400 Series 420 Surge Protective Device Submittal Specification
General Specifications Maximum Continuous Operating Voltage Short Circuit Current Rating (SCCR) Maximum Surge Current Rating Operating Frequency Range Location Type Nominal Discharge Current (In) Status Indication Certifications Standard Enclosure Weights Warranty
120VAC 150%, all others 115% 200kAIC 50kA per Mode/50kA per Phase 47-63Hz Type 1 / Type 2 20kA Green/Red LED, Relay Alarm Contacts ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL (ROHS Compliant) NEMA Type 4X 1.2 lbs (.54 kg) 5 Year Replacement
ANSI/UL 1449 Third Edition, Type 1 VPR’s Source Configuration SA, YA YC YD DB DF DG
Model Number
420SA05BWRJ1S 420YA05BWRJ1S 420YC05BWRJ1S 420YD05BWRJ2S 420DB05EWRJ1S 420DF05EWRJ1S 420DG05EWRJ2S
Surge Rating
50kA Mode 50kA Phase
L-N
L-G
L-L
N-G
700V 1200V 1500V N/A N/A N/A
1200V 2500V 3000V N/A N/A N/A
1200V 2500V 2500V 1200V 2500V 2500V
700V 1200V 1500V N/A N/A N/A
Source Configuration (Consult Factory for additional source configurations) “SA” - 120/240VAC, 120/208VAC, Single Split Phase, 3W+G
Modes Of Protection L-N, N-G
“YA” - 120/208VAC, 127/220VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 1
“YC” - 277/480VAC, 254/440VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 1
“YD” - 346/600VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 2
“DB” - 240VAC, Three Phase DELTA, 3W+G
L-L
Type 1
UL Location Type Type 1
“DF” - 480VAC, Three Phase DELTA, 3W+G
L-L
Type 1
“DG” - 600VAC, Three Phase DELTA, 3W+G
L-L
Type 2
For applications requiring CUL approval, change the SPD model number from a UL Type 1 (420xxxxxxxx1x) to a UL Type 2 (420xxxxxxxx2x)
Dimensions:
Top View
Side View
100 Emerson Parkway Binghamton, NY 13905 P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E
[email protected]
SS-70104 Rev 1 8-14