Preview only show first 10 pages with watermark. For full document please download

8 Ton Submmy0964ht9ul 208-230v

   EMBED


Share

Transcript

SMMSi Single VRF Heat Pump Outdoor Unit HFGTYUT Model: MMY – MAP0964HT9UL Submittal Data Unit – (s) #: SMMSi VRF Heat Pump Features • • • • • • • • • • • 6, 8, and 10 Ton modules available Modules have 2 or 3 inverter - driven, twin Rotary compressors Backup capability due to the multiple compressors Compressor speed is varied in increments of 0.1 Hz for comfort and efficiency Direct drive, inverter - driven outdoor motor with 64 steps Modules can be twinned to form larger systems up to 20 Tons 985 ft. (300 m) actual total system piping (liquid line) 590 ft. (180 m) actual piping length from outdoor unit to furthest fan coil Up to 330 ft. (100 m) outdoor control wiring Up to 6560 ft. (2000 m) control wiring between the outdoor and indoor units Operating temperature range: o Cooling operating range DB: 23°F (-5°C) - 109°F (42.8°C) o Heating operating range WB: 5°F (-15°C) - 60°F (15.6°C) • Protection: High-pressure switch, Low-pressure sensor & switch, PC board fuse, inverter overload protection • 7 Years limited compressor warranty, 1 Year limited parts warranty System Header Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MMY-MAP0964HT9UL Nominal Cooling Capacity (Btu/h) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96,000 Physical Characteristics External Finish. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Munsell 1Y8.5/0.5 Physical Dimensions Nominal Heating Capacity (Btu/h). . . . . . . . . . . . . . . . . . . . . . . . . . . . .108,000 Inches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 7/8 H x 47 9/16 W x 30 11/16 D Maximum Total Connected Indoor Unit Capacity. . . . . . . . . . . . . . .Up to 125% mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1851.7 H x 1209.0 W x 779.8 D Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 742 lbs. / 336.6 kg Cooling Efficiency* EER / IEER (Ducted FCU's) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.10 / 17.50 Fan System EER / IEER (Ductless FCU's) . . . . . . . . . . . . . . . . . . . . . . . . . . .11.00 / 18.10 Type x Quantity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Propeller x 1 EER / IEER (Ducted plus Ductless FCU's). . . . . . . . . . . . . . . . . .11.05 / 17.80 Airflow Rate CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,600 Motor Type x Steps . . . . . . . . . . . . . . . . . . . . . . . . Inverter Direct Driven x 64 Heating Efficiency* COP @ 47°F / 17°F (Ducted FCU's) . . . . . . . . . . . . . . . . . . . . . . . . 3.30 / 2.42 Motor Output kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.0 External Static Pressure (In WG)** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.20 COP @ 47°F / 17°F (Ductless FCU's). . . . . . . . . . . . . . . . . . . . . . . 3.30 / 2.35 COP @ 47°F / 17°F (Ducted plus Ductless FCU's). . . . . . . . . . . . . 3.30 / 2.39 Refrigerant / Piping Connections Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R–410 A Electrical Factory Charge *** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25.4 lbs / 11.5 kg Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 / 230V, 3-Phase, 60Hz Liquid (High Pressure). . . . . . . . . . . . . . . . . . . . . . . . . . .1/2" / 12.7 mm (Flare) Minimum Circuit Amps (MCA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 A Suction (Low Pressure). . . . . . . . . . . . . . . . . . . . . . . . .7/8" / 22.2 mm (Brazed) Maximum Over Current Protection (MOCP) . . . . . . . . . . . . . . . . . . . . . . . 60 A Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3/8" / 9.5 mm (Flare) Compressors Number x Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 x Inverter Twin Rotary Sound Pressure Levels Cooling / Heating dB(A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 / 62 Motor Output kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 2.1 * Rated Per AHRI 1230 Standard Cooling: Indoor 80°F (35°C) DB / 67°F (27°C) WB, Outdoor 95°F (35°C) DB Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB ** Requires setting by dip switches *** Additional charge required DIMENSIONAL DRAWING - OUTDOOR UNIT To outdoor flange Spacing between anchor bolt holes NOTES: 1. A minimum clearance of 78.7” (2000 mm) is required above the unit. 2. Any wall or barrier should not exceed 31.5” (800 mm) from the bottom of the unit. 3. If the interconnecting pipe exits the front of outdoor unit, it must extend at least a minimum of 19.7” (500 mm) before it can turn 90o in either left or right direction. Spacing between anchor bolt holes Heat Pump / Single Unit Model: MMY--MAP0964HT6UL, MAP0964HT9UL Spacing between anchor bolt holes (Slot) 72.9" Spacing between anchor bolt holes Cut length of L-shape pipe Knockout for piping/wiring Knockout for piping (Plan view) Liquid service valve connection port Discharge gas service valve conn. port Balance service valve connection port Square hole (for rigging) Copyright 2014 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 10/14 Edition Date: 02/14 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No:SUBMMY0964HT9UL---01 02 Replaces: NEW Replace: SUBMMY0964HT9UL-01