P R O D U C T S E L E C T I O N D ATA
●● Modular false ceiling
ducted unit
●● Extremely quiet operation ●● Low Energy Consumption ●● Flexibility for simplified installation
●● Improved comfort ●● Efficient Indoor Air Quality
Hydronic Ducted Fan Coil Units
42EM CARRIER participates in the ECP programme for LCP/HP Check ongoing validity of certificate: www.eurovent-certification.com www.certiflash.com
Original document
Contents 1 - FUNCTIONS................................................................................................................................................................................ 3 2 - FEATURES.................................................................................................................................................................................. 3 2.1 - Configuration flexibility............................................................................................................................................................ 3 2.2 - Low noise levels........................................................................................................................................................................ 3 2.3 - Compact design ........................................................................................................................................................................ 3 2.4 - Physical and electrical data at Eurovent conditions............................................................................................................. 4 2.4 - Physical and electrical data at Eurovent conditions (continued)........................................................................................ 5 2.4 - Physical and electrical data at Eurovent conditions (continued)........................................................................................ 6 2.5 - Dimensional drawings.............................................................................................................................................................. 7 2.6 - Spigot configuration.................................................................................................................................................................. 9 2.6 - Spigot configuration (continued)........................................................................................................................................... 10 3 - MAIN MODULES AND COMPONENTS.......................................................................................................................... 11 3.1 - Fan motor assemblies.............................................................................................................................................................. 11 3.2 - Water coil.................................................................................................................................................................................. 11 3.3 - One-piece condensate drain pan........................................................................................................................................... 11 3.4 - Filter and filter access............................................................................................................................................................. 11 3.5 - Fan wiring solutions................................................................................................................................................................ 11 3.6 - Fresh air controller.................................................................................................................................................................. 12 3.7 - Electric heater (option).......................................................................................................................................................... 12 4 - TECHNICAL SPECIFICATIONS & OPTIONS................................................................................................................. 13 4.1 - Valves (option)......................................................................................................................................................................... 13 4.2 - Technical specification, flexible water pipes (option).......................................................................................................... 13 4.3 - Filters ....................................................................................................................................................................................... 14 4.4 - Condensate pump (option).................................................................................................................................................... 14 5 - CONTROL (OPTION)............................................................................................................................................................ 15 6 - ATMOSPHERA PERFORMANCE DATA......................................................................................................................... 16 6.1 - Cooling capacity - water coil.................................................................................................................................................. 16 6.2 - Heating capacity - water coil.................................................................................................................................................. 19 6.3 - Sound power levels................................................................................................................................................................. 21 6.4 - Electrical data.......................................................................................................................................................................... 23 6.5 - Water coil pressure drop ........................................................................................................................................................ 27 6.6 - Air flow data............................................................................................................................................................................ 27 7 - GUIDE SPECIFICATION...................................................................................................................................................... 29
The photograph on the front cover is for illustrative purposes only and is not part of any offer for sale or contract. The manufacturer reserves the right to change the design at any moment without prior warning. 2
• • • • • • • • • • • • • •
2 - FEATURES 2.1 - Configuration flexibility Depending on the size, several motor drive selections are available: • Sizes 0 and 1: one multi-speed motor drive (models 05 and 10) and one low-consumption variable-speed motor drive (models 09 and 19) • Sizes 2 and 3: three multi-speed motor drive selections possible (models 21, 22, 23 and 31, 32, 33) and one low-consumption variable-speed motor drive (models 29 and 39) There are two unit models available: • modular models for all sizes, with side connection spigots for maximised flexibility. This model consists of a nonducted base unit. In this configuration filter removal is from the rear:
Filter
In models with ducted return air it is possible to add a factory-assembled return air plenum.
Sizes 0x Base unit
Sizes 1x Base unit
Sizes 2x and 3x Accessory return air plenum
The Carrier 42EM Atmosphera is available in different sizes with 2-pipe, 2-pipe plus electric heater or 4-pipe coils, with an air flow range from 27 to 440 l/s, a total nominal cooling capacity range from 0.65 to 10 kW and a nominal heating capacity range from 1.1 to 18 kW. Compact ducted unit, designed for false ceiling installation. Reliable and economical for light commercial and office applications. Low height of 250 mm. Two versions for increased installation flexibility: modular or compact. Compatible with the Carrier 35BD diffuser range. Air outlet configuration modularity with different plenums. Extremely low sound levels for ducted applications. Six-speed fan motor offers a wide choice of medium speeds. Available with low-consumption variable-speed EC motor (LEC = low energy consumption). High-pressure centrifugal fan. G3 filters as standard. Safe factory-installed electric heater with multiple capacity stages choices. Low water pressure drop with factory-installed valves. Factory-installed options (valves and controllers) for fast and easy installation in false ceilings.
Accessory return air plenum
•
Connection possibilities
Accessory return air plenum
1 - FUNCTIONS
Base unit
Filter
NOTE: Carrier recommends not to exceed an air velocity of 4 m/s (125 l/s 450 m3/h) per spigot. •
One-piece compact in-line units (all sizes) are models with in-line ducted supply and return air (only 125 mm diameter fresh air ducts can be connected on the sides). Sizes 0x
Sizes 1x
Sizes 2x and 3x
This version does not allow the use of 200 mm diameter spigots on the sides. Filter removal is from below.
Filter
2.2 - Low noise levels In order to further enhance occupant comfort this product range offers especially low noise levels. The casing of the 42EM Atmosphera is made of galvanised sheet steel with full high-efficiency internal lining for optimised thermal and sound insulation of the unit. In order to comply with the various local regulations (fire class) the 42EM Atmosphera is available with class M1 type insulation (according to NF P 92-507). It is also equipped with anti-vibration mounts as standard. 42EM is available on request with insulation material Euroclass level B-s3-d0 (according to EN 13501) compliant with British Class O requirements. 2.3 - Compact design The condensate removal pan height is optimised at 215 mm. In order to reduce the dimensions of the 42EM Atmosphera to the minimum, the units are equipped with high-efficiency heat exchangers with very high cooling capacity/treated air flow ratios. 3
2.4 - Physical and electrical data at Eurovent conditions 42EM Fan speed Air flow Available static pressure Cooling mode, two pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, two pipes** Heating capacity Cooling mode, four pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, four pipes*** Heating capacity Water flow rate
l/s m3/h Pa
05 L 58 210 23
kW kW l/s l/h kPa l
1.57 1.14 0.07 270 13 0.35
2.18 1.61 0.10 374 24
2.27 1.68 0.11 389 25
0.91 0.64 0.04 156 4 0.35
2.25 1.67 0.11 387 25
2.86 2.17 0.14 492 38
1.87 1.39 0.09 321 11 0.5
2.76 2.11 0.13 475 23
3 2.31 0.14 516 27
kW
1.91
2.69
2.8
1.08
2.77
3.59
2.44
3.75
kW kW l/s l/h kPa l
1.43 1.08 0.07 247 9 0.32
1.98 1.52 0.09 342 17
2.06 1.58 0.10 355 19
0.83 0.61 0.04 143 3 0.32
2.05 1.57 0.10 353 18
2.6 2.03 0.12 447 28
1.8 1.36 0.09 310 14 0.45
kW l/s l/h kPa l
1.47 2.00 2.08 0.04 0.05 0.05 129 175 182 10 17 19 0.11 230 V ± 10 % - 1 ph - 50 Hz 1600 6.95
0.87 0.02 76 4 0.11
2.06 0.05 181 19
2.60 0.06 228 28
2.44 0.04 209 7 0.15
M 86 309 50
H 90 324 58
Water pressure drop Water content Electric heater Maximum capacity W Current drawn A Sound levels Sound power level (return and radiated) dB(A) 43 54 57 Sound power level (supply) dB(A) 42 49 50 Electrical data, motor 230 V ± 10 % - 1 ph - 50 Hz Power input W 45 77 102 Current drawn A 0.2 0.34 0.45 Air filter (G3) mm 230 x 420 Technical data (compact model, overall dimensions) Connection diameter, cold and hot-water coils in 1/2 gas (unit nuts female) Spigot connection diameter mm 200 Height mm 250 Depth mm 700 Length mm 870 Unit weight kg 20
09 L 32 115 6
M 89 320 50
H 121 436 93
1600 6.95 33 29
10 L 74 271 19
M 119 438 50
H 132 490 62
M 127 456 50
H 151 544 75
1.01 0.73 0.04 162 3 0.5
2.90 2.23 0.14 499 25
3.31 2.59 0.16 569 33
4.1
1.26
3.97
4.6
2.6 2.03 0.12 446 29
2.8 2.21 0.13 482 34
0.91 0.66 0.04 155 4 0.45
2.67 2.1 0.13 457 30
3.01 2.4 0.14 518 39
3.46 0.06 298 14
3.73 0.06 320 16
1.36 0.02 110 2 0.15
3.63 0.06 311 16
4.09 0.07 352 20
1600 6.95
1600 6.95
50 47
57 54
41 38
4 33 230 x 420
72 -
44 82 0.17 0.35 230 x 570
200 250 700 870 20
51 49
53 51
34 32
52 51
57 56
113 0.48
6 51 230 x 570
83 -
200 250 850 870 22
Fan speed: L = Low, M = Medium, H = High * Eurovent conditions: Entering air temperature = 27°C db/47% rh – entering water temperature = 7°C, water temperature difference = 5 K. ** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling. *** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 70°C, water temperature difference = 10 K.
4
19 L 37 122 4
200 250 850 870 22
2.4 - Physical and electrical data at Eurovent conditions (continued) 42EM Fan speed Air flow Available static pressure Cooling mode, two pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, two pipes** Heating capacity Cooling mode, four pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, four pipes*** Heating capacity Water flow rate
l/s m3/h Pa
21 L 69 250 12
kW kW l/s l/h kPa l
1.85 1.36 0.09 324 6 1.0
3.65 2.77 0.18 634 23
3.90 2.98 0.19 677 26
2.32 1.70 0.11 399 9 1.0
4.23 3.21 0.20 726 30
4.70 3.61 0.22 808 36
2.70 2.03 0.13 472 13 1.0
5.40 4.22 0.26 929 50
5.60 4.44 0.27 972 54
kW
2.33
4.77
5.12
2.87
5.44
6.13
3.47
7.26
kW kW l/s l/h kPa l
2.21 1.69 0.11 392 10 0.8
3.45 2.66 0.17 598 22
3.70 2.85 0.18 637 25
2.23 1.65 0.11 382 10 0.8
3.96 3.06 0.19 679 29
4.38 3.43 0.21 753 35
2.61 1.97 0.13 450 12 0.8
kW l/s l/h kPa l
1.85 3.50 3.70 0.05 0.09 0.09 166 310 328 2 6 7 0.2 230 V ± 10 % - 1 ph - 50 Hz 3200 13.91
2.29 0.06 201 3 0.2
3.98 0.10 349 9
4.39 0.11 386 10
2.60 0.07 234 4 0.2
M 150 540 50
H 163 585 58
Water pressure drop Water content Electric heater Maximum capacity W Current drawn A Sound levels Sound power level (return and radiated) dB(A) 39 53 55 Sound power level (supply) dB(A) 36 48 50 Electrical data, motor 230 V ± 10 % - 1 ph - 50 Hz Power input W 43 94 104 Current drawn A 0.20 0.43 0.45 Air filter (G3) mm 230 x 990 Technical data (compact model, overall dimensions) Connection diameter, cold and hot-water coils in 1/2 gas (unit nuts female) Spigot connection diameter mm 200 Height mm 250 Depth mm 1270 Length mm 870 Unit weight kg 41
22 L 85 306 12
M 173 623 50
H 199 716 66
3200 13.91 39 37
M 247 890 50
H 263 945 56
54 52
29 L 55 198 3
M 211 760 50
H 237 853 63
1.56 1.13 0.07 269 4 1.0
4.92 3.80 0.24 845 39
5.36 4.18 0.26 921 45
7.63
1.9
6.43
7.08
4.97 3.96 0.24 864 46
5.20 4.17 0.25 896 50
1.51 1.1 0.07 260 4 0.8
4.57 3.59 0.22 785 37
4.95 3.94 0.24 850 43
4.90 0.12 439 13
5.20 0.13 457 14
1.57 0.04 138 2 0.2
4.57 0.11 402 11
4.95 0.12 435 13
52 51
55 53
3200 13.91
62 112 0.29 0.52 230 x 990 200 250 1270 870 41
23 L 106 380 9
3200 13.91
57 55
46 40
59 55
128 0.62
102 139 0.55 0.63 230 x 990
61 58
43 43
149 0.68
4 73 0.05 0.61 230 x 990
200 250 1270 870 41
96 0.74
200 250 1270 870 39
Fan speed: L = Low, M = Medium, H = High * Eurovent conditions: Entering air temperature = 27°C db/47% rh – entering water temperature = 7°C, water temperature difference = 5 K. ** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling. *** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 70°C, water temperature difference = 10 K.
