Preview only show first 10 pages with watermark. For full document please download

502 Bad Gateway

   EMBED


Share

Transcript

Maintenance LQQA Humidifier, for circulated water 18 3 1 17 1. Control box, on the outside 2. Control box, on the inside 3. Shut-off valve (not included) 4. Water filter, max. 500 mm mesh (not included) 5. LQAZ-08 Water trap (accessory) 6. Water supply pipe 7. Humidifier fill 8. Droplet eliminator 9. Spray pipe 10. Pump 11. Flow controller 12. Valve with motor actuator 13. Overflow hose 14. Water level sensor 15. Solenoid valve 16. Flushing hose 17. End plug 18. Side wall 2 9 4 16 Size 60-84 15 14 7 8 10 6 5 11 Fig. 1 12 13 Maintenance adjustments Water: Determine the calcium and bicarbonate content and the pH value of the water. These values can be obtained from a water analysis or from the local water authority. Plot the values of bicarbonate, calcium and pH in chart Level monitors A B C 1 on page 5 to determine in which zone the water can be classified. If the water is of zone 4 type, it should be softened. Level monitors fig. 2 Level monitor A: Level monitor A: Closes the water supply valve when the water reaches max. level A. Setting A: 65 mm from the upper edge of the water tray (sizes 60–84). N ZO 3 2 1 Zone Scale Level monitor B: Opens the drain valve for water bleed-off. Setting B: The zone value obtained (see page 5) determines at which setting level monitor B (Fig. 2) is to be preset. Level monitor C: Setting C: Level monitor B: Adjustable Adjusting screw Zon 3 Stops the circulation pump and opens the water supply valve if the water level drops below level C. 25 mm from the bottom of the water tray (sizes 60–84) Fig. 2 2 1 Level relays: NR 1, NR 2 and NR 3 are shown in Fig. 7. The level relays are preset at a sensibility of 40 kΩ. If softened water is used and the level monitors don’t work, the sensibility setting can be increased to 100 kΩ. Fläkt Woods 9206 GB 2011.11 1 Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water Maintenance adjustments (Contd.) Table 3. Supply water flow The humidifier function: – switch on the power supply to the humidifier. The water tray will start to fill with water. Check: – that the pump has started and that it is pumping water. If there is no water flow, change the direction of rotation of the pump, see Fig. 5. – preset the required supply water flow rate according to Table 1. This is done by setting the adjustment screw on the flow controller, shown in Fig. 4. – that water is being discharged from all of the holes in the spray pipe(s). If any holes are clogged, use a needle to unclog them. If the spray pipe(s) is/are extremely clogged, remove the end plugs (17), brush inside them using a round brush and then flush them clean. – that the flow of supply water stops when the water level in the tray reaches level monitor A. – that water bleed-off can be done by manually opening the drain valve approx. half way (45°), see Fig. 3. The valve can be reclosed by pressing a reset button on the control unit. When the water level has drop ped below the lowest point of sensor B, the drain valve should open fully. If the water level continues to drop below the lowest point of sensor C, water inlet valve should begin to open and after a preset period (see Table 2, Fig. 6) the drain valve should start to close. When the water reaches level C, the pump should soon stop. (The pump should not run when the water level is below level C.) – The preset period on the time relay should be according to Table 2, 3 and Fig. 6. Size Supply water flow, l/min Aluminium 90% 60% 60 62 64 30 40 50 15 20 25 71 73 40 50 20 25 80 82 84 40 50 60 20 25 30 Droplet eliminator The droplet eliminator fills must be correctly fitted for the direction of air flow, see the arrow on the droplet eliminator. EUQA 2;1 EUQA Pump 0 2 0 4 6 4 30 20 10 Fig. 3 Fläkt Woods Fig. 4 9206 GB 2011.11 2 2 Adjusting screw Reading point Fig. 5 Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water Table 