001: 1994. Each unit is supplied complete with a Test Certificate and Declaration of Conformity. All units carry the “CE” mark and fully comply with European Directives concerning mechanical, electrical and electromagnetic safety.
Applications The MiniMate EX unit is ideally suited for precision close control of many different applications where internal floorspace is unavailable. Typical applications would be: · Telecommunications Base Stations · Computer Rooms · Telephone Exchanges · Network Controllers (LAN) · Telecom Repeater Stations · Laboratories
2
System type The MiniMate EX is a split unit comprising of two distinct sections: · Direct Expansion Evaporator Section (including the Fresh Air Free Cooling Module) · Condensing Unit Section The evaporator section consists an evaporator coil, two direct driven fans, refrigeration components and EU3 filter. The fresh air free cooling module consists of a motorised modulating damper. The condenser section consists of an high efficiency compressor, a condenser coil, a direct driven axial fan, and a refrigerant condensing pressure controller. Models MMX04E, MMX05E and MMX06E are designed for operation at 230V/1ph/50Hz. Models MMX08E, MMX10E and MMX14E are designed for operation at 400V/3ph/50Hz. All models can operate from an emergency supply of 24V or 48V DC, (evaporator fan, controls and freecooling damper only), to maintain emergency cooling during periods of mains power loss.
Accessibility In the Evaporator unit, access to the air filters, fans, reheats, freecooling damper and the electrical panel is available from the base through removable panels. In the Condensing unit, access to the compressor, electrical panel, refrigeration components and condenser fan is available through removable panels.
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Standard features - all systems Cabinet The cabinet of both the Evaporator unit and the Condensing unit is manufactured from zinc coated steel, it is then de-greased and painted in “Pearl White” (RAL7032) dry powder epoxy resin paint. The paint finish is easily cleaned and is hard wearing. The Condensing unit cabinet has been designed specifically for outdoor applications, all materials, fittings and components have been selected to provide maximum weather protection, durability and security (vandal-proof cabinet). The unit has removable panels (a special key is required) which give access to all internal components. The condenser air inlet is through the rear of the unit and discharges through the front. A metal safety grid prevents accidental contact with the fan and the coil. The compressor is located in the side of the Condensing unit, separated from the airstream. In the Evaporator unit, which is mounted indoors, air inlet is from the rear of the unit and air discharge is from the front through a double deflecting grille. The evaporator panels are insulated with 10 mm, 70 kg/m3 density, mineral wool.
Refrigeration circuit The units are single circuit with a hermetic compressor (rotary o n models MMX04/05/06E, scroll on m odel s MMX08/10/14E). The circuit incorporates a thermostatic expansion valve (capillary tube on models MMX04/05/06E) which controls the refrigerant flow to the evaporator. A filter dryer is provided in the liquid line to eliminate moisture from the system and maximum efficiency for increased working life. The compressor has a manual-reset high pressure switch for high pressure protection and a high pressure alarm circuit to warn of high system pressures, allowing corrective action to be taken before a significant loss of temperature control occurs. The low pressure switch is auto-resetting and detects low pressure conditions such as loss of refrigerant charge. The low-pressure switch incorporates a delay for winter start operation.
Evaporator section Evaporator coil The evaporator coil is constructed from copper tubes with aluminium fins to ensure maximum heat transfer. It is designed to maximise the available surface area resulting in low face velocities, low internal air pressure drops and the high sensible heat ratios. A corrosion resistant drain pan is provided on all models.
SLE MMX TDM E.2 (08/99)
Evaporator fan motor The units are equipped with two centrifugal fans with forward curved impellers, housed in galvanised steel. A single double-shafted motor is directly coupled to the fans (Model MMX14E has two direct drive fan motors). The fan impellers are statically and dynamically balanced and equipped with self-lubricating bearings. The fan is mounted on vibration-absorbing rubber supports to reduce vibration transmission between the fan and the unit frame. This vibration attenuation helps to keep noise emission to a minimum. The fan motor is single-phase, IP44 rated and complete with internal thermal protection.
Condensing section Condenser coil The condenser coil is constructed from copper tubes with aluminium fins to ensure maximum heat transfer. It is designed to maximise the available surface area resulting in low face velocities and low internal air pressure drops.
