Transcript
Sentrol 6250FM Series Flush Mount SureShot
TM
PIR
Installation Instructions Models 6255FM, 6257FM
Lens
PET
ALLEY
Sliding LED cover ®
Tamper switch (6257FM only)
Mounting screws
Terminal block LED
Flush mount cover plate
WID ANGLE E
V E R T I C A L
B A R R I E R
PET SPO T ALLE Y
Masking kit
1
Single gang box (not included)
Installing the Flush Mount Sureshot Note: The masks have two notches to prevent incorrect installation. One notch matches a rib in the front cover. The second notch matches a dimple in the lens.
Avoid False Alarm Sources Sunlight or reflected sunlight
Hot or cold air directed onto sensor
Align notch with dimple
Align notch with rib
WIDE ANGLE
Pets Intermittent heat sources
Inside of front cover
For false-alarm-free operation, a PIR should not “see" sources of heat or cold.
Masking 1. Choose the mask you need, if any.
Note: To correctly mount the Pet Alley Mask, the lens must be removed from the front cover and rotated 180o.
2. Press in on side latches of unit and pull the back cover off.
SIDE VIEW Strain Relief Hanger
Rotate lens 180° PET ALLEY
Side Latches
ROTATE LENS 180o
Terminal Block
Align notch with dimple
Inside of front cover
3. Insert the mask behind lens on front cover by pressing over four mounting pins. Once back cover is snapped back on, the mask will be held tight against the lens. Note:
4. Replace back cover and proceed with mounting.
Mounting The unit can be mounted into a standard single gang electrical box, a remodel single gang box, or a rough-in plate. It can be mounted in the wall or on the ceiling. The following directions apply to any of the above. 1. Feed wire through the single gang box or rough-in plate and hook up to the terminals on the back of the unit. 2. Connect wires per “wiring” diagrams on following pages. 3. Tie the wire to the strain relief hanger on the back of the unit using the tie wrap provided in the box. 4. Place the cover plate over the unit and set into the single gang box or rough-in plate. 5. Tighten screws on the cover plate. 6. After walk testing, the LED cover can be slid up to cover the LED.
When mounting on the ceiling, align the unit to maximize the oblong detection pattern for the room. Always use “center spot” mask when mounting on ceiling.
Capture zone at 8' mounting height
20'
2
15'
ZONE PATTERNS Wall Mount–No Mask
With "Vertical Barrier" Mask
29 Zones 58 Beams
7 Zones 14 Beams
Top View 54°
Side View
38.4° 20°
Side View +54°
0'
Top View
+38.4°
0°
+18°
0'
10°
20° 54°
7' 2.13m
38.4°
0'
40' 12.19m
5.9°
0' 30' 9.14m
7' 2.13m 10' 20' 30' 40' 3.04m 6.09m 9.14m 12.19m
10' 20' 30' 40' 3.04m 6.09m 9.14m 12.19m
40' 12.19m
With "Wide Angle" Mask Top View
With "Pet Alley" Mask
18 Zones 36 Beams
7 Zones 14 Beams
Top View
Note: Lens must be inverted for pet alley 0'
90°
0'
90°
Side View Side View
7' 2.13m
30' (9.14m)
3' .91m 0'
40' (12.19m)
40' 10' 20' 30' 3.04m 6.09m 9.14m 12.19m
Ceiling Mount–Center Spot Mask
Capture Zone
29 Zones 58 Beams
0'
40' 12.19m
30' 9.14m
40' 10' 20' 30' 3.04m 6.09m 9.14m 12.19m
Wiring Strip back the outer jacket on your wiring cable. This will allow wires to flex in the case. Use cable strain relief built into back cover to prevent stressing wires at their connection.
8' (2.4m)
15' (4.59m) X 20' (6.12m) capture zone
6255FM Model –
NC COM
–
+
Power-In 7 to 16 VDC
+
25' diameter (7.5m) coverage pattern
NO COM T/NO Tamp
Note: Intruder must enter capture zone in order to be detected. False alarm sources, such as heaters, should be kept out of the coverage pattern. Be sure to insert center spot mask to reduce potential for false alarms.
6257FM Model
With "Single Spot" Mask
Top View
1 Zone 2 Beams
Note: The unit should be connected to a UL listed power supply, capable of providing four hours of standby power.
Side View 10°
0'
Power-In 7 to 16 VDC
40' 12.19m
7' 2.13m 0'
7° 10' 20' 30' 40' 3.04m 6.09m 9.14m 12.19m
3
SPECIFICATIONS FEATURES Pulse Count ......................... Bi-directional, 1 zone (2 pulses) with Motion Verification Capture Zone (at 70½ F) Wide Angle (90½) ................... 30' (9.14m) x 30' (9.14m) Single Spot ...................................... 40' (12.19m) range Vertical Barrier ................................. 40' (12.19m) range Pet Alley (90½) ................................... 30' (9.14m) range 360°Ceiling ...... 15' x 20' (4.57m x 6.10m) at 8' (2.44cm) mounting height ....... 16' x 30' (4.88m x 9.14m) at 12' (3.65m) mounting height .... Ceiling mounting height up to 12' (3.65m) Mounting ............................................ Wall, corner, or ceiling LED indicator ............................................................ Walktest Size ...................................................... 2.75" (6.99cm) Width 4.50" (11.43cm) Height 1.63" (4.13cm) Total Depth 1.37" (3.49cm) Depth behind wall 0.25" (0.64cm) Depth in front of wall Color .................................................................. White/White
ELECTRICAL Voltage ............................................................... 7 to 16 VDC Current ............................................ 8 mA typical, 10mA max. Maximum relay rating ..................................... 16VDC, 50 mA Alarm output ............. Fail safe contacts w/ 10 ohms in series, 6255FM - Form A, Normally Closed (NC) 6257FM - Form C, Normally Closed and Open (SPDT) Alarm duration ................................................ 2 to 5 seconds Cover tamper contacts ................................ Normally Closed, rating: 50 mA, 12VDC (6257FM only) ENVIRONMENTAL Operating Temperature ........... 0°F to 120°F (-17°C to +50°C) Humidity ................................... 10% to 90% noncondensing RFI immunity ...... greater than 10V/meter from 0 to 1000MHz Static/lightning immunity ............. 2.5KV, 2 joules max energy impulse, 1 msec rise / 50 msec decay
NOTE: This unit will fit in most standard single gang electrical boxes or rough-in plates, available at any electrical supply store. Front View
Side View 1.63" 4.13 cm
2.75" 6.99 cm
4.50" 11.43 cm
4.5" 11.43 cm
®
.25" 0.64 cm
1.37" 3.49 cm
ORDERING INFORMATION PART NUMBER 6255FM 6257FM
LOOP TYPE Normally Closed Normally Closed or Open
ELECTRICAL CONFIGURATION N.C. – Form A SPDT (N.C. and N.O.) – Form C
CORPORATE HEADQUARTERS 12345 SW Leveton Dr. Tualatin, OR 97062 Tel.: 503.692.4052 Fax: 503.691.7566
SENTROL
U.S. & Canada: 800.547.2556 Technical Service: 800.648.7424 FaxBack: 800.483.2495
COMMENTS
LISTING
No Tamper Incl. Tamper
UL UL
Sentrol reserves the right to change specifications without notice. © 2000 Sentrol
13048 Rev. B 06/00