2. Presetting the time relay Table 3. Presetting time relay TR1 Seconds 0 Time required for emptying Size Normal operation preset value High humidification over a long period Δx >8 gram Δx >5 gram 90% 60% 90% 60% 60 62 64 30 60 60 0 0 30 30 90 240 0 0 120 71 73 60 90 30 60 180 240 90 120 80 82 84 90 90 120 60 60 60 180 240 300 120 120 120 Time relay TR1 has been preset for normal operation. If the time required for emptying has to be increased due to humidification over a long period, this can be done as follows: 1. Select Function 12 2. Select the Range 3. Select Time – If Range has red digits, Time shows tenths of Range – If Range has black digits, Time . shows thirtieths of Range Example: Size 64, Δx>8 gram. Set a time of 240 sec. – Select a Range of 300 sec. (black digits) – Select a Time of 24 (black digits) A1~+ 15 B1 Range 1s Time 0 10 10 s 10 red 20 30 s 20 black 30 30 s 30 black 40 100 s 4 red 50 100 s 5 red 60 100 s 6 red 70 100 s 7 red 80 100 s 8 red 90 100 s 9 red 100 100 s 10 red 120 300 s 12 black 180 300 s 18 black 240 300 s 24 black 300 300 s 30 black TR1 M 1s Range 1.5 .5 Time 12 Function TR1 Q1 ETR4–69–A Rel 16 NR1 NR2 NR3 Power 18 A2~- K1 Fig. 6 R1 Fig. 7 Fläkt Woods 9206 GB 2011.11 3 Components inside the control box Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water Water quality To set the timer for emptying and flushing Evaporation causes an increase in the concentration of minerals in the circulating water, which necessitates continuous bleed-off and make-up with fresh water. The bleed-off rate is dependent on factors such as: For normal function, the timer should be preset to ”ON”. When emptying, which can be programmed to occur once or several (optional) times every 24-hour period, the timer will reset itself to the ”OFF” setting for 10 minutes. After that, the timer will reset itself to ”ON” for 2 minutes to allow flushing. The timer will then reset itself to the ”OFF” setting for 3 minutes for additional emptying before resetting itself back to ”ON” for normal operation. In the following example, emptying and flushing are required once every 24 hours from 12.00 to 12.15 as scheduled below. ■ the pH of the water ■ the bicarbonate concentration (HCO3 ), mg/l ■ the calcium concentration (Ca2+), mg/l This data can be obtained from a municipal water authority or by analysing the water. Lime precipitation can be prevented by plotting the pertinent data in Chart 1 on page 4 to determine the current risk zone. Water level monitor B can then be set according to the relevant zone. If the water is too hard, it may be necessary to subject it to partial softening. In addition to the risk of lime precipitation, the concentration of chlorine (Cl) and copper (Cu) must be taken into account. To ensure acceptable performance, the concentration of Cl in the fresh water must not exceed 50 mg/l and that of Cu must not exceed 0.02 mg/l. Fläkt Woods 9206 GB 2011.11 Period 00.00–12.00 12.00–12.10 12.10–12.12 12.12–12.15 12.15–24.00 Timer setting Activity ON OFF ON OFF ON Normal operation Emptying Flushing Additional emptying Normal operation This can be done most easily by programming the operation times from 12.15 to 12.00 and from 12.10 to 12.12 on a daily basis! Emptying and additional emptying will then occur from 4 Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water The timer has also been preset for the following: – Summer and winter time in the country where it is to be used. – Date and time in the time zone where it is to be used. Timer The timer has been preset at the factory for emptying and flushing as described above once every 24-hour period. Day-by-day summary of the programmed connection times. Example: 5 = Friday L 24 Duct status ON = On, OFF = OFF Maintenance voltage OK: Indicated by 2 flashing points between the numbers on the display. Running reserve mode: Indicated by 3 flashing points between the numbers on the display. Choice of function: Ex: Auto, Prog, Pulse, Cycle, Delete Auto 0 Manual operation Permanent ON/OFF Symbols which indicate summer/winter function: Summer Winter ❄ 1234567 MENU Display of special functions: - + OK The numbers under the display indicate days of the week 1 = Monday, 2 = Tuesday, etc. Choice Yes means choice of programming. 