Condenser fan The condenser section is equipped with a single axial fan with integral motor. It is also statically and dynamically balanced. The fan impeller and casing are made from zinc-coated steel to protect against corrosion. The direct drive motor includes sealed-for-life bearings.The fan motor is IP54 rated and complete with internal thermal protection. The fan motor is controlled by a pressure switch to maintain a steady condensing temperature. Fan speed control A factory fitted solid state fan speed controller is installed to maintain the refrigerant condensing pressure. The controller varies airflow through the condenser to maintain a constant pressure. The advantages of fan speed control are two-fold. Higher reliability of the system due to less starts/stops of the compressor and a lower noise level because the fan is running at a lower speed, mainly during night-time.
Filters The direct expansion filter is EU3 and is located within the cabinet before the evaporating coil. The filter provides filtration of both the recirculated and the fresh air to obtain the required degree of air cleanliness in the room. The filters can easily be removed from the unit. The filters are 45 mm deep on models MMX04/05/06E and 60mm deep on models MMX08/10/14E. The filters are pleated air filters, specially designed to minimise the air pressure drop and improve efficiency.
3
MiniMate EX - Technical Data Manual
Standard features - all systems (continued) SIDE VIEW
SIDE VIEW
1
3
4
9
5
8
6
7
11
Return air
3
2
4
5
1
Return air
10
6
9
10
11
Conditioned air FRONT VIEW
Conditioned air
Outside air
537
690
FRONT VIEW
1050 770
15
15
800
TOP VIEW
AIR FLOW N.4 x ø8
AIR
TOP VIEW
526
AIR FLOW
=
887
=
AIR FLOW
MMX04/05/06E without Freecooling Section ITEM 1 2 3 4 5 6 7 8
DESCRIPTION Air return grille Freecooling damper (Freecooling models only) Air filter Evaporator coil Evaporator fan Air discharge duct Damper motor (Freecooling models only) Air suction grille (Freecooling models only)
MMX08/10/14E with Freecooling Section ITEM 9 10 11 12 13 14 15 16
DESCRIPTION Electric heaters (optional) Heater safety thermostat (optional) Electrical panel (evaporator unit) Condenser fan Electrical panel (condensing unit) Compressor Fan speed controller Condenser coil
Figure 1 - Layout of components in the MiniMate Unit
4
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Standard features - all systems (continued) Electric panel The electrical panel of the Evaporator unit is housed in a secure compartment isolated from the air stream, and is in compliance with EN 60204-1. The panel contains the controller PCB, MCBs for individual components and contactors. A mains MCB is supplied as standard. A single phase transformer powers the 24 V rail to the controller. Automatic restart is provided as standard. The Condensing unit receives mains power and control signals from the Evaporator unit.
Controls T he Microface environm ental control s ys t em i s microprocessor based and can be programmed to match the unique needs of any application. The processor integrates the separate mechanical and electrical components into a ‘state-of-the-art’ conditioned space support system that controls and monitors temperature, air flow and air cleanliness. The control system offers a tailored and well proven advance in reliability and control flexibility allowing the unit to modify its performance in response to changing critical space conditions. The controller allows local monitoring and programming of the following room conditions: Temperature (oC) Temperature setpoint (5.0oC – 40.0oC in steps of 0.1 oC) Temperature sensitivity (1.0oC - 10oC in steps of 0.1 oC) The parameters are enunciated using symbols and text on an LCD display. Normal operating modes are indicated by symbols on the display. Alarm conditions activate a visual indicator. The following alarms are standard: · High temperature
For a full list of all the options and alarms available with the Microface controller, refer to the Microface Controller Operation Manual (P/N SLE MF OM). The controller also incorporates a sequential auto-restart timer, allowing field adjustable time delays to be applied to unit restart after a power loss (or other shutdown). The timers allow multiple units to be restarted while limiting instantaneous inrush current.
Fresh air free cooling Fresh air free cooling consists of a hinged damper plate and motorised actuator. When ambient temperatures permit, compressorised cooling will be deactivated and cool outside ambient air is diverted directly to the conditioned space to provide “free” cooling. The duct collar for the fresh air freecooling module is available in rectangular and circular form.
Refrigerant R22 HCFC is the standard refrigerant used in the MiniMate EX range. An optional “Zero ODP” refrigerant, R407C is available to special order.
Packaging As standard, the units are wrapped in bubble-wrap to protect painted surfaces, enclosed in a cardboard box and mounted on a wooden pallet.
Warranty clauses The warranty does not cover any damage or malfunction of the unit which may occur during or as a result of operating the unit outside of the specified application limits. Liebert does not accept responsibility for any damage caused by improper use of the product.
