INSTALLATION INSTRUCTIONS TCURBF, TCURBT, TFCF, TFCT T-FLEX CURBS The T-Flex Curbs are accessory items used to retrofit a C**H unit to the structure and are intended to lower the building’s interior sound level. This is accomplished by using the following principles: • • The offset return will require a different supply to return spacing for the applied structure than specified by the wall-mounted unit. The first is accomplished by isolating the vibrations created by the mechanical devices of the wall mount operation using rubber isolation mounts to prevent the energy from transferring into the wall of the structure that it is mounted on. (This will be more beneficial on wood or steel frame structures in eliminating the drumming effect of the wall than on masonry structures.) The second is the T-Flex Curb creates an indirect return air path and has additional sound attenuation material to lower sound transmission into the structure through the return air opening. CONTENTS Wall Curb Application Guide.................................... 2 Figure 11 Wall Mounting Instructions................... 8 TCURBF****-*, TCURBT****-* New Installations..... 6 Figure 12 Wall Mounting Instructions................... 8 TFCT-32A-*, TFCF-32A-*, TFCT-53A-*, TFCF-53A-* Retrofit Installations............................................... 7 Figure 13 Electric Heat Clearance........................ 9 Figure 14 TCURBF2430 Supply and Return Openings................................ 10 Figure 15 TCURBT2430, TFCF-32A and TFCT-32A Supply and Return Openings............... 11 Figure 16 TCURBT3642A and TCURBT4860A Supply and Return Openings............... 12 TCURBF3642A and TCURBF4860A Supply and Return Openings............... 13 Figures Figure 1 TCURBF2430..................................... 3 Figure 2 TCURBF3642A................................... 3 Figure 3 TCURBF4860A .................................. 3 Figure 4 TCURBT2430..................................... 3 Figure 5 TCURBT3642A................................... 4 Figure 17 Figure 6 TCURBT4860A................................... 4 Figure 18 TFCF-53A Supply and Return Openings.. 14 Figure 7 TFCF-32A........................................... 5 Figure 19 TFCT-53A Supply and Return Openings...15 Figure 8 TFCF-53A........................................... 5 Figure 20 Fastening Unit to Curb....................... 16 Figure 9 TFCT-32A............................................ 5 Figure 21 Sealing with Caulk............................. 17 TFCT-53A............................................ 5 Figure 22 Sealing with Caulk (Top Outlet Curb).... 18 Figure 10 Patent No. 8,540,557 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 7960-689D Supersedes: 7960-689C Date: 4-22-16 Page 1 of 18 Wall Curb Application Guide Unit Indoor Air Connections Curb Indoor Air Connections Fig. # Curb Model  Used with Unit Model Supply Air HxW Return Air HxW Spacing SA to RA Supply Air HxW Return Air HxW 1 TCURBF2430 C24H C30H 7.88 x 27.88 13.88 x 27.88 17.93 7.88 x 27.88 13.88 x 27.88 6.125 17.93 2 TCURBF3642A C36H C42H 9.88 x 29.88 15.88 x 29.88 30.00 9.88 x 29.88 15.88 x 29.88 6.125 30.00 Used to direct replace CH3S models. 3 TCURBF4860A C48H C60H 9.88 x 29.88 15.88 x 29.88 30.00 9.88\x 29.88 15.88 x 29.88 6.125 30.00 Used to direct replace CH4S and CH5S models. 4 TCURBT2430 C24H C30H 7.88 x 27.88 13.88 x 27.88 17.93 7.88 x 27.88 13.88 x 27.88 17.93 ---- Used to install 2 or 2½-ton cabinet machines installed in a soffit. 5 TCURBT3642A C36H C42H 9.88 x 29.88 15.88 x 29.88 30.00 9.88 x 29.88 15.88 x 29.88 30.00 ---- Used to install 3 or 3½-ton cabinet machines installed in a soffit. 6 TCURBT4860A C48H C60H 9.88 x 29.88 15.88 x 29.88 30.00 9.88 x 29.88 15.88 x 29.88 30.00 ---- Used to install 4 or 5-ton cabinet machines installed in a soffit. 7 TFCT-32A C24H 7.88 x 27.88 13.88 x 27.88 17.93 7.88 x 19.88 11.88 x 19.88 20.56 ---- Used to install new 2 or 2½-ton in place of old 2-ton in a soffit. 