Runtime Charts For Eaton 93PS 8-40kW UPS
93PS UPS on‐battery runtimes with different load ratings
Content Internal batteries for 8‐20kVA ‐ Small Frame
2
5-year internal battery (9Ah) 10-year internal battery (7Ah)
2 2
Internal batteries for 8‐40kVA ‐ Large Frame
3
5-year internal battery (9Ah) 10-year internal battery (7Ah)
3 4
External batteries ‐ Small battery cabinet
5
5-year battery (9Ah) in Small Battery Cabinet 10-year battery (7Ah) in Small Battery Cabinet
5 5
External batteries ‐ Large battery cabinet
6
10-year battery (CSB HRL12200W) in Large Battery Cabinet
6
External batteries with internal batteries ‐ Small Frame
7
9Ah 5-year internal and external battery
7
External batteries with internal batteries ‐ Large Frame
8
CSB HRL12200W with 9Ah 5-year battery CSB HRL12200W with 7Ah 10-year battery
8
Page 1 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
Internal batteries for 8‐20kVA ‐ Small Frame 5‐year internal battery (9Ah) Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 0.8: Battery 9Ah 12V 9Ah 12V
Qty 1x32 2x32
8kVA 14 33
10kVA 10 25
15kVA ‐ 15
20kVA ‐ 10
min min
Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 0.9: Battery 9Ah 12V 9Ah 12V
Qty 1x32 2x32
8kVA 12 28
10kVA 8 22
15kVA ‐ 13
20kVA ‐ 8
min min
Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 1.0: Battery 9Ah 12V 9Ah 12V
Qty 1x32 2x32
8kVA 10 25
10kVA 7 19
15kVA ‐ 11
20kVA ‐ 7
min min
10‐year internal battery (7Ah) Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 0.8: Battery 7Ah 12V 7Ah 12V
Qty 1x32 2x32
8kVA 10 30
10kVA 7 22
15kVA ‐ 12
20kVA ‐ 7
min min
Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 0.9: Battery 7Ah 12V 7Ah 12V
Qty 1x32 2x32
8kVA 9 26
10kVA 5 18
15kVA ‐ 9
20kVA ‐ 5
min min
Internal battery back‐up table for UPS ratings 8‐20 kVA (small frame), p.f. 1.0: Battery 7Ah 12V 7Ah 12V
Qty 1x32 2x32
8kVA 7 22
10kVA ‐ 15
15kVA ‐ 8
20kVA ‐ ‐
min min
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 2 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
Internal batteries for 8‐40kVA ‐ Large Frame 5‐year internal battery (9Ah) Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 0.8: Battery 9Ah 12V 9Ah 12V 9Ah 12V 9Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 14 33 55 77
10kVA 10 25 42 59
15kVA ‐ 15 25 36
20kVA ‐ 10 17 25
30kVA ‐ ‐ 10 15
40kVA ‐ ‐ 6 10
min min min min
30kVA ‐ ‐ 8 13
40kVA ‐ ‐ ‐ 8
min min min min
30kVA ‐ ‐ 7 11
40kVA ‐ ‐ ‐ 7
min min min min
Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 0.9: Battery 9Ah 12V 9Ah 12V 9Ah 12V 9Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 12 28 47 68
10kVA 8 22 36 51
15kVA ‐ 13 22 30
20kVA ‐ 8 15 22
Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 1.0: Battery 9Ah 12V 9Ah 12V 9Ah 12V 9Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 10 25 42 59
10kVA 7 19 31 44
15kVA ‐ 11 19 27
20kVA ‐ 7 13 19
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 3 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
10‐year internal battery (7Ah) Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 0.8: Battery 7Ah 12V 7Ah 12V 7Ah 12V 7Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 10 30 49 70
10kVA 7 22 38 53
15kVA ‐ 12 22 33
20kVA ‐ 7 14 22
30kVA ‐ ‐ 7 12
40kVA ‐ ‐ ‐ 7
min min min min
30kVA ‐ ‐ 5 9
40kVA ‐ ‐ ‐ 5
min min min min
30kVA ‐ ‐ ‐ 8
40kVA ‐ ‐ ‐ ‐
min min min min
Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 0.9: Battery 7Ah 12V 7Ah 12V 7Ah 12V 7Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 9 26 43 60
10kVA 5 18 33 45
15kVA ‐ 9 18 28
20kVA ‐ 5 12 18
Internal battery back‐up table for UPS ratings 8‐40 kVA (large frame), p.f. 1.0: Battery 7Ah 12V 7Ah 12V 7Ah 12V 7Ah 12V
Qty 1x32 2x32 3x32 4x32
8kVA 7 22 38 53
10kVA ‐ 15 28 41
15kVA ‐ 8 15 24
20kVA ‐ ‐ 10 15
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 4 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
External batteries ‐ Small battery cabinet 5‐year battery (9Ah) in Small Battery Cabinet External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Battery 9Ah 12V 9Ah 12V
Qty 2x32 3x32
8kVA 33 55
10kVA 25 42
15kVA 15 25
20kVA 10 17
30kVA ‐ 10
40kVA ‐ 6
min min
20kVA 8 15
30kVA ‐ 8
40kVA ‐ ‐
min min
20kVA 7 13
30kVA ‐ 7
40kVA ‐ ‐
min min
20kVA 7 14
30kVA ‐ 7
40kVA ‐ ‐
min min
20kVA 5 12
30kVA ‐ 5
40kVA ‐ ‐
min min
20kVA ‐ 10
30kVA ‐ ‐
40kVA ‐ ‐
min min
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Battery 9Ah 12V 9Ah 12V