· Low temperature · Fan failure · High pressure alarm · Low pressure alarm · Electrical reheat high temperature · Memory failure · Common alarm
SLE MMX TDM E.2 (08/99)
5
MiniMate EX - Technical Data Manual
Standard features - all systems (continued) Crankcase heaters Crankcase heaters are fitted to all models. They maintain minimum refrigerant temperature and are energised while the unit is powered and the compressor is off.
Operating limits MiniMate EX units are designed for operation within the following working limits (the limits are applicable to newly commissioned machines which have been correctly installed and maintained).
Models MMX04/05/06E Power Supply: 230 VAC ± 10%/1/50 Hz 48±16% VDC (with the emergency cooling option) 24±16% VDC (with the emergency cooling option)
Models MMX08/10/14E Power Supply: 400 VAC ± 10%/3/50 Hz
Models MMX04/05/08/10E External ambient: From -25°C (with fan speed control) to 50°C.
Models MMX06/14E External ambient: From -25°C (with fan speed control) to 48°C.
All models Internal ambient: From 20°C, (30% to 80% R.H.) to 32°C, 40% R.H. Storage conditions: From -40°C, 5% R.H. to 55°C, 90% R.H.
6
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Optional features - all systems Electric reheat The reheat option is available for all models. Models MMX04E, MMX05E, and MMX06E are supplied with two reheat elements for a total capacity of 3 kW. Models MMX08E, MMX10E, and MMX14E are supplied with two reheat elements for a total capacity of 6 kW. For special applications where power consumption is of critical importance, the units can be supplied with 1 reheat element only (capacity of 1.5 and 3kW respectively). Reheat control is of the ON-OFF type. The reheat is provided with a manual reset, reheat safety thermostat, to disable the reheat in the event of high temperature. The reheat safety thermostat also incorporates a magneto-thermal switch which protects the reheat from short circuits, should the cable harness be damaged accidentally.
R407C An optional “Zero ODP” refrigerant, R407C is available with the unit.
Emergency cooling The unit can be supplied with an emergency cooling system that allows the indoor fans, the controller and the motor damper to run from a 48V or 24V DC power supply. This allows the unit to maintain air circulation inside the room in the event of mains power failure. For the emergency cooling option, the standard evaporator fans are replaced by two free wheel fans with backward curved blades, each driven by a DC motor. The DC supply is provided by 24V or 48V batteries located inside the conditioned space. The evaporator fans, the controller and the damper actuator are permanently powered from a battery DC supply. The other components, compressor, reheat etc. are mains powered (230V or 400V depending on the model). In the event of mains failure, these other components will not operate.
Grilles Air inlet and discharge grilles, mounted in the conditioned space, are available in a range of colours. The grilles are manufactured in zintec and finished in epoxy powder paint.
Freecooling options The freecooling module of the Evaporator Unit can be supplied complete with all main accessories for the installation: · Indoor wall plate for Freecooling flexible duct connections (two circular holes) · Fr eecool i ng f l exi bl e duct s ( ø202 m m f o r MMX04/05/06E models, ø250 mm for MMX08/10/14E) complete with fixing clamps · Indoor wall plate for Freecooling rigid duct connection (single rectangular hole) · External rain-proof grille with metallic prefilter for Freecooling air intake · Overpressure gravity damper, to discharge the exhaust air from inside, designed specially for this unit · External rain-proof grille, to protect the overpressure damper from bad weather and foreign bodies All grilles and dampers are made of extruded aluminium, to achieve maximum lifetime.
Special packaging Where the unit is to be transported by sea or in other cases where heavy duty packaging is required, special crating is available. This can consist of either a wooden crate over the standard cardboard/bubble wrap packaging or the entire unit can be encased in a wooden box complete with silicon desiccant.
Interconnection cables A full range of interconnecting cables is available for applications where the units are configured as Run and Standby or where the controller display is mounted remotely from the unit, consult Liebert Application Engineers for specific details.
