TMS 12:46:27 PM 12/3/2015 COMPACTING FILL AROUND PROPOSED CONCRETE ENCASEMENT. COMPACTING FILL AROUND MAKE SURE CONCRETE HAS SET PROPOSED CONCRETE ENCASEMENT. MAKE SURE CONCRETE HAS SET BEFORE CONTINUING FILLING & 1A43 TYPE CONCRETE TO BEFORE CONTINUING FILLING & 1A43 TYPE CONCRETE TO COMPACTING IN THIS ARE ENCAPSULATE PROPOSED 2" SPLIT CONDUIT. LET CONCRETE COMPACTING IN THIS ARE ENCAPSULATE PROPOSED 2" HARDEN PRIOR TO FILLING IN THE SPLIT CONDUIT. LET CONCRETE REST OF THE TRENCH HARDEN PRIOR TO FILLING IN THE REST OF THE TRENCH VAR. 6" MIN. 6" MIN. 6" MIN. 6" MIN. F&I 2" SPLIT CONDUIT AROUND THE INPLACE 1-FO CABLE (12 MM, 18 SM) USE SPLIT COUPLER TO INPLACE 2" RSC CONNECT TO INPLACE 2" RSC 6" MIN. 6" MIN. A UNDISTURBED INPLACE GROUND c:\projectwise\pw_working\cooz1sco\d1747103\FO CABLE ENCASEMENT_dt1.dgn cooz1sco MDROSFRW7D023 PLOTTED: USE EXTREME CAUTION WHEN USE EXTREME CAUTION WHEN UNDISTURBED 1' MIN. INPLACE GROUND END VIEW SIDE VIEW A PLACE CONCRETE AT LEAST 1 (ONE) FOOT AROUND THE INPLACE CONDUIT AND COUPLER. NOTES: EXCAVATE MATERIAL BY HYDRO VAC METHOD PLACE SPLIT DUCT CONDUIT AROUND INPLACE FO CABLE PLACE HOSE CLAMPS AT 1' INTERVALS AROUND SPLIT DUCT TO AVOID CONCRETE FROM ENTERING DUCT CONCRETE TO BE 1A43 FIBER OPTIC CABLE ENCASEMENT REV. NO. DATE: / / REV. NO. DATE: / / CERTIFIED BY LIC.NO. LICENSED PROFESSIONAL ENGINEER DATE 2016 STATE PROJ. NO. XXXX-XXX (TH XXX) SHEET NO.XXXX?OF XXXXX SHEETS