8 TFCT-53A C36H 9.88 x 29.88 15.88 x 29.88 30.00 7.88 x 27.88 13.88 x 27.88 17.93 ---- Used to install new 3 or 3½-ton in place of old 3-ton in a soffit. 9 TFCF-32A C24H 7.88 x 27.88 13.88 x 27.88 17.93 7.88 x 19.88 11.88 x 19.88 20.56 ---- Used to install new 2 or 2½-ton in place of old 2-ton. 10 TFCF-53A C36H 9.88 x 29.88 15.88 x 29.88 30.00 7.88 x 27.88 13.88 x 27.88 17.93 ---- Used to install new 3 or 3½-ton in place of old 3-ton. Spacing Alt. SA Spacing to SA to RA RA Application NOTE A: A TCURB***** is required for all economizer applications. For T24 and T30 installations with CHCRV-3, a TCURB is also required. 7960-689D Page 2 of 18 NOTE A  All curb model numbers are followed by -X (beige), -4 (gray), etc. to match unit color.  All curbs have four rubber isolation mounts to reduce vibration to the installation wall. FIGURE 1 TCURBF2430 FIGURE 2 TCURBF3642A 1 17 8 " 22 7/16" 1 7 38 8 " 5 27 8 " 40 16 " 44 3/16" 42 1/16" 29 7/8" 31 3/4" 26 7/16" 9 7/8" 7 78" 6 1/8" 1 68" 30" 17 15/16 15 7/8" 7 13 8 " 9 70 16 " ALT. RETURN POSITION 5 70 16 " 84 7/8" 85 5/16" ALT. RETURN POSITION TCURBF2430 C24H C30H 9 5/16" TCURBF3642 C36H C42H MIS-3216 A FIGURE 3 TCURBF4860A 9 5/16" MIS-3217 A FIGURE 4 TCURBT2430 17 1/8" 22 7/16" 29 13/16" 42 1/16" 3 44 3/16" 3 40 8 " 7 38 16 " 27 8 " 31 3/4" 26 7/16" 9 7/8" 7 78" 12" 6 1/8" 30" 15 17 16 " 15 7/8" 85 5/16" 7 93 1/8" 13 8 " ALT. RETURN POSITION 5 82 16 " 9 70 16 " TCURBF4860 TCURBT2430 9 5/16" C48H C60H 7 13/16" MIS-3218 A C24H C30H 9 5/16" MIS-3213 A 7960-689D Page 3 of 18 FIGURE 5 TCURBT3642A 22 7/16" 44 1/4" 42 1/16" 29 7/8" 31 3/4" 9 7/8" 24" 30" 15 7/8" 109 1/4" 84 7/8" TCURBT3642 9 5/16" C36H C42H MIS-3214 A FIGURE 6 TCURBT4860A 22 7/16" 42 1/16" 29 7/8" 44 1/4" 31 3/4" 9 7/8" 24" 30" 15 7/8" 117 1/8" 109 1/4" 93 1/8" TCURBT4860 9 5/16" C48H C60H 7960-689D Page 4 of 18 7 7/8" MIS-3215 A FIGURE 7 TFCF-32A FIGURE 8 TFCF-53A 22 7/16" 17 1/8" 27 7/8" 38 7/16" 42 1/8" 38 3/16" 33 5/16" 19 7/8" 26 3/4" 31 3/4" 7 7/8" 7 7/8" 17 7/8" 20 9/16" 70 9/16" 70 3/8" 70 3/8" 11 13/16" 13 7/8" 85" TFCF32 TFCF53 14 5/8" C36H C42H 9 5/16" C24H C30H 9 5/16" MIS-3225 A MIS-3266 A FIGURE 9 TFCT-32A FIGURE 10 TFCT-53A 22 7/16" 1 17 8 " 3 33 8 " 7 19 8 " 3 38 16 " 38 1/2" 42 1/16" 27 7/8" 31 3/4" 26 3/4" 10" 12 1/8" 7 7 7/8" 78" 17 15/16" 9 20 16 " 13 7/8" 7 11 8 " 82 1/4" 84 7/8" 9 70 16 " 5 80 16 " TFCT53 TFCT32 14 3/4" C36H C42H C24H C30H 9 5/16" 5 9 16 " MIS-3222 A MIS-3223 A 7960-689D Page 5 of 18 TCURBF****-*, TCURFT****-* NEW INSTALLATIONS 1. Frame the wall in accordance with these installation instructions. See Figures 11-17. 2. Remove the packaging from the curb, but leave attached to the skid for now. 3a. TCURB*2430 models: Measure the distance between the SA (supply air) and RA (return air) opening in the wall and verify the curb has the correct back orientation for the wall. The curbs come out of the box set up for nominal 6" spacing between SA and RA. To convert to nominal 18" spacing, remove the RA panel from the back, rotate the RA panel 180˚ and place into position covering the lower open area. There should now be nominal 18" spacing between the SA and RA openings. Once verified, replace all screws securing the RA panel into place. 3b. TCURB*3642A and TCURB*4860A models: Measure the distance between the SA (supply air) and RA (return air) opening in the wall and verify the curb has the correct back orientation for the wall. The curbs come out of the box set up for nominal 6" spacing between SA and RA. To convert to nominal 30" spacing, remove the solid panel and RA panels from the back, move the solid panel up and attach to the bottom of the SA panel. Rotate the RA panel 180˚ and place into position covering lower open area. There should now be nominal 30" spacing between the SA and RA openings. Once verified, replace all screws securing the RA panel into place. 4. Remove curb from skid and lay flat on the back on the ground or on saw horses. 