SLE MMX TDM E.2 (08/99)
7
MiniMate EX - Technical Data Manual
Optional features - all systems (continued) Hiromatic graphic The Hiromatic Graphic sets even higher standards in p u r pos e-des igned control system s for preci s i on air-conditioning. It simultaneously monitors the critical space and signals alarms either locally or remotely. The graphics screen displays all the major parameters, including symbolic representation of unit functions, such as heating, cooling etc.; in addition temperature variations with time can be presented graphically on the screen. All diagnostic procedures, including the checking and calibration of input and output signals, and of the microprocessor itself, can be run from the front panel
Features · Backlit LCD graphics display · User interface via pushkeys · Battery-backed clock for date/time and real time functions · Password control for setpoints, unit/control setup and service functions · Graphics display of temperature and humidity over a 24 hour period The Hiromatic Graphic is specifically designed for group management of a number of individual units although it can be used in stand-alone applications. Due to its large graphical display area, combined with exceptional contrast, it allows the user to move around easily within the network of connected unit controllers (up to max. 16). It is possible to control/adjust each connected units operations from a single point. The controller is menu-driven and user menu’s are available in 10 languages. The controller records the last 120 “events” (Alarms, Warnings etc.) occurring in the system along with a “Graphic Data Record” for each connected unit. The Graphic Data Record displays the temperature readings from each unit for the last 24 hours (stored since the last start-up of the unit). The Hiromatic Graphic controls date and time functions using them as operating information for the customer and as a reference whenever a status change occurs, logging the status change in the “Status Report”. Details of the event which occurred, the date and time at which the event occurred are also stored. Using buffered RAM, the Hiromatic also stores the operating hours of each component (compressor, fan, electric heaters, etc.) for each connected unit.
BEMS Interface The Hiromatic Graphic controller allows units on a network to be integrated with the Hirolink Communications Bus when an RS422 card is installed at the back of Hiromatic. Hiromatic can control up to 8 Microface units in this configuration and communicate the relevant data to Hirolink. Hirolink works as a communications manager between the Hiromatic Graphic and Microface units and industry standard field busses and protocols used in Building Management Systems such as Mod-Bus, J-Bus, Satchwell, etc. Note: For full details of the controller, refer to the Hiromatic Graphic Operations Manual, (P/N SLE HG OM ).
TXV on models MMX04/05/06E An externally equalised, adjustable, thermostatic expansion valve is available as a special option on models MMX04/05/06E. Consult Liebert Applications Engineers for details.
Freecooling prefilter An optional pre-filter is available for models with the freecooling module. The pre-filter protects the main unit filter from excess dirt and dust and increases the main filter lifetime. It is recommended for applications where the ambient air is likely to be dirty.
Humidity control If required, the unit can be supplied to control temperature and humidity in the conditioned area, it is supplied as standard for temperature control only.
Extended alarm board For applications where remote indication of alarms is required, a special extended alarm board is available. A volt-free warning contact is available for remote indication of High Temperature, Low Temperature and Reheat Overtemperature. A further contact is available for remote indication of High Pressure, Low Pressure, Fan Failure and Controls Failure.
