Preview only show first 10 pages with watermark. For full document please download

38ycb-c1pd

   EMBED


Share

Transcript

Product Data 38YCB 50 Hz Heat Pump ® 38YCB Sizes 024 thru 060 Quality Assurance The 38YCB 50 Hertz Outdoor Sections of Split-System Heat Pumps are designed for quiet, reliable heating during the winter and cooling during the summer. With a SEER up to 10.0 and COP up to 3.0, these heat pump systems provide economy of operation through energy conservation when used with components designated by manufacturer. They recover heat for indoor comfort from outdoor air during the heating season and, by automatically reversing the refrigerant system, remove indoor heat and excess humidity during the cooling season. FEATURES/BENEFITS Electrical Range — Units are offered in single phase 220–240v. Threephase units are available in sizes 036, 048, and 060 in 400v. Size Range — The 38YCB is available in nominal sizes 024, 036, 048 and 060 to meet the needs for residential and light commercial applications. Compressor — Designed specifically for heat pump duty, with energy efficiency during heating and cooling operation. Each compressor is hermetically sealed against contamination to assure long life and dependable performance, internally sprung (units with reciprocating compressor) and externally mounted on rubber isolators for quiet operation. Continuous compressor operation is approved down to –30°F (–34.4°C) in the heating mode, and down to 55°F (12.8°C) in the cooling mode. Copyright 1994 Carrier Corporation Form 38YCB-C1PD Thi d t t d ith F M k 404 (See heating and cooling performance tables.) For compressor usage, see Compressor data table. Built-in-Reliability Components — Includes a suctiontube accumulator that reduces the amount of liquid refrigerant that reaches the compressor; a lowpressure switch to stop the compressor if refrigerant charge is lost; a crankcase heater on units with reciprocating compressor and all 3-phase units to keep compressor oil warm and free of refrigerant for maximum lubricity; an internal compressor relief valve for high-pressure protection. Discharge Muffler — Minimizes low frequency sound and pressure pulsation generated by compressor discharge gas. Defrost Control Board — Incorporates a defrost relay, defrost timer, and low-voltage terminations. The defrost control is a time and temperature initiation/termination control which includes 3 fieldselectable time periods of 30, 50, and 90 minutes. The control includes builtin 5-minute compressor delay for units equipped with scroll compressors (see Compressor data table). Weather-Protective Cabinet — Steel is protected with a heavy coating commonly called “galvanizing,” and treated with a layer of zinc phosphate. A coat of modified polyester powder coating is then applied and baked-on, providing each unit with a hard, smooth finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting rust-resistant, quality appearance. Unit Design — All units are equipped with totally enclosed fan motors for greater reliability under rain and snow conditions. The large, wraparound coil uses copper tube and enhanced aluminum fin and is designed for optimum heat transfer during heating and cooling. The vertical air discharge carries the sound and air up and away from adjacent patio areas and foliage. Coils can be cleaned with a common garden hose. External Service Valves — Both service valves are brass, front seating type. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures. The 38YCB has sweat field connections. Safety — All units are designed and manufactured in accordance with Underwriters Laboratories (U.L. 1995) standard for safety, heating and cooling equipment. Model number nomenclature 38YCB 036 9 0 1 Electric Heat Pump Packaging Series Nominal Capacity 024 — 24,000 Btuh (7.0 Kw) 048 — 48,000 Btuh (14.1 Kw) 036 — 36,000 Btuh (10.6 Kw) 060 — 60,000 Btuh (17.6 Kw) 2 Electrical 7 — 230-1-50 9 — 400-3-50 Physical data UNIT SIZE 024 036 048 SERIES 70 70, 90 70, 90 90 145/65.9 222/100.9 225/102 261/118.6 Copeland & Recip Copeland & Recip Millennium & Scroll Millennium &Scroll 9.5/4.32 13.0/5.9 OPERATING WT (Lb/Kg) COMPRESSOR Manufacturer & Type REFRIGERANT Control Charge (Lb/Kg) @ 15 ft CONDENSER FAN Air Discharge Air Qty (CFM L/S) Motor RPM (60 Hz) CONDENSER COIL Face Area (Sq ft/m 2) 060 22 Piston 5.5/2.5 7.0/3.18 Propeller Type, Direct Drive Vertical 3300/1541 1125/525 2600/1214 12.42/1.15 22.40/2.08 18.67/1.73 Sweat CONNECTION (In./mm ID) Vapor Liquid 5/8 / 15.875 REFRIGERANT TUBES* (In./mm OD) Vapor Liquid 5/8 / 15.875 3/4 / 19.05 7/8 / 22.225 3/8 / 9.525 3/4 / 19.05 1-1/8 / 28.575 3/8 / 9.525 * Tube sizes are for lengths up to 50 ft (15.24m). For lengths over 50 ft (15.24m), consult Long-Line Application Guideline. NOTE: See unit Installation Instructions for proper installation. METERING DEVICE UNIT SIZE OUTDOOR PISTON INDOOR PISTON* 024-70 49 63 036-70, 90 61 76 048-70, 90 73 88 060-90 76 96 *Piston listed is for any approved coil combination. 3 Accessories ORDERING NUMBER DESCRIPTION KAAWS0101AAA Winter Start Control KAATD0101TDR Time-Delay Relay KAAFT0101AAA Evaporator Freeze Thermostat† KHAIR0101AAA Isolation Relay† KSACY0101AAA Cycle Protector N/A Compressor Start Assist (Capacitor/Relay) — Sizes 036 (90), 048 (90) 060 (90) KAAHS0601AAA Compressor Start Assist (Capacitor/Relay) — Size 024 KAAHS0401AAA Compressor Start Assist (Capacitor/Relay) — Sizes 036 (70), 048 (70) KAACS0201PTC Start Assist (PTC) — Sizes 036, 048 (70) Standard N/A Standard Start Assist (PTC) — Size 024 Start Assist (PTC) — Sizes 036, 048 (90) and 060 (90) Crankcase Heater — All Sizes KSASH1101COP Sound Blanket — Size 024 KSASH2001CYL Sound Blanket — Sizes 036; 048; 060 KHAOT0301FST Outdoor Thermostat KHAOT0201SEC Secondary Outdoor Thermostat KHAIC0101AAA Interface Control (Optimizer II) KHAIC0201AAA Interface Control (Outdoor Thermostat and Lockout Relay) KHATX1001HSO‡ TXV (Hard Shut-off) — Size 024 KHATX1201HSO‡ TXV (Hard Shut-off) — Sizes 036 KHATX1301HSO TXV (Hard Shut-off) — Size 048 KHATX1401HSO TXV (Hard Shut-off) — Size 060 KHATX0301RPB TXV (RPB) — Size 024 KHATX0501RPB TXV (RPB) — Sizes 036 KHATX0601RPB TXV (RPB) — Size 048 KHATX0701RPB TXV (RPB) — Size 060 Standard Low-Pressure Switch KSAHI0201HPS High-Pressure Switch KHALS0101LLS Liquid Solenoid Valve (LSV) P251-0083 Low-Ambient Controller* (RCD) P504-8083S Filter Drier — Bi-flow Sizes 024-036 P504-8163S Filter Drier — Bi-flow Sizes 048-060 N/A — Not applicable in this application. * Isolation relay required. † Consult low-ambient controller Installation Instructions for application. ‡ Hard shut-off TXV requires compressor start assist on reciprocating compressors. THERMOSTAT TSTATCCNHP01 TSTATCCPHP01-A --HH--07AT-215 TSTATCCSEN01 4 DESCRIPTION Thermostat, Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool Thermostat, Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool Thermostat, Manual Changeover, Non-Programmable, °F, 2-Stage Heat, 1-Stage Cool Outdoor Sensor Accessory Description and Usage 1. Time-Delay Relay A SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE:For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) 2. Evaporator Freeze Thermostat A SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE:All units where low-ambient controller has been added. 