5. Attach the bug screen frame to the bottom of the curb with screws provided. Insert the bug screen. 6. Remove the four (4) bolts and lock washers holding the outer frame to the inner frame. 7. On top outlet versions, leave the upper support angle on the outer frame at this time. 11. Mount the inner frame to the wall using lag bolts. Be sure to center the supply and return flanges of the back in the wall openings. Verify the curb is square. 12. Remove the lower partition blank-off plate if the unit has an economizer installed in it. On C24H and C30H units, also remove the lower partition blank-off plate if the unit has a CHCRV-3 installed in it. 13. Slide the outer frame back over the inner frame and reattach using the four (4) bolts and lock washers removed in Step 6. The bug screen should be at the bottom of the curb. The top outlet sides must slide under the top outlet box sides. NOTE: The outside curb will need to be compressed slightly to get the bolts started. Clamps or pliers may be needed to compress the rear seal to align the bolt holes. It is necessary for the seal to be under compression so when the wall mount is installed, adequate weather sealing is maintained. 14. Remove the upper support angle now if a top outlet curb. 15. Verify the curb is square. 16. Raise the unit to the curb with a suitable lift and engage the top of the unit to the curb first by slightly tipping the unit toward the curb. On top outlet curbs, ensure the unit is underneath the lip on the top outlet box. Caulk may be applied under the lip of the top outlet box if desired. 17. Engage nuts and washers (supplied) loosely to the top two (2) bolts in the curb to help keep the top of the unit in position. 18. Pivot the unit down to engage the remainder of the bolts and fasten securely to the curb with nuts and washers (supplied) (see Figure 18). 8. Slide the outer frame off of the inner frame and set aside. 19. Apply a liberal amount of caulk across the top seam of the curb where it meets the unit or top outlet box. Also apply caulk where the curb or top box meet the wall (see Figures 19 and 20). 9. On the TCURBT3642A-* and TCURBT4860A-X mount the top box to the inner frame using the screws provided. The top box is shipped attached on all other curbs. 20. Connect power wires and thermostat wires to the unit. Use flexible conduit to maintain vibration isolation. Use of rigid conduit is not recommended and could cancel the benefits of the curb. 10. On the inner frame locate the TL side indicating Top Left. On the rear of the mounting flange, apply a liberal amount of silicone caulk to weather seal the inner curb to the structure. 21. Connect ductwork per standard practices. 7960-689D Page 6 of 18 TFCT-32A-*, TFCF-32A-*, TFCT-53A-*, TFCF-53A-* RETROFIT INSTALLATIONS Adding to Existing Installation 1. Disconnect the electrical entrance and thermostat wires from the old unit. 2. Disconnect the duct work as required from the old unit. 3. Supporting the unit, remove the mechanical fasteners retaining the wall mount unit to the structure, then lower the unit and move it off to the side. 4. Remove and discard bottom mounting bracket for wall mount. 5. Remove the packaging from the curb, but leave attached to the skid for now. 6. Measure the distance between the supply and return opening in the wall and verify the curb has the correct back orientation for the wall. If not, remove the inner back and turn 180˚ and reattach. Verify the correct dimensions are correct. 7. Remove curb from skid and lay flat on the back on the ground or on saw horses. 8. Attach the bug screen frame to the bottom of the curb with screws provided. Insert the bug screen. 9. Remove the four (4) bolts and lock washers holding the outer frame to the inner frame. 10. On top outlet versions, leave the upper support angle on the outer frame at this time. compression so when the wall mount is installed, adequate weather sealing is maintained. 16. Remove the upper support angle now if a top outlet curb. 17. Verify the curb is square. 