A feature uniquely available with the Hiromatic controller is “Sleep Mode” Sleep Mode allows units to be programmed to switch on and off at different times of the day, and on different days of the week. The Hiromatic Graphic controller can be supplied installed in a unit, or in kit form for installation in a remote control panel.
8
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Technical data - MMX04E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
4.2 4.0 0.9 3.9
4.1 3.9 1.0 4.3
3.9 3.9 1.1 4.8
3.8 3.8 1.3 5.3
3.6 3.6 1.4 5.9
4.5 4.1 0.9 4.0
4.4 4.1 1.0 4.4
4.2 4.0 1.2 4.9
4.1 4.0 1.3 5.4
3.9 3.9 1.4 6.0
4.9 4.5 1.0 4.0
4.6 4.4 1.1 4.4
4.5 4.4 1.2 4.9
4.3 4.3 1.3 5.4
4.1 4.1 1.4 6.0
5.0 5.0 1.0 4.1
4.9 4.9 1.1 4.5
4.8 4.8 1.2 5.0
4.6 4.6 1.3 5.5
4.4 4.4 1.4 6.0
Indoor condition: 21°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 24°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 27°C, 47% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 30°C, 40% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
5.1
2.8
0.5
kW
6.6
4.2
1.9
kW
8.0
5.6
3.3
kW
9.4
7.0
4.7
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE MMX TDM E.2 (08/99)
9
MiniMate EX - Technical Data Manual
Technical data - MMX05E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
5.1 4.5 1.2 5.4
4.9 4.5 1.3 5.7
4.7 4.4 1.5 6.2
4.5 4.3 1.6 6.8
4.4 4.2 1.8 7.6
5.5 4.7 1.3 5.6
5.3 4.6 1.4 5.9
5.1 4.6 1.5 6.3
4.9 4.5 1.7 7.0
4.8 4.4 1.8 7.8
5.8 5.0 1.3 5.7
5.6 5.0 1.4 6.0
5.5 4.9 1.5 6.4
5.2 4.8 1.7 7.1
5.0 4.8 1.8 7.9
6.0 5.8 1.3 5.8
5.7 5.7 1.4 6.1
5.6 5.6 1.5 6.5
5.4 5.4 1.7 7.3
5.2 5.2 1.9 8.2
Indoor condition: 21°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 24°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 27°C, 47% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 30°C, 40% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
5.1
2.8
0.5
kW
6.6
4.2
1.9
kW
8.0
5.6
3.3
kW
9.4
7.0
4.7
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
10
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Technical data - MMX06E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
5.9 5.2 1.5 6.6
5.6 5.1 1.6 7.2
5.5 5.0 1.8 8.0
5.3 4.9 2.0 8.8
5.0 4.8 2.2 9.7
6.3 5.3 1.5 6.7
6.1 5.3 1.7 7.3
5.9 5.1 1.8 8.1
5.7 5.1 2.0 8.9
5.5 5.0 2.2 9.9
6.7 5.7 1.5 6.3
6.5 5.7 1.7 7.4
6.3 5.6 1.9 8.2
6.0 5.5 2.1 9.1
5.8 5.4 2.3 10.1
6.9 6.5 1.5 6.8
6.7 6.4 1.7 7.5
6.4 6.4 1.9 8.3
6.2 6.2 2.1 9.2
6.1 6.1 2.3 10.2
Indoor conditions: 21°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 24°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 27°C, 47% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 30°C, 40% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
5.1
2.8
0.5
kW
6.6
4.2
1.9
kW
8.0
5.6
3.3
kW
9.4
7.0
4.7
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE MMX TDM E.2 (08/99)
11
MiniMate EX - Technical Data Manual
Technical data - MMX08E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
7.5 7.5 1.4 2.9
7.5 7.5 1.5 3.0
7.2 7.2 1.7 3.2
7.0 7.0 1.9 3.5
6.8 6.8 2.1 3.9
8.1 8.1 1.4 3.1
7.9 7.9 1.5 3.1
7.8 7.8 1.7 3.2
7.6 7.6 1.9 3.5
7.2 7.2 2.1 3.9
8.7 8.7 1.4 3.1
8.5 8.5 1.5 3.1
8.2 8.2 1.7 3.2
8.0 8.0 1.9 3.5
7.8 7.8 2.1 3.9
9.2 9.2 1.4 3.0
9.0 9.0 1.5 3.1
8.7 8.7 1.7 3.3
8.5 8.5 1.9 3.6
8.2 8.2 2.2 3.6
Indoor condition: 21°C, 50% RH Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 24°C, 50% RH Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 27°C, 47% RH Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor condition: 30°C, 40% RH Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
7.8
4.3
0.7
kW
10.0
6.4
2.8
kW
12.1
8.5
5.0
kW
14.2
10.7
7.1
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
12
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Technical data - MMX10E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
10.0 9.4 2.1 3.9
9.7 9.3 2.3 4.2
9.3 9.1 2.5 4.6
9.0 9.0 2.8 4.9
8.8 8.8 3.0 5.3
10.8 9.7 2.1 4.0
10.5 9.6 2.3 4.3
10.1 9.5 2.5 4.6
9.7 9.3 2.8 5.0
9.4 9.2 3.1 5.4
11.3 10.4 2.1 4.0
11.0 10.3 2.3 4.3
10.7 10.2 2.6 4.6
10.4 10.1 2.8 5.0
9.9 9.9 3.1 5.4
11.9 11.9 2.1 4.0
11.5 11.5 2.4 4.3
11.2 11.2 2.6 4.7