1 2 3 N Choice No means continue. N L2 Change of current time of day 1. Press menu 2 times flashes 2. Press OK Display shows YEAR, change with + or – 3. Press OK Display shows MONTH, change with + or – 4. Press OK and continue for DAY, HOUR, MINUTE, SU/WI… (SU = Summer, WI = Winter) Change of ON/OFF 1. Press menu 1 time - Prog flashes 2. Press OK Read text in the display! Select with + or – Store with OK Manual operation of ON/OFF 1. Press both + and – at the same time. ~1 sec gives manual ON/OFF, (returns automatically) ~2 sec gives permanent ON/OFF For switching ON/OFF 1. Press menu 1 time - Prog flashes 2. Press OK 3. Change to QUESTION with + or – 4. Press OK 5. Press OK for next time. To INTERRUPT And continue to END Press menu 6. Press OK Fläkt Woods 9206 GB 2011.11 L1 Resetting: Briefly press both + and – at the same time. For further particulars, see the separate instructions supplied with the timer. 5 Specifications are subject to alteration without notice EU Air Handling Unit INSTALLATION Maintenance EUQA Humidifier, for circulated water LQQA Humidifier, for circulated water Determining the water quality zone Example The following particulars are required to be able to determine the water quality zone. Chart 1 the water ■ the pH of – mg/l ■ the bicarbonate Zone 1 is the safeconcentration zone, in which(HCO the water soft or 3 ), is 2+ ■ the calcium concentration (Ca ), mg/l demineralized. Data from the municipal water authority: pH = 7,6 Example Bikarbonate 70 mg/l Calcium 30 mg/lwater authority: Data from the municipal pH = 7,6 From Chart 1, the point is in zone 1 (safe Bikarbonate 70operating mg/l zone). Calcium 30 mg/l Zone 2 is the lower part of the transition zone, in which This cancan be be obtained from a municipal water authothedata water said to be of normal drinking quality. is the upper part of the transition zone, in which rityZone or by3 analysing the water the water is relatively hard. Zone 4 is the precipitation zone, in which the water is very hard. The water must be subjected to partial softening, so that its quality will be within zone 2–3. However, the softening treatment must not lower the quality of the water to zone 1. From Chart 1, the operating point is in zone 1 (safe zone). 2+ mg/l Calcium Ca2+ m g/l 2 pH-value pH-value 4 6 10 20 40 60 100 1000 10 000 5 6 Max. Max. pH pH of of aluminium aluminium 7 8 8,5 9 9,5 10 000 6000 4000 2000 1000 600 400 200 n tio ita ip ec Pr 100 60 40 zo ne 20 10 6 4 3 2 n io sit an Tr 4 ne zo f Sa 1 Bikarbonate BikarbonateHCO HCO3–3– mg/l mg/l e on ez 2 1 Water consumption The water consumption consists of the water evaporated and a certain amount of water bleed-off. This bleedZone is the safe zone,toinreduce whichthe theconsumption water is softoforsalts off 1flow is necessary demineralized. in the circulating water. If the concentration of salts is Zone is thesalts lower part the transition in which too2high, may be of deposited on the zone, humidifier fill, thewhich water will can have be said to be of normal quality. a detrimental effect drinking on the performanZone 3 isthethe upper part of the transition zone, in which ce of humidifier. theThe water is relatively hard. chart above can be used to determine the appropriate bleed-off flow. If the humidifier has been sized for running over a long period at a high humidification rate Δx above 8 grams per kg of air (90% humidifier) and Δx above 5 grams per kg of air (60% humidifier) respecFläkt Woods Fläkt Woods 3214 GB 05.08 9206 GB 2011.11 tively is recommended if the water tray is emptied and flushed twice a day. (See: To set the timer for emptying Zone 4 is the precipitation zone, in which the water is and flushing.) very hard. The water must be subjected to partial softening, so that will be within zone 2–3. Periods outitsofquality service However, the softening treatment must notemptying lower the The controller of the humidifier switches to the quality of the water 1. out. mode whenever the fantoiszone switched Clean the water tray if the system is to be shut down for an extended period, such as during the annual holiday and long weekends. If the humidifier is to be out of service for some time, the humidifier fills should be removed, cleaned and stored in a place where they will not sustain damage. 