5
2.4 - Physical and electrical data at Eurovent conditions (continued) 42EM Fan speed Air flow Available static pressure Cooling mode, two pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, two pipes** Heating capacity Cooling mode, four pipes* Total cooling capacity Sensible cooling capacity Water flow rate Water pressure drop Water content Heating mode, four pipes*** Heating capacity Water flow rate
l/s m3/h Pa
31 L 69 250 12
kW kW l/s l/h kPa l
2.26 1.53 0.11 389 6 1.7
4.55 3.19 0.22 792 24
4.90 3.44 0.24 854 28
2.84 1.92 0.13 484 9 1.7
5.34 3.73 0.26 918 32
6.02 4.23 0.29 1034 41
3.35 2.31 0.16 580 13 1.7
7.01 4.99 0.34 1210 56
7.35 5.26 0.35 1260 61
kW
2.48
5.19
5.60
3.05
5.94
6.72
3.75
8.01
kW kW l/s l/h kPa l
2.20 1.50 0.11 378 8 1.5
4.40 3.13 0.21 766 31
4.80 3.37 0.23 824 36
2.75 1.89 0.13 472 12 1.5
5.18 3.65 0.25 890 42
5.83 4.14 0.28 1002 53
3.20 2.26 0.16 565 17 1.5
kW l/s l/h kPa l
1.85 3.50 3.70 0.05 0.09 0.09 166 310 328 2 6 7 0.2 230 V ± 10 % - 1 ph - 50 Hz 3200 13.91
2.29 0.06 201 3 0.2
3.98 0.10 349 9
4.39 0.11 386 10
2.60 0.07 234 4 0.2
M 150 540 50
H 163 585 58
Water pressure drop Water content Electric heater Maximum capacity W Current drawn A Sound levels Sound power level (return and radiated) dB(A) 39 53 55 Sound power level (supply) dB(A) 36 48 50 Electrical data, motor 230 V ± 10 % - 1 ph - 50 Hz Power input W 43 94 104 Current drawn A 0.20 0.43 0.45 Air filter (G3) mm 230 x 990 Technical data (compact model, overall dimensions) Connection diameter, cold and hot-water coils in 1/2 gas (unit nuts female) Spigot connection diameter mm 200 Height mm 250 Depth mm 1270 Length mm 870 Unit weight kg 43
32 L 85 306 12
M 173 623 50
H 199 716 66
3200 13.91 39 37
M 247 890 50
H 263 945 56
54 52
H 237 853 63
1.82 1.23 0.09 313 4 1.7
6.18 4.34 0.30 1062 42
6.8 4.81 0.32 1166 49
8.50
1.99
7.07
7.82
6.70 4.87 0.32 1160 71
7.10 5.14 0.34 1224 79
1.78 1.21 0.09 306 5 1.5
5.99 4.26 0.29 1030 53
6.57 4.7 0.31 1127 54
4.90 0.12 439 13
5.20 0.13 457 14
1.47 0.04 130 1 0.2
4.09 0.10 360 9
4.40 0.11 389 11
52 51
55 53
3200 13.91
57 55
46 40
59 55
128 0.62
102 139 0.55 0.63 230 x 990
61 58
43 43
149 0.68
4 73 0.05 0.61 230 x 990
200 250 1270 870 43
Fan speed: L = Low, M = Medium, H = High * Eurovent conditions: Entering air temperature = 27°C db/47% rh – entering water temperature = 7°C, water temperature difference = 5 K. ** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling. *** Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 70°C, water temperature difference = 10 K.
6
39 L 55 198 3
M 211 760 50
3200 13.91
62 112 0.29 0.52 230 x 990 200 250 1270 870 43
33 L 106 380 9
200 250 1270 870 41
96 0.74
2.5 - Dimensional drawings NOTE: All drawings shown have the coil connections on the right-hand side. Units with left-hand connections are symmetrical. Size 0 - Modular model (with optional return air plenum) Return air plenum
Return air spigots ø 200 mm or Return air spigots ø 200 mm
Fresh-air cutout ø 125 mm
or Fresh-air cutout ø 125 mm
Size 0 - Compact in-line model, ducted return air
Fresh-air cutout ø 125 mm
Size 1 - Modular model (with optional return air plenum) Return air plenum 904 234
60
60
670 622
232
125 250
4
117
117 276
Return air spigots ø 200 mm
or
Air flow direction
90
650
23
Fresh-air cutout ø 125 mm
Return air spigots ø 200 mm or Fresh-air cutout ø 125 mm
300 16
600 187
All dimensions are in mm.
7
Size 1 - Compact in-line model, ducted return air 650 75
0
750 704
60 23
232
60
78
204
78
300 600
16 Fresh-air cutout ø 125 mm
187
Sizes 2 and 3 - Modular model (with optional return air plenum) Return air spigots ø 200 mm
Return air plenum
or Fresh-air cutout ø 125 mm
Filter access Return air spigots ø 200 mm or Fresh-air cutout ø 125 mm
Sizes 2 and 3 - Compact in-line model, ducted return air
Filter access Fresh-air cutout ø 125 mm
8
Air flow direction All dimensions are in mm.
2.6 - Spigot configuration 42EM 05 and 09
42EM 10 and 19
42EM 2x and 3x
Modular models 1 spigot
2 spigots
3 spigots
4 spigots
5 spigots
Modular models with return air plenum 1 spigot
2 spigots
3 spigots
4 spigots
5 spigots
Compact models
1 spigot
2 spigots
3 spigots
Fresh air inlet
9
2.6 - Spigot configuration (continued) 42EM 05 and 09
42EM 10 and 19
U-shaped modular models without return air plenum Left-hand coil connection
Right-hand coil connection
Left-hand coil connection
Right-hand coil connection
U-shaped modular models with return air plenum Left-hand coil connection
Left-hand coil connection
Right-hand coil connection
Right-hand coil connection
Fresh air inlet
NOTE: 42EM sizes 29 & 39 are available with plenum U type on special request. IMPORTANT: The fresh air inlet is always opposite the spigot side that is by default opposite the coil connection side.
10
3 - MAIN MODULES AND COMPONENTS
3.4 - Filter and filter access
3.1 - Fan motor assemblies 3.1.1 - Multi-speed fan motor assembly according to ERP 2015
The 42EM includes as standard a non-regenerable G3 filter according to EN 779, medium fire rating M1, metal wire frame.
Description/codification
3.5 - Fan wiring solutions
Unit size (chassis): 0, 1, 2, 3 Multi-speed fan motor assembly, size: 0, 1, 2, 3, 5 Variable speed: 9
• • •
Asynchronous motors, 230 V - 1 ph - 50 Hz, 4 poles with internal overload protection. Permanent capacitor. Class B winding insulation, varnish class F.
The 42EM Atmosphera sizes 0x and 1x have a multi-speed fan motor assembly with forward-curved, double-inlet, single-wheel fans. Sizes 2x and 3x are available with doublewheel fans and three speed arrangements (21, 22, 23 and 31, 32, 33), depending on the required air flows/pressures. Six speeds are available as standard. From these three speeds must be selected to allow connection of the fan motor in accordance with the applicable electromechanical or electronic regulations. • Minimum speed: terminal 6 • Maximum speed: terminal 1 • 42EM units are supplied with Carrier numerical controls and prewired to the factory settings, for speeds 1, 3 and 5. • For other fan motor speed wiring combinations refer to the unit codification. 3.1.2 - Low-consumption fan motor assembly (variablespeed LEC) Atmosphera sizes 09, 19, 29 and 39 are equipped with the variable-speed LEC fan motor, that is controlled by a 0 to 10 V signal, available with the Carrier NTC type electronic control. NOTE: In this case the minimum control signal that allows motor start-up is 2 V for two- and four-pipe versions and 3 V for the versions equipped with electric heaters. If the product is supplied without a Carrier control device, verification of EMC conformity is the responsibility of the installer. 3.2 - Water coil • • • •
Aluminium fins mechanically bonded by expansion onto copper tubes 1/2” threaded water inlet and outlet connections (female) Air purge valves and drain are standard. Service pressure 1600 kPa.
The coil is integral with the drain pan and coil access door to ease of removal during service and maintenance.
3.5.1 - Multi-speed unit with bare wires (standard) The fan motor assembly has six speeds taken from an auto-transformer offering the unit greater flow control flexibility. When ordering, three of the six speeds must be selected to allow connection of the fan motor in accordance with the applicable electronic regulations. Three speeds are connected - the default factory wiring is 5-3-1 (minimum speed = 6, maximum speed =1). 3.5.2 - Multi-speed unit with optional 6 speeds bare wires on connector All motor fan speeds are factory wired and available as bare wires on connector. 3.5.3 - Multi-speed unit with optional control box This option allows the installer to connect the unit to a terminal board inside a control box. To comply with the applicable regulations, the control box can be opened with a screw driver. The control box option permits changing the speed wiring without access to the motor. Three of the available six speeds are connected - the default factory wiring is 5-3-1 (minimum speed = 6, maximum speed = 1). Default factory wiring 5-3-1 Three speeds available, easy access
3.5.4 - Variable-speed low energy consumption (LEC) fan motor option with bare wires (standard) The variable-speed low energy consumption (LEC) fan motor must be controlled by a 0-10 V d.c. signal. 3.5.5 - Variable-speed low energy consumption (LEC) fan motor option with control box option This option allows the installer to connect the unit to a terminal board inside a control box. To comply with the applicable regulations, the control box can be opened with a screw driver. The 0-10 V d.c. signal that controls the variable fan speed is directly accessible at the terminal board. 0-10 V factory wiring
3.3 - One-piece condensate drain pan Pan with a 16 mm external drain connection diameter and insulation class M1 in accordance with standard NFP 92-507. 11
3.5.6 - Cover only option An accessory plastic cover can be provided for a control supplied by the customer (max. dimensions L = 200 mm x D = 100 mm x H = 95 mm) and is installed on site or at the factory on a multi-speed unit or a variable-speed low energy consumption (LEC) fan motor. NOTE: This option is not compatible with the control box option.
3.6.2 - Variable volume fresh air controller The 42EM Atmosphera can be equipped with an optional variable fresh air flow controller from 0-55 l/s (0-200 m3/h). This is connected to the numeric Carrier controller and can regulate the fresh air intake in two ways: • either using a fixed rate set by the installer that can be reconfigured as required • or based on the CO2 level; in this case it is connected to a CO2 sensor via the Carrier numeric controller (the CO2 sensor is located opposite the fresh air inlet). NOTE: With the variable fresh air flow controller the upstream pressure in the fresh air duct must be 180 Pa. 3.7 - Electric heater (option)
3.6 - Fresh air controller 3.6.1 - Constant volume fresh air controller The 42EM Atmosphera can be fitted with a constant fresh air flow controller, fixed at 8.5 l/s (30 m3/h) or adjustable from 17 l/s (60 m3/h) to 44 l/s (160 m3/h) to allow contol of the introduction of fresh air and of the air change rate. The fresh air supply is normally located ahead of the water coil.
Electric heater-resistance wire type • Supply voltage: 230 V - 1 ph - 50 Hz • Heater size and capacity per unit (+5% ; -10%): Electrical Heater Total capacity (W) 42EM 05/09 42EM 10/19 42EM 21 42EM 22/23/29 42EM 31 42EM 32/33/39
Controllers with adjustable fresh air flow:
12 3 4
A 12 3 4
43 2 1
B 43 2 1
MR60 MR75 MR85 MR90 MR100 MR105 MR110 MR120 MR130 MR140 MR160
l/s 17 21 24 25 28 29 31 33 36 39 44
m3/h 60 75 85 90 100 105 110 120 130 140 160
A 4-4 4-3 3-3 3-2 2-1 2-1 1-1 3-3 2-1 1-1 -
B 4-4 4-3 3-2 2-2 2-1 1-1 1-1 -
The 17 1/s (60 m3/h) or fresh air controller may be modified on site by relocating or removing two plastic restrictors in order to increase the maximum constant fresh air flow capacity to 44 1/s (160 m3/h). IMPORTANT: If the 42EM includes a return air temperature sensor, the constant fresh air flow rate must not exceed 50% of the unit supply air flow rate at minimum speed. NOTE: To operate correctly, the 8.5 l/s (30 m3/h) the constant fresh air flow controller requires a differential pressure in the range of 50 Pa to 200 Pa. The controller with adjustable fresh air flow from 17 l/s (60 m3/h) to 44 l/s (160 m3/h) requires a differential pressure in the range of 70 to 200 Pa.
12
•
500
800
1000
1600
2000
3200
1 x 500 1 x 500 NA NA NA NA
1 x 800 1 x 800 NA NA NA NA
1 x 1000 1 x 1000 2 x 500 2 x 500 2 x 500 2 x 500
1 x 1600 1 x 1600 2 x 800 2 x 800 2 x 800 2 x 800
NA NA NA 2 x 1000 NA 2 x 1000
NA NA NA 2 x 1600 NA 2 x 1600
The heater is protected with a dual safety device: a) Self-holding automatically reset integrated safety thermostat b) Destructive thermofuse link
NOTE: Minimum air flow must be maintained to avoid damaging the electric heaters: • Unit sizes 05, 09, 10, 19: minimum air flow 28 l/s (100 m3/h) • Unit sizes 21, 31: minimum air flow 42 l/s (150 m3/h) • Unit sizes 22, 23, 29, 32, 33, 39: minimum air flow 55 l/s (200 m3/h)
4 - TECHNICAL SPECIFICATIONS & OPTIONS 4.1 - Valves (option)
4.2 - Technical specification, flexible water pipes (option)
NOTE: The motor valve assembly is normally closed. 4.1.1 - Valve actuators A wide choice of actuators is available with two or four-way valve bodies (three-way with integral bypass) to offer the right solution for any controller type and customer requirement, from on/off to proportional types, with either 230 V or 24 V power supply: • • • • •
On/off 230 V actuator On/off 24 V actuator Floating 3-point 230 V actuator Floating 3-point 24 V actuator Modulating 0-10 V/24 V actuator
When combined with LEC motors and the NTC controller, floating 3-point 230-V actuators are recommended to increase energy savings and enhance comfort. NOTE: 24V power supply actuators are not compatible with Carrier controllers (Thermostats A/B/C/D, HDB & NTC). 4.1.2 - Two-way valve body Features of the 1/2” two-way valve • 1/2” male BSP connection for union nuts • Straight valve body with arrow indicating direction of flow embossed on valve body • Nominal size DN 15 for 1/2” valve • Fluid: water and glycol solution (max. 40% glycol) • Operating range: 2-90°C • Nominal pressure: PN 16 bar • Kvs = 1.6 4.1.3 - Three-way valve body (with integral bypass) Features of the 1/2” three-way valve • 1/2” male BSP connection for union nuts • Straight valve body with arrow indicating direction of flow embossed on valve body • Nominal size DN 15 for 1/2” valve • Fluid: water and glycol solution (max. 40% glycol) • Operating range: 2-90°C • Nominal pressure: PN 16 bar • Kvs = 1.6
4.2.1 - Materials • Pipes: MEPD-based elastomer (modified ethylenepropylene-diene) • Braid: 304L stainless steel • Insulation: cellular foam rubber with M1 fire rating (9 mm thick, flexible water pipes). 4.2.2 - Characteristics • Minimum bend radius: 106 mm • The flexible water pipes are designed for treated or untreated water (maximum 40% ethylene glycol or propylene glycol). • Maximum hot water temperature 90 °C • Maximum operating pressure: 16 bar • 1/2” flat gas connections • Length: 1 m. KV Valves
42EM 05/09 42EM 10/19 42EM 21 42EM 22/23/29 42EM 31 42EM 32/33/39 Course
On/Off
V3PTS
Cooling V2V V4V 1.6 1.6 1.6 1.6 1.6 1.6 2.5mm
1.6 1.6 1.6 1.6 1.6 1.6
Heating V2V V4V 1.6 1.6 1.6 1.6 1.6 1.6
1.6 1.6 1.6 1.6 1.6 1.6
Cooling V2V V4V 1.0 1.0 1.0 1.0 1.6 1.6 6.5mm
1.0 1.0 1.0 1.0 1.6 1.6
Heating V2V V4V 1.0 1.0 1.0 1.0 1.0 1.0
1.0 1.0 1.0 1.0 1.0 1.0
Note: By-pass KV = 0.63 for V4V valve KV=1 type By-pass KV = 1 for VAV valve KV=1.6 type
4.1.4 - Water valve pressure drop
Water flow rate, l/s (l/h)
4 3 2 1
Legend 1. Kvs = 0.63 2. Kvs = 1
Pressure drop, kPa 3. Kvs = 1.6 (standard valve) 4. Kvs = 2.5
13
4.3 - Filters 42EM offers multiple filters choices: • • •
Without filters: this option is available only on Compact units when another filter is already provided on air inlet diffuser or grilles. G3 filter: supplied as standard, medium fire rating M1, metal wire frame. G4 filter: medium efficiency solution, medium fire rating M1, metal wire frame.
