TECHNICAL DATA SHEET 02-17/2011 CAPACITY 0 Standby @ 40 C 0 Standby @ 40 C 0 Standby @ 50 C 0 Standby @ 50 C 0 Prime Power @ 40 C 0 Prime Power @ 40 C Prime Power @ 500C 0 Prime Power @ 50 C Full load Amps No of Phases Voltage Altitude Altitude Deration Factor Single Step Load Acceptance Maximum Starting kVA @ 30% Voltage Dip
POWER OUTLETS 15 Amp Single Phase Auto Switched 20 Amp Single Phase Man Switched 20 Amp Three Phase Man Switched 32 Amp Three Phase Man Switched 50 Amp Three Phase Man Switched 63 Amp Three Phase Man Switched Australian Complaint Clipsal, ABL Surum, PDL outlets Battery Charger RCD Test Outlet Hard Wire Mains Terminals Main Circuit Breaker Ability to lock off main circuit breaker RCD Relay Adjustable mA Range/Adjustable Time Range/Factory Setting (mA/Time) Auxiliary Mounted Shunt Mechanism Make/Model 10 amp test outlet with momentary 2 & 3 Pole RCDs 30mA each outlet
39.7 49.6 37.2 46.2 36 45 33.8 42 62.6 3 415/240 <1000 1% per 100m 29 110
Qty 2 1 1 0 2 0
V m kW kVA
Protection C/Breaker RCD Amps/No of Poles/Brand 16/2/GWR 20/2/GWR 20/3/GWR 40/4/GWR 50/3/GE
63/4/GWR
ENGINE Engine Model Engine Manufacturer Number of Cylinders Cylinder Arrangement Cycle Aspiration Compression Ratio Bore Stroke Cubic Capacity Tier
1
10/2/GWR 2/2/GE 10/3/GWR 40/4/GWR 63/3/GE Yes Schneider RH99P 0.03-30A NHP/shunt trip
0-4.5s
Yes Yes Yes
Lockable Isolating Switch Outlet Board External Emergency Stop (Yellow Background Panel Emergency Stop Cable Gland Access Plate GPOs Isolator
Yes Yes No Yes
Unit 1103A-33TG1 Perkins 3 Vertical in-line Four stroke Turbocharged aspiration 17.25:1 105 127 3.3 N.A.
mm mm Litres
Unit kPa mm
ALTERNATOR Alternator Model Alternator Manufacturer Type Excitation Type Voltage Regulator Voltage Regulation
Unit
Insulation Protection 12 Wire Reconnectable 2/3 Pitch 3 Phase Sensing Rated Power Factor 30mA/ 0S
A
EXHAUST 10 Maximum Back Pressure Exhaust Outlet Size and Insulation Details 63 Exhaust Lagging Inside Engine Area with Turbo Yes Guard 15m3/min/Universal/2.5'' Imperial Spark Arrester
Winding Connection 1 1 1 1
ELR Test Facility
FUEL Speed Governor Fuel Consumption @ Full Load Fuel Consumption @ 75% Load Fuel Consumption @ 50% Load
Unit kW kVA kW kVA kW kVA kW kVA A
S45PS
Frequency
ELECTRICAL CONTROLS Controller Type/Model 2-Wire Start Remote Controller (No Keys; with Instrumentation V, A, HZ, WT, OP) Battery Charge Indicator/Failure Single Machine Island Operation Only Program No Factory Default Parameters
LSA 43.2 S25 LEROY SOMER Tropical AREP R438 ±0.5
%
12 CLASS H Class 4 Tropicalised Yes Yes Yes 0.8 50
Hz
Unit ComAp/AMF25NT Yes(Read from the controller) Yes Supplied separately
1 63/3/GE
Unit Mechanical 10.7 8.2 5.7
Running Time @ Full Load Running Time @ 75% Load Fuel tank capacity
26 34 280
PROTECTIONS High Coolant Temperature Low Oil Pressure Low Coolant Level Overcurrent Protection at Prime Rating Overspeed Underspeed
Yes Yes Yes Yes Yes Yes
L/Hr L/Hr L/Hr Hours
NOISE
Hours Litres
Sound Level at 7m @ Full Load Sound Level at 7m @ 75% Load
Unit
Y:\Karl O\Generators\Specifications\Technical Data Sheet\S45PS-2011-02-17
DIMENSIONS Length Width Height Dry Weight Wet Weight
2740 1140 1690 1638 1880
Unit mm mm mm kg kg
Unit 66.4 64.2
dB(A) dB(A)