6 6 Specifications are subject to alteration without notice Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water To shut down the humidifier A. Isolate the power supply B. Stop the fans, if they are operating. Cleaning or replacement of the humidifier fills and droplet eliminators A. Shut down the humidifier. B. Open the inspection door. C. Withdraw the spacer plate as shown in Fig. 8. D. Withdraw the droplet eliminators and humidifier fills straight out of the humidifier. See Fig. 8. Important! The inner humidifier fills can be reached if you carefully step on the edge of the water tray. Avoid walking on the bottom of the water tray, guide rails or electric cables. E. The fills are relatively fragile and therefore should be treated with great care. Clean by spraying with a jet of clean water, possibly containing the ULCZ-01 cleaning agent. When replacing the humidifier fills, see the appropriate instructions supplied with the new fills. F. Refit the components in the reverse order. G. Check the position of the spacer plate and close the door. Fig. 8 To clean the water tray A. Shut down the humidifier. B. Withdraw the humidifier fills and the droplet eliminators. C. Open the drain valve manually to drain the water tray. Important! Do not walk on the bottom of the water tray, guide rails or electric cables. D. The water tray is now exposed and can easily be cleaned with the flushing hose supplied. E. Refit the components in the reverse order. F. Check the position of the spacer plate and close the door. Fläkt Woods 9206 GB 2011.11 7 Specifications are subject to alteration without notice Maintenance LQQA Humidifier, for circulated water Service intervals Component Service work Interval, months Casing (water tray, ends, top, guide rails) Drain the water tray. Clean the interior by flushing, wiping or brushin if necessary. 3 Humidifier fills Droplet eliminator Clean by flushing with water, possibly with ULCZ-01 cleaning agent, particularly if the humidification performance has deteriorated. 3 Water filter Clean or replace the filter cartridge, if necessary. (The mesh must not exceed 500 μm.) 3 Level monitor Check the water level and adjust as necessary. 3 Water flow Clean the spray tubes as necessary. 3 Water trap Clean and refill. 6 Water quality See under “maintenance adjustments”. 12 Wiring diagram L1 L2 L3 N PE 1 3 5 HB 0 1 2 4 6 G/G 1 2 SU1 6A 1 2 3 4 Q1 1 5 3 4 7 M C 1 3 5 Q2 4 – TF 2 no Interlock GM 3 4 c no Humidity control A1 A2 19 8 6 5 18 1 3 5 Level relay Prevents operation when the tray is dry A1 11 14 12 A1 2 4 6 1 3 5 K1 2 4 6 A1 1 3 5 B1 B2 B3 A 16 2 4 6 U V W M 3 M 3 CP1 CP2 15 Level relay Maintains correct level R1 21 16 18 15 B B1 17 11 A1 B3 9206 GB 2011.11 Aux. relay Time relay Level monitor 8 Solenoid valve Maintains correct level B1 B2 R1 TR1 NR1, NR2 12 TR1 16 18 TR1 15 R1 18 16 34 32 13 31 NR3 Level monitor HB Main switch SV1 Valve actuator Delayed closure, SV1 A2 SV1 3 1 14 Q1, Q2 Motor protection switch F1 Automatic fuse SU1 Timer MV1 24 22 NR3 A2 A1 Fläkt Woods Contactor CP2 A2 Level relay Bleed-off U V W A2 NR2 K2 2 4 6 Contactor CP1 K2 A1 I> I> I> A2 K1 R1 18 16 A2 A1 A2 Control box on inside Auxiliary relay Emptying/ Flushing R1 B1 B2 B3 Control box on outside Timer Emptying/ Flushing c NR1 15 I> I> I> N SU1 F1 15 Valve actuator 2 K1, K2 Contactor TF Supply air fan GM Hygrostat Specifications are subject to alteration without notice