10.9 10.9 2.8 5.1
10.5 10.5 3.1 5.4
Indoor conditions: 21°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 24°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 27°C, 47% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 30°C, 40% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
7.8
4.3
0.7
kW
10.0
6.4
2.8
kW
12.1
8.5
5.0
kW
14.2
10.7
7.1
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE MMX TDM E.2 (08/99)
13
MiniMate EX - Technical Data Manual
Technical data - MMX14E DX Capacity (50Hz)* Outdoor temperature [°C] 25
30
35
40
45
14.0 13.0 3.3 7.0
13.5 12.8 3.7 7.4
13.0 12.6 4.1 8.0
12.4 12.4 4.6 8.5
11.8 11.8 5.1 9.1
15.1 13.4 3.4 7.0
14.6 13.3 3.8 7.4
13.8 13.0 4.2 7.9
13.3 12.8 4.7 8.4
12.7 12.7 5.2 9.0
15.8 14.4 3.4 7.1
15.3 14.3 3.8 7.6
14.7 14.1 4.3 8.0
14.1 14.1 4.8 8.5
13.5 13.5 5.3 9.1
16.3 16.3 3.5 7.2
15.9 15.9 3.9 7.7
15.4 15.4 4.3 8.1
15.0 15.0 4.8 8.7
14.4 14.4 5.4 9.3
Indoor conditions: 21°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 24°C, 50% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 27°C, 47% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Indoor conditions: 30°C, 40% r.h. Total cooling capacity Sensible cooling capacity Compressor absorbed power Compressor absorbed current
kW kW kW A
Freecooling Capacity Outdoor temperature [°C] 10
15
20
kW
11.6
6.3
1.1
kW
14.7
9.5
4.2
kW
17.9
12.6
7.4
kW
21.1
15.8
10.5
Indoor temperature: 21°C Sensible cooling capacity
Indoor temperature: 24°C Sensible cooling capacity
Indoor temperature: 27°C Sensible cooling capacity
Indoor temperature: 30°C Sensible cooling capacity
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engineers. Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
14
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Technical data - all models MODEL MMX04E MMX05E MMX06E MMX08E MMX10E MMX14E POWER SUPPLY 230V/1ph/50Hz 400V/3ph/50Hz CABINET Frame Galvanised steel with epoxy powder paint Insulation Type Mineral wool, 10 mm thick OVERALL DIMENSIONS (Evaporator Unit) Height mm 310 395 Width mm 800 1055 Depth mm 800 (1050 with freecooling) 1100 (1395 with freecooling) Weight kg 54 (62 with freecooling) 96 (108 with freecooling) OVERALL DIMENSIONS (Condensing Unit) Height mm 537 690 Width mm 800 1050 Depth mm 285 500 Weight kg 49 49 56 87 90 111 EVAPORATOR COIL Tubes/Fins Copper tubes/ aluminium deep wave fins EVAPORATOR FAN 2 direct Quantity/Type 2 fans, single motor drive fan motors No. of Poles 4 Blade Material Galvanised sheet steel Drive Type Direct drive 3 Air Flow (without freecooling) m /h 1510 2590 4140 Air Flow (with freecooling) m3/h 1400 2230 3600 AIR FILTER Quantity/ Type 1 pleated / EU3 (Eurovent EU 4/5) ELECTRIC REHEAT (Optional) Type / No. of Steps Sheath Type / 1 Total Heating Capacity kW 3 6 COMPRESSOR Type Rotary Scroll Refrigerant R22 (R407C option) CONDENSER COIL Tubes/ Fins Copper tubes/ aluminium fins CONDENSER FAN Quantity/Type 1 / Axial fan - direct drive Poles 4 Control Type Modulating fan speed control Max. Rotation Speed RPM 1390 1210 Blade Material Galvanised sheet steel Drive Type Direct drive Air Flow m3/h 2410 5500
SLE MMX TDM E.2 (08/99)
15
MiniMate EX - Technical Data Manual
Electrical data - all models Standard features Model MMX04E MMX05E MMX06E MMX08E MMX10E MMX14E
Model MMC04 MMC05 MMC06 MMC08 MMC10 MMC14 +
Power Supply
Evaporator fan
230/1/50 230/1/50 230/1/50 400/3/50 400/3/50 400/3/50
Power Supply
Electric heating (opt.)
OA
FLA
LRA
1.1 1.1 1.1 3.2 3.2 2.5x2
1.2 1.2 1.2 5.0 5.0 3.6x2
1.75 1.75 1.75 -
Absorbed Power [kW] 0.2 0.2 0.2 0.7 0.7 0.6x2
Condenser fan
230/1/50 230/1/50 230/1/50 400/3/50 400/3/50 400/3/50
Rated Power [kW] 3 3 3 6 6 6
FLA 13.1 13.1 13.1 8.70 8.70 8.70
Compressor (R22)
OA
FLA
LRA
1.3 1.3 1.3 3.4 3.4 3.4
1.4 1.4 1.4 3.5 3.5 3.5
3.0 3.0 3.0 7.4 7.4 7.4
Rated Power [kW] 0.3 0.3 0.3 0.8 0.8 0.8
OA+
FLA
LRA
5.9 7.1 8.8 3.9 5.3 8.5
10 12 15 4.8 6.6 12.4
34 37 48 31 43 65
Rated Power [kW] 1.4 1.7 2.0 2.1 3.0 4.7
Compressor Operating Amps are quoted at 55oC condensing temperature.