3. Isolation Relay A SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode. SUGGESTED USE:All heat pumps where low-ambient controller has been added. 4. Compressor Start Assist-Capacitor/Relay Type Start capacitor and start relay gives “hard” boost to compressor motor at each start-up. SUGGESTED USE:Installations where interconnecting tube length exceeds 50 ft (15.24m). Installations where outdoor design temperature exceeds 105°F (40.6°C). Replacement installations with hard shut-off expansion valve or liquid line solenoid on indoor coil. Units installed with low-ambient controller. 5. Sound Blanket Wraparound sound attenuation cover for the compressor. Reduces the sound level by about 0.2 bels. SUGGESTED USE:Unit installed closer than 15 ft (4.55m) to quiet areas—bedrooms, etc. Unit installed between 2 houses less than 10 ft (3.04m) apart. 6. Outdoor Thermostat A SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point. SUGGESTED USE:Heat pump installations with multiple-stage supplemental heaters 7. Secondary Outdoor Thermostat A SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point. SUGGESTED USE:Heat pump installations where 3-stage operation of supplemental heaters is desired. 8. Interface Control (Optimizer II) An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat to be adjusted for economic balance point temperature. SUGGESTED USE:All heat pump and gas- or oil-fired furnace combination systems. 9. Thermostatic Expansion Valve (TXV) A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shut-off and RPB valves are available. SUGGESTED USE:For improved system performance in cooling mode. 10. High-Pressure Switch Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about 425 psig. Provides additional protection against compressor damage due to loss of outdoor airflow. SUGGESTED USE:Installations exposed to very “dirty” outdoor air. Installations where condenser inlet air temperature exceeds 125°F (51.7°C). 11. Filter Drier—Bi-flow A device for removing contaminants from refrigerant circulating in an air conditioner or heat pump system; bi-flow for heat pumps. SUGGESTED USE:All field-connected split-system units. 12. Liquid Solenoid Valve (LSV) An electrically operated shut-off valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. Note: Compressor start assist–capacitor/relay type (Item 4) must be used on single-phase reciprocating compressors. SUGGESTED USE:In certain long-line applications. (Refer to Long-Line Application Guideline.) 5 Electrical data OPER VOLTS* COMPRESSOR MIN WIRE SIZE** 60°C/ 75°C MAX LENGTH (Ft)‡ 60°C/ 75°C MAX MAX FUSE† LENGTH OR HACR (m)‡ TYPE CKT 60°C/ 75°C BKR AMPS LRA RLA FAN FLA 82.0 15.0 1.4 20.2 12/12 60/57 14.0/13.4 30 102.0 13.5 1.6 18.5 14/14 41/39 17.4/16.5 30 048-70 140.0 19.2 1.6 25.6 10/10 77/73 27.7/17.1 40 036-90 42.0 6.4 0.7 8.7 14/14 260/247 79.2/75.3 15 66.5 8.0 0.7 10.7 14/14 165/157 50.3/47.9 15 73.0 9.5 0.7 12.6 14/14 165/157 50.3/47.9 20 OUTDOOR UNIT Max V/PH Min 024-70 036-70 048-90 230-1 253 400-3 207 440 360 060-90 MCA * † ‡ ** Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure. Time-delay fuse. Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%. If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathedcable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-36. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70). NOTE: Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compressors contain internal overload protection. FLA — Full Load Amps HACR — Heating, Air Conditioning, Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps Performance summary* HEATING CAPACITY UNIT SIZESERIES 024-70 036-70, 90 048-70, 90 060-90 NOMINAL AIRFLOW COOLING CAP @ 95°F (35°C) Rated Capacity INDOOR MODEL CFM L/ S BTUH KW Power KW F(A,B)4ASF024† F(A,B)4ASF030 FG3ASA024 F(A,B)4ASF036† F(A,B)4AS(F,B)042 FG3ASA036 F(A,B)4AS(F,B)048† F(A,B)4AS(F,B)060 FG3ASA048 FG3ASA060 F(A,B)4AS(F,B)060† FB4ASB070 FG3ASA060 800 800 800 1200 1200 1200 1600 1600 1600 1600 1900 1900 1900 380 380 380 550 550 550 750 750 750 750 900 900 900 23,000 23,600 22,000 35,000 35,500 34,000 46,500 47,500 45,500 46,500 57,500 58,000 56,500 6.7 6.9 6.4 10.3 10.4 10.0 13.6 13.9 13.3 13.6 16.8 17.0 16.6 2.72 2.73 2.77 3.85 3.80 3.83 5.19 5.23 5.19 5.22 6.29 6.39 6.26 Hi Temp 47°F (8°C) Rated EER 9.00 9.00 8.50 9.00 9.20 8.80 9.00 9.00 8.50 8.50 9.00 9.00 9.00 Rated Capacity BTUH KW Power KW 23,000 23,000 23,000 36,000 37,000 36,000 47,000 47,000 47,000 47,000 59,000 59,000 57,500 6.7 6.7 6.7 10.5 10.8 10.5 13.8 13.8 13.8 13.8 17.3 17.3 16.8 2.40 2.38 2.51 3.40 3.30 3.43 4.03 3.89 4.13 4.09 5.49 5.23 5.67 Lo Temp 17°F (–3°C) Rated Capacity Power BTUH KW KW 14,000 14,000 13,829 22,100 22,145 21,949 28,000 27,665 27,910 27,906 39,100 38,677 38,850 4.1 4.1 4.1 6.5 6.5 6.4 8.2 8.1 8.2 8.2 11.5 11.3 11.4 1.72 1.70 1.80 2.65 2.57 2.67 3.45 3.33 3.54 3.50 4.89 4.66 5.05 * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit. High-Temperature Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit. Low-Temperature Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (–8°C) db 15°F (11°C) wb air entering outdoor unit. † Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are determined under DOE computer simulation procedures. Sound power UNIT SIZE SOUND RATING (BELS) 125 250 500 1000 2000 4000 8000 024 036 048 060 7.8 7.6 8.0 7.8 42.4 43.4 45.4 45.9 52.9 52.9 57.4 54.9 63.3 61.3 68.8 61.8 64.0 72.5 71.5 66.5 72.2 63.2 66.7 65.2 60.5 62.5 67.0 62.5 59.4 59.9 63.4 59.4 Sound Power — Lw (dB) Per ARI 270 Bels — Sound Rating (1 Bel = 10dB) 6 OCTAVE BAND CENTER FREQUENCY (Hz) Detailed cooling capacities* (S.I.) CONDENSER ENTERING AIR TEMPERATURES °C COIL AIR 28 32 36 40 44 48 52 Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Sys. Sys. Sys. Sys. Sys. Sys. Sys. (C) Power Power Power Power Power Power Power EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** L/S 