4.4 - Condensate pump (option)
The condensate pump option is factory fitted on the side on the 42EM drain pan. Electrical power supply 230V-50/60Hz. Condensate pump discharge performances: TABLE OF ACTUAL DISCHARGE (l/h)
Total length of pipe (Ø int. 6 mm ) A
Discharge head (B) 0m 2m 4m 6m 8m 10 m
14
5m 20 16 11.5
10 m 19 15 11 8.5 6 4
20 m 18 14 10.5 7.5 5 3.5
30 m 17 13.5 10 6.5 4 2.5
5 - CONTROL (OPTION) The Atmosphera can be supplied with a wide range of Carrier controls. These offer functions to suit the various application requirements, summarised in the table below. Control algorithms Valve management Fan control Main functions
User interface
On-Off Proportional-integral Air flow control only (no valve) On-off actuators Proportional valves Three speeds Automatic fan speed selection LEC motor control Setpoint control Occupied/unoccupied mode Frost protection mode Window contact input Measurement of water inlet temperature for automatic seasonal changeover (2 pipes) Automatic seasonal changeover (4 pipes and 2 pipes + electric heater) Manual changeover Continuous ventilation within dead-band Periodical ventilation within dead-band Unit grouping Louvre control On-site configuration Supply air temperature monitoring limiting Communication (CCN) Electrical heater loadshed Dirty filter alarm Alarm reporting IAQ control Demand control ventilation (DCV) Free cooling mode Digital display Automatic or manual fan speed control Operating mode selection Eco/unoccupied button
Thermostats X
HDB X
X X
X X
Type A-B X Type C-D X X X X Type A & C Type B & D X X X
X X
X X X
X X X X X X X X X X X X
X X X X
NTC X X O X X X X X X X X X X X X X X X X X X X X O O O X X X X
Legend HDB Hydronic Dual Board NTC New Terminal Controller X Standard function O Available as an option
NOTE: For the features and specifications of the Carrier controllers refer to the technical documentation for each controller. Upon special request other controller types can be factoryinstalled on the units (supplied by Carrier or the customer).
15
6 - ATMOSPHERA PERFORMANCE DATA 6.1 - Cooling capacity - water coil 6.1.1 - Two-pipe water coil Entering/ leaving water temperature, °C 6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Entering/ leaving water temperature, °C
6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Entering/ leaving water temperature, °C
6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Sizes 05 and 09 Relative humidity 50% Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 27 25 23 27 25 0.86 0.70 0.55 1.62 1.31 0.58 0.51 0.45 1.10 0.98 9.6 9.7 9.6 10.3 10.4 123 100 79 231 188 0.85 0.68 0.53 1.59 1.29 0.44 1.09 0.97 0.57 0.50 9.8 9.9 9.9 10.5 10.5 145 118 90 273 222 0.76 0.61 0.47 1.43 1.14 0.53 0.47 0.41 1.02 0.90 10.8 11.0 10.7 11.5 11.5 131 104 80 246 196 0.47 0.37 1.12 0.87 0.60 0.46 0.41 0.36 0.89 0.78 13.0 12.8 12.2 13.5 13.3 102 80 63 192 150 Sizes 10 and 19 Relative humidity 50% Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 0.82 0.67 0.53 1.55 1.24 0.94 0.56 0.49 0.44 1.07 0.94 0.82 10.1 10.1 9.9 10.7 10.8 10.7 117 96 76 221 177 135 0.81 0.65 0.51 1.53 1.23 0.82 0.55 0.49 0.43 1.07 0.94 0.82 10.3 10.4 10.2 10.8 10.9 10.8 139 112 87 263 211 160 0.73 0.57 0.45 1.38 1.08 0.82 0.52 0.45 0.40 1.00 0.87 0.76 11.3 11.4 11.0 11.8 11.9 11.6 125 99 77 236 185 141 0.56 0.45 0.36 1.06 0.82 0.65 0.45 0.40 0.35 0.87 0.76 0.65 13.3 13.0 12.5 13.8 13.5 13.3 97 77 61 183 142 112
23 1.00 0.85 10.3 143 0.98 0.84 10.5 168 0.86 0.78 11.3 148 0.68 0.67 12.9 116
27 2.28 1.59 11.0 326 2.25 1.57 11.1 386 2.03 1.48 12.1 348 1.57 1.29 14.0 270
25 1.85 1.40 11.0 265 1.82 1.39 11.1 313 1.60 1.30 12.1 276 1.23 1.13 13.7 212
83 (300) 27 2.19 1.55 11.3 314 2.18 1.55 11.4 375 1.95 1.45 12.4 335 1.50 1.27 14.2 258
25 1.75 1.36 11.3 251 1.74 1.36 11.4 299 1.53 1.27 12.3 262 1.18 1.11 13.9 202
111 (400) 23 1.41 1.22 10.8 202 1.38 1.21 10.9 238 1.22 1.13 11.7 210 0.97 0.97 13.4 167
Relative humidity 50% Air flow, l/s (m3/h) 83 (300) 125 ( 450) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 2.38 1.91 1.46 3.38 2.71 2.09 1.64 1.44 1.25 2.37 2.08 1.83 10.5 10.6 10.5 11.1 11.1 10.9 340 274 208 483 388 299 2.35 1.89 1.44 3.35 2.68 2.06 1.63 1.43 1.25 2.35 2.07 1.81 10.6 10.7 10.6 11.1 11.2 11.0 404 325 248 575 461 353 2.12 1.67 1.27 3.00 2.36 1.82 1.52 1.33 1.16 2.21 1.93 1.69 11.6 11.6 11.4 12.1 12.1 11.8 363 286 218 516 406 313 1.64 1.28 1.00 2.33 1.83 1.44 1.33 1.16 0.99 1.93 1.69 1.43 13.6 13.4 13.2 14.0 13.7 13.5 283 220 171 401 314 247
27 2.87 2.03 11.6 410 2.82 2.01 11.8 484 2.54 1.89 12.7 436 1.98 1.66 14.4 341
23 1.34 1.19 11.1 192 1.33 1.19 11.2 228 1.17 1.11 12.0 260 0.93 0.93 13.7 161
27 2.78 2.00 11.9 397 2.76 1.99 11.9 475 2.47 1.87 12.8 425 1.90 1.64 14.6 327
25 2.21 1.75 11.8 317 2.20 1.75 11.8 378 1.93 1.63 12.7 332 1.50 1.43 14.3 258
139 (500)
25 2.33 1.80 11.5 334 2.30 1.79 11.6 394 2.02 1.67 12.5 348 1.57 1.46 14.1 270
111 (400)
Size 21
Legend TC Total cooling capacity (kW) SHC Sensible cooling capacity (kW) SAT Supply air temperature (°C) WF Water flow rate (l/h) NOTE: To convert l/h to l/s, divide by 3600.
16
83 (300)
23 1.78 1.57 11.3 255 1.75 1.56 11.4 301 1.56 1.46 12.1 268 1.24 1.24 13.7 213
27 3.39 2.44 12.2 484 3.33 2.41 12.4 572 3.00 2.27 13.2 515 2.35 2.01 14.8 404
139 (500) 23 1.70 1.54 11.5 243 1.68 1.53 11.16 289 1.49 1.43 12.3 257 1.20 1.20 14.1 206
27 3.31 2.41 12.4 473 3.28 2.40 12.4 564 2.94 2.26 13.3 505 2.27 1.99 15.0 390
25 2.63 2.12 12.2 376 2.62 2.12 12.3 450 2.30 1.98 13.1 395 1.80 1.73 14.6 310
25 2.76 2.17 12.0 395 2.71 2.15 12.1 466 2.40 2.02 13.0 412 1.88 1.77 14.4 324
167 (600) 23 2.13 1.90 11.6 305 2.09 1.89 11.7 359 1.86 1.76 12.5 320 1.49 1.49 14.1 257
167 (600) 23 2.03 1.86 11.9 290 2.01 1.85 11.9 346 1.79 1.73 12.7 308 1.44 1.44 14.4 247
27 3.78 2.80 12.9 541 3.74 2.78 12.9 643 3.35 2.62 13.8 576 2.61 2.31 15.3 448
25 3.01 2.46 12.6 431 3.00 2.46 12.7 516 2.64 2.30 13.5 454 2.08 2.01 14.9 357
Size 22 Size 29 167 (600) 27 4.28 3.05 11.6 612 4.24 3.03 11.7 728 3.80 2.85 12.6 653 2.95 2.50 14.4 507
25 3.42 2.68 11.6 490 3.40 2.67 11.6 583 2.99 2.49 12.5 513 2.32 2.17 14.1 400
27 5.08 3.68 12.1 727 5.04 3.66 12.2 865 4.51 3.44 13.1 775 3.52 3.03 14.8 605
25 4.08 3.24 12.0 583 4.04 3.23 12.1 694 3.56 3.02 12.9 612 2.78 2.63 14.4 478
25 3.14 2.51 12.5 450 3.09 2.49 12.6 530 2.73 2.34 13.4 469 2.17 2.06 14.7 373
23 2.45 2.21 12.0 351 2.40 2.19 12.1 413 2.15 2.05 12.8 370 1.73 1.73 14.4 298
194 (700) 23 2.33 2.16 12.2 334 2.32 2.16 12.3 398 2.07 2.00 13.0 356 1.66 1.66 14.7 286
27 4.21 3.16 13.3 602 4.17 3.14 13.4 716 3.72 2.96 14.2 640 2.91 2.62 15.7 501
25 3.37 2.79 13.0 482 3.34 2.78 13.1 574 2.95 2.61 13.8 508 2.34 2.27 15.2 403
23 2.62 2.62 12.6 375 2.60 2.60 12.6 446 2.33 2.33 13.3 400 1.88 1.88 15.0 323
Size 23
208 (750) 23 2.65 2.35 11.3 378 2.61 2.34 11.4 448 2.31 2.18 12.2 397 1.84 1.83 13.9 316
27 3.85 2.82 12.8 551 3.80 2.79 12.9 652 3.41 2.63 13.7 586 2.68 2.33 15.2 460
264 (950) 23 3.16 2.84 11.7 452 3.12 2.83 11.7 536 2.77 2.63 12.5 475 2.21 2.20 14.2 379
27 6.04 4.46 12.8 865 5.98 4.43 12.9 1027 5.36 4.17 13.7 920 4.19 3.69 15.7 721
25 4.86 3.94 12.5 695 4.80 3.92 12.6 825 4.25 3.67 13.4 729 3.34 3.20 14.9 574
319 (1150) 23 3.78 3.45 12.1 541 3.75 3.45 12.2 643 3.32 3.20 12.9 571 2.66 2.66 14.6 458
27 6.89 5.17 13.4 986 6.83 5.14 13.5 1172 6.11 4.85 14.2 1049 4.81 4.30 15.7 828
25 5.55 4.58 13.0 794 5.49 4.55 13.1 943 4.86 4.27 13.8 836 3.85 3.72 15.3 663
347 (1250) 23 4.35 4.02 12.6 623 4.31 4.01 12.6 739 3.84 3.72 13.3 660 3.09 3.09 15.0 531
27 7.28 5.51 13.7 1041 7.22 5.48 13.7 1239 6.45 5.17 14.5 1109 5.09 4.59 15.9 876
25 5.88 4.88 13.3 841 5.81 4.86 13.3 997 5.15 4.56 14.0 884 4.09 3.97 15.4 704
23 4.63 4.63 12.7 662 4.57 4.57 12.8 784 4.08 4.08 13.5 701 3.29 3.29 15.1 565
NOTE: Operating limits: air discharge temperature 12°C when the unit is installed in an ambient temperature of 27°C dry bulb and 65% relative humidity.
