Transcript
SPECIFICATION
Design Number:
50 PAIR #24 AWG UTP CAT 3 PLENUM
HT32940
DESCRIPTION UNSHIELDED TWISTED PAIR (UTP) CATEGORY 3 CABLE FOR USE IN BACKBONE CABLING SYSTEMS PER ANSI/TIA-568-C. THE CABLE CONSISTS OF #24 AWG SOLID BARE COPPER INSULATED CONDUCTORS, ASSEMBLED INTO TWISTED PAIRS, WITH A RIPCORD, UNDER AN OVERALL JACKET.
Jacket Insulation
THE CABLE IS PLENUM RATED FOR USE IN AIR HANDLING DUCTS AND SPACES IN ACCORDANCE WITH ARTICLE 800 OF THE NATIONAL ELECTRICAL CODE (NEC). THE CABLE IS UL (USA) & cUL (CANADA) LISTED FOR THIS APPLICATION BY PASSING NFPA 262 (FT6 OR PREVIOUSLY UL 910 STEINER TUNNEL) TEST.
Conductor
SUPPORTED APPLICATIONS ANALOG & DIGITAL VOICE, ISDN, IBM 3270 & 3x, IEEE 802.5 4 Mbps TOKEN RING®, IEEE 802.3 1BASE-5 & 10BASE-T, 10 Mbps ETHERNET®, 100BASE VG-ANYLAN
CONSTRUCTION PRIMARIES:
CONDUCTOR: 24 AWG (.5 mm) SOLID BARE COPPER INSULATION: PLENUM RATED THERMOPLASTIC
PAIR ASSEMBLY: SUBASSEMBLY: CABLE ASSEMBLY:
STRUCTURAL RETURN LOSS (SRL):
12 dB MIN (1-10 MHz) 12 - 10 log10 (f /10) dB MIN (>10 MHz)
2 PRIMARIES TWISTED IN VARIED LAYS
ATTENUATION:
2.320 f + .238f dB/100m MAX
25 PAIRS CABLED TOGETHER
NEAR END CROSSTALK (NEXT):
47 - 15 log10 (f /0.772) dB/100m MIN
2 GROUPS OF 25 PAIRS CABLED TOGETHER
POWER SUM NEAR END CROSSTALK (PS-NEXT): 43 - 15 log10 (f /0.772) dB/100m MIN
*GRAY PLENUM RATED THERMOPLASTIC NOMINAL OD: .539" (13.69 mm) *WHITE JACKET VERSION M58231 *GREEN JACKET VERSION M58466
JACKET:
LISTING:
PROPAGATION DELAY:
534 + 36/√f ns/100m MAX
DELTA DELAY (SKEW):
45 ns/100m MAX
NOMINAL VELOCITY OF PROPAGATION (NVP): 64%
C(UL)US OR C(ETL)US TYPE CMP
WHERE f = FREQUENCY IN MHz from .772 to 16 MHz
ELECTRICAL CHARACTERISTICS STANDARDS:
ANSI/TIA-568-C.2 CAT 3 POWER SUM BACKBONE CABLE
CONDUCTOR DCR:
9.38 Ω/100m (28.6 Ω/Mft) MAX
BENDING RADIUS:
5.4” (137 mm) MIN (10 x CABLE OD)
DCR UNBALANCE:
5% MAX
OPERATING TEMP.:
-20°C to +60°C (-4°F to +140°F)
MUTUAL CAPACITANCE:
66 pF/m NOM
STORAGE TEMP.:
-20°C to +75°C (-4°F to +167°F)
FREQ (MHz) .772 1.0 4.0 8.0 10.0 16.0
CABLE WEIGHT w/reel:
REFERENCE ELECTRICAL CHARACTERISTICS NEXT ACR* POWER SUM NEXT (dB/100m) (dB/100m) (dB/100m) avg min avg avg min 52 47 50.1 48 43 50 45 47.8 46 41 41 36 36.0 37 32 36 31 28.3 32 27 35 30 26.2 31 26 32 27 20.1 28 23 *ACR − MINIMUM ATTENUATION TO CROSSTALK RATIO
MOHAWK
Cabling Excellence for Open Architecture (978) 537-9961 Fax: (978) 537-4358 (800) 422-9961 www.mohawk-cable.com
This document is the property of Mohawk. The information contained herein is considered proprietary and not to be reproduced by any means without written consent of Mohawk.
0°C to +60°C (+32°F to +140°F)
∗THE INSTALLATION TEMPERATURE REFERS TO THE TEMPERATURE OF THE CABLE WHILE BEING INSTALLED OR PULLED. DO NOT INSTALL BELOW 0°C (+32°F).
100 Ω ± 15% (1-16 MHz) ATTENUATION (dB/100m) avg max 1.9 2.2 2.2 2.6 5.0 5.6 7.7 8.5 8.8 9.7 11.9 13.1
236 lbs/1000ft (351 kg/km)
∗INSTALLATION TEMP.:
CAPACITANCE UNBALANCE PAIR/GROUND: 330 pF/100m MAX CHARACTERISTIC IMPEDANCE:
PHYSICAL CHARACTERISTICS
PS-ACR* (dB/100m) avg 46.1 43.8 32.0 24.3 22.2 16.1
SRL (dB) min − 12 12 12 12 10
Rev
Description
N
CHANGE LISTINGS & DESC
12/13/05
Date
JS
O
ADD ROHS COMPLIANCE
01/09/08
JS
P
UPD DESC, STDS, DIA, WGT, BEND RADIUS, FTR
09/09/14
JS
Q
UPDATE FOOTER
02/23/17
JS
Date: 02/15/94
Page 1 of 1
Orig:
Review:
Mohawk reserves the right to change any specification in the interest of product enhancement. This cable complies with the EU-RoHS directive 2002/95/EC (restrictions on hazardous substances) regulations.
Init.
Part Number:
M56126