38YCB024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 340 380 420 7.83 7.32 6.84 6.46 6.25 7.96 7.45 6.97 6.61 6.47 8.06 7.55 7.08 6.74 6.65 3.94 4.64 5.33 5.89 6.22 4.09 4.86 5.62 6.20 6.45 4.23 5.08 5.89 6.48 6.64 2.56 2.49 2.43 2.38 2.35 2.61 2.54 2.48 2.43 2.41 2.66 2.59 2.53 2.48 2.47 7.50 7.01 6.55 6.19 6.03 7.62 7.12 6.67 6.34 6.23 7.72 7.22 6.77 6.46 6.41 3.81 2.68 7.17 3.69 2.80 6.84 3.57 2.91 6.50 3.44 3.02 4.51 2.61 6.70 4.39 2.72 6.38 4.26 2.83 6.06 4.14 2.93 5.20 2.54 6.25 5.06 2.65 5.96 4.93 2.75 5.66 4.79 2.85 5.74 2.49 5.93 5.58 2.59 5.66 5.42 2.70 5.39 5.25 2.80 6.00 2.46 5.80 5.79 2.57 5.57 5.56 2.68 5.34 5.33 2.79 3.96 2.73 7.28 3.84 2.85 6.93 3.71 2.96 6.58 3.59 3.07 4.74 2.66 6.80 4.61 2.77 6.47 4.48 2.88 6.14 4.35 2.99 5.48 2.59 6.36 5.34 2.70 6.06 5.20 2.81 5.76 5.04 2.91 6.03 2.54 6.06 5.87 2.65 5.79 5.69 2.76 5.52 5.49 2.86 6.22 2.53 6.00 5.99 2.64 5.76 5.75 2.75 5.51 5.51 2.86 4.11 2.78 7.37 3.98 2.89 7.01 3.86 3.01 6.65 3.73 3.12 4.95 2.70 6.88 4.82 2.82 6.54 4.70 2.93 6.21 4.57 3.03 5.75 2.64 6.46 5.60 2.75 6.16 5.43 2.86 5.86 5.24 2.96 6.30 2.59 6.18 6.11 2.70 5.91 5.90 2.81 5.65 5.65 2.92 6.40 2.59 6.16 6.15 2.70 5.91 5.91 2.81 5.65 5.65 2.92 Multipliers for Determining the Performance With Other Indoor Sections Cooling 6.16 5.73 5.36 5.12 5.09 6.23 5.80 5.46 5.26 5.26 6.29 5.87 5.56 5.39 5.39 3.32 4.01 4.64 5.06 5.09 3.47 4.23 4.86 5.26 5.26 3.61 4.44 5.05 5.39 5.39 3.13 3.03 2.95 2.90 2.89 3.18 3.09 3.01 2.96 2.96 3.23 3.13 3.07 3.03 3.03 5.81 5.40 5.05 4.84 4.84 5.88 5.47 5.17 5.00 5.00 5.93 5.52 5.26 5.12 5.13 3.20 3.88 4.48 4.84 4.84 3.35 4.10 4.67 5.00 5.00 3.49 4.31 4.84 5.12 5.13 3.23 3.13 3.05 2.99 2.99 3.28 3.18 3.11 3.07 3.07 3.33 3.23 3.17 3.13 3.13 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.02 030 1.02 1.00 — — — 38YCB036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section 500 5.60 640 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 11.9 11.1 10.3 9.78 9.51 12.1 11.3 10.5 10.0 9.84 12.3 11.5 10.8 10.3 10.2 6.04 7.14 8.21 9.05 9.47 6.29 7.51 8.67 9.53 9.82 6.61 7.98 9.24 10.1 10.2 3.60 3.51 3.42 3.36 3.32 3.68 3.58 3.49 3.43 3.41 3.77 3.67 3.59 3.53 3.52 11.4 10.6 9.91 9.39 9.18 11.6 10.8 10.1 9.61 9.49 11.8 11.0 10.3 9.87 9.84 5.86 3.77 10.9 5.68 3.94 10.4 5.50 4.11 9.92 5.32 4.27 6.95 3.67 10.2 6.77 3.83 9.69 6.58 3.99 9.21 6.40 4.14 8.01 3.58 9.48 7.81 3.74 9.04 7.61 3.89 8.60 7.40 4.04 8.82 3.51 8.99 8.58 3.67 8.60 8.34 3.82 8.21 8.07 3.96 9.15 3.48 8.85 8.83 3.64 8.51 8.49 3.80 8.16 8.15 3.95 6.11 3.85 11.1 5.93 4.02 10.6 5.75 4.18 10.1 5.56 4.35 7.32 3.75 10.3 7.13 3.91 9.83 6.94 4.07 9.33 6.75 4.22 8.47 3.65 9.65 8.25 3.81 9.21 8.03 3.97 8.77 7.77 4.12 9.28 3.59 9.21 9.02 3.75 8.81 8.74 3.90 8.43 8.40 4.06 9.47 3.58 9.14 9.13 3.74 8.78 8.77 3.90 8.42 8.41 4.06 6.43 3.94 11.3 6.24 4.11 10.7 6.06 4.28 10.2 5.87 4.44 7.78 3.84 10.5 7.59 4.00 9.98 7.40 4.16 9.47 7.20 4.32 9.00 3.75 9.85 8.75 3.91 9.41 8.46 4.07 8.98 8.16 4.23 9.79 3.69 9.47 9.47 3.86 9.09 9.09 4.02 8.70 8.70 4.18 9.84 3.69 9.47 9.47 3.86 9.09 9.09 4.02 8.70 8.70 4.18 Multipliers for Determining the Performance With Other Indoor Sections Cooling 9.42 8.73 8.17 7.82 7.80 9.53 8.84 8.33 8.04 8.04 9.65 8.96 8.53 8.31 8.31 5.14 6.21 7.16 7.77 7.80 5.38 6.56 7.49 8.04 8.04 5.69 7.01 7.86 8.31 8.31 4.42 4.29 4.18 4.11 4.11 4.50 4.37 4.27 4.21 4.21 4.60 4.47 4.38 4.34 4.34 8.90 8.25 7.73 7.43 7.43 8.99 8.34 7.90 7.66 7.66 9.10 8.45 8.08 7.91 7.92 4.96 6.03 6.90 7.43 7.43 5.20 6.37 7.20 7.66 7.66 5.50 6.81 7.56 7.91 7.92 4.58 4.43 4.32 4.26 4.26 4.65 4.51 4.42 4.36 4.36 4.75 4.61 4.53 4.49 4.49 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.98 1.00 F(A,B)4AS(F,B) 042 1.02 0.99 — — — See notes on pg. 8. 7 Detailed cooling capacities* (S.I.) continued CONDENSER ENTERING AIR TEMPERATURES °C COIL AIR L/S 28 32 36 40 44 48 52 Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Capacity Kw† Sys. Sys. Sys. Sys. Sys. Sys. Sys. (C) Power Power Power Power Power Power Power EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** 38YCB048-70, 90 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 650 750 850 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 15.1 14.2 13.4 12.7 12.4 15.3 14.5 13.6 13.0 12.9 15.5 14.6 13.9 13.3 13.3 7.73 9.20 10.6 11.8 12.4 8.10 9.77 11.4 12.5 12.9 8.47 10.3 12.0 13.2 13.3 4.59 4.49 4.41 4.35 4.32 4.69 4.59 4.51 4.45 4.44 4.78 4.69 4.60 4.55 4.55 14.6 13.7 12.9 12.3 12.1 14.8 13.9 13.2 12.6 12.5 15.0 14.1 13.4 12.9 12.9 7.53 4.94 14.1 7.34 5.31 13.5 7.14 5.71 13.0 6.94 6.13 9.00 4.84 13.2 8.80 5.21 12.7 8.60 5.60 12.2 8.39 6.01 10.4 4.75 12.5 10.2 5.11 12.0 10.0 5.50 11.5 9.79 5.89 11.5 4.69 11.9 11.3 5.05 11.4 11.0 5.43 11.0 10.8 5.82 12.0 4.66 11.7 11.7 5.03 11.3 11.3 5.42 10.9 10.9 5.81 7.91 5.04 14.3 7.72 5.41 13.7 7.52 5.81 13.1 7.31 6.23 9.57 4.94 13.4 9.37 5.31 12.9 9.16 5.70 12.3 8.95 6.11 11.2 4.85 12.7 10.9 5.22 12.2 10.7 5.61 11.7 10.4 6.01 12.3 4.79 12.2 12.0 5.16 11.7 11.7 5.55 11.3 11.3 5.95 12.5 4.78 12.1 12.1 5.15 11.7 11.7 5.55 11.3 11.3 5.95 8.28 5.13 14.4 8.08 5.51 13.8 7.88 5.91 13.2 7.68 6.33 10.1 5.03 13.6 9.93 5.40 13.0 9.71 5.80 12.5 9.50 6.21 11.8 4.95 12.9 11.5 5.32 12.4 11.2 5.71 11.9 10.8 6.12 12.8 4.90 12.5 12.5 5.27 12.0 12.0 5.66 11.6 11.6 6.07 12.9 4.90 12.5 12.5 5.27 12.1 12.1 5.66 11.6 11.6 6.08 Multipliers for Determining the Performance With Other Indoor Sections Cooling 12.4 11.6 11.0 10.5 10.5 12.5 11.8 11.2 10.9 10.9 12.6 11.9 11.4 11.2 11.2 6.73 8.18 9.53 10.4 10.5 7.10 8.74 10.1 10.8 10.9 7.47 9.28 10.5 11.2 11.2 6.56 6.42 6.29 6.21 6.20 6.67 6.53 6.42 6.35 6.36 6.76 6.63 6.54 6.49 6.49 11.8 11.1 10.4 10.0 10.0 11.9 11.2 10.7 10.4 10.4 12.0 11.3 10.9 10.7 10.7 6.53 7.97 9.22 10.0 10.0 6.90 8.53 9.71 10.4 10.4 7.26 9.06 10.1 10.7 10.7 6.99 6.83 6.69 6.59 6.59 7.10 6.95 6.83 6.76 6.76 7.20 7.05 6.96 6.91 6.91 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00 060 1.03 1.01 060 1.00 1.01 38YCB060-90 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 850 900 950 1000 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 19.0 17.8 16.7 16.0 15.6 19.1 17.9 16.9 16.1 15.9 19.2 18.0 17.0 16.3 16.1 19.3 18.1 17.1 16.4 16.3 9.77 11.7 13.5 15.0 15.6 9.95 12.0 13.9 15.4 15.9 10.2 12.3 14.3 15.7 16.1 10.3 12.5 14.6 16.1 16.3 5.74 5.59 5.46 5.37 5.33 5.80 5.65 5.52 5.43 5.40 5.86 5.71 5.58 5.49 5.47 5.91 5.76 5.63 5.55 5.54 18.3 17.2 16.2 15.5 15.2 18.4 17.3 16.3 15.6 15.5 18.5 17.4 16.4 15.8 15.7 18.6 17.5 16.5 15.9 15.8 9.53 6.13 17.7 9.30 6.54 17.0 9.07 6.98 16.4 8.83 7.44 11.4 5.98 16.6 11.2 6.38 16.0 11.0 6.81 15.4 10.7 7.26 13.3 5.84 15.6 13.1 6.24 15.1 12.8 6.66 14.5 12.5 7.10 