6.1.1 - Two-pipe water coil (cont.) Entering/ Size 31 leaving water temperature, Relative humidity 50% °C Air flow, l/s (m3/h) 83 (300) 125 ( 450) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 6-12 TC 2.93 2.45 1.93 4.24 3.53 2.77 SHC 1.89 1.68 1.47 2.76 2.45 2.15 SAT 7.9 8.1 8.4 8.4 8.6 8.7 WF 419 351 276 606 505 396 7-12 TC 2.83 2.36 1.84 4.10 3.40 2.65 SHC 1.84 1.64 1.43 2.69 2.40 2.09 SAT 8.4 8.6 8.8 8.9 9.0 9.1 WF 485 404 316 704 585 455 8-13 TC 2.59 2.12 1.62 3.76 3.05 2.34 SHC 1.73 1.53 1.33 2.54 2.24 1.95 9.9 10.0 10.0 SAT 9.5 9.7 9.7 WF 446 364 279 645 525 401 10-15 TC 2.10 1.64 1.23 3.03 2.36 1.78 SHC 1.52 1.32 1.16 2.23 1.94 1.70 SAT 11.7 11.7 11.5 12.0 12.0 11.7 WF 362 282 212 521 406 307
Size 32 Size 39 167 (600) 27 5.45 3.58 8.9 780 5.29 3.51 9.3 909 4.84 3.31 10.3 831 3.88 2.90 12.4 667
25 4.53 3.19 9.0 648 4.38 3.12 9.4 752 3.92 2.91 10.4 673 3.03 2.53 12.3 521
Size 33
208 (750) 23 3.55 2.79 9.1 507 3.41 2.73 9.4 585 3.00 2.54 10.3 516 2.30 2.21 12.0 396
27 6.59 4.37 9.3 943 6.41 4.29 9.7 1100 5.85 4.04 10.7 1004 4.67 3.55 12.7 803
264 (950)
25 5.46 3.89 9.4 781 5.29 3.81 9.7 908 4.72 3.56 10.7 812 3.66 3.10 12.6 629
23 4.27 3.41 9.4 611 4.11 3.34 9.7 706 3.62 3.11 10.6 622 2.79 2.71 12.2 480
27 7.99 5.37 9.9 1143 7.76 5.27 10.2 1332 7.08 4.97 11.1 1217 5.65 4.37 13.1 972
25 6.61 4.78 9.9 945 6.41 4.69 10.1 1101 5.71 4.38 11.1 982 4.43 3.83 12.9 762
319 (1150) 23 5.17 4.20 9.8 740 4.99 4.11 10.1 857 4.39 3.84 10.9 755 3.41 3.33 12.5 586
27 9.25 6.30 10.4 1323 8.98 6.18 10.7 1542 8.19 5.84 11.6 1407 6.56 5.16 13.4 1128
25 7.66 5.61 10.3 1095 7.42 5.51 10.6 1275 6.62 5.16 11.5 1138 5.16 4.52 13.2 887
347 (1250) 23 6.00 4.94 10.2 858 5.80 4.85 10.4 995 5.11 4.53 11.2 878 3.98 3.92 12.8 685
27 9.83 6.74 10.6 1407 9.55 6.62 11.0 1641 8.71 6.25 11.8 1496 6.97 5.53 13.6 1199
25 8.15 6.01 10.5 1166 7.89 5.90 10.8 1355 7.04 5.53 11.7 1210 5.50 4.85 13.3 946
23 6.39 6.39 10.3 915 6.18 6.18 10.6 1062 5.45 5.45 11.4 937 4.26 4.26 12.9 732
6.1.2 - Four-pipe water coil Entering/ leaving water temperature, °C
6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Entering/ leaving water temperature, °C
6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Sizes 05 and 09 Relative humidity 50% Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 27 25 23 27 25 0.78 0.64 0.51 1.46 1.19 0.54 0.48 0.43 1.04 0.92 10.6 10.5 10.2 11.3 11.3 112 92 73 209 170 0.78 0.63 0.49 1.45 1.17 0.42 1.03 0.91 0.54 0.48 10.7 10.7 10.5 11.4 11.3 133 108 84 249 202 0.70 0.56 0.43 1.31 1.04 0.51 0.44 0.39 0.97 0.85 11.7 11.6 11.2 12.3 12.2 120 96 75 224 178 0.43 0.35 1.02 0.79 0.55 0.44 0.39 0.34 0.85 0.74 13.6 13.2 12.8 14.2 13.9 94 75 60 175 137 Sizes 10 and 19 Relative humidity 50% Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 0.81 0.66 0.53 1.50 1.21 0.95 0.55 0.49 0.44 1.05 0.93 0.82 10.2 10.3 10.0 11.1 11.1 10.8 117 96 76 221 177 135 0.80 0.65 0.51 1.48 1.20 0.93 0.55 0.48 0.43 1.04 0.92 0.81 10.4 10.4 10.2 11.2 11.2 10.9 137 111 87 254 206 159 0.72 0.58 0.45 1.33 1.07 0.82 0.51 0.45 0.40 0.98 0.86 0.76 11.4 11.3 11.0 12.2 12.0 11.7 124 100 77 229 183 140 0.58 0.45 0.36 1.06 0.82 0.65 0.45 0.40 0.35 0.86 0.75 0.64 13.2 13.0 12.5 13.9 13.6 13.4 99 77 62 182 141 112
Legend TC Total cooling capacity (kW) SHC Sensible cooling capacity (kW) SAT Supply air temperature (°C) WF Water flow rate (l/h) NOTE: To convert l/h to l/s, divide by 3600.
83 (300) 23 0.90 0.80 11.1 129 0.89 0.79 11.1 153 0.79 0.74 12.0 135 0.62 0.62 13.7 107
27 2.06 1.48 12.0 294 2.05 1.48 12.1 351 1.84 1.39 13.0 316 1.43 1.22 14.7 246
25 1.67 1.32 11.9 239 1.65 1.31 11.9 284 1.46 1.22 12.8 250 1.13 1.06 14.4 194
83 (300) 27 2.08 1.49 11.9 314 2.07 1.49 12.0 355 1.86 1.40 12.9 319 1.47 1.23 14.6 252
25 1.69 1.32 11.8 251 1.67 1.31 11.9 286 1.48 1.23 12.7 255 1.14 1.08 14.2 197
111 (400) 23 1.27 1.14 11.6 182 1.26 1.14 11.7 216 1.12 1.06 12.5 192 0.89 0.88 14.2 152
27 2.59 1.90 12.6 370 2.56 1.88 12.7 440 2.30 1.78 13.6 396 1.80 1.56 15.2 309
111 (400) 23 1.31 1.16 11.5 192 1.29 1.15 11.6 221 1.14 1.08 12.3 195 0.91 0.91 14.0 156
27 2.60 1.89 12.7 397 2.56 1.88 12.8 440 2.31 1.77 13.6 396 1.82 1.57 15.1 314
25 2.10 1.67 12.4 317 2.08 1.66 12.5 356 1.85 1.56 13.3 317 1.43 1.36 14.7 246
139 (500)
25 2.10 1.68 12.4 300 2.08 1.68 12.5 357 1.83 1.57 13.3 315 1.43 1.36 14.8 246
23 1.61 1.46 12.1 230 1.59 1.46 12.1 273 1.41 1.36 12.9 243 1.13 1.13 14.6 194
27 3.05 2.27 13.2 437 3.02 2.26 13.3 518 2.72 2.13 14.1 467 2.13 1.88 15.6 367
139 (500) 23 1.63 1.47 12.0 243 1.60 1.46 12.1 276 1.42 1.36 12.8 244 1.14 1.14 14.5 196
27 3.03 2.25 13.3 473 2.99 2.24 13.5 514 2.69 2.11 14.2 462 2.14 1.87 15.7 368
25 2.46 2.00 13.0 376 2.43 1.99 13.1 418 2.17 1.86 13.8 372 1.43 1.63 15.2 291
25 2.49 2.02 12.9 356 2.46 2.01 13.0 422 2.17 1.88 13.7 373 1.71 1.64 15.2 294
167 (600) 23 1.91 1.76 12.5 273 1.89 1.75 12.5 325 1.69 1.63 13.2 291 1.35 1.35 14.9 232
27 3.46 2.62 13.8 495 3.43 2.60 13.9 589 3.09 2.46 14.6 530 2.43 2.18 16.0 418
167 (600) 23 1.91 1.75 12.5 290 1.89 1.74 12.6 324 1.68 1.62 13.3 289 1.14 1.35 14.9 233
27 3.42 2.58 14.0 541 3.37 2.56 14.1 579 3.03 2.42 14.8 521 2.14 2.15 16.2 415
25 2.79 2.29 13.5 431 2.74 2.28 13.6 471 2.45 2.14 14.3 420 1.93 1.87 15.6 332
25 2.83 2.34 13.4 405 2.79 2.32 13.4 480 2.47 2.18 14.2 424 1.97 1.90 15.5 339
23 2.20 2.04 12.8 314 2.18 2.03 12.9 374 1.95 1.89 13.6 335 1.56 1.56 15.2 269
194 (700) 23 2.17 2.01 13.0 334 2.15 2.00 13.0 368 1.92 1.87 13.7 330 1.55 1.55 15.3 266
27 3.76 2.88 14.5 602 3.72 2.87 14.6 639 3.34 2.71 15.3 574 2.66 2.40 16.6 458
25 3.07 2.56 14.0 482 3.02 2.54 14.1 519 2.69 2.39 14.7 463 2.15 2.09 16.0 370
23 2.41 2.41 13.4 375 2.38 2.38 13.4 409 2.14 2.14 14.1 368 1.73 1.73 15.6 297
NOTE: Operating limits: air discharge temperature 12°C when the unit is installed in an ambient temperature of 27°C dry bulb and 65% relative humidity.
17
6.1.2 - Four-pipe water coil (cont.) Entering/ leaving water temperature, °C
6-12
7-12
8-13
10-15
TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF TC SHC SAT WF
Size 21 Relative humidity 50% Air flow, l/s (m3/h) 83 (300) 125 ( 450) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 2.28 1.83 1.40 3.21 2.57 1.98 1.59 1.40 1.22 2.28 2.01 1.76 10.9 11.0 10.8 11.6 11.6 11.3 326 262 200 459 368 283 2.26 1.81 1.38 3.18 2.55 1.94 1.58 1.39 1.22 2.27 2.00 1.75 11.0 11.0 10.9 11.7 11.6 11.4 388 311 238 546 437 334 2.02 1.60 1.23 2.85 2.24 1.73 1.48 1.30 1.14 2.13 1.87 1.63 12.0 12.0 11.7 12.7 12.5 12.1 348 275 211 489 385 297 1.57 1.23 0.97 2.20 1.74 1.38 1.30 1.14 0.97 1.87 1.63 1.38 13.9 13.6 13.4 14.4 14.1 13.8 270 212 167 378 299 238
Entering/ Size 31 leaving water temperature, Relative humidity 50% °C Air flow, l/s (m3/h) 83 (300) 125 ( 450) Entering air dry-bulb temperature, °C 27 25 23 27 25 23 6-12 TC 2.86 2.38 1.87 4.13 3.42 2.68 SHC 1.85 1.65 1.44 2.71 2.40 2.11 SAT 8.3 8.5 8.6 8.8 8.9 9.0 WF 409 340 267 590 489 383 7-12 TC 2.76 2.29 1.79 4.00 3.30 2.57 SHC 1.81 1.61 1.41 2.65 2.35 2.06 SAT 8.7 8.9 9.0 9.2 9.3 9.3 WF 474 393 307 687 567 442 8-13 TC 2.52 2.06 1.57 3.65 2.96 2.27 SHC 1.70 1.50 1.31 2.49 2.20 1.92 SAT 9.8 9.9 10.0 10.2 10.3 10.3 WF 434 354 271 627 509 390 10-15 TC 2.04 1.59 1.20 2.93 2.29 1.74 SHC 1.49 1.30 1.14 2.19 1.91 1.67 SAT 11.9 12.0 11.6 12.3 12.2 11.9 WF 351 274 206 504 394 299 Legend TC Total cooling capacity (kW) SHC Sensible cooling capacity (kW) SAT Supply air temperature (°C) WF Water flow rate (l/h) NOTE: To convert l/h to l/s, divide by 3600.
18
Size 22 Size 29 167 (600) 27 4.02 2.91 12.3 576 3.98 2.89 12.4 684 3.56 2.72 13.3 612 2.77 2.40 14.9 476
25 3.22 2.56 12.1 461 3.20 2.55 12.2 549 2.81 2.39 13.0 482 2.19 2.09 14.5 377
Size 23
208 (750) 23 2.48 2.25 11.8 355 2.45 2.24 11.9 421 2.18 2.09 12.6 375 1.75 1.75 14.3 301
27 4.74 3.49 12.9 678 4.69 3.47 13.0 805 4.19 3.26 13.8 721 3.27 2.88 15.4 562
25 3.80 3.08 12.6 544 3.76 3.06 12.7 646 3.31 2.87 13.5 569 2.61 2.51 14.9 448
264 (950) 23 2.94 2.70 12.3 420 2.90 2.69 12.3 499 2.60 2.51 13.0 446 2.09 2.09 14.7 359
27 5.58 4.19 13.6 798 5.52 4.16 13.7 948 4.93 3.92 14.5 847 3.87 3.47 15.9 665
25 4.48 3.70 13.3 641 4.43 3.68 13.3 761 3.91 3.46 14.1 672 3.11 3.02 15.5 534
319 (1150) 23 3.49 3.25 12.8 500 3.45 3.24 12.8 592 3.10 3.01 13.5 532 2.50 2.50 15.1 430
27 6.31 4.82 14.3 903 6.25 4.80 14.4 1074 5.58 4.53 15.1 959 4.39 4.01 16.4 755
25 5.07 4.27 13.8 726 5.01 4.25 13.9 861 4.45 3.99 14.6 764 3.55 3.48 15.9 611
Size 32 Size 39 167 (600) 27 5.30 3.51 9.2 758 5.15 3.45 9.6 885 4.69 3.24 10.6 806 3.75 2.85 12.6 646
25 4.38 3.12 9.3 627 4.24 3.06 9.7 728 3.79 2.86 10.7 652 2.94 2.49 12.5 505
27 6.39 4.28 9.7 914 6.22 4.20 10.0 1068 5.65 3.96 11.0 972 4.52 3.48 13.0 777
25 5.27 3.80 9.7 754 5.11 3.73 10.0 878 4.56 3.49 11.0 784 3.54 3.04 12.8 609
23 3.99 3.75 13.2 571 3.93 3.73 13.3 675 3.54 3.48 14.0 609 2.88 2.88 15.5 495
27 6.65 5.12 14.6 951 6.59 5.10 14.6 1132 5.88 4.81 15.3 1011 4.64 4.26 16.7 797
25 5.35 4.54 14.1 765 5.28 4.51 14.1 907 4.69 4.24 14.8 806 3.76 3.69 16.1 647
23 4.22 4.22 13.5 604 4.16 4.16 13.5 714 3.75 3.75 14.2 645 3.05 3.05 15.7 525
Size 33
208 (750) 23 3.43 2.74 9.4 491 3.30 2.68 9.7 567 2.91 2.50 10.6 500 2.24 2.17 12.2 385
347 (1250)
264 (950) 23 4.12 3.34 9.7 590 3.98 3.27 10.0 683 3.51 3.05 10.8 603 2.71 2.64 12.5 466
27 7.72 5.24 10.3 1105 7.50 5.14 10.6 1288 6.82 4.85 11.5 1171 5.45 4.28 13.4 937
25 6.37 4.66 10.2 911 6.18 4.58 10.5 1061 5.51 4.28 11.4 947 4.28 3.75 13.1 737
319 (1150) 23 4.98 4.10 10.1 713 4.81 4.02 10.3 826 4.25 3.76 11.2 730 3.30 3.25 12.8 568
27 8.90 6.13 10.8 1274 8.66 6.03 11.1 1488 7.87 5.68 12.0 1352 6.29 5.03 13.8 1082
25 7.36 5.47 10.7 1053 7.13 5.37 11.0 1224 6.37 5.03 11.8 1094 4.97 4.41 13.5 855
347 (1250) 23 5.77 4.81 10.5 826 5.58 4.73 10.7 958 4.93 4.42 11.5 848 3.85 3.81 13.1 663
27 9.45 6.56 11.1 1353 9.21 6.45 11.4 1581 8.36 6.08 12.3 1436 6.68 5.38 14.0 1150
25 7.82 5.85 10.9 1119 7.57 5.74 11.2 1301 6.76 5.39 12.0 1162 5.30 4.73 13.6 911
23 6.14 6.14 10.7 879 5.95 5.95 10.9 1021 5.26 5.26 11.7 904 4.12 4.12 13.2 708
NOTE: Operating limits: air discharge temperature 12°C when the unit is installed in an ambient temperature of 27°C dry bulb and 65% relative humidity.
