Preview only show first 10 pages with watermark. For full document please download

425-4-air Distribution-2007

   EMBED


Share

Transcript

ME 425 - Air Distribution & ASHRAE Outlet Selection 1 ME 425 Air Distribution & ASHRAE Outlet Selection Keith E. Elder, P.E. The Air Distribution System The purpose of air distribution system is to create the proper combination of temperature, humidity and air velocity in the occupied zone of the conditioned room. If not properly designed, the air distribution system has the potential to compromise the comfort conditions it was designed to maintain. 1 ME 425 - Air Distribution & ASHRAE Outlet Selection 2 ASHRAE Air Distribution Design Recommendations Already defined in one lawsuit as “The Acceptable Standard of Care” Two Basic Rules   Cooling - diffuser selection should be based on the ratio of the diffuser’s throw to the length of the area supplied to achieve high ADPI (minimize draft) Heating - diffuser-to-room ∆t should not exceed 15°F to minimize stratification (minimize stratification) Expanded Comfort Criteria Comfort is maintained through the change in seasons when the following conditions are maintained in the space occupied zone.     Air temp maintained between 73-77°F RH maintained between 25-60% Maximum air motion in the occupied zone  50 fpm cooling  25 fpm heating Maximum temperature gradient  1-2° cooling  4° heating 2 ME 425 - Air Distribution & ASHRAE Outlet Selection 3 Successful Design Achieves: Good ventilation effectiveness Avoids dumping Avoids draft Occupied Zone 3 inches to 72 inches above the floor level. Two feet in from the walls 2 F t. 2 F t. O cc u p ied Zone 3 "-6 '-0 " F t. 3 ME 425 - Air Distribution & ASHRAE Outlet Selection 4 Definition of “Draft” Koestel, Tuve and Reinmannn studied the effect of air motion in the 1950’s, measuring the warmth or coolness of a draft above or below a room temperature of 76°F at 30 inches above the floor at room center, with air velocity at 30 fpm. They defined “draft” as: Any localized feeling of coolness or warmth of any portion of the body due to both air movement and temperature, with humidity and radiation considered constant. Impact of Draft on Comfort 4 ME 425 - Air Distribution & ASHRAE Outlet Selection 5 Percentage of Occupants Objecting to Drafts Effective Draft Temperature The physiological effects on a human body due to air temperature & air motion can be described by Effective Draft Temperature (the difference in temperature between any point in the occupied zone and the control condition). E.D.T. can be quantified as: θ = tx - tc - 0.07(Vx - 30) Where: θ = effective draft temperature  tx = local airstream temperature, °F  tc = average room temperature, °F  Vx = local airstream velocity, fpm • 5 ME 425 - Air Distribution & ASHRAE Outlet Selection 6 Room Air Distribution Methods Displacement Ventilation Localized Ventilation Mixing Systems Conventional Mixing Systems 6 ME 425 - Air Distribution & ASHRAE Outlet Selection 7 Entrainment Flow Conventional Mixing Terminal Velocity A targeted value of interest – usually 50, 100 or 150 fpm 7 ME 425 - Air Distribution & ASHRAE Outlet Selection 8 Terminology Outlet/Inlet Terminals Grille Register Diffuser Two Other Important Concepts Throw  The distance from the outlet to a point where the maximum velocity in the stream cross section has been reduced to a selected terminal velocity. Characteristic Room Length  The distance from the diffuser to the nearest boundary wall in the principle horizontal direction of the airflow 8 ME 425 - Air Distribution & ASHRAE Outlet Selection 9 Outlet Classification Group A. Outlets mounted in or near the ceiling that discharge air horizontally. Group B. Outlets mounted in or near the floor that discharge air vertically in a non-spreading jet. Group C. Outlets mounted in or near the floor that discharge air vertically in a spreading jet. Group D. Outlets mounted in or near the floor that discharge air horizontally. Group E. Outlets mounted in or near the ceiling that project primary air vertically. Group A Outlets 9 ME 425 - Air Distribution & ASHRAE Outlet Selection 10 Group A High Sidewall Grilles Group A – Ceiling Diffusers 10 ME 425 - Air Distribution & ASHRAE Outlet Selection 11 Neck, face, core & free area Neck Area & Neck Velocity Vneck = Qsa Aneck Vneck Aneck 11 ME 425 - Air Distribution & ASHRAE Outlet Selection 12 Neck Velocity Coanda Effect The attachment of a jet flow introduced parallel to a ceiling or other surface. This “surface” effect creates a lower-pressure region above the jet stream than below it, causing the higher pressure in the room to hold the airstream to the ceiling. Conditions necessary for surface effect include:     Angle of discharge < 40° from parallel surface A side wall outlet is within one foot of the ceiling A Floor or sill outlet is within 10 inches of a wall A ceiling outlet discharges along the ceiling 12 ME 425 - Air Distribution & ASHRAE Outlet Selection 13 Coanda Effect Coanda Effect 13 ME 425 - Air Distribution & ASHRAE Outlet Selection 14 Outlet Discharge Patterns Circular Diffuser The downward-jetpattern may be of benefit when the outlet is installed in a tall space and HVAC is in heating mode The visualization shows consequences for cooling mode 14 ME 425 - Air Distribution & ASHRAE Outlet Selection 15 Square/Rectangular Diffusers Square Diffuser Still capable of establishing Coanda adherence to ceiling, but provides flexibility for distributing air in a variety of patterns 15 ME 425 - Air Distribution & ASHRAE Outlet Selection 16 Slot Diffuser Slot Diffuser Also capable of Coanda adherence, but allows directing the air downward 16 ME 425 - Air Distribution & ASHRAE Outlet Selection 17 Air Diffusion Performance Index ADPI statistically relates the space conditions of local temperatures and velocities to occupant’s thermal comfort Quantitatively, ADPI is the percentage of locations where measurements show that the effective draft temperature, θ, is between - 3 and +2°F and the air velocity is less than 70 fpm. Isodrafts for a space with an ADPI of 94%. 17 ME 425 - Air Distribution & ASHRAE Outlet Selection 18 Designing to ADPI Criteria ADPI performance can be predicted based on air outlet “throw” data referenced to room “characteristic room length” ASHRAE Mixed Air System Outlet Selection Steps 1. Determine Air Volume Requirements & Room Size 2. Select diffuser type and location within room 3. Determine room characteristic length, L 4. Select recommended Tv/L ratio 5. Calculate throw distance by multiplying Tv/L ratio by room characteristic length 6. Locate appropriate outlet size from mfgr’s catalog. 7. Check static pressure & noise criteria 18 ME 425 - Air Distribution & ASHRAE Outlet Selection 19 Select diffuser type and location Ceiling Diffuser Perforated Panel Ceiling Slot Diffuser High Wall Grille 0 1 2 3 4 5 CFM/SF Determine Characteristic Room Length Type of Outlet High Sidewall Grille Ceiling Slot Diffuser Characteristic Length Distance to wall perpendicular to jet Distance to wall or midplane between outlets Perforated Ceiling Diffusers Distance to wall or midplane between outlets Circular Ceiling Diffuser Distance to closest wall or intersecting air jet Light Troffer Diffuser Distance to midplane between outlets, plus distance from ceiling to top of occupied zone 19 ME 425 - Air Distribution & ASHRAE Outlet Selection 20 Select Recommended Tv/L ratio Check noise criteria Design Guidelines for HVAC System Noise in Unoccupied Spaces Private residences, apartments, condominiums Hotels/Motels Individual rooms, Meeting/banquet rooms Halls, corridors, lobbies Office buildings Private offices and Conference rooms Teleconference rooms Open plan offices Circulation and public lobbies Hospitals and clinics Private rooms, Operating rooms Wards Corridors, Public Areas RC(N) Level Space 25-35 25-35 35-45 25-35 25 (max) 30-40 40-45 25-35 30-40 30-40 From 1995 ASHRAE Handbook, HVAC Applications, Chapter 43 (Abridged for this slide) 20 ME 425 - Air Distribution & ASHRAE Outlet Selection 21 Return Air Grilles   Ideally located in stagnant areas Usually placed in ceiling  Low inlet velocities mean placement not normally the cause of short-circuiting on welldesigned systems  Number  Generally one per 4 supply outlets  Minimum one per occupied room  Air-flows under-specified 5 – 10% relative to supply for pressurization Outlet Selection Example Select and locate appropriate ceiling air supply diffusers for the space shown below so as to maximize comfort in the occupied space. The ceiling is 11 ft and design supply air requirement is 350 CFM. 12’ 24’ 21 ME 425 - Air Distribution & ASHRAE Outlet Selection 22 Homework Read 05F33.1 - 33.18 Select and locate appropriate ceiling air supply diffusers on the reflected ceiling plan so as to maximize comfort in the occupied space. The ceiling is 10 feet above the floor and the design supply air requirement is 1400 CFM. The tile dimensions are 2’ x 4’ 16’ 42’ Reflected Ceiling Plan 22