14.7 5.74 15.0 14.4 6.14 14.5 14.1 6.56 13.9 13.7 7.00 15.2 5.71 14.8 14.8 6.11 14.3 14.3 6.54 13.9 13.9 6.99 9.72 6.19 17.8 9.49 6.60 17.1 9.26 7.04 16.5 9.02 7.50 11.7 6.04 16.7 11.5 6.44 16.1 11.3 6.87 15.5 11.0 7.32 13.7 5.90 15.8 13.4 6.30 15.2 13.1 6.72 14.6 12.8 7.16 15.1 5.81 15.1 14.8 6.20 14.6 14.4 6.62 14.1 14.0 7.07 15.4 5.78 15.0 15.0 6.19 14.5 14.5 6.61 14.1 14.1 7.07 9.92 6.25 17.9 9.68 6.66 17.2 9.45 7.10 16.5 9.21 7.56 12.0 6.09 16.8 11.8 6.50 16.2 11.5 6.92 15.5 11.3 7.37 14.0 5.96 15.9 13.8 6.36 15.3 13.5 6.78 14.7 13.1 7.23 15.4 5.87 15.3 15.1 6.27 14.7 14.7 6.69 14.3 14.2 7.14 15.6 5.85 15.2 15.2 6.26 14.7 14.7 6.69 14.2 14.2 7.14 10.1 6.30 18.0 9.87 6.72 17.3 9.64 7.15 16.6 9.40 7.61 12.3 6.15 16.9 12.1 6.55 16.3 11.8 6.98 15.6 11.6 7.43 14.4 6.01 16.0 14.1 5.41 15.4 13.7 6.84 14.8 13.3 7.29 15.7 5.93 15.4 15.3 6.33 14.9 14.9 6.76 14.4 14.4 7.21 15.8 5.92 15.4 15.4 6.33 14.9 14.9 6.76 14.4 14.4 7.21 Multipliers for Determining the Performance With Other Indoor Sections Cooling 15.7 14.7 13.9 13.4 13.4 15.8 14.8 14.0 13.6 13.6 15.8 14.9 14.2 13.7 13.7 15.9 14.9 14.3 13.9 13.9 8.59 10.5 12.2 13.3 13.4 8.78 10.8 12.5 13.6 13.6 8.97 11.0 12.7 13.7 13.7 9.15 11.3 12.9 13.9 13.9 7.92 7.73 7.57 7.46 7.46 7.98 7.79 7.63 7.54 7.54 8.04 7.85 7.70 7.62 7.62 8.09 7.90 7.77 7.69 7.69 15.0 14.1 13.3 12.9 12.9 15.1 14.1 13.5 13.1 13.1 15.1 14.2 13.6 13.2 13.2 15.2 14.3 13.7 13.4 13.4 8.36 10.2 11.9 12.9 12.9 8.54 10.5 12.1 13.1 13.1 8.72 10.8 12.3 13.2 13.2 8.91 11.1 12.6 13.4 13.4 8.41 8.21 8.05 7.95 7.95 8.47 8.27 8.12 8.03 8.03 8.53 8.33 8.19 8.11 8.12 8.59 8.39 8.26 8.19 8.19 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.00 FB4ASB 070 1.02 1.02 — — — * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 4.55m of tubing. If other than 4.55m of tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower motor heat has been subtracted. ‡ Sensible capacities shown are based on 27°C entering air at the indoor coil. For sensible capacities at other than 27°C, deduct 245 kw per 480 L/S of indoor coil air for each degree below 27°C, or add 245 kw per 480 L/S of indoor coil air per degree above 27°C. ** System kw is total of indoor and outdoor unit kilowatt’s. EWB — Entering Wet Bulb L/S — Liters per second 8 Detailed cooling capacities* (English) CONDENSER ENTERING AIR TEMPERATURES °F COIL AIR CFM (F) EWB 75 85 95 Capacity MBtuh† Capacity MBtuh† Capacity MBtuh† Total Sys. Power Sens‡ Kw** Total Sys. Power Sens‡ Kw** Total Sys. Power Sens‡ Kw** 105 115 Capacity MBtuh† Total Sys. Power Sens‡ Kw** 125 Capacity MBtuh† Total Sys. Power Sens‡ Kw** Capacity MBtuh† Total Sys. Power Sens‡ Kw** 38YCB024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section 700 800 900 72 67 62 57 72 67 62 57 72 67 62 57 27.9 25.4 23.1 21.9 28.5 26.0 23.7 22.8 29.0 26.4 24.2 23.6 13.5 16.7 19.9 21.9 14.1 17.7 21.3 22.8 14.6 18.7 22.6 23.6 2.43 2.35 2.27 2.22 2.49 2.40 2.32 2.29 2.54 2.46 2.38 2.36 26.4 12.9 2.60 24.8 12.3 2.76 23.3 11.7 2.92 21.7 24.0 16.1 2.51 22.6 15.5 2.66 21.1 14.9 2.81 19.6 21.8 19.3 2.42 20.5 18.7 2.56 19.2 18.0 2.70 17.8 20.8 20.8 2.38 19.8 19.8 2.53 18.7 18.7 2.68 17.6 26.9 13.5 2.66 25.3 12.9 2.83 23.6 12.3 2.98 22.0 24.5 17.1 2.56 23.0 16.5 2.72 21.5 15.9 2.87 19.9 22.3 20.6 2.48 21.0 19.9 2.63 19.6 19.2 2.77 18.3 21.7 21.7 2.45 20.6 20.6 2.61 19.5 19.5 2.76 18.3 27.3 14.0 2.71 25.7 13.4 2.88 23.9 12.8 3.04 22.2 24.9 18.1 2.62 23.4 17.5 2.77 21.8 16.8 2.93 20.2 22.8 21.9 2.53 21.4 21.1 2.68 20.1 20.1 2.83 18.9 22.5 22.5 2.52 21.3 21.3 2.68 20.1 20.1 2.83 18.9 Multipliers for Determining the Performance With Other Indoor Sections Cooling 11.2 14.3 17.3 17.6 11.7 15.3 18.3 18.3 12.3 16.2 18.9 18.9 3.08 2.95 2.84 2.83 3.14 3.01 2.91 2.91 3.19 3.07 2.99 2.99 20.0 18.1 16.5 16.5 20.3 18.3 17.1 17.1 20.5 18.6 17.6 17.6 10.6 13.7 16.5 16.5 11.1 14.7 17.1 17.1 11.7 15.6 17.6 17.6 3.22 3.08 2.97 2.97 3.28 3.15 3.05 3.06 3.34 3.20 3.13 3.13 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.02 030 1.02 1.00 — — — 38YCB036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section 1050 1200 1350 72 67 62 57 72 67 62 57 72 67 62 57 42.5 38.6 35.0 33.5 43.4 39.4 35.9 34.9 44.1 40.1 36.6 36.0 20.8 25.9 31.0 33.5 21.7 27.6 33.1 34.9 22.6 29.1 35.1 36.0 3.43 3.31 3.20 3.15 3.52 3.39 3.28 3.25 3.60 3.47 3.37 3.35 40.2 19.9 3.67 37.9 19.1 3.91 35.6 18.2 4.14 33.2 36.5 25.1 3.54 34.3 24.2 3.76 32.1 23.3 3.98 29.9 33.1 30.0 3.42 31.2 29.1 3.63 29.2 28.1 3.83 27.3 31.9 31.9 3.37 30.4 30.4 3.60 28.8 28.8 3.81 27.1 41.1 20.9 3.76 38.6 20.0 4.00 36.2 19.1 4.23 33.7 37.2 26.7 3.62 35.0 25.8 3.85 32.6 24.9 4.07 30.3 33.9 32.1 3.51 31.9 31.0 3.72 30.0 29.8 3.93 28.1 33.2 33.2 3.48 31.6 31.6 3.71 29.9 29.9 3.93 28.1 41.7 21.8 3.84 39.2 20.9 4.08 36.7 20.0 4.31 34.0 37.8 28.2 3.70 35.4 27.3 3.93 33.1 26.4 4.15 30.7 34.6 33.9 3.59 32.6 32.6 3.81 30.8 30.8 4.04 29.0 34.3 34.3 3.58 32.6 32.6 3.81 30.8 30.8 4.04 29.0 Multipliers for Determining the Performance With Other Indoor Sections Cooling 17.4 22.4 27.0 27.1 18.3 23.9 28.1 28.1 19.2 25.4 29.0 29.0 4.36 4.18 4.04 4.03 4.45 4.27 4.15 4.15 4.54 4.36 4.26 4.26 30.7 27.6 25.4 25.4 31.1 28.0 26.3 26.3 31.4 28.4 27.1 27.1 16.5 21.5 25.4 25.4 17.4 23.0 26.3 26.3 18.3 24.5 27.1 27.1 4.57 4.38 4.24 4.24 4.67 4.47 4.36 4.36 4.75 4.56 4.48 4.48 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.98 1.00 F(A,B)4AS(F,B) 042 1.02 0.99 — — — See notes on pg. 10. 9 Detailed cooling capacities* (English) continued CONDENSER ENTERING AIR TEMPERATURES °F COIL AIR CFM (F) EWB 75 85 95 Capacity MBtuh† Capacity MBtuh† Capacity MBtuh† Total Sys. Power Sens‡ Kw** Total Sys. Power Sens‡ Kw** Total Sys. Power Sens‡ Kw** 105 115 Capacity MBtuh† Total Sys. Power Sens‡ Kw** 125 Capacity MBtuh† Total Sys. Power Sens‡ Kw** Capacity MBtuh† Total Sys. Power Sens‡ Kw** 38YCB048-70, 90 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 1400 1600 1800 72 67 62 57 72 67 62 57 72 67 62 57 53.7 49.4 45.3 43.7 54.6 50.2 46.3 45.3 55.2 50.9 47.1 46.6 26.6 33.7 40.6 43.7 27.7 35.7 43.3 45.3 28.8 37.7 45.8 46.6 4.27 4.15 4.04 4.00 4.36 4.24 4.13 4.11 4.45 4.33 4.22 4.21 51.4 25.7 4.73 48.9 24.8 5.23 46.2 23.9 5.78 43.5 47.2 32.8 4.60 44.9 31.8 5.09 42.4 30.8 5.63 39.9 43.3 39.6 4.48 41.2 38.6 4.97 39.0 37.5 5.50 36.8 42.0 42.0 4.45 40.3 40.3 4.94 38.5 38.5 5.48 36.6 52.1 26.8 4.82 49.5 25.9 5.33 46.8 25.0 5.88 44.0 47.9 34.8 4.69 45.5 33.8 5.19 43.0 32.8 5.73 40.4 44.2 42.2 4.58 42.1 41.1 5.07 39.9 39.7 5.61 37.8 43.6 43.6 4.56 41.7 41.7 5.06 39.8 39.8 5.61 37.9 52.7 28.0 4.91 50.1 27.0 5.42 47.3 26.1 5.97 44.4 48.5 36.7 4.78 46.0 35.8 5.27 43.4 34.8 5.82 40.8 45.0 44.5 4.67 42.9 42.9 5.17 