6.2 - Heating capacity - water coil 6.2.1 - Two-pipe changeover coil Entering/ leaving water temperature, °C 70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Entering/ leaving water temperature, °C 70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Entering/ leaving water temperature, °C
70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Entering/ leaving water temperature, °C
70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Sizes 05 and 09 Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 21 20 19 21 20 1.56 1.60 1.64 3.01 3.08 67.4 67.4 67.4 65.5 65.5 137 141 144 264 271 1.21 1.25 1.29 2.32 2.39 57.0 57.0 57.0 55.3 55.3 203 209 106 109 113 0.92 0.96 1.01 1.73 1.81 48.4 48.5 48.6 46.6 46.7 54 56 59 101 105 0.85 0.89 0.93 1.61 1.68 46.2 46.3 46.3 44.8 44.8 74 77 81 140 147 Sizes 10 and 19 Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 21 20 19 21 20 19 1.57 1.61 1.65 3.08 3.16 3.24 67.5 67.5 67.5 66.7 66.7 66.7 138 141 145 270 277 284 1.22 1.25 1.29 2.38 2.46 2.54 57.1 57.1 57.2 56.3 56.4 56.4 106 110 113 208 215 222 0.93 0.97 1.02 1.79 1.88 1.96 48.7 48.8 48.9 47.6 47.7 47.8 54 57 59 104 109 114 0.86 0.89 0.93 1.66 1.74 1.82 46.4 46.5 46.5 45.6 45.7 45.8 75 78 81 145 151 158
83 (300) 19 3.15 65.5 277 2.46 55.3 215 1.89 46.8 110 1.76 44.9 153
21 4.33 63.6 381 3.32 53.7 290 2.46 45.2 143 2.30 43.6 200
20 4.44 63.6 390 3.42 53.7 299 2.57 45.3 150 2.40 43.6 209
83 (300) 21 4.52 65.7 397 3.48 55.4 304 2.60 46.7 151 2.42 44.9 211
20 4.63 65.7 407 3.59 55.4 314 2.72 46.8 158 2.53 45.0 221
111 (400) 19 4.54 63.6 398 3.52 53.6 308 2.68 45.3 156 2.50 43.6 218
19 4.75 65.7 417 3.71 55.4 324 2.84 46.9 165 2.65 45.0 231
21 5.88 64.7 517 4.51 54.5 385 3.36 45.9 195 3.13 44.2 272
125 (450)
Entering air dry-bulb temperature, °C 21 20 19 21 20 19 4.87 4.98 5.10 7.17 7.34 7.52 69.1 69.2 69.2 68.3 68.3 68.3 427 438 448 630 645 661 4 4 4 6 6 6 58.9 58.9 58.9 58.0 58.0 58.0 335 345 355 491 506 521 3.1 3.2 3.3 4.5 4.6 4.8 52 52 52 50 51 51 180 187 194 260 271 281 2.75 2.87 2.99 4.01 4.18 4.36 48.3 48.3 48.4 47.4 47.5 47.5 240 250 260 349 364 379
20 6.04 64.6 530 4.66 54.5 408 3.51 46.0 204 3.27 44.2 285
19 5.82 61.9 511 4.50 52.2 394 3.39 44.0 198 3.18 42.4 277
21 6.70 60.5 588 5.10 51.1 446 3.73 43.0 217 3.49 41.6 304
139 (500) 19 6.19 64.6 544 4.81 54.5 421 3.67 46.0 213 3.42 44.2 298
21 7.18 63.6 631 5.49 53.6 480 4.07 45.1 237 3.79 43.5 330
20 7.37 63.6 647 5.68 53.6 496 4.25 45.2 247 3.97 43.5 346
20 6.85 60.4 602 5.25 51.0 459 3.89 42.9 226 3.64 41.5 317
167 (600) 19 7.01 60.3 615 5.41 50.9 473 4.05 42.9 236 3.80 41.4 331
167 (600) 21 8.73 64.2 767 6.68 54.1 584 4.95 45.5 288 4.61 43.8 402
20 8.95 64.1 786 6.90 54.0 604 5.18 45.5 301 4.83 43.8 421
19 7.55 63.5 664 5.86 53.6 512 4.44 45.2 258 4.15 43.5 361
21 8.41 62.6 739 6.42 52.8 561 4.73 44.4 275 4.41 42.8 384
20 8.63 62.5 758 6.63 52.7 580 4.94 44.4 288 4.62 42.8 403
21 10.59 62.9 931 8.09 53.0 707 5.94 44.5 446 5.56 43.0 484
20 10.87 62.9 955 8.36 53.0 731 6.21 44.5 362 5.82 43.0 507
264 (950)
21 9.36 67.3 822 7 57.1 638 5.7 49 334 5.18 46.7 452
20 9.59 67.3 843 8 57.1 658 6.0 49 348 5.41 46.7 472
19 11.15 62.8 979 8.63 52.9 755 6.49 44.5 377 6.09 42.9 530
21 11.44 66.3 1005 9 56.2 777 6.9 48 404 6.29 45.9 548
20 11.72 66.2 1030 9 56.1 801 7.2 49 421 6.56 45.9 572
19 8.85 62.5 777 6.85 52.7 599 5.16 44.3 300 4.83 42.7 421
21 9.58 61.6 841 7.30 51.9 638 5.34 43.7 311 5.00 42.2 336
20 9.83 61.5 863 7.54 51.9 659 5.59 43.6 325 5.24 42.1 457
19 10.08 61.4 885 7.79 51.8 681 5.83 43.6 340 5.48 42.1 477
21 12.92 61.4 1135 9.83 51.7 860 7.16 43.4 416 6.72 42.0 585
20 13.26 61.3 1165 10.16 51.6 888 7.49 43.3 436 7.04 41.9 613
19 13.60 61.2 1194 10.49 51.6 917 7.82 43.3 455 7.37 41.9 642
21 15.08 59.9 1325 11.44 50.5 1001 8.27 42.4 482 7.79 41.1 679
20 15.47 59.8 1359 11.83 50.4 1035 8.66 42.3 504 8.17 41.0 712
347 (1250) 19 15.87 59.7 1394 12.22 50.3 1068 9.05 42.2 526 8.55 40.9 745
21 16.10 59.2 1415 12.21 50.0 1068 8.80 41.9 512 8.30 40.7 723
20 16.53 59.1 1452 12.62 49.9 1104 9.21 41.8 536 8.70 40.6 758
19 16.95 59.0 1489 13.03 49.7 1140 9.62 41.7 560 9.10 40.5 793
Size 33
208 (750) 19 9.82 67.3 863 8 57.1 678 6.2 50 362 5.64 46.7 491
19 8.12 58.9 713 6.26 49.7 547 4.65 41.9 271 4.38 40.5 382
194 (700)
319 (1150)
Size 32 Size 39 167 (600)
20 7.94 59.0 697 6.07 49.8 531 4.47 41.9 260 4.20 40.6 366
Size 23
208 (750) 19 9.18 64.1 806 7.13 54.0 623 5.40 45.5 314 5.05 43.8 440
21 7.76 59.1 682 5.89 50.0 515 4.28 42.0 249 4.02 40.7 350
167 (600)
Size 22 Size 29
Size 31 Air flow, l/s (m3/h) 83 (300)
20 5.69 61.9 500 4.37 52.2 382 3.26 44.0 190 3.05 42.5 265
111 (400)
Size 21 Air flow, l/s (m3/h) 83 (300) 125 (450) Entering air dry-bulb temperature, °C 21 20 19 21 20 19 4.62 4.74 4.86 6.74 6.91 7.09 66.8 66.8 66.8 65.5 65.4 65.4 406 417 427 592 607 623 3.58 3.69 3.81 5.18 5.35 5.52 56.4 56.4 56.4 55.2 55.2 55.2 313 323 333 453 468 483 2.70 2.82 2.94 3.87 4.05 4.23 47.7 47.8 47.9 46.5 46.6 46.7 157 164 171 225 236 246 2.50 2.61 2.73 3.60 3.77 3.94 45.7 45.8 45.8 44.7 44.8 44.8 218 228 238 314 328 343
21 5.56 62.0 488 4.24 52.3 371 3.13 44.0 182 2.91 42.5 254
139 (500)
264 (950) 19 12.01 66.2 1055 9 56.1 826 7.5 49 438 6.84 45.9 596
21 14.05 64.9 1234 11 55.0 950 8.4 47 489 7.64 44.9 666
20 14.40 64.8 1265 11 54.9 980 8.8 47 510 7.98 44.8 695
319 (1150) 19 14.75 64.8 1296 12 54.9 1010 9.1 47 531 8.32 44.8 725
21 16.49 63.6 1448 13 53.8 1112 9.8 46 567 8.89 43.9 774
20 16.90 63.5 1485 13 53.7 1147 10.2 46 591 9.29 43.9 809
347 (1250) 19 17.32 63.4 1521 14 53.7 1182 10.6 46 615 9.69 43.8 844
21 17.65 62.9 1550 14 53.3 1188 10.4 46 604 9.48 43.5 826
20 18.09 62.8 1589 14 53.2 1226 10.8 46 630 9.91 43.4 863
19 18.54 62.7 1629 14 53.1 1264 11.3 46 655 10.34 43.4 901
For the legend and notes see page 19.
19
6.2.2 - Four-pipe coil, heating circuit Entering/ leaving water temperature, °C 70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Entering/ leaving water temperature, °C 70-60 60-50 55-40 50-40
HC SAT WF HC SAT WF HC SAT WF HC SAT WF
Sizes 05 and 09 Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 21 20 19 21 20 0.75 0.77 0.79 1.38 1.42 43.4 42.9 42.4 41.4 40.9 66 68 70 121 124 0.57 0.59 0.61 1.05 1.08 38.1 37.6 37.1 36.5 36.0 92 95 50 52 54 0.41 0.43 0.45 0.75 0.79 33.3 32.8 32.4 32.1 31.6 24 25 26 44 46 0.39 0.41 0.43 0.71 0.75 32.6 32.1 31.7 31.5 31.0 34 36 37 62 65 Sizes 10 and 19 Air flow, l/s (m3/h) 28 (100) 56 (200) Entering air dry-bulb temperature, °C 21 20 19 21 20 19 1.03 1.05 1.08 1.89 1.94 1.99 51.5 51.2 50.9 49.0 48.6 48.3 90 93 95 166 170 174 0.78 0.81 0.83 1.43 1.48 1.53 44.1 43.9 43.6 42.2 41.8 41.5 68 71 73 125 129 133 0.55 0.58 0.61 1.00 1.05 1.10 37.5 37.2 37.0 35.8 35.5 35.2 32 34 35 58 61 64 0.53 0.55 0.58 0.96 1.01 1.06 36.7 36.4 36.1 35.2 34.9 34.6 46 48 51 83 88 92
Entering/ Size 21 leaving water temperature, Air flow, l/s (m3/h) °C 83 (300) 125 (450) Entering air dry-bulb temperature, °C 21 20 19 21 20 19 70-60 HC 2.13 2.18 2.24 2.96 3.03 3.11 SAT 42.2 41.7 41.2 40.6 40.1 39.6 WF 187 192 197 260 267 274 60-50 HC 1.61 1.66 1.72 2.22 2.30 2.38 SAT 37.0 36.5 36.0 35.8 35.2 34.7 WF 140 145 150 194 201 208 55-40 HC 1.10 1.16 1.21 1.51 1.59 1.67 SAT 31.9 31.5 31.0 31.0 30.5 30.0 WF 64 67 71 88 93 97 50-40 HC 1.07 1.12 1.18 1.47 1.55 1.63 SAT 31.6 31.1 30.7 30.8 30.3 29.7 WF 93 98 103 128 135 142 Entering/ Size 31 leaving water temperature, Air flow, l/s (m3/h) °C 83 (300) 125 (450) Entering air dry-bulb temperature, °C 21 20 19 21 20 19 70-60 HC 2.14 2.20 2.26 2.97 3.05 3.13 SAT 42.2 41.7 41.2 40.6 40.1 39.5 WF 188 193 198 261 268 275 60-50 HC 1.62 1.68 1.73 2.24 2.32 2.40 SAT 37.0 36.5 36.0 35.8 35.3 34.7 WF 142 147 152 196 203 210 55-40 HC 1.12 1.18 1.24 1.55 1.63 1.70 SAT 32.1 31.6 31.2 31.2 30.7 30.2 WF 65 69 72 90 95 99 50-40 HC 1.08 1.14 1.19 1.50 1.57 1.65 SAT 31.7 31.2 30.7 30.9 30.3 29.8 WF 94 99 104 130 137 144 Legend HC Heating capacity (kW) SAT Supply air temperature (°C) WF Water flow rate (l/h) NOTE: To convert l/h to l/s, divide by 3600.
