Transcript
CONTROLS
CONTROLS
EU SERIES VOLTAGE CONTROL RELAY UL cUL listed
• • • •
2 Product Types – .2 to 60 V and 10 to 600 V Selectable Under or Over Voltage Modes Space Saving 22.5mm Wide Enclosure DIN-Rail / Surface Mount
TWO PRODUCT TYPES: EUL (.2 TO 60V) AND EUH (10 TO 600V) PROVIDE SELECTABLE OVER OR UNDER VOLTAGE CONTROL. Control of AC / DC voltage without memory When the value of the controlled voltage, AC or DC, reaches the threshold Ue displayed on the front face, the output relay changes state at the end of a time delay T which can be set on the front face at between 0.1 and 3 s. Once the voltage drops below 5 to 50% of the threshold (hysteresis), the output relay changes state again instantly. Changing the hysteresis on the front face does not therefore modify the value of the preset threshold. Control of AC / DC voltage with memory When the value of the controlled voltage, AC or DC, reaches the threshold Ue displayed on the front face, the output relay changes state at the end of a time delay T which can be set on the front face at between 0.1 and 3 s, and stays locked in this position.
MODE OF OPERATION VOLTAGE CONTROL WITHOUT MEMORY Unit power-up
Threshold Ue Hysteresis
Input power. . . . . . . . . . . . . . . . . . . . . . . . Max. power consumption . . . . . . . . . . . . Frequency of measured signal. . . . . . . . Threshold value . . . . . . . . . . . . . . . . . . . . Hysteresis. . . . . . . . . . . . . . . . . . . . . . . . . Display Accuracy . . . . . . . . . . . . . . . . . . . Delay on threshold overun . . . . . . . . . . . Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contact material. . . . . . . . . . . . . . . . . . . . Maximum loading. . . . . . . . . . . . . . . . . . . Maximum switching voltage . . . . . . . . . . Operating temperature . . . . . . . . . . . . . . Storage temperature . . . . . . . . . . . . . . . . Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controlled voltage Hysteresis
T1
UNDER function VOLTAGE CONTROL WITH MEMORY Un
Unit power-up
24 VDC, 24, 120, 230 VAC ±15%, 50/60 Hz 3 VA 40 to 500 Hz 1 to 100% of measurement range 5 to 50% of displayed threshold ±10% of full scale .1 to 3 sec. SPDT relay AgCdO 8 Amp resistive 250 VAC -4°F to 140°F, (-20°C to 60°C) -22°F to 158°F, (-30°C to 70°C) 4.9 oz. (140g)
Controlled voltage
T1
UPPER function Controlled voltage Hysteresis Threshold Ue T1
UNDER function
WIRING 11
A1 11 M
MEASUREMENT RANGE TYPES
Controlled voltage
T1
UPPER function
Threshold Ue Hysteresis
SPECIFICATIONS
2
Un
E1 E2 E3
EUL
EUH
14 12 A2
Input
E1-M
E2-M
E3-M
E1-M
E2-M
E3-M
Sensitivity
0.2 to 2V
1 to 10 V
6 to 60 V
15 to 150 V
30 to 300 V
60 to 600 V
Input resistance
2 kΩ
10 kΩ
60 kΩ
100 kΩ
300 kΩ
600 kΩ
*Important: For 24 VDC Input power models, the supply voltage and the measured voltage must be from separate sources. The “negative” poles of the auxiliary power and the measurement circuit are connected inside the unit.
12
14
A1 & A2 power supply
DIMENSIONS inches (mm)
.17˝ (4.2)
Measurement Range .2 to 60 V .2 to 60 V .2 to 60 V .2 to 60 V 10 to 600 V 10 to 600 V 10 to 600 V 10 to 600 V
.14˝ (3.5)
2.84˝ (72) 3.94˝ (100)
.20˝ (5)
3.92˝ (99.3)
Supply Voltage *24 VDC* 24 VAC 120 VAC1 230 VAC2 *24 VDC* 24 VAC 120 VAC1 230 VAC2
3.53˝ (89.7)
Type EUL EUL EUL EUL EUH EUH EUH EUH
3.10˝ (78.5)
Part Number 84 872 020 84 872 021 84 872 023 84 872 024 84 872 030 84 872 031 84 872 033 84 872 034
2.25˝ (57)
ORDERING INFORMATION:
(22.5) .89˝
*See “Important” in Specifications
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 2/91 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com