40.9 40.9 5.72 38.8 44.8 44.8 4.67 42.9 42.9 5.17 40.9 40.9 5.72 38.8 Multipliers for Determining the Performance With Other Indoor Sections Cooling 22.9 29.9 36.3 36.6 24.0 31.8 37.8 37.9 25.1 33.7 38.8 38.8 6.38 6.20 6.04 6.03 6.48 6.30 6.17 6.17 6.57 6.39 6.29 6.29 40.8 37.3 34.4 34.4 41.2 37.8 35.6 35.6 41.5 38.1 36.6 36.6 21.9 28.8 34.4 34.4 23.0 30.8 35.6 35.6 24.1 32.7 36.6 36.6 6.98 6.77 6.58 6.58 7.09 6.88 6.73 6.74 7.18 6.97 6.88 6.88 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00 060 1.03 1.01 060 1.00 1.01 38YCB060-90 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 1750 1900 2000 2150 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 67.1 61.5 56.4 54.3 67.7 62.1 57.1 55.6 68.1 62.5 57.5 56.3 68.7 63.0 58.1 57.5 33.1 42.0 50.6 54.3 34.0 43.5 52.7 55.6 34.5 44.5 54.0 56.3 35.4 46.0 56.0 57.5 5.34 5.15 4.99 4.93 5.43 5.23 5.07 5.03 5.48 5.29 5.12 5.09 5.56 5.36 5.20 5.18 64.2 32.0 5.86 61.2 30.9 6.42 58.1 29.8 7.03 54.9 58.8 40.9 5.66 56.0 39.7 6.20 53.2 38.6 6.79 50.3 53.9 49.4 5.48 51.5 48.2 6.01 49.0 47.0 6.59 46.5 52.4 52.4 5.43 50.4 50.4 5.97 48.3 48.3 6.56 46.2 64.7 32.9 5.95 61.6 31.8 6.51 58.5 30.7 7.11 55.3 59.3 42.4 5.74 56.5 41.3 6.29 53.6 40.1 6.87 50.7 54.6 51.5 5.57 52.1 50.2 6.10 49.6 48.8 6.68 47.1 53.6 53.6 5.53 51.5 51.5 6.07 49.3 49.3 6.67 47.0 65.2 33.5 6.00 61.9 32.4 6.56 58.8 31.3 7.17 55.5 59.7 43.4 5.79 56.8 42.3 6.34 53.9 41.1 6.93 50.9 55.0 52.8 5.62 52.5 51.4 6.16 50.0 49.9 6.74 47.7 54.4 54.4 5.59 52.2 52.2 6.14 50.0 50.0 6.74 47.7 65.6 34.3 6.08 62.3 33.2 6.64 59.2 32.1 7.25 55.8 60.1 44.9 5.87 57.2 43.8 6.41 54.3 42.6 7.01 51.2 55.6 54.6 5.70 53.1 53.0 6.24 50.8 50.8 6.84 48.4 55.3 55.3 5.69 53.0 53.0 6.24 50.8 50.8 6.84 48.4 Multipliers for Determining the Performance With Other Indoor Sections Cooling 28.7 37.5 45.6 46.2 29.6 39.0 47.1 47.0 30.1 39.9 47.7 47.7 31.0 41.4 48.4 48.4 7.67 7.41 7.20 7.19 7.76 7.50 7.30 7.31 7.82 7.56 7.37 7.38 7.90 7.64 7.48 7.48 51.7 47.3 43.9 43.8 51.9 47.5 44.7 44.7 52.1 47.8 45.2 45.1 52.3 48.1 45.9 45.9 27.6 36.3 43.9 43.8 28.4 37.7 44.7 44.7 29.0 38.7 45.2 45.1 29.8 40.2 45.9 45.9 8.36 8.08 7.87 7.87 8.45 8.17 7.99 7.99 8.51 8.23 8.06 8.06 8.59 8.31 8.17 8.17 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.00 FB4ASB 070 1.02 1.02 — — — * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 25 ft of tubing. If other than 25 ft of tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower motor heat has been subtracted. ‡ Sensible capacities shown are based on 80°F entering air at the indoor coil. For sensible capacities at other than 80°F, deduct 835 Btuh per 1000 CFM of indoor coil air for each degree below 80°F, or add 835 Btuh per 1000 CFM of indoor coil air per degree above 80°F. ** System kw is total of indoor and outdoor unit kilowatt’s. EWB — Entering Wet Bulb 10 Heat pump heating performance (S.I.) OUTDOOR COIL ENTERING AIR TEMPERATURES •C –16 INDOOR AIR (C) EDB Capacity Kw –8 Total Power Capacity Kw 0 Total Power Capacity Kw 4 Total Power Capacity Kw 8 Total Power Capacity Kw 12 Total Power Capacity Kw 16 Total Power 20 Capacity Kw Total Power Capacity Kw Total Power L/ S Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ 340 380 420 340 380 420 340 380 420 340 380 420 340 380 420 3.39 3.44 3.49 3.28 3.33 3.37 3.16 3.21 3.26 3.05 3.10 3.14 2.92 2.98 3.02 38YCB024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section 12 15 18 21 24 3.12 3.17 3.21 3.01 3.06 3.10 2.91 2.95 3.00 2.80 2.85 2.89 2.69 2.74 2.78 1.39 1.41 1.43 1.41 1.43 1.45 1.43 1.45 1.47 1.44 1.47 1.49 1.46 1.48 1.50 4.44 4.51 4.56 4.33 4.39 4.45 4.21 4.27 4.33 4.10 4.16 4.21 3.98 4.04 4.10 4.04 4.10 4.15 3.94 4.00 4.05 3.83 3.89 3.94 3.73 3.78 3.83 3.63 3.68 3.73 1.63 1.65 1.66 1.66 1.68 1.69 1.69 1.71 1.72 1.72 1.74 1.75 1.75 1.76 1.78 5.64 5.73 5.80 5.51 5.60 5.66 5.38 5.46 5.53 5.25 5.33 5.39 5.12 5.19 5.26 5.08 5.16 5.21 4.96 5.04 5.09 4.84 4.92 4.97 4.73 4.80 4.85 4.61 4.68 4.73 1.90 1.91 1.92 1.94 1.95 1.96 1.98 1.99 2.01 2.02 2.03 2.05 2.06 2.07 2.09 6.32 6.42 6.49 6.18 6.28 6.34 6.04 6.13 6.20 5.89 5.98 6.06 5.75 5.84 5.91 5.90 5.99 6.05 5.76 5.85 5.91 5.63 5.71 5.78 5.49 5.58 5.65 5.36 5.44 5.51 2.05 2.06 2.07 2.10 2.11 2.12 2.14 2.15 2.17 2.19 2.20 2.21 2.23 2.25 2.26 7.04 7.15 7.22 6.89 6.99 7.07 6.74 6.84 6.92 6.59 6.69 6.77 6.43 6.53 6.61 7.01 7.11 7.18 6.86 6.96 7.03 6.71 6.81 6.89 6.56 6.66 6.74 6.40 6.50 6.58 2.22 2.22 2.23 2.27 2.28 2.28 2.32 2.33 2.34 2.37 2.38 2.39 2.42 2.43 2.44 7.87 7.98 8.06 7.70 7.82 7.90 7.54 7.65 7.74 7.37 7.49 7.58 7.20 7.32 7.41 7.87 7.98 8.06 7.70 7.82 7.90 7.54 7.65 7.74 7.37 7.49 7.58 7.20 7.32 7.41 2.42 2.42 2.43 2.47 2.48 2.48 2.53 2.54 2.54 2.59 2.59 2.60 2.64 2.65 2.66 8.75 8.88 8.97 8.57 8.70 8.79 8.39 8.52 8.61 8.21 8.34 8.44 8.02 8.15 8.26 8.75 8.88 8.97 8.57 8.70 8.79 8.39 8.52 8.61 8.21 8.34 8.44 8.02 8.15 8.26 2.64 2.64 2.65 2.70 2.70 2.71 2.76 2.77 2.77 2.83 2.83 2.83 2.89 2.89 2.89 9.67 9.82 9.93 9.48 9.63 9.73 9.28 9.43 9.54 9.08 9.23 9.35 8.88 9.03 9.14 9.67 9.82 9.93 9.48 9.63 9.73 9.28 9.43 9.54 9.08 9.23 9.35 8.88 9.03 9.14 2.88 2.88 2.89 2.95 2.95 2.95 3.01 3.01 3.02 3.08 3.08 3.09 3.14 3.14 3.15 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.99 1.05 030 1.00 0.99 — — — 38YCB036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section 2 15 18 21 24 500 560 640 500 560 640 500 560 640 500 560 640 500 560 640 5.42 5.49 5.60 5.22 5.30 5.41 5.02 5.11 5.21 4.83 4.91 5.02 4.61 4.70 4.81 4.98 5.05 5.15 4.80 4.87 4.97 4.62 4.69 4.79 4.44 4.52 4.61 4.24 4.32 4.42 2.22 2.26 2.31 2.25 2.28 2.34 2.27 2.31 2.37 2.30 2.34 2.40 2.33 2.37 2.42 7.03 7.13 7.26 6.84 6.94 7.06 6.65 6.75 6.87 6.46 6.56 6.68 6.26 6.36 6.48 6.40 6.49 6.60 6.22 6.32 6.43 6.05 6.14 6.25 5.88 5.97 6.08 5.70 5.79 5.90 2.49 2.52 2.56 2.54 2.57 2.61 2.58 2.61 2.66 2.63 2.66 2.71 2.67 2.70 2.75 8.86 9.00 9.15 8.65 8.78 8.93 8.44 8.57 8.71 8.23 8.35 8.49 8.01 8.14 8.28 7.98 8.10 8.23 7.79 7.90 8.03 7.60 7.71 7.84 7.40 7.52 7.64 7.21 7.32 7.45 2.78 2.80 2.83 2.84 2.86 2.90 2.91 2.93 2.96 2.97 2.99 3.03 3.03 3.05 3.09 9.93 10.1 10.2 9.70 9.84 10.0 9.46 9.60 9.76 9.22 9.37 9.53 8.99 9.13 9.29 9.26 9.40 9.54 9.04 9.17 9.32 8.82 8.95 9.10 8.60 8.73 8.88 8.38 8.51 8.66 2.95 2.97 2.99 3.02 3.04 3.06 3.09 3.11 3.13 3.16 3.18 3.21 3.22 3.24 3.28 11.1 11.2 11.4 10.8 11.0 11.1 10.6 10.7 10.9 10.3 10.5 10.6 10.0 10.2 10.4 11.0 11.2 11.4 10.8 10.9 11.1 10.5 10.7 10.8 10.2 10.4 10.6 9.99 10.1 10.3 3.14 3.14 3.16 3.21 3.22 3.24 3.29 3.30 3.32 3.36 3.38 3.40 3.44 3.45 3.48 12.3 12.5 12.7 12.1 12.2 12.4 11.8 12.0 12.2 11.5 11.7 11.9 11.2 11.4 11.6 12.3 12.5 12.7 12.1 12.2 12.4 11.8 12.0 12.2 11.5 11.7 11.9 11.2 11.4 11.6 3.36 3.36 3.37 3.44 3.44 3.46 3.52 3.52 3.54 3.60 3.61 3.62 3.68 3.69 3.71 13.7 13.9 14.1 13.4 13.6 13.8 13.1 13.3 13.5 12.8 13.0 13.2 12.4 12.7 12.9 13.7 13.9 14.1 13.4 13.6 13.8 13.1 13.3 13.5 12.8 13.0 13.2 12.4 12.7 12.9 3.61 3.60 3.62 3.69 3.69 3.70 3.78 3.78 3.79 3.86 3.86 3.88 3.95 3.95 3.96 15.1 15.3 15.6 14.8 15.0 15.2 14.4 14.7 14.9 14.1 14.3 14.6 13.7 14.0 14.2 15.1 15.3 15.6 14.8 15.0 15.2 14.4 14.7 14.9 14.1 14.3 14.6 13.7 14.0 14.2 3.88 3.87 3.88 3.97 3.96 3.97 4.06 4.05 4.06 4.14 4.14 4.15 4.23 4.23 4.24 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.99 1.01 F(A,B)4AS(F,B) 042 1.00 0.97 — — — See notes on pg. 12. 