20
83 (300) 19 1.45 40.4 127 1.12 35.5 98 0.82 31.1 48 0.78 30.5 68
21 1.92 39.9 168 1.45 35.3 127 1.04 31.2 60 0.98 30.7 85
20 1.96 39.3 173 1.50 34.7 131 1.08 30.7 63 1.03 30.1 90
83 (300) 21 2.60 46.8 229 1.96 40.4 172 1.37 34.5 80 1.32 34.0 115
20 2.67 46.4 235 2.03 40.0 178 1.44 34.2 84 1.39 33.7 121
111 (400) 19 2.01 38.8 177 1.54 34.2 135 1.13 30.1 66 1.07 29.6 94
21 2.39 38.6 210 1.80 34.3 158 1.28 30.4 74 1.21 30.0 106
111 (400) 19 2.74 46.0 241 2.10 39.6 184 1.51 33.8 88 1.45 33.3 127
21 3.22 44.9 283 2.42 39.0 212 1.69 33.5 98 1.62 33.0 141
20 3.31 44.5 291 2.51 38.5 219 1.77 33.1 103 1.70 32.6 148
139 (500)
20 2.44 38.0 215 1.86 33.7 163 1.34 29.9 78 1.27 29.4 111
19 2.50 37.4 220 1.92 33.1 168 1.40 29.3 81 1.33 28.8 116
21 2.81 37.5 247 2.12 33.5 185 1.50 29.8 87 1.42 29.4 124
139 (500) 19 3.39 44.0 298 2.59 38.1 227 1.86 32.7 108 1.79 32.2 156
21 3.77 43.4 331 2.83 37.8 247 1.97 32.7 114 1.89 32.2 164
20 3.87 42.9 340 2.92 37.3 256 2.06 32.2 120 1.98 31.7 173
20 2.87 36.9 252 2.18 32.9 191 1.56 29.2 91 1.49 28.8 130
167 (600) 19 2.94 36.3 258 2.25 32.3 197 1.63 28.6 95 1.56 28.2 136
167 (600) 19 3.97 42.4 348 3.02 36.8 264 2.16 31.8 126 2.08 31.3 181
21 4.25 42.0 373 3.19 36.8 279 2.21 31.9 129 2.12 31.5 185
20 4.36 41.5 383 3.30 36.3 288 2.32 31.4 135 2.23 31.0 194
Size 22 Size 29 167 (600) 21 3.67 39.3 323 2.75 34.7 241 1.87 30.3 109 1.83 30.1 159
20 3.77 38.7 331 2.85 34.2 249 1.97 29.8 115 1.92 29.6 168
21 4.30 38.2 378 3.22 33.8 282 2.19 29.7 127 2.14 29.5 186
20 4.42 37.6 388 3.33 31.3 292 2.30 29.1 134 2.25 28.9 196
264 (950)
21 3.69 39.3 324 2.78 34.7 243 1.91 30.5 111 1.86 30.2 162
20 3.79 38.7 333 2.87 34.2 251 2.01 29.9 117 1.95 29.6 170
19 4.54 37.0 399 3.45 30.6 302 2.42 28.6 141 2.36 28.3 205
21 4.33 38.1 380 3.25 33.9 284 2.24 29.9 130 2.17 29.6 189
20 4.44 37.5 390 3.36 33.3 294 2.35 29.3 137 2.28 29.0 199
19 4.48 41.0 393 3.41 35.7 298 2.43 30.9 141 2.34 30.5 204
21 4.69 40.9 412 3.51 35.9 307 2.43 31.3 141 2.33 30.9 203
20 4.81 40.3 423 3.63 35.4 318 2.55 30.8 148 2.45 30.4 214
19 4.94 39.8 434 3.76 34.8 328 2.67 30.2 155 2.57 29.8 224
21 5.05 36.9 444 3.77 31.2 330 2.56 29.1 149 2.49 28.8 217
20 5.19 36.3 456 3.90 30.5 341 2.70 28.5 157 2.62 28.2 229
19 5.32 35.6 467 4.04 29.8 353 2.83 27.9 165 2.75 27.6 240
21 5.71 35.8 501 4.26 30.6 372 2.89 28.5 168 2.81 28.3 245
20 5.86 35.2 515 4.41 29.9 385 3.04 27.9 177 2.95 27.7 257
347 (1250) 19 6.02 34.5 528 4.56 29.1 399 3.19 27.2 186 3.10 27.0 270
21 6.01 35.4 528 4.48 30.3 392 3.04 28.3 177 2.95 28.1 257
20 6.17 34.7 542 4.64 29.6 406 3.20 27.6 186 3.10 27.4 271
19 6.33 34.0 556 4.80 28.8 419 3.35 27.0 195 3.26 26.7 284
Size 33
208 (750) 19 3.89 38.1 342 2.97 33.6 260 2.11 29.4 123 2.05 29.1 178
19 3.34 35.4 294 2.55 31.5 223 1.85 28.1 107 1.76 27.7 154
194 (700)
319 (1150)
Size 32 Size 39 167 (600)
20 3.26 36.0 287 2.48 32.2 217 1.77 28.7 103 1.69 28.3 147
Size 23
208 (750) 19 3.87 38.2 340 2.95 33.6 258 2.07 29.2 120 2.02 29.0 176
21 3.19 36.7 280 2.40 32.8 210 1.69 29.3 98 1.61 28.9 140
264 (950) 19 4.56 36.9 401 3.48 32.7 304 2.47 28.7 144 2.39 28.4 208
21 5.07 36.9 446 3.80 32.9 333 2.62 29.2 152 2.53 28.9 221
20 5.21 36.2 458 3.94 32.3 344 2.76 28.6 160 2.66 28.3 232
319 (1150) 19 5.35 35.6 470 4.07 31.6 356 2.89 28.0 168 2.79 27.7 243
21 5.73 35.8 504 4.29 32.1 375 2.95 28.6 172 2.85 28.4 248
20 5.89 35.1 517 4.44 31.4 388 3.10 28.0 181 3.00 27.7 261
347 (1250) 19 6.04 34.5 531 4.59 30.8 402 3.25 27.3 189 3.14 27.1 274
21 6.04 35.3 530 4.52 31.7 395 3.11 28.4 181 3.00 28.1 261
20 6.20 34.7 545 4.67 31.1 409 3.26 27.7 190 3.15 27.5 274
19 6.36 34.0 559 4.83 30.4 423 3.42 27.1 199 3.30 26.8 288
WARNING: The SAT must not exceed 60°C otherwise the supply air spigot connections may be damaged. NOTE: The supply air temperature should be kept below 35°C in order to avoid the risk of stratification. If the Atmosphera unit size 2 or 3 has only two spigots, the above performance data is reduced by 3%.
6.3 - Sound power levels 42EM 05 with one discharge spigot (multi-speed version) Octave band frequency (Hz) Speed Typ 125 250 500 1K 2K R1 SUP 55 50 49 42 40 RET 61 60 56 51 40 RAD 62 49 45 41 34 R2 SUP 54 49 48 41 39 RET 59 58 54 49 39 RAD 55 46 44 40 32 R3 SUP 53 48 47 40 39 RET 58 57 53 49 38 RAD 51 44 42 38 31 R4 SUP 51 46 44 37 36 RET 56 55 51 46 35 RAD 50 43 41 37 30 R5 SUP 49 44 43 35 34 RET 53 52 48 43 33 RAD 47 40 38 34 27 R6 SUP 47 42 41 34 33 RET 52 50 47 42 30 RAD 46 38 35 31 24
4K 33 32 23 32 31 21 31 29 19 27 26 * 23 * * 22 * *
42EM 09 with one discharge spigot (variable-speed LEC motor) Octave band frequency (Hz) Volt Typ 125 250 500 1K 2K 4K 10 SUP 60 59 53 50 48 41 RET 68 66 61 51 44 42 RAD 58 57 52 49 46 39 9 SUP 59 58 52 49 46 40 RET 67 65 59 50 43 41 RAD 57 56 51 48 45 38 8 SUP 58 57 51 48 45 39 RET 66 64 58 49 42 39 RAD 57 55 50 47 44 37 7 SUP 56 54 48 46 41 35 RET 63 61 56 47 39 36 RAD 55 52 48 45 41 34 6 SUP 53 51 45 42 36 30 RET 61 59 53 45 35 32 30 RAD 53 49 45 41 37 5 SUP 50 47 42 38 32 26 RET 58 54 49 41 31 27 RAD 50 46 41 38 33 26 4 SUP 46 43 38 32 27 22 RET 53 49 45 36 26 23 RAD 46 41 37 33 27 22 3 SUP 41 38 33 24 22 19 RET 48 43 40 29 23 21 RAD 41 35 31 25 22 19 2 SUP 37 34 29 18 18 17 RET 44 39 36 24 21 20 RAD 38 31 26 19 18 17 42EM 10 with one discharge spigot (multi-speed version) Octave band frequency (Hz) Speed Typ 125 250 500 1K 2K R1 SUP 57.3 55.1 46.2 43.1 37.1 RET 60 57.8 52 46.8 43.5 RAD 57.6 50.3 45.2 37.6 32.2 R2 SUP 55.8 52.4 43.7 40.4 34.4 RET 57.8 54.1 49 43.3 39.9 RAD 54.1 46.8 41.7 34.2 28.4 R3 SUP 51.5 48.8 40.1 36.5 30.4 RET 55 51.5 46.4 40.8 36.8 RAD 53.2 44.1 37 31 25.6 R4 SUP 48.4 45.2 36.9 33 26.4 RET 51.9 47.7 43.2 37.1 32.5 RAD 49.9 40.7 33.8 27.4 21.7 R5 SUP 46.4 43.5 35.1 30.7 23.4 RET 49.9 45.6 41.6 34.7 29 19.1 RAD 47.6 39.2 32.3 25.6 R6 SUP 45.1 42.1 34.1 28.9 21 RET 48.7 44.6 40.6 32.9 26.5 RAD 45.2 37.3 30.5 22.9 16.4
4K 31.3 38.7 24.7 27.1 34 19.9 22.2 29.8 16.8 18 23.9 14.2 16.8 20.2 14.6 17 18.9 14.3
dB(A) 50 57 49 49 55 46 48 54 44 45 52 43 43 49 39 42 48 37
dB(A) 56 62 55 55 61 54 54 59 53 51 57 50 48 54 47 44 50 44 40 46 39 34 40 33 29 36 28
dB(A) 50.3 54.3 47.3 47.8 51 43.8 44 48.3 41.1 40.6 44.7 37.8 38.7 42.7 36 37.4 41.5 34
42EM 19 with one discharge spigot (variable-speed LEC motor) Octave band frequency (Hz) Volt Typ 125 250 500 1K 2K 4K 10 SUP 64 62 56 51 49 44 RET 68 67 61 54 49 46 RAD 57 58 53 50 45 39 9 SUP 63 61 55 50 48 43 RET 66 66 60 53 48 45 RAD 57 57 52 49 43 37 8 SUP 62 59 54 49 46 42 RET 65 65 58 52 47 44 RAD 56 56 50 48 42 36 7 SUP 60 57 51 46 43 38 RET 63 63 56 50 44 41 RAD 55 54 48 46 39 32 6 SUP 57 54 48 43 40 35 RET 61 60 53 47 41 37 28 RAD 53 51 46 43 36 5 SUP 54 50 45 40 35 29 RET 58 56 49 44 37 32 RAD 50 47 42 39 31 22 4 SUP 50 45 41 35 29 23 RET 53 50 45 39 32 26 RAD 47 43 38 34 26 17 3 SUP 45 39 35 27 21 19 RET 47 44 39 32 26 21 RAD 41 39 33 27 20 17 2 SUP 41 34 32 22 15 15 RET 43 39 35 28 22 17 RAD 37 36 29 21 16 17 42EM 21 and 31 with two discharge spigots (multi-speed version) Octave band frequency (Hz) Speed Type 125 250 500 1K 2K 4K R1 SUP 54 53 49 44 39 35 RET 58 58 52 47 42 35 RAD 53 45 39 31 27 25 R2 SUP 53 51 47 42 37 32 RET 56 56 50 45 39 32 RAD 50 42 36 28 22 20 R3 SUP 51 49 46 40 35 28 RET 54 54 49 43 37 28 RAD 47 38 33 24 18 15 R4 SUP 47 46 42 36 30 22 RET 50 50 45 39 32 22 RAD 45 37 30 20 16 13 R5 SUP 43 42 38 31 24 13 RET 46 47 42 34 28 16 10 RAD 42 34 27 17 13 R6 SUP 40 39 35 27 19 11 RET 43 43 38 30 26 12 RAD 41 33 26 16 12 9
dB(A) 59 63 55 57 61 54 56 60 53 54 58 51 51 55 48 47 51 45 42 46 40 36 40 35 32 36 31
dB(A) 50 54 42 48 52 39 47 50 35 43 46 33 39 43 31 35 39 30
Legend SUP Supply (dB re = 10-12 W) RET Return (dB re = 10-12 W) RAD Radiated (dB re = 10-12 W) R Fixed speed
NOTE: The measurements are based on ISO standards and are without supply and return octopus plenums. The room sound level calculations must take account of the sound absorption of the duct, the plenum, the room and ceiling. For a selected speed the sound level can vary within a tolerance of ± 2.5 dB(A), depending on the available static pressure.
