Transcript
s
5312p01
5
312
Universal digital indicator
BAU200
For programmable input signal Universal single point digital indicator • Suitable for front-mounting in control panel • With LED display • Input signal (type of signal and measuring range) can be set with buttons • For all Siemens Building Technologies sensors (LG-Ni 1000, T1, PT100, PT 1000, 0 ... 10 V) • 0 ..10 V analog output signal • For nominal voltage AC 24 V, 50/60 Hz
Application The BAU200 universal digital indicator is suitable for mounting in the control panel front, or in control panel doors or covers. It can be programmed for use with a wide range of input signals.
Functions The type of signal and measuring range can be programmed by use of the buttons (see table on page 4). The measured value is displayed digitally and transmitted as a 0…10 V signal. The supply voltage, input signal and output signal are electrically isolated (see technical data).
CE1N5312en 03 July 2008
Building Technologies
Ordering When ordering, please specify the quantity, product name and type code. Example:
1 BAU200 universal digital indicator
Mechanical design Multi-part plastic housing, comprising: − LED 3 ½ -digit display (max. display range 1999 / –1999) − Front panel with membrane keyboard − PCB with screw terminals
Mounting and installation Mounting instructions (CE1G5312X) are enclosed with the unit. The digital indicator is suitable for mounting in the control panel front, or in control panel doors or covers. It is pushed into the cut-out from the front. It is secured without screws by means of a slide fitting on the sides of the unit.
Disposal The device includes electrical and electronic components and must not be disposed of as domestic waste. Current local legislation must be observed.
Commissioning Refer to the operating instructions enclosed with the device (CE1G5312) for information on the settings.
2/6 Building Technologies
BAU200 – Universal digital indicator
CE1N5312en 03 July 2008
Technical data Supply
Inputs
Operating voltage Max. voltage tolerance Power consumption External fuse Measurement input DC 0 ...10 V input
Resistance sensor (2-wire)
Measuring cables
Outputs
Analog output DC 0 ..10 V
Display
Display
Environmental conditions
Standards
Overflow indication Out-of-range by < ± 20% Display of the value, flashing at rate of 2 Hz Display of EEE, flashing at rate of 2 Hz Open circuit at input (out-of-range by > +20%) Display of–EEE, flashing at rate of 2 Hz Short-circuit at input (out-of-range by > –20%) Operation to IEC 60 721-3-3 Climatic conditions class 3K5 0 ...50 °C Temperature (housing and electronics) Transport to IEC 60 721-3-2 Climatic conditions class 2K3 Temperature − 25...+ 70 °C Product safety Safety requirements for electrical equipment for measurement, control and laboratory use EN 61010-1 Electromagnetic compatibility For use in industrial and domestic environments Immunity Emissions Home and Building Electronic System (HBES) Conformity
Housing, device
Weight
AC 24 V, 50/60 Hz ± 20% ≤ 8 VA (4 W) T 1.6 A Electrically isolated from supply voltage and output Input resistance ≥200kΩ Accuracy 0 … 5 V: ± (0.02 V + 3 digit) Accuracy 5 … 10 V: ± (0.02 V + 2 digit) Overvoltage max. 50 V LG-Ni 1000, Pt 1000, Pt 100, T1 Sensor correction –3 ... +3°C / –3 ... +3°F Measuring current 800 μA Accuracy ± (0.5% of the reading + 5 digit) Overvoltage max. 5 V Standard cable, max. 300 m (shielded if heavy electromagnetic load) Electrically isolated from supply voltage and input Load ≥10kΩ Accuracy ± 0.2% (± 20 mV) Digital, 3½-characters, with – sign. Engineering unit indicated with adhesive labels supplied
conformity to EMC directive Low-voltage directive Electrical connection Protection standard to IEC529 Orientation Maintenance Weight (including packaging)
Electrically isolating Measured inputs Output analog 24 VAC supply
EN 60730-1 EN 60730-1 EN 50 090-2-2 CE, RoHS, WEEE 2004/108/EG 2006/95/EG 2 12 screw-terminals, 2.5 mm IP50 (mounted in control panel), IP 20 (terminals) Any No maintenance required 0.340 kg Measured inputs (Pin 1…6) 500 V 4 kV
Output analog (Pin 8, 9) 500 V 4 kV
24 VAC supply (Pin 14, 16) 4 kV 4 kV -
3/6 Building Technologies
BAU200 – Universal digital indicator
CE1N5312en 03 July 2008
Selectable ranges
LG-Ni1000 range from 1 0 2 –30 3 –30 4 –30 5 –50 6 –50 7 32 8 –22 9 –22 10 –22 11 –58 12 –58
… … … … … … … … … … … …
to 50 50 90 130 70 180 122 122 194 266 158 356
unit °C °C °C °C °C °C °F °F °F °F °F °F
T1 range 1 2 3 4
from –50 –30 –58 –22
to … 80 … 130 … 176 … 266
unit °C °C °F °F
Pt100 range 1 2 3 4 5 6
from 0 –50 –30 32 –58 –22
… … … … … …
to 60 80 130 140 176 266
unit °C °C °C °F °F °F
Pt1000 range 1 2 3 4 5 6
from –50 –30 –20 –58 –22 –4
… … … … … …
to 80 130 400 176 266 752
unit °C °C °C °F °F °F
0-10V range 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
from 0 0 0 0 –10 –35 –50 32 32 32 32 14 –31 –58 0 0 0 0 0 0 0 0 0 –50 0 0 0 0 0 0 0 20 50 100 0 0 0 0 0 0 0 0 0 0 0 0 0 0 –1 –1
… … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … … …
to 50 70 100 130 120 35 50 122 158 212 266 248 95 122 100 95 90 1999 10 1000 5 10 15 50 100 200 250 300 500 1000 1500 300 500 1000 25 30 100 200 500 1000 2 4 5 10 16 20 25 40 9 24
unit °C °C °C °C °C °C °C °F °F °F °F °F °F °F % % % ppm V W/m2 m/s m/s m/s Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa mbar mbar mbar mbar mbar mbar bar bar bar bar bar bar bar bar bar bar
4/6 Building Technologies
BAU200 – Universal digital indicator
CE1N5312en 03 July 2008
5312A01
Connection terminals
Pt1000 LG-Ni1000 T1 Pt100
Vdc
1 2 3 4 5 6
Analog Out
24VAC
8 9 10
14 15 16
Dimensions
11
All dimensions in mm
48
5312M01
83
Indicator unit
96
Cut-out (96)
(48)
5312M01
+0.6
45 -0.3
< 10.0
92
+0.8 -0.3
5/6 Building Technologies
BAU200 – Universal digital indicator
CE1N5312en 03 July 2008
6/6
© 2006 - 2008 Siemens Switzerland Ltd.
Building Technologies
BAU200 – Universal digital indicator
Subject to change CE1N5312en 03 July 2008