18. Raise the unit to the curb with a suitable lift and engage the top of the unit to the curb first by slightly tipping the unit toward the curb. On top outlet curbs, ensure the unit is underneath the lip on the top outlet box. Caulk may be applied under the lip of the top outlet box if desired. 19. Engage nuts and washers (supplied) loosely to the top two (2) bolts in the curb to help keep the top of the unit in position. 20. Pivot the unit down to engage the remainder of the bolts and fasten securely to the curb with nuts and washers (supplied) (see Figure 18). 21. Apply a liberal amount of caulk across the top seam of the curb where it meets the unit or top outlet box. Also apply caulk where the curb or top box meet the wall (see Figures 19 and 20). 22. Connect power wires and thermostat wires to the units. Use flexible conduit to maintain vibration isolation. Use of rigid conduit is not recommended and could cancel the benefits of the curb. 23. Connect ductwork per standard practices. 11. Slide the outer frame off of the inner frame and set aside. 12. On the inner frame locate the TL side indicating top Left. On the rear of the mounting flange, apply a liberal amount of silicone caulk to weather seal the inner curb to the structure. 13. Mount the inner frame to the wall using lag bolts. Be sure to center the supply and return flanges of the back in the wall openings. Verify the curb is square. 14. Remove the lower partition blank-off plate if the unit has an economizer installed in it. On C24H and C30H units, also remove the lower partition blank-off plate if the unit has a CHCRV-3 installed in it. 15. Slide the outer frame back over the inner frame and reattach using the four (4) bolts and lock washers removed in Step 9. The bug screen should be at the bottom of the curb. The top outlet sides must slide under the top outlet box sides. NOTE: The outside curb will need to be compressed slightly to get the bolts started. Clamps or pliers may be needed to compress the rear seal to align the bolt holes. It is necessary for the seal to be under 7960-689D Page 7 of 18 FIGURE 11 Wall Mounting Instructions WALL STRUCTURE SUPPLY AIR OPENING SUPPLY AIR OPENING SUPPLY AIR DUCT RETURN AIR OPENING RETURN AIR OPENING RETURN AIR OPENING WOOD OR STEEL SIDING CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION SIDE VIEW MIS-3280 FIGURE 12 Wall Mounting Instructions SEE APPLICABLE CURB DIMENSIONS, FIGURE 2, A-D, FOR ACTUAL DIMENSIONS. ATTACH TO TOP PLATE OF WALL F + 1.000 B D 1.000" CLEARANCE ALL AROUND DUCT INTERIOR FINISHED WALL OVER FRAME SUPPLY DUCT OPENING B E RETURN DUCT OPENING G EXTERIOR FINISH WALL OVER FRAME MIS-3281 7960-689D Page 8 of 18 FRAMING MATERIAL 4 x 4'S, 2 x 4'S, 2 x 6'S &/OR STRUCTURAL STEEL ATTACH TO BOTTOM PLATE OF WALL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS. FIGURE 13 Electric Heat Clearance SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3' of ducting. It is important to ensure that the 1/4" minimum spacing is maintained at all points. Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death. 7960-689D Page 9 of 18 7960-689D Page 10 of 18 E 12" 12" 12" 12" 12" D 28" Return Opening Supply Opening A C E B 14" Wall Opening and Hole Location View C F WALL 6 4 5/8 4 7/16 D REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM 29 7/8 9 7/8 COMBUSTIBLE MATERIALS C 5 3/8 3 11/16 5 3/4 B REQUIRED DIMENSIONS TO MAINTAIN 28 3/8 8 3/8 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS A 39 1/8 39 1/8 F 14 14 G Right Side View NOTES: 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE MIS-3276 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING SUPPLY AIR DUCT FOAM AIR SEAL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 14 TCURBF2430 Supply and Return Openings 7960-689D Page 11 of 18 D E C 4 1/2 14" E B WALL 4 9/16 16 7/8 5 1/4 3 13/16 5 3/4 C Wall Opening and Hole Location View 28" 12" 12" Return Opening Supply Opening