21
42EM 22 and 32 with three discharge spigots (multi-speed version) Octave band frequency (Hz) Speed Type 125 250 500 1K 2K 4K R1 SUP 59 59 54 48 43 40 RET 62 63 56 53 47 40 RAD 58 52 46 39 35 25 R2 SUP 58 57 53 47 41 38 RET 62 62 56 52 45 38 RAD 57 51 44 38 33 22 R3 SUP 55 55 50 45 39 35 RET 59 60 54 50 43 36 RAD 55 47 41 34 30 19 R4 SUP 52 51 47 41 35 29 RET 57 58 52 47 40 32 RAD 52 44 38 31 25 16 R5 SUP 46 46 42 35 26 19 RET 51 52 47 41 32 20 13 RAD 48 39 33 24 19 R6 SUP 41 40 35 28 19 17 RET 44 45 40 33 22 19 RAD 43 35 29 18 15 13 42EM 23 and 33 with three discharge spigots (multi-speed version) Octave band frequency (Hz) Speed Type 125 250 500 1K 2K 4K R1 SUP 62 62 55 50 44 43 RET 66 67 59 53 48 42 RAD 59 55 47 41 36 29 R2 SUP 60 60 53 48 42 41 RET 64 65 57 52 47 41 RAD 57 53 45 39 34 27 R3 SUP 58 58 51 46 40 39 RET 62 62 55 50 45 38 RAD 56 51 43 38 33 25 R4 SUP 54 53 48 42 36 34 RET 58 57 52 46 40 35 RAD 54 48 41 36 30 22 R5 SUP 49 48 43 38 31 30 RET 52 52 49 41 34 33 18 RAD 52 46 39 33 28 R6 SUP 45 43 39 33 26 27 RET 49 49 45 37 29 29 RAD 47 41 35 27 21 15
dB(A) 55 59 49 54 58 47 51 56 44 48 54 41 42 48 36 36 41 32
dB(A) 57 61 50 55 59 48 53 57 47 49 53 44 45 49 42 40 46 37
42EM 29 and 39 with three discharge spigots (variable-speed LEC motor) Octave band frequency (Hz) Volt Type 125 250 500 1K 2K 4K dB(A) 10 SUP 64 59 56 52 45 46 58 RET 65 62 58 56 48 30 59 RAD 67 62 54 50 44 45 58 9 SUP 62 57 54 50 43 44 55 RET 63 59 56 53 47 28 57 RAD 60 57 50 47 38 39 53 8 SUP 59 54 51 47 40 40 53 RET 62 57 54 51 47 22 55 RAD 53 53 47 45 33 33 50 7 SUP 58 52 50 45 38 38 51 RET 60 55 53 49 45 24 54 RAD 49 50 44 43 30 30 47 6 SUP 56 51 48 44 36 36 50 RET 59 54 51 48 44 22 52 28 45 RAD 47 48 42 42 28 5 SUP 54 49 47 42 34 34 48 RET 57 52 50 45 43 16 50 RAD 43 46 40 40 25 25 43 4 SUP 53 48 45 40 32 31 46 RET 57 51 48 44 41 21 49 RAD 39 43 38 38 22 22 41 3 SUP 51 46 43 38 30 30 44 RET 55 48 46 42 40 19 47 RAD 37 40 35 37 19 19 39 2 SUP 49 44 42 36 28 28 43 RET 52 46 44 39 38 15 45 RAD 35 38 33 35 17 17 37 Legend SUP Supply (dB re = 10-12 W) RET Return (dB re = 10-12 W) RAD Radiated (dB re = 10-12 W) R Fixed speed
22
NOTE: The measurements are based on ISO standards and are without supply and return octopus plenums. The room sound level calculations must take account of the sound absorption of the duct, the plenum, the room and ceiling. For a selected speed the sound level can vary within a tolerance of ± 2.5 dB(A), depending on the available static pressure. Return air plenum attenuation The sound power level measurements were carried out on a non-ducted unit without return air plenum. If the unit includes a return air plenum, correct the sound power levels (RET) using the correction factors in the table below: Unit size 42EM 0 1, 2, and 3
Octave band frequency (Hz) 125 250 500 1K -4 -7 -6 -5 -0.4 -1.1 -2.6 -7.4
2K -9 -10.7
4K -3 -6.8
dB(A) -6 -2.5
6.4 - Electrical data 42EM 05 (multi-speed version) Speed I P (A) (W) R1 0.49 112 0.49 112 0.48 110 0.47 107 0.47 105 0.46 103 0.45 101 0.45 101 0.44 100 0.43 99 0.43 99 R2 0.36 83 0.36 83 0.35 78 0.34 77 0.34 76 0.33 74 0.32 72 0.31 70 0.31 69 0.31 69 R3 0.31 71 0.31 71 0.30 67 0.29 66 0.29 65 0.28 64 0.28 64 0.28 62 0.27 61 0.26 58 0.26 57 R4 0.26 59 0.26 59 0.24 57 0.24 55 0.24 55 0.23 53 0.23 52 0.22 50 0.22 49 R5 0.22 50 0.22 50 0.21 49 0.21 48 0.20 47 0.20 47 0.20 45 0.19 45 R6 0.19 46 0.19 46 0.19 45 0.19 0.18 0.18 0.17 0.17
45 44 42 41 39
Qv (l/s) 170 164 147 130 119 110 88 78 66 39 26 149 145 119 103 93 79 59 38 30 20 131 128 114 98 90 81 74 64 51 31 21 110 108 91 74 65 54 42 28 19 93 92 81 70 58 53 35 25 84 80 71 63 52 40 23 14
Qv (m3/h) 612 592 528 469 429 395 316 280 236 141 93 537 523 430 371 334 286 213 139 107 74 473 462 411 353 325 292 266 231 184 111 74 397 390 328 265 234 193 151 102 70 336 330 293 252 210 192 127 91 301 289 256 228 187 143 85 50
Legend I Current drawn by the fan motor P Power input to the fan motor Qv Air flow rate PR Available static pressure R Fixed speed
PR (Pa) 0 6 27 41 54 64 81 91 101 113 119 0 5 34 53 63 75 95 106 110 115 0 5 21 43 52 62 71 82 92 103 110 0 4 27 51 63 77 85 96 103 0 2 17 33 51 59 78 88 0 6 19 30 47 60 79 90
42EM 09 (variable-speed LEC motor) Control I Cos P (Volt) (A) (W) 10 1.00 0.54 123 0.96 0.53 116 0.92 0.52 110 0.89 0.52 106 0.85 0.52 101 0.82 0.51 97 0.78 0.51 93 0.75 0.51 88 9 0.85 0.55 108 0.82 0.54 101 0.79 0.53 96 0.76 0.53 91 0.73 0.52 87 0.70 0.52 83 0.67 0.51 79 0.64 0.51 75 8 0.68 0.59 92 0.66 0.56 86 0.65 0.55 81 0.53 77 0.63 0.61 0.53 73 0.58 0.52 70 0.56 0.51 66 0.54 0.51 63 7 0.56 0.49 64 0.53 0.49 60 0.50 0.49 56 0.47 0.49 53 0.44 0.49 50 0.41 0.49 47 0.39 0.49 44 0.36 0.49 41 6 0.45 0.47 48 0.41 0.48 45 0.38 0.48 42 0.36 0.48 40 0.34 0.48 37 0.31 0.48 35 0.29 0.48 32 0.27 0.47 30 5 0.31 0.46 33 0.28 0.48 31 0.25 0.49 29 0.23 0.51 26 0.20 0.52 24 0.18 0.52 21 0.15 0.52 18 4 0.11 0.77 19 0.11 0.71 18 0.10 0.72 17 0.10 0.65 15 0.10 0.58 13 0.10 0.50 11 3 0.11 0.48 12 0.11 0.40 10 0.10 0.39 9 0.10 0.38 8 0.08 0.38 7 2 0.05 0.35 4 0.05 0.35 4 0.05 0.35 4
Qv (l/s) 222 208 194 181 167 153 139 125 208 194 181 167 153 139 125 111 194 181 167 153 139 125 111 97 167 153 139 125 111 97 83 69 153 139 125 111 97 83 69 56 125 111 97 83 69 56 42 97 83 69 56 42 28 69 56 42 28 14 42 28 14
Qv (m3/h) 800 750 700 650 600 550 500 450 750 700 650 600 550 500 450 400 700 650 600 550 500 450 400 350 600 550 500 450 400 350 300 250 550 500 450 400 350 300 250 200 450 400 350 300 250 200 150 350 300 250 200 150 100 250 200 150 100 50 150 100 50
P (Pa) 2 24 45 66 85 103 121 137 4 26 48 68 86 104 120 134 7 30 51 69 86 102 116 129 15 34 51 65 78 89 100 110 5 23 38 51 63 73 83 92 1 19 34 46 56 65 72 1 17 29 38 45 50 3 15 22 27 31 4 8 10
NOTE: Voltage supply: 230 V (± 10%)
23
42EM 10 (multi-speed version) Speed I P (A) (W) R1 0.52 119 0.52 118 0.51 117 0.50 115 0.50 114 0.48 111 0.48 110 0.47 108 0.46 107 R2 0.37 87 0.37 85 0.36 82 0.35 81 0.34 78 0.34 78 0.34 77 0.33 76 0.33 75 R3 0.31 73 0.31 72 0.30 69 0.29 68 0.29 67 0.28 65 0.28 64 R4 0.26 60 0.25 59 0.25 58 0.24 57 0.24 55 0.23 54 R5 0.21 51 0.21 51 0.21 49 0.20 48 0.20 47 R6 0.19 45 0.18 44 0.18 43 0.18 43 0.18 42 0.17 41 0.17 41
Qv (l/s) 196 188 181 166 156 114 89 63 39 165 146 128 111 93 82 62 50 41 145 131 109 92 77 60 50 121 107 88 68 52 41 103 87 71 50 42 92 76 54 42 33 24 18
Qv (m3/h) 705 675 650 596 560 410 321 227 141 594 525 460 400 335 294 222 180 149 522 473 393 332 278 217 179 437 385 315 246 187 147 370 312 255 179 150 330 274 196 150 120 87 63
Legend Current drawn by the fan motor I P Power input to the fan motor Qv Air flow rate PR Available static pressure R Fixed speed
NOTE: Voltage supply: 230 V (± 10%)
24
PR (Pa) 0 10 20 39 50 92 114 135 149 0 28 50 69 89 102 122 130 135 0 22 51 72 91 110 118 0 23 53 80 100 110 1 25 48 80 90 0 20 52 70 80 90 99
42EM 19 (variable-speed LEC motor) Control I Cos P (Volt) (A) (W) 10 1.04 0.53 127 0.99 0.53 121 0.95 0.53 115 0.91 0.53 111 0.87 0.53 106 0.84 0.53 102 0.81 0.53 97 9 0.91 0.53 110 0.87 0.53 105 0.83 0.53 100 0.80 0.52 96 0.77 0.52 92 0.73 0.52 88 0.70 0.52 84 0.66 0.52 79 8 0.79 0.52 94 0.76 0.52 90 0.72 0.52 86 0.69 0.52 82 0.51 78 0.66 0.63 0.51 75 0.60 0.51 71 0.57 0.51 66 0.53 0.51 62 7 0.62 0.51 72 0.59 0.51 68 0.56 0.50 65 0.54 0.50 62 0.51 0.50 59 0.48 0.50 56 0.46 0.50 52 0.43 0.49 49 0.40 0.49 45 6 0.47 0.49 53 0.44 0.49 50 0.42 0.49 47 0.40 0.49 45 0.37 0.49 42 0.35 0.49 39 0.33 0.49 36 0.30 0.48 34 0.33 0.48 36 5 0.31 0.48 34 0.29 0.48 32 0.27 0.48 29 0.25 0.47 27 0.23 0.47 25 0.21 0.47 23 0.19 0.46 20 4 0.30 0.31 22 0.27 0.33 21 0.24 0.34 19 0.21 0.36 17 0.18 0.38 16 0.15 0.40 13 0.12 0.41 11 3 0.14 0.37 12 0.13 0.39 11 0.12 0.41 11 0.10 0.43 10 0.09 0.44 9 0.08 0.42 8 0.08 0.39 7 2 0.05 0.35 4 0.05 0.35 4 0.05 0.35 4 0.05 0.35 4
Qv (l/s) 239 222 208 194 181 167 153 229 208 194 181 167 153 139 125 208 194 181 167 153 139 125 111 97 194 181 167 153 139 125 111 97 83 167 153 139 125 111 97 83 69 139 125 111 97 83 69 56 42 111 97 83 69 56 42 28 83 69 56 42 28 14 3 42 28 14 3
Qv (m3/h) 860 800 750 700 650 600 550 823 750 700 650 600 550 500 450 750 700 650 600 550 500 450 400 350 700 650 600 550 500 450 400 350 300 600 550 500 450 400 350 300 250 500 450 400 350 300 250 200 150 400 350 300 250 200 150 100 300 250 200 150 100 50 10 150 100 50 10
PR (Pa) 0 29 52 73 93 111 127 0 34 55 75 92 109 123 136 17 38 57 74 90 104 118 129 140 3 22 40 56 70 82 94 104 113 10 27 43 56 67 77 86 94 11 26 38 48 57 64 71 76 11 21 29 37 43 48 52 7 14 20 26 31 34 35 4 8 10 10
42EM 21 and 31 (multi-speed version) Speed I P Qv (A) (W) (l/s) R1 0.50 115 245 0.49 113 231 0.48 111 213 0.46 107 180 0.45 104 161 0.44 100 139 0.43 98 121 0.42 96 105 0.40 93 81 R2 0.44 101 215 0.43 99 201 0.42 97 182 0.40 93 151 0.39 90 135 0.38 87 114 0.37 86 98 0.36 83 80 0.35 80 60 R3 0.38 87 182 0.37 85 175 0.36 83 161 0.35 81 139 0.34 77 110 95 0.33 75 0.32 73 77 0.31 71 60 R4 0.30 68 148 0.29 67 143 0.29 67 133 0.28 65 111 0.28 64 89 0.27 63 75 0.27 61 62 0.26 59 40 R5 0.24 55 120 0.24 54 114 0.23 53 95 0.23 52 67 0.22 51 53 0.22 51 44 0.22 51 27 R6 0.20 44 98 0.19 43 94 0.19 43 71 0.19 43 49 0.18 42 18
Qv (m3/h) 882 831 765 650 578 501 437 376 290 774 723 654 544 488 410 353 289 214 655 632 581 502 397 343 276 215 532 515 480 400 321 269 223 145 432 411 342 241 191 159 98 352 337 254 175 63
Legend Current drawn by the fan motor I P Power input to the fan motor Qv Air flow rate PR Available static pressure R Fixed speed
PR (Pa) 0 12 28 52 66 77 86 94 102 0 12 29 55 65 77 86 93 104 0 6 18 39 60 71 81 91 0 4 11 29 45 56 66 81 0 4 17 36 45 53 64 0 2 14 27 46
42EM 22 and 32 (multi-speed version) Speed I P Qv (A) (W) (l/s) R1 0.82 171 330 0.76 158 301 0.72 149 283 0.66 138 255 0.62 128 224 0.58 120 198 0.55 112 170 0.53 108 153 0.52 106 145 R2 0.72 152 285 0.68 145 269 0.60 128 234 0.56 119 210 0.53 111 185 0.50 105 165 0.48 99 143 0.45 94 124 R3 0.64 136 230 0.62 130 221 0.56 119 202 0.51 110 179 0.48 101 156 0.45 95 138 119 0.42 89 0.39 83 95 R4 0.51 109 187 0.50 107 182 0.46 98 157 0.44 93 143 0.40 85 121 0.38 80 103 0.36 75 85 0.33 69 67 R5 0.40 84 136 0.39 83 133 0.38 80 116 0.37 78 108 0.34 73 92 0.33 71 81 0.31 67 67 0.29 62 54 R6 0.31 65 102 0.30 64 99 0.30 63 93 0.28 60 67 0.27 58 56 0.25 54 35
Qv (m3/h) 1188 1085 1020 919 805 711 614 551 521 1026 969 842 755 666 594 516 447 828 795 726 644 563 495 429 341 673 655 564 516 436 369 307 241 489 478 418 388 332 292 240 193 367 357 336 241 193 125
PR (Pa) 0 17 28 46 66 82 96 102 104 0 13 41 60 77 88 96 102 0 12 34 56 75 85 95 106 0 7 37 51 71 82 92 102 0 4 23 32 52 62 72 85 0 3 7 32 41 63
NOTE: Voltage supply: 230 V (± 10%)
25