11 Heat pump heating performance (S.I.) continued OUTDOOR COIL ENTERING AIR TEMPERATURES •C –16 INDOOR AIR (C) EDB Capacity Kw –8 Total Power Capacity Kw 0 Total Power Capacity Kw 4 Total Power Capacity Kw 8 Total Power Capacity Kw 12 Total Power Capacity Kw 16 Total Power 20 Capacity Kw Total Power Capacity Kw Total Power L/ S Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ 650 750 850 650 750 850 650 750 850 650 750 850 650 750 850 6.43 6.50 6.57 6.35 6.42 6.49 6.26 6.34 6.41 6.17 6.26 6.34 6.07 6.16 6.24 38YCB048-70, 90 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 12 15 18 21 24 5.91 5.97 6.03 5.83 5.90 5.97 5.75 5.83 5.90 5.67 5.75 5.83 5.58 5.66 5.74 2.73 2.75 2.77 2.87 2.89 2.92 3.02 3.04 3.06 3.16 3.18 3.21 3.30 3.32 3.35 8.33 8.43 8.52 8.29 8.39 8.47 8.26 8.34 8.42 8.22 8.30 8.38 8.16 8.25 8.32 7.58 7.67 7.75 7.55 7.63 7.71 7.51 7.59 7.67 7.48 7.55 7.62 7.43 7.50 7.57 2.92 2.93 2.95 3.10 3.11 3.12 3.28 3.28 3.29 3.46 3.45 3.47 3.64 3.63 3.64 10.8 10.9 11.1 10.8 10.9 11.0 10.7 10.8 10.9 10.6 10.7 10.8 10.5 10.6 10.7 9.74 9.85 9.95 9.68 9.78 9.87 9.61 9.71 9.79 9.54 9.63 9.71 9.47 9.56 9.65 3.19 3.17 3.18 3.38 3.36 3.37 3.58 3.55 3.55 3.77 3.75 3.74 3.97 3.95 3.94 12.2 12.4 12.5 12.1 12.3 12.4 12.1 12.2 12.3 12.0 12.1 12.2 11.9 12.0 12.1 11.4 11.5 11.7 11.3 11.5 11.6 11.2 11.4 11.5 11.2 11.3 11.4 11.1 11.2 11.3 3.33 3.31 3.31 3.54 3.51 3.50 3.75 3.71 3.70 3.95 3.91 3.89 4.17 4.12 4.10 13.7 13.9 14.1 13.7 13.8 14.0 13.6 13.7 13.9 13.5 13.6 13.7 13.4 13.5 13.6 13.7 13.8 14.0 13.6 13.8 13.9 13.5 13.7 13.8 13.5 13.6 13.7 13.3 13.5 13.6 3.49 3.46 3.44 3.71 3.67 3.65 3.93 3.89 3.86 4.15 4.10 4.07 4.37 4.32 4.29 15.7 15.9 16.1 15.6 15.8 15.9 15.4 15.6 15.8 15.3 15.5 15.6 15.2 15.3 15.5 15.7 15.9 16.1 15.6 15.8 15.9 15.4 15.6 15.8 15.3 15.5 15.6 15.2 15.3 15.5 3.71 3.66 3.64 3.94 3.88 3.85 4.17 4.10 4.07 4.40 4.32 4.28 4.63 4.55 4.51 17.8 18.1 18.3 17.6 17.9 18.0 17.5 17.7 17.8 17.3 17.5 17.6 17.1 17.3 17.5 17.8 18.1 18.3 17.6 17.9 18.0 17.5 17.7 17.8 17.3 17.5 17.6 17.1 17.3 17.5 3.95 3.89 3.86 4.19 4.12 4.08 4.43 4.35 4.30 4.67 4.58 4.52 4.92 4.82 4.76 20.0 20.3 20.6 19.8 20.1 20.3 19.6 19.9 20.1 19.4 19.7 19.8 19.2 19.5 19.7 20.0 20.3 20.6 19.8 20.1 20.3 19.6 19.9 20.1 19.4 19.7 19.8 19.2 19.5 19.7 4.21 4.14 4.11 4.46 4.38 4.34 4.72 4.62 4.56 4.97 4.86 4.79 5.23 5.12 5.04 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 1.00 1.03 060 0.99 0.96 060 1.00 1.02 38YCB060-90 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 12 15 18 21 24 850 900 950 1000 850 900 950 1000 850 900 950 1000 850 900 950 1000 850 900 950 1000 9.55 9.60 9.65 9.70 9.43 9.49 9.54 9.59 9.32 9.37 9.43 9.48 9.20 9.26 9.32 9.37 9.05 9.12 9.18 9.24 8.78 8.82 8.87 8.91 8.67 8.72 8.77 8.82 8.57 8.62 8.67 8.72 8.46 8.52 8.57 8.62 8.32 8.38 8.44 8.49 4.00 4.02 4.06 4.09 4.21 4.23 4.27 4.30 4.42 4.45 4.48 4.51 4.63 4.66 4.69 4.72 4.84 4.87 4.90 4.93 11.8 11.8 11.9 12.0 11.7 11.7 11.8 11.9 11.6 11.7 11.7 11.8 11.5 11.6 11.6 11.7 11.4 11.5 11.5 11.6 10.7 10.8 10.8 10.9 10.6 10.7 10.7 10.8 10.6 10.6 10.7 10.7 10.5 10.5 10.6 10.6 10.4 10.5 10.5 10.6 4.16 4.18 4.21 4.23 4.40 4.42 4.44 4.47 4.63 4.65 4.68 4.70 4.87 4.89 4.91 4.94 5.12 5.14 5.16 5.19 14.4 14.5 14.5 14.6 14.3 14.3 14.4 14.5 14.2 14.2 14.3 14.4 14.1 14.1 14.2 14.2 13.9 14.0 14.1 14.1 12.9 13.0 13.1 13.1 12.8 12.9 13.0 13.0 12.7 12.8 12.9 12.9 12.6 12.7 12.8 12.8 12.5 12.6 12.7 12.7 4.36 4.38 4.39 4.42 4.62 4.63 4.65 4.67 4.88 4.89 4.90 4.92 5.14 5.14 5.16 5.18 5.40 5.41 5.42 5.44 15.8 15.9 16.0 16.1 15.7 15.8 15.9 15.9 15.6 15.7 15.8 15.8 15.5 15.6 15.7 15.7 15.4 15.4 15.5 15.6 14.8 14.8 14.9 15.0 14.7 14.7 14.8 14.9 14.6 14.6 14.7 14.8 14.5 14.5 14.6 14.7 14.3 14.4 14.5 14.5 4.49 4.50 4.51 4.54 4.75 4.76 4.78 4.80 5.02 5.03 5.04 5.06 5.29 5.30 5.30 5.32 5.57 5.57 5.57 5.59 17.5 17.6 17.7 17.7 17.4 17.4 17.5 17.6 17.2 17.3 17.4 17.5 17.1 17.2 17.2 17.3 16.9 17.0 17.1 17.1 17.4 17.5 17.6 17.7 17.3 17.4 17.4 17.5 17.1 17.2 17.3 17.4 17.0 17.1 17.2 17.2 16.8 16.9 17.0 17.1 4.64 4.65 4.66 4.68 4.92 4.92 4.93 4.95 5.19 5.19 5.20 5.21 5.47 5.47 5.47 5.48 5.75 5.75 5.75 5.76 19.5 19.6 19.7 19.7 19.3 19.4 19.5 19.5 19.1 19.2 19.3 19.4 18.9 19.0 19.1 19.2 18.7 18.8 18.9 19.0 19.5 19.6 19.7 19.7 19.3 19.4 19.5 19.5 19.1 19.2 19.3 19.4 18.9 19.0 19.1 19.2 18.7 18.8 18.9 19.0 4.84 4.84 4.86 4.87 5.13 5.12 5.13 5.15 5.41 5.40 5.41 5.42 5.69 5.68 5.68 5.69 5.99 5.98 5.97 5.97 21.6 21.7 21.8 21.9 21.3 21.5 21.6 21.6 21.1 21.2 21.3 21.4 20.9 21.0 21.1 21.2 20.7 20.8 20.9 21.0 21.6 21.7 21.8 21.9 21.3 21.5 21.6 21.6 21.1 21.2 21.3 21.4 20.9 21.0 21.1 21.2 20.7 20.8 20.9 21.0 5.08 5.08 5.09 5.11 5.37 5.37 5.37 5.38 5.66 5.65 5.66 5.66 5.96 5.94 5.94 5.94 6.26 6.24 6.23 6.23 23.7 23.9 24.0 24.1 23.5 23.6 23.7 23.8 23.3 23.4 23.5 23.6 23.0 23.1 23.3 23.4 22.8 22.9 23.0 23.1 23.7 23.9 24.0 24.1 23.5 23.6 23.7 23.8 23.3 23.4 23.5 23.6 23.0 23.1 23.3 23.4 22.8 22.9 23.0 23.1 5.35 5.34 5.36 5.37 5.65 5.64 5.64 5.65 5.95 5.93 5.93 5.94 6.25 6.23 6.22 6.22 6.57 6.54 6.53 6.52 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.03 FB4ASB 070 0.99 0.95 — — — † The kw heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The kw heating from supplement heaters should be added to those values to obtain total system capacity. ‡ The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to obtain total system kw’s. EDB — Entering Dry Bulb 12 Heat pump heating performance (English) OUTDOOR COIL ENTERING AIR TEMPERATURES •F –3 INDOOR AIR (F) EDB Capacity Kw 7 Total Power Capacity Kw 17 Total Power Capacity Kw 27 Total Power Capacity Kw 37 Total Power Capacity Kw 47 Total Power Capacity Kw 57 Total Power 67 Capacity Kw Total Power Capacity Kw Total Power CFM Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ 38YCB024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section 65 70 75 700 800 900 700 800 900 700 800 900 9.25 9.45 9.62 8.87 9.07 9.25 8.45 8.66 8.84 8.51 8.69 8.85 8.16 8.35 8.51 7.77 7.96 8.14 1.32 1.34 1.37 1.33 1.35 