Optional features Model MMX04E MMX05E MMX06E MMX08E MMX10E MMX14E
Evaporator fan motor 48 Vdc (2 motors)* FLA [A] 2.7 x 2 2.7 x 2 2.7 x 2 NA NA NA
Rated Power [Watts] 70 x 2 70 x 2 70 x 2 NA NA NA
Evaporator fan motor 24 Vdc (2 motors)** FLA [A] 5.4 x 2 5.4 x 2 5.4 x 2 NA NA NA
Rated power [Watts] 102 x 2 102 x 2 102 x 2 NA NA NA
OA = Absorbed current, in standard operation. FLA = Full Load Amps, LRA = Locked Rotor Amps NA = Not available at the current time. This feature will be available in the near future, consult Liebert Applications Engineers * With emergency cooling 48 Vdc option ** With emergency cooling 24 Vdc option
16
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Electrical data - all models (continued) Mains disconnect switch and cabling recommendations * VERSION OF MODEL
MCB (Differential current = 0.3 A) 230V/1/50Hz
400V/3/50Hz
MMX04/05/06E
20A
-
MMX08/10/14E
-
20A
MMX04/05/06E
20A
-
MMX08/10/14E
-
20A
MMX04/05/06E
20A
-
MMX08/10/14E
-
20A
Cooling only
Cooling/ Heating Cooling/ Heating/ Freecooling
VERSION OF MODEL Emergency Cooling
MMX04/05/06E MMX08/10/14E
MCB (Differential current = 0.3 A) 24V DC 10A -
48V DC 16A -
Cable sizing 2 x 4 mm2 Earth x 4 mm2 4 x 4 mm2 Earth x 4 mm2 2 x 4 mm2 Earth x 4 mm2 4 x 4 mm2 Earth x 4 mm2 2 x 4 mm2 Earth x 4 mm2 4 x 4 mm2 Earth x 4 mm2
Cable sizing 2 x 2.5 mm2 -
* Recommendations only, superceded by local and national codes and regulations.
SLE MMX TDM E.2 (08/99)
17
MiniMate EX - Technical Data Manual
Sound data - all models Sound Pressure Levels
Model MMX04E MMX05E MMX06E MMX08E MMX10E MMX14E MMC04 MMC05 MMC06 MMC08 MMC10 MMC14
Indoor/ Outdoor
Octave Band Frequency (Hz)
Sound Pressure Level [dB(A)]
31.5
63
125
250
500
1000
2000
4000
8000
Indoor
58
52
56
50
48
51
49
46
42
55
Indoor
48
55
61
58
56
54
52
51
49
60
Indoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor
49 55 55 55 46 46 48
56 57 57 55 52 53 55
61 54 54 55 57 58 59
58 46 46 50 56 56 57
57 44 44 47 54 54 55
55 40 40 41 50 52 53
52 37 37 38 47 48 49
51 28 28 28 46 46 47
50 23 23 24 45 45 45
62 46 47 48 56 57 59
* Sound Pressure levels are quoted at 2m from the unit, in the free field.