42EM 23 and 33 (multi-speed version) Speed I P Qv (A) (W) (l/s) R1 0.96 208 410 0.92 199 389 0.86 187 361 0.80 176 333 0.75 165 306 0.70 154 278 0.66 144 250 0.62 135 222 0.58 126 194 0.55 119 167 R2 0.87 189 347 0.83 181 333 0.76 166 306 0.70 153 278 0.64 140 250 0.59 129 222 0.55 120 194 0.51 112 167 0.48 105 139 0.46 100 111 R3 0.79 164 261 0.74 156 250 0.70 146 236 222 0.65 138 0.61 130 208 0.58 123 194 0.54 116 181 0.51 111 167 0.49 106 153 0.47 101 139 R4 0.65 131 176 0.61 123 169 0.59 121 167 0.53 109 153 0.48 100 139 0.44 94 125 0.41 89 111 0.40 86 97 0.39 84 83 0.39 83 69 R5 0.56 117 146 0.55 110 139 0.51 100 125 0.48 92 111 0.45 86 97 0.42 81 83 0.39 78 69 0.37 76 56 0.35 74 42 0.34 73 28 R6 0.56 107 114 0.49 96 97 0.44 88 83 0.40 82 69 0.37 77 56 0.35 73 42 0.34 71 28
Qv (m3/h) 1475 1400 1300 1200 1100 1000 900 800 700 600 1250 1200 1100 1000 900 800 700 600 500 400 940 900 850 800 750 700 650 600 550 500 635 610 600 550 500 450 400 350 300 250 525 500 450 400 350 300 250 200 150 100 410 350 300 250 200 150 100
Legend Current drawn by the fan motor I P Power input to the fan motor Qv Air flow rate PR Available static pressure R Fixed speed
NOTE: Voltage supply: 230 V (± 10%)
26
PR (Pa) 2 12 25 39 52 65 77 88 99 108 1 11 30 47 62 76 88 98 107 113 1 15 31 46 58 69 78 87 94 99 2 18 24 50 70 83 92 97 100 100 2 21 52 75 90 100 105 108 110 111 0 47 72 88 98 102 104
42EM 29 and 39 (variable-speed LEC motor) Control I P Qv (Volt) (A) (W) (l/s) 10 1.35 192 444 1.28 178 417 1.22 169 389 1.17 160 361 1.12 152 333 1.06 144 306 1.01 136 278 0.95 129 250 0.90 121 222 0.84 113 194 0.79 105 167 0.72 95 139 9 1.12 150 417 1.04 140 389 0.98 132 361 0.94 126 333 0.89 120 306 0.85 114 278 0.81 107 250 0.76 100 222 0.71 93 194 0.65 85 167 0.61 78 139 119 389 8 0.94 0.87 111 361 0.81 104 333 0.77 99 306 0.73 93 278 0.69 87 250 0.64 81 222 0.60 75 194 0.55 68 167 7 0.68 85 333 0.65 80 306 0.61 75 278 0.58 70 250 0.54 65 222 0.50 60 194 0.46 55 167 0.41 49 139 0.37 44 111 6 0.50 62 306 0.48 58 278 0.45 54 250 0.42 50 222 0.39 46 194 0.35 42 167 0.32 37 111 0.30 33 56 250 5 0.33 38 0.31 35 222 0.29 33 194 0.26 30 167 0.24 27 139 0.21 23 83 0.20 21 56 0.20 19 28 4 0.21 23 194 0.20 21 167 0.18 20 139 0.14 14 83 0.10 11 56 0.08 7 28 0.07 6 14 3 0.15 15 167 0.13 13 139 0.11 11 83 0.10 10 56 0.10 9 28 0.09 8 14 2 0.04 4 83 0.05 4 56 0.05 4 28 0.05 4 14
Qv (m3/h) 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 1500 1400 1300 1200 1100 1000 900 800 700 600 500 1400 1300 1200 1100 1000 900 800 700 600 1200 1100 1000 900 800 700 600 500 400 1100 1000 900 800 700 600 400 200 900 800 700 600 500 300 200 100 700 600 500 300 200 100 50 600 500 300 200 100 50 300 200 100 50
PR (Pa) 8 36 59 79 96 110 122 132 141 149 157 166 17 35 51 66 80 92 104 114 123 130 137 11 27 42 56 68 79 89 98 106 17 31 44 55 65 74 81 87 93 5 19 30 40 49 56 63 68 5 15 24 32 39 45 49 52 6 14 20 31 34 37 37 0 6 16 20 23 24 2 6 10 12
6.5 - Water coil pressure drop Water flow rate, l/s Water flow rate, l/h Water coil type Sizes Two-pipe cooling and changeover 05-09 Four-pipe cooling Four-pipe heating Sizes Two-pipe cooling and changeover 10-19 Four-pipe cooling Four-pipe heating Sizes Two-pipe cooling and changeover 21-22-23-29 Four-pipe cooling Four-pipe heating Sizes Two-pipe cooling and changeover 31-32-33-39 Four-pipe cooling Four-pipe heating
0.03 100
0.05 200
0.08 300
0.11 400
0.14 500
0.17 600
0.19 700
0.22 800
0.25 900
0.28 1000
0.30 1100
0.33 1200
0.36 1300
2 1 5 1 1 2 1 1 1 1 1 1
6 6 22 4 6 6 2 2 3 1 2 3
14 13 49 9 13 14 5 5 6 3 5 6
26 23 87 16 23 24 9 10 11 6 8 11
40 36 26 36 38 14 15 17 9 13 18
58 52 37 52 55 19 22 25 13 18 26
79 71 50 71 75 26 29 34 18 25 35
65 93 35 38 44 24 33 46
83 44 49 56 30 41 58
54 60 69 37 51 71
84 44 62 86
100 53 73 -
117 62 86 -
6.6 - Air flow data Static pressure available (Pa) as a function of the air flow, l/s (m3/h) Size 10 multi-speed - unit without spigot
140
160 160
120
140 140
Available static pressure (Pa)
Available static pressure (Pa)
Size 05 multi-speed - unit without spigot
100 80 60 40 R6
R5
20
R4
R3
R1
R2
120 120 100 100 80 80 60 60 40 40
R6 R6
R5 R5
00
0 0 (0)
50 (180)
100
150 (540)
(360)
200 (720)
(0)
0 0 (0)
50 50 (180) (180)
R3 R3
100 100 (360) (360)
Air flow, l/s (m3/h)
R2 R2
R1 R1
Maximum recommended range
Maximum recommended range
140
140
120
120
100 R9
Available static pressure (Pa)
160
R10
R8 R7
60 R6 40
R5
R4
20
R3
R2
200 200 (720) (720)
Size 19 (variable-speed LEC motor) - unit without spigot
160
80
150 150 (540) (540)
Air flow, l/s (m3/h)
Size 09 (variable-speed LEC motor) - unit without spigot
Available static pressure (Pa)
R4 R4
20 20
R10
100
R9 R8
80 R7 60
R6 R5
40 R4
20
R3
R2 0
0 0 (0)
150 (540)
100 (360)
50 (180)
200 (720)
250 (900)
0 (0)
100 (360)
50 (180)
250 (900)
Air flow, l/s (m3/h)
Air flow, l/s (m3/h)
Pressure too high
200 (720)
150 (540)
Pressure drop (Pa) for supply and return air plenum boxes as a function of the number of spigots (ø 200 mm) Size 0 Air flow, l/s Air flow, m3/h 1 spigot Supply Return 2 spigots Supply Return
0 0 0 0 0 0
28 100 1 0 0 0
56 200 2 1 1 0
83 300 5 2 2 0
111 400 9 3 3 1
139 500 14 5 5 2
167 600 19 6 6 3
Size 1 Air flow, l/s Air flow, m3/h 1 spigot Supply Return 2 spigots Supply Return 3 spigots Supply Return
28 100 1 2 0 0 0 0
56 200 4 7 1 2 0 1
83 300 9 15 2 4 1 2
111 400 15 27 3 6 1 3
125 450 19 35 4 8 2 4
139 500 24 43 5 10 2 5
153 550 6 12 3 6
167 600 8 16 3 7
181 650 9 18 4 8
194 700 10 20 4 10
27
Static pressure available (Pa) as a function of the air flow, l/s (m3/h)
Sizes 22 and 32 - unit without spigot
120
120
100
100
Available static pressure (Pa)
Available static pressure (Pa)
Sizes 21 and 31 - unit without spigot
80 60 40 20
R5
R6
R2
R3
R4
80 60 40 20
R1
R5
R6
0 0
50
100
150
200
250
(0)
(180)
(360)
(540)
(720)
(900)
0
0
50
(0)
Air flow, l/s (m /h) 3
(180)
100
R4
150
(540)
(360)
R3
200
250
(720)
R1
R2 300
(900)
350
(1080) 1080)
(1260)
Air flow, l/s (m3/h)
Sizes 23 and 33 - unit without spigot
Sizes 29 and 39 - unit without spigot Maximum recommended range 180 180
120
Available static pressure (Pa)
Available static pressure (Pa)
160 160
100 80 60 40
R6
20 0
0
50
100
(0)
(180)
(360)
R5
R4
150 (540)
R3
200
250
(720)
(900)
R2
300 350 (1080) (1260)
R1
140 140 120 120 100 100 80 80 60 60
R9 R9
40 40 20 20
R2 R2
R3 R3
R4 R4
R5 R5
R6 R6
R7 R7
R10 R10
R8 R8
0
400 450 (1440) (1620)
00 (0) (0)
50 50 (180) (180)
100 100 (360) (360)
150 150 (540) (540)
Air flow, l/s (m3/h)
200 200 (720) (720)
250 300 350 400 250 300 350 400 450 (900) (1080) (1080) (1260) (1260) (1440) (1440) (1620) (1620) (900)
Air flow, l/s (m3/h) Pressure too high
IMPORTANT: The curves were derived by smoothing, based on the information shown in the electrical data table.
NOTE: The data is for units without supply and return plenums. See chapter “Pressure drop for supply and return air plenum boxes as a function of the number of spigots” for the plenum pressure drops.
Pressure drop (Pa) for supply and return air plenum boxes as a function of the number of spigots (ø 200 mm) Sizes 21 - 22 - 23 - 29 - 31 - 32 - 33 - 39 Air flow (l/s) Air flow (m3/h) 1 spigot Supply Return 2 spigots Supply Return 3 spigots Supply Return 4 spigots Supply Return 5 spigots Supply Return
28
0 0 0 0 0 0 0 0 0 0 0 0
28 100 0.9 0.7 0.2 0.2 0.1 0.2 0.0 0.1 0.0 0.0
56 200 3.5 2.7 0.7 0.7 0.5 0.7 0.1 0.2 0.1 0.2
83 300 7.9 6.1 1.6 1.7 1.1 1.5 0.3 0.5 0.3 0.4
111 400 14 10.9 2.9 3.0 2.0 2.6 0.6 0.9 0.5 0.7
139 500 21.8 17.1 4.5 4.6 3.1 4.1 0.9 1.3 0.7 1.1
167 600 31.4 24.6 6.5 6.7 4.4 5.9 1.3 1.9 1.0 1.6
194 700
222 800
250 900
278 1000
306 1100
333 1200
361 1300
389 1400
417 1500
8.9 9.1 6.0 8.0 1.7 2.6 1.4 2.1
11.6 11.9 7.9 10.5 2.3 3.4 1.8 2.8
14.7 15.0 10.0 13.3 2.9 4.3 2.3 3.5
18.1 18.6 12.3 16.4 3.6 5.3 2.9 4.3
21.9 22.5 14.9 19.8 4.3 6.5 3.5 5.3
17.7 23.6 5.1 7.7 4.1 6.3
20.8 27.7 6.0 9.0 4.9 7.3
24.1 32.1 7.0 10.4 5.6 8.5
27.7 36.9 8.0 12.0 6.5 9.8
7 - GUIDE SPECIFICATION • Supply 42EM Atmosphera fan coil units in accordance with the certified drawings. • The performance of each 42EM unit shall conform to the published technical and performance data. • The casings of 42EM units shall be made from galvanised sheet steel, thermally and acoustically insulated, and shall be provided with adequate access for service and maintenance. 42EM units shall be provided with suspension lugs with rubber anti-vibration mounts. • The supply and return air connection spigots (200 mm diameter) shall be integral with each 42EM unit. • 42EM units shall be equipped with either a cooling/ heating changeover coil, a monobloc heating and cool-ing coil or a cooling coil and an electric heater. The water coils shall be provided with manual air purge valves. • The cooling and heating coils shall be made from copper tubes of 3/8” external diameter and aluminium fins. The maximum water side working pressure shall not exceed 10 bar (1000 kPa). • The aluminium drain pan beneath the coil and valves shall be monobloc to avoid the possibility of leaks. • The two-way or three-way on/off water flow control valves shall be provided with flexible water pipes with 1/2” BSP union nuts to simplify connections on site and maintenance and servicing work. • 42EM units supplied shall be provided with disposable 85% gravimetric (G3) and M1 fire class filters. • Filter access shall be: - From below the unit for ducted models, - From the rear of the unit for non-ducted models.
•
The 42EM shall be equipped with a LEC (Low Energy Consumption) type fan motor assembly. • This direct-drive motor shall be electronically commutated (EC motor), controlled by a 0-10 V signal, allowing it to operate precisely, simply and quietly with a wide range of rotational speeds in variation from the original speed. • Fans shall be a double-inlet centrifugal forward-curved type, with 1 or 2 fans per unit depending upon unit size. • 42EM units shall be suitable for connection to electronic controllers (wall-mounted thermostats) that allow fan speed changes to adjust the unit’s heating and cooling capacity. • Electrical connections carried out on 42EM units shall be the quick-connection type in order to simplify maintenance. A plastic cover shall protect the terminals. Numerical control • The numerical controls shall use the CCN (Carrier Comfort Network) communication protocol. • These controls shall have the following functions: - Control of the Atmosphera fan speed. - Control of the water flow through the on/off type two or three-way valves with reference to internal and external loads, in order to maintain a constant ambient temperature in the conditioned space. - Provide on/off control of the resistance wire type electric heater. - Be controlled by a Zone User Interface. • The power supply to the controller shall be 230 V a.c. (± 10%) single-phase, 50 Hz, to avoid the need for a transformer. The electric heater shall be controlled directly from the numerical controller to avoid the need for a power Triac.
29
Order No.: 14225-20, 01.2015. Supersedes order No.: 14225-20, 09.2014. Manufacturer reserves the right to change any product specification without notice.
Manufacturer: Carrier SCS, Montluel, France Printed in the European Union.