A F 12" 12" 12" D C 10 REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS 30 8 1/2 B REQUIRED DIMENSIONS TO MAINTAIN 28 1/2 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS A 39 1/8 39 1/8 F 14 14 G Right Side View NOTES: MIS-3277 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING SUPPLY AIR DUCT 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE FOAM AIR SEAL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 15 TCURBT2430, TFCF-32A and TFCT-32A Supply and Return Openings 7960-689D Page 12 of 18 12" 12" 12" 12" 12" D 28" Return Opening Supply Opening A 12 C D E 16" E B 2 WALL 29 1 1/4 29 3/4 Wall Opening and Hole Location View C F 32 5 1/2 C REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS B 6 1/4 A REQUIRED DIMENSIONS TO MAINTAIN 30 1/2 10 1/2 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS 43 43 F 16 16 G Right Side View NOTES: MIS-3278 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING SUPPLY AIR DUCT 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE FOAM AIR SEAL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 16 TCURBT3642A and TCURBT4860A Supply and Return Openings 7960-689D Page 13 of 18 12" 12" 12" 12" 12" D 28" Return Opening Supply Opening A C D 16" E B 2 1 1/4 Wall Opening and Hole Location View C F 12 5 1/2 32 REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS C 6 1/4 B REQUIRED DIMENSIONS TO MAINTAIN 30 1/2 10 1/2 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS A WALL 5 5 3/4 E 43 43 F 16 16 G Right Side View NOTES: MIS-3279 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING SUPPLY AIR DUCT 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE FOAM AIR SEAL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 17 TCURBF3642A and TCURBF4860A Supply and Return Openings 7960-689D Page 14 of 18 E 12" 12" 12" 12" 12" D 28" Return Opening Supply Opening A 10 C E B 14" Wall Opening and Hole Location View C F 30 WALL 4 1/2 4 9/16 16 7/8 D REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS C 5 1/4 3 13/16 5 3/4 B REQUIRED DIMENSIONS TO MAINTAIN 28 1/2 8 1/2 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS A 39 1/8 39 1/8 F 14 14 G Right Side View NOTES: 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE MIS-3840 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING SUPPLY AIR DUCT FOAM AIR SEAL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 18 TFCF-53A Supply and Return Openings 7960-689D Page 15 of 18 12" 12" 12" 12" 12" D F 28" Return Opening Supply Opening A D E C 4 1/2 39 1/8 F 16" E B WALL 4 9/16 16 7/8 39 1/8 5 1/4 3 13/16 5 3/4 C Wall Opening and Hole Location View C 10 30 REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS B 8 1/2 A REQUIRED DIMENSIONS TO MAINTAIN 28 1/2 1/4" MIN. CLEARANCE FROM COMBUSTIBLE MATERIALS 14 14 G Right Side View NOTES: MIS-3841 IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION. RETURN AIR OPENING 1/4" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS WALL STRUCTURE FOAM AIR SEAL SUPPLY AIR DUCT SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 19 TFCT-53A Supply and Return Openings FIGURE 20 Fastening Unit to Curb 5 4 3 INNER CURB 6 7 CAULK THIS SURFACE 8 1 OUTER CURB 2 MIS-3086 7960-689D Page 16 of 18 FIGURE 21 Sealing with Caulk Seal with (2) beads of caulking along entire length of top and 2" down sides. Wall 22 11/32" 9 5/16" 1/4" Minimum distance required. 1" Recommended. Supply Air Duct Return Air Duct It is recommended that a bead of silicone caulking be placed behind the inner curb mounting flanges at time of installation. MIS-3274 7960-689D Page 17 of 18 FIGURE 22 Sealing with Caulk (Top Outlet Curb) Seal with (2) beads of caulking along entire length of top and 2" down sides. Wall Supply Air Duct 24" 22 3/8" 1/4" Minimum distance required. 1" Recommended. 9 3/8" Return Air Duct It is recommended that a bead of silicone caulking be placed behind the inner curb mounting flanges at time of installation. MIS-3275 7960-689D Page 18 of 18