1.38 1.34 1.36 1.39 11.6 11.8 12.0 11.2 11.5 11.6 10.9 11.1 11.3 10.7 10.9 11.0 10.3 10.5 10.7 9.99 10.2 10.4 1.49 1.51 1.54 1.51 1.53 1.56 1.52 1.55 1.57 14.1 14.4 14.6 13.8 14.0 14.2 13.4 13.6 13.8 12.9 13.1 13.3 12.5 12.8 13.0 12.2 12.4 12.6 1.68 1.70 1.72 1.70 1.72 1.75 1.73 1.75 1.77 16.7 17.0 17.3 16.4 16.7 16.9 16.0 16.3 16.5 14.9 15.1 15.4 14.5 14.8 15.0 14.2 14.4 14.6 1.87 1.89 1.91 1.91 1.92 1.94 1.94 1.96 1.98 19.7 20.1 20.4 19.3 19.6 19.9 18.9 19.2 19.5 18.0 18.3 18.5 17.6 17.9 18.1 17.2 17.5 17.7 2.09 2.10 2.12 2.13 2.14 2.16 2.17 2.19 2.20 23.0 23.5 23.8 22.6 23.0 23.3 22.1 22.5 22.8 23.0 23.5 23.8 22.6 23.0 23.3 22.1 22.5 22.8 2.34 2.35 2.36 2.39 2.40 2.41 2.44 2.44 2.46 26.8 27.3 27.7 26.3 26.8 27.2 25.8 26.3 26.6 26.8 27.3 27.7 26.3 26.8 27.2 25.8 26.3 26.6 2.64 2.64 2.65 2.69 2.70 2.70 2.75 2.75 2.76 31.0 31.6 32.1 30.4 31.0 31.5 29.8 30.4 30.8 31.0 31.6 32.1 30.4 31.0 31.5 29.8 30.4 30.8 2.99 2.99 2.99 3.05 3.05 3.05 3.11 3.10 3.11 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.99 1.05 030 1.00 0.99 — — — 38YCB036-70, 90 Outdoor Section With F(A,B)4AS(F,B)036 Indoor Section 65 70 75 1050 1200 1350 1050 1200 1350 1050 1200 1350 14.7 15.1 15.4 14.0 14.4 14.7 13.3 13.7 14.0 13.6 13.9 14.2 12.9 13.2 13.5 12.2 12.6 12.8 2.15 2.19 2.24 2.16 2.21 2.27 2.18 2.23 2.28 18.5 18.8 19.1 17.9 18.2 18.5 17.2 17.6 17.9 17.0 17.3 17.6 16.4 16.7 17.0 15.8 16.2 16.5 2.35 2.40 2.44 2.38 2.43 2.48 2.41 2.45 2.50 22.3 22.7 23.1 21.7 22.1 22.5 21.1 21.5 21.9 20.4 20.7 21.1 19.8 20.2 20.5 19.3 19.6 20.0 2.57 2.61 2.65 2.61 2.65 2.69 2.65 2.69 2.73 26.3 26.8 27.2 25.7 26.2 26.6 25.1 25.6 25.9 23.4 23.8 24.2 22.8 23.2 23.6 22.3 22.7 23.0 2.79 2.82 2.85 2.84 2.87 2.91 2.89 2.92 2.96 31.0 31.6 32.0 30.3 30.8 31.3 29.6 30.1 30.6 28.2 28.7 29.1 27.6 28.1 28.5 26.9 27.4 27.8 3.03 3.06 3.08 3.10 3.12 3.15 3.16 3.18 3.21 36.2 36.8 37.3 35.3 36.0 36.5 34.5 35.2 35.7 36.2 36.8 37.3 35.3 36.0 36.5 34.5 35.2 35.7 3.31 3.32 3.34 3.38 3.40 3.42 3.45 3.47 3.49 42.0 42.8 43.4 41.0 41.8 42.5 40.1 40.9 41.5 42.0 42.8 43.4 41.0 41.8 42.5 40.1 40.9 41.5 3.64 3.64 3.66 3.72 3.72 3.74 3.79 3.80 3.81 48.4 49.3 50.0 47.3 48.3 49.0 46.3 47.2 47.9 48.4 49.3 50.0 47.3 48.3 49.0 46.3 47.2 47.9 4.03 4.02 4.03 4.11 4.11 4.12 4.19 4.19 4.20 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.99 1.01 F(A,B)4AS(F,B) 042 1.00 0.97 — — — See notes on pg. 14. 13 Heat pump heating performance (English) continued OUTDOOR COIL ENTERING AIR TEMPERATURES •F –3 INDOOR AIR (F) EDB Capacity Kw 7 Total Power Capacity Kw 17 Total Power Capacity Kw 27 Total Power Capacity Kw 37 Total Power Capacity Kw 47 Total Power Capacity Kw 57 Total Power 67 Capacity Kw Total Power Capacity Kw Total Power CFM Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ Total Integ† Kw‡ 38YCB048-70, 90 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 65 70 75 1400 1600 1800 1400 1600 1800 1400 1600 1800 18.5 18.7 19.0 18.1 18.4 18.7 17.8 18.1 18.3 17.0 17.2 17.5 16.7 16.9 17.2 16.4 16.6 16.8 2.91 2.94 2.97 3.04 3.06 3.10 3.17 3.19 3.22 23.1 23.4 23.6 22.9 23.2 23.4 22.6 22.9 23.1 21.2 21.5 21.7 21.0 21.3 21.5 20.8 21.0 21.3 3.11 3.12 3.14 3.25 3.26 3.28 3.38 3.40 3.42 27.9 28.1 28.4 27.7 28.0 28.2 27.6 27.8 28.1 25.4 25.7 25.9 25.3 25.5 25.8 25.1 25.4 25.6 3.29 3.29 3.30 3.45 3.45 3.46 3.62 3.61 3.62 33.3 33.6 33.9 33.1 33.4 33.7 32.9 33.2 33.4 29.6 29.9 30.1 29.4 29.7 29.9 29.2 29.5 29.7 3.48 3.47 3.48 3.66 3.64 3.65 3.84 3.82 3.82 39.6 39.9 40.2 39.3 39.6 39.9 39.0 39.4 39.7 36.0 36.3 36.6 35.7 36.0 36.3 35.5 35.9 36.1 3.71 3.68 3.67 3.90 3.86 3.85 4.09 4.05 4.04 46.8 47.3 47.7 46.6 47.0 47.3 46.1 46.6 47.0 46.8 47.3 47.7 46.6 47.0 47.3 46.1 46.6 47.0 3.97 3.92 3.90 4.17 4.12 4.09 4.38 4.32 4.29 55.7 56.3 56.8 55.2 55.7 56.2 54.7 55.3 55.8 55.7 56.3 56.8 55.2 55.7 56.2 54.7 55.3 55.8 4.30 4.23 4.19 4.51 4.43 4.39 4.73 4.65 4.61 65.9 66.7 67.3 65.3 66.0 66.6 64.7 65.5 66.1 65.9 66.7 67.3 65.3 66.0 66.6 64.7 65.5 66.1 4.69 4.61 4.55 4.92 4.83 4.76 5.16 5.06 5.00 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 1.00 1.03 060 0.99 0.96 060 1.00 1.02 38YCB060-90 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 65 70 75 1750 1900 2000 2150 1750 1900 2000 2150 1750 1900 2000 2150 28.3 28.6 28.7 29.0 27.8 28.1 28.3 28.6 27.2 27.5 27.7 28.0 26.0 26.3 26.4 26.7 25.5 25.8 26.0 26.3 25.1 25.3 25.5 25.8 4.32 4.37 4.40 4.45 4.51 4.55 4.59 4.64 4.69 4.74 4.77 4.83 33.7 34.0 34.2 34.4 33.4 33.7 33.9 34.2 33.0 33.3 33.5 33.8 31.0 31.2 31.4 31.6 30.7 31.0 31.2 31.4 30.3 30.6 30.8 31.0 4.49 4.53 4.56 4.60 4.69 4.73 4.76 4.80 4.89 4.93 4.96 5.00 39.1 39.4 39.5 39.8 38.8 39.1 39.3 39.5 38.6 38.8 39.0 39.3 35.6 35.9 36.1 36.3 35.4 35.6 35.8 36.0 35.2 35.4 35.6 35.8 4.64 4.67 4.69 4.73 4.86 4.89 4.91 4.95 5.09 5.12 5.14 5.17 44.9 45.2 45.4 45.7 44.5 44.8 45.0 45.3 44.2 44.5 44.7 45.0 39.9 40.2 40.3 40.6 39.5 39.8 40.0 40.2 39.3 39.5 39.7 40.0 4.81 4.82 4.84 4.87 5.04 5.05 5.07 5.10 5.28 5.30 5.31 5.34 51.4 51.8 52.0 52.4 51.1 51.5 51.7 52.0 50.7 51.1 51.3 51.6 46.8 47.1 47.4 47.6 46.5 46.9 47.1 47.3 46.2 46.5 46.7 46.9 5.00 5.01 5.02 5.04 5.25 5.25 5.26 5.28 5.50 5.50 5.51 5.53 59.0 59.4 59.7 60.1 58.6 59.0 59.3 59.6 58.0 58.4 58.7 59.0 59.0 59.4 59.7 60.1 58.6 59.0 59.3 59.6 58.0 58.4 58.7 59.0 5.24 5.24 5.24 5.26 5.49 5.49 5.49 5.51 5.76 5.75 5.75 5.76 68.0 68.5 68.8 69.2 67.3 67.8 68.1 68.5 66.8 67.2 67.5 67.9 68.0 68.5 68.8 69.2 67.3 67.8 68.1 68.5 66.8 67.2 67.5 67.9 5.55 5.54 5.54 5.55 5.82 5.80 5.80 5.80 6.10 6.07 6.07 6.07 78.1 78.7 79.0 79.5 77.3 77.9 78.3 78.7 76.6 77.2 77.5 77.9 78.1 78.7 79.0 79.5 77.3 77.9 78.3 78.7 76.6 77.2 77.5 77.9 5.95 5.93 5.93 5.93 6.23 6.20 6.19 6.19 6.52 6.49 6.48 6.47 Multipliers for Determining the Performance With Other Indoor Sections Heating Heating Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.03 FB4ASB 070 0.99 0.95 — — — † The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity. ‡ The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to obtain total system kw’s. EDB — Entering Dry Bulb System Design 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 14 Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wg. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C). Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C), except for some 3 phase models it is 115°F (46.7°C). Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C). Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C). For reliable operation, unit should be level in all horizontal planes. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft (15.24m), indoor coil below = 150 ft (45.72m). (See items 8 and 9 following.) For interconnecting refrigerant tube lengths greater than 50 ft (15.24m), consult Long-Line Application Guideline available from equipment distributor. Not more than 36 in. (912mm) of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. (152mm) vertical rise to the valve connections at the unit. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort. Certified drawing—38YCB UNIT SERIES 38YCB024 38YCB036 38YCB036 38YCB048 38YCB048 38YCB060 0 0 1 0 1 0 O X X X X X 400-3-50 ENGLISH X X X X X O X X X X X O O X X X X X A B mm mm C D E F G H J K L M N SHIPPING WEIGHT P mm mm mm mm mm mm mm mm mm mm mm mm kg 81.0 82.6 82.6 82.6 82.6 82.6 15.9 19.1 19.1 22.2 22.2 22.2 93.6 165.1 165.1 165.1 165.1 165.1 460.4 596.9 596.9 596.9 596.9 596.9 501.7 692.2 692.2 692.2 692.2 692.2 549.3 739.8 739.8 739.8 739.8 739.8 365.1 508.0 508.0 508.0 508.0 508.0 479.4 669.9 669.9 669.9 669.9 669.9 560.4 750.9 750.9 750.9 750.9 750.9 317.5 381.0 381.0 381.0 381.0 400.1 304.8 400.1 400.1 400.1 400.1 396.9 355.6 393.7 393.7 393.7 393.7 381.0 65.9 100.9 100.0 100.0 104.1 118.6 B C D E F G H J K L M N P SHIPPING WEIGHT In. In. In. In. In. In. In. In. In. In. 5⁄8 3 11⁄16 6 1⁄2 6 1⁄2 6 1⁄2 6 1⁄2 6 1⁄2 18 1⁄8 23 1⁄2 23 1⁄2 23 1⁄2 23 1⁄2 23 1⁄2 19 3⁄4 27 1⁄4 27 1⁄4 27 1⁄4 27 1⁄4 27 1⁄4 571.5 862.0 762.0 1014.4 762.0 1014.4 762.0 862.0 762.0 862.0 762.0 862.0 X = YES O = NO A ELECTRICAL CHARACTERISTICS 400-3-50 0 0 1 0 1 0 230-1-50 38YCB024 38YCB036 38YCB036 38YCB048 38YCB048 38YCB060 ELECTRICAL CHARACTERISTICS 230-1-50 UNIT SERIES S.I. In. 22 1⁄2 30 30 30 30 30 33 15⁄16 3 3⁄16 39 15⁄16 3 1⁄4 39 15⁄16 3 1⁄4 33 15⁄16 3 1⁄4 33 15⁄16 3 1⁄4 33 15⁄16 3 1⁄4 3⁄4 3⁄4 7⁄8 7⁄8 7⁄8 21 5⁄8 14 3⁄8 29 1⁄8 20 29 1⁄8 20 29 1⁄8 20 29 1⁄8 20 29 1⁄8 20 In. 18 7⁄8 26 3⁄8 26 3⁄8 26 3⁄8 26 3⁄8 26 3⁄8 22 1⁄16 12 1⁄2 29 9⁄16 15 29 9⁄16 15 29 9⁄16 15 29 9⁄16 15 29 9⁄16 15 3⁄4 In. In. Lb. 12 15 3⁄4 15 3⁄4 15 3⁄4 15 3⁄4 15 5⁄8 14 15 1⁄2 15 1⁄2 15 1⁄2 15 1⁄2 15 145 222 220 220 229 261 X = YES O = NO A SQ AIR IN M AIR DISCHARGE AIR DISCHARGE FIELD POWER SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE WITH 1 1/8 IN. (28.6mm) DIA KNOCKOUT AND 1 3/8 IN. (34.9mm) DIA KNOCKOUT N J K L AIR IN 3/8 IN. (9.5mm) DIA TIEDOWN KNOCKOUTS (2) PLACES IN BASEPAN FIELD CONTROL SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE AIR IN B 3/8 IN. (9.5mm) DIA LIQUID LINE CONN P 2 7/8″ C (73.0mm) AIR DISCHARGE E AIR IN D DIA SERVICE LINE CONN F G 1 1/4″ (31.8mm) H UNIT SIZE 024 36 48, 60 MINIMUM MINIMUM MOUNTING PAD MOUNTING PAD DIMENSIONS (mm) DIMENSIONS (In.) 571.5 x 571.5 22 1⁄2 x 22 1⁄2 762.0 x 762.0 30 x 30 NOTES: 1. Allow 30 In. (762.0mm) clearance to service side of unit, 48 In. (1219.2mm) above unit, 6 In. (152.4mm) on one side, 12 In.(304.8mm) on remaining side, and 24 In. (609.6mm) between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55°F(13°C), max 125°F(52°C). 3. Maximum outdoor operating ambient in the heating mode is 66°F(19°C). 4. Series designation is the 13th position of the unit model number. 5. Center of gravity A94379 15 40 30 20 10 -20 Printed in U.S.A. 11-94 0 10 38YCB048 FB4AS048 38YCB036 FB4AS036 38YCB024 FB4AS024 BASED ON INDOOR ENT. AIR AT 21°C AND AT RATED CFM 20 38YCB060 FB4AS060 38YCB BALANCE POINT WORKSHEET -10 OUTDOOR TEMPERATURE, °C 25 16 BUILDING HEAT LOSS, KW UNIT INTEGRATED HEATING CAPACITY, KW A94370 80 70 60 50 40 30 20 10 -10 Printed in U.S.A. 11-94 BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR 10 20 30 40 50 60 70 BASED ON INDOOR ENT. AIR AT 70°F AND AT RATED CFM 38YCB024 FB4AS024 38YCB036 FB4AS036 38YCB048 FB4AS048 38YCB060 FB4AS060 38YCB BALANCE POINT WORKSHEET 0 OUTDOOR TEMPERATURE, °F 80 A94369 17 Guide specifications GENERAL System Description Outdoor-mounted, air-cooled, split-system heat pump unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit. Quality Assurance Unit shall be manufactured in a facility registered to ISO9002/ BS5750 Part II, International Standard for Quality Systems. Unit will be rated in accordance with the latest edition of ARI Standard 240 and 270. Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC (U.S.A. Standard). Unit will be constructed in accordance with UL standards. Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test (U.S.A. Standard). Air-cooled condenser coils will be leak tested at 150 psig (1034 KPa) and pressure tested at 300 psig (2068 KPa). Delivery, Storage, and Handling Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations. PRODUCTS Equipment Factory-assembled, single piece, air-cooled heat pump unit. Contained within the unit enclosure will be all factory wiring, piping, controls, compressor, refrigerant charge (R-22), and special features required prior to field start-up. Unit Cabinet Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint. Fans Condenser fan will be direct-drive propeller type, discharging air upward. Air-Cooled, Split-System Heat Pump 38YCB 2 To 5 Tons Nominal (7 To 17.5 Kw) Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings. Shafts will be corrosion resistant. Fan blades will be statically and dynamically balanced. Condenser fan openings will be equipped with PVC-coated steel wire safety guards. Compressor Compressor will be hermetically sealed. Compressor will be mounted on rubber vibration isolators. Condenser Coil Condenser coil will be air cooled. Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components Refrigeration circuit components will include liquid line shutoff valve with sweat connections, suction shut-off valves with sweat connections, system charge of refrigerant R-22, compressor oil, accumulator, and reversing valve. Operating Characteristics The capacity of the unit will meet or exceed ____ Btuh (____ kw) at a suction temperature of ____ F (____ C). The power consumption at full load will not exceed ____ kw. Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of ____ Btuh (____ kw) or greater at conditions of ____ CFM (____ L/S) entering air temperature at the evaporator at ____ F (____ C) wet bulb and ____ F (____ C) dry bulb, and air entering the unit at ____ F (____ C). Electrical Requirements Nominal unit electrical characteristics will be ____ v, 1 phase, 50 hertz. The unit will be capable of satisfactory operation within voltage limits of ____ v to ____ v. Unit electrical power will be single point connection. Control circuit will be 24v. Special Features Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements. Carrier Corporation • Syracuse, New York 13221 595 12-94 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 Tab 5a 5a 4 Page 18 Catalog No. 013-871 Printed in U.S.A. PC 101 Form 38YCB-C1PD Replaces: New