18
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Dimensional data - MMX04/05/06E MMX04E, MMX05E AND MMX06E without freecooling
310
800
29
800
29
E E SIDE VIEW
800
350
60
FRONT VIEW
350
6 no. Mounting Holes ø8mm
Conditioned air
40
E
E
Return air
12
834
12
TOP VIEW
I U S REAR VIEW
Item E S U I
SLE MMX TDM E.2 (08/99)
Description Electrical connections Condensate drain Refrigerant outlet Refrigerant inlet
19
MiniMate EX - Technical Data Manual
Dimensional data - MMX04/05/06E (continued) MMX04E, MMX05E AND MMX06E with Freecooling
310
1050
29
800
29
E SIDE VIEW
60
250
FRONT VIEW
350
air return
800
conditioned air outside air
350
6 no.Mounting Holes ø8mm
E 40
E
12
834
12
TOP VIEW
Duct Flange 190 x 560 x 35mm
185
S 220
Item E S U I
20
300
280
I
190
310
310
I U
U
90
125
30
2 no. Duct Flanges 200 Diameter, Height 35 mm
S 90
560
REAR VIEW
REAR VIEW
Circular duct
Rectangular duct
150
Description Electrical connections Condensate drain Refrigerant outlet Refrigerant inlet
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Dimensional data - MMX08/10/14E MMX08E, MMX10E and MMX14E without Freecooling
395
1100
30
1055
E
30
SIDE VIEW
320
1100
320
90
FRONT VIEW
320
6 no. Mounting Holes ø8mm
Return air
50
Conditioned air
12
1086
12
TOP VIEW
395
I U S REAR VIEW
Item E S U I
SLE MMX TDM E.2 (08/99)
Description Electrical connections Condensate drain Refrigerant outlet Refrigerant inlet
21
MiniMate EX - Technical Data Manual
Dimensional data - MMX08/10/14E (continued) MMX08E, MMX10E and MMX14E with Freecooling
395
1395
30
1055
30
E SIDE VIEW
Return air 1100
320
320
90
295
FRONT VIEW
Conditioned air Outside air
50
320
6 no. Mounting Holes ø8 mm
TOP VIEW
Duct Flange 190 x 560 x 35mm
2 no. Duct Flanges 200 Diameter, Height 35 mm
I
395
395
I U
U
S REAR VIEW Circular duct
Item E S U I
22
S REAR VIEW Rectangular duct
Description Electrical connections Condensate drain Refrigerant outlet Refrigerant inlet
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Dimensional data - MMC04/05/06 MMC04, MMC05 and MMC06 Condensing units
537
285
42
190
40
2 no. Square-head caged nuts M6 (2 per side - 4 in total)
SIDE VIEW
15
15
770 2 no. Square-head caged nuts M6 (2 per face - 4 in total) 800
FRONT VIEW
AIR FLOW
AIR FLOW
REAR VIEW
Item E U I
SLE MMX TDM E.2 (08/99)
TOP VIEW
Description Electrical connections Refrigerant outlet Refrigerant inlet
23
MiniMate EX - Technical Data Manual
Dimensional data - MMC08/10/14 MMC08, MMC10 and MMC14 Condensing unit I 500
690
690
U
1050
SIDE VIEW
FRONT VIEW
E
REAR VIEW
AIR FLOW 4 no. ø8 mm Mounting Holes
AIR FLOW 526
AIR FLOW
=
887
=
AIR FLOW
TOP VIEW
Item E U I
24
Description Electrical connections Refrigerant outlet Refrigerant inlet
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Typical ceiling mounted installation 1
11
2
6
7
210
8 9
3 10
5 4
550
200 400
Item 1 2 3 4 5 6 7 8 9 10 11
SLE MMX TDM E.2 (08/99)
Description Unit with freecooling module (optional rectangular ope.) Unit with freecooling module (standard circular ope) Over-pressure damper Grille for over-pressure damper Hole in wall 2 freecooling flexible ducts with fixing clamps Wall-plate for freecooling circular duct Aluminium grille with metallic prefilter Metallic prefilter Hole in wall Wall-plate for freecooling rectangular duct
25
MiniMate EX - Technical Data Manual
Typical wall mounted installation
With freecooling
Without freecooling
1300 (MMX08/10/14E)
1000 (MMX04/05/06E)
800 (MMX04/05/06E) RETURN AIR
1100 (MMX08/10/14E)
CONDITIONED AIR
min. 200
1895 (MMX08/10/14E)
1550 (MMX04/05/06E)
1050 (MMX04/05/06E)
1395 (MMX08/10/14E))
CONDITIONED AIR
RETURN AIR
min. 500
OUTSIDE AIR
SIDE VIEW
26
SIDE VIEW
SLE MMX TDM E.2 (08/99)
MiniMate EX - Technical Data Manual
Refrigerant connections
SLE MMX TDM E.2 (08/99)
27
Liebert
European Headquarters
Liebert Globe Park, Marlow, Buckinghamshire, SL7 1YG, England. Tel: 44-1628-403200 Fax: 44-1628-403203 Telex: 449716
International Headquarters
Liebert Corporation 1050 Dearborn Drive, P.O. Box 29186 Columbus, Ohio 43229 USA Tel: 1-614-888-0246
© Liebert
® All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the logo, are While every precaution has been taken to ensure accuracy and completeness in this manual, Liebert assumes no responsibility and disclaims all liability for damages resulting from the use of the information contained herein or any errors or omissions.
registered trademarks of Liebert Corporation. Printed in England. LPN: SLE MMX TDM E.2 HPN: 272033 (17/8/99)