Qty 2x32 3x32
8kVA 28 47
10kVA 22 36
15kVA 13 22
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Battery 9Ah 12V 9Ah 12V
Qty 2x32 3x32
8kVA 25 42
10kVA 19 31
15kVA 11 19
10‐year battery (7Ah) in Small Battery Cabinet External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Battery 7Ah 12V 7Ah 12V
Qty 2x32 3x32
8kVA 30 49
10kVA 22 38
15kVA 12 22
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Battery 7Ah 12V 7Ah 12V
Qty 2x32 3x32
8kVA 26 43
10kVA 18 33
15kVA 9 18
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Battery 7Ah 12V 7Ah 12V
Qty 2x32 3x32
8kVA 22 38
10kVA 15 28
15kVA 8 15
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 5 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
External batteries ‐ Large battery cabinet 10‐year battery (CSB HRL12200W) in Large Battery Cabinet External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Battery 200W 12V
Qty 1x32
8kVA 126
10kVA 107
15kVA 72
20kVA 48
30kVA 29
40kVA 19
min
20kVA 42
30kVA 25
40kVA 17
min
20kVA 37
30kVA 21
40kVA 14
min
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Battery 200W 12V
Qty 1x32
8kVA 114
10kVA 97
15kVA 60
External battery back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Battery 200W 12V
Qty 1x32
8kVA 107
10kVA 88
15kVA 52
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 6 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
External batteries with internal batteries ‐ Small Frame 9Ah 5‐year internal and external battery External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Internal battery Battery Qty 9Ah 12V 2x32 9Ah 12V 2x32
External battery Battery Qty 9Ah 12V 2x32 9Ah 12V 3x32
8kVA 77 94
10kVA 59 77
15kVA 36 47
20kVA 25 32
min min
20kVA 22 28
min min
20kVA 19 25
min min
20kVA 22 30
min min
20kVA 18 26
min min
20kVA 15 22
min min
External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Internal battery Battery Qty 9Ah 12V 2x32 9Ah 12V 2x32
External battery Battery Qty 9Ah 12V 2x32 9Ah 12V 3x32
8kVA 67 84
10kVA 51 67
15kVA 30 41
External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Internal battery Battery Qty 9Ah 12V 2x32 9Ah 12V 2x32
External battery Battery Qty 9Ah 12V 2x32 9Ah 12V 3x32
8kVA 59 77
10kVA 44 59
15kVA 27 36
7Ah 10‐year internal and external battery External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Internal battery Battery Qty 7Ah 12V 2x32 7Ah 12V 2x32
External battery Battery Qty 7Ah 12V 2x32 7Ah 12V 3x32
8kVA 70 86
10kVA 53 70
15kVA 33 43
External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Internal battery Battery Qty 7Ah 12V 2x32 7Ah 12V 2x32
External battery Battery Qty 7Ah 12V 2x32 7Ah 12V 3x32
8kVA 60 78
10kVA 45 60
15kVA 28 38
External battery and 2 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Internal battery Battery Qty 7Ah 12V 2x32 7Ah 12V 2x32
External battery Battery Qty 7Ah 12V 2x32 7Ah 12V 3x32
8kVA 53 70
10kVA 41 53
15kVA 24 33
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.
Page 7 of 8
Runtime Charts For Eaton 93PS 8-40kW UPS
External batteries with internal batteries ‐ Large Frame CSB HRL12200W with 9Ah 5‐year battery External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Internal battery Battery Qty 9Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 235
10kVA 185
15kVA 115
20kVA 86
30kVA 53
40kVA 36 min
20kVA 76
30kVA 45
40kVA 30 min
20kVA 66
30kVA 40
40kVA 27 min
20kVA 83
30kVA 51
40kVA 35 min
20kVA 73
30kVA 43
40kVA 29 min
20kVA 63
30kVA 38
40kVA 26 min
External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Internal battery Battery Qty 9Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 210
10kVA 165
15kVA 103
External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Internal battery Battery Qty 9Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 185
10kVA 146
15kVA 91
CSB HRL12200W with 7Ah 10‐year battery External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.8: Internal battery Battery Qty 7Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 229
10kVA 178
15kVA 112
External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 0.9: Internal battery Battery Qty 7Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 203
10kVA 159
15kVA 99
External battery and 4 internal strings back‐up table for UPS ratings 8‐40 kVA, p.f. 1.0: Internal battery Battery Qty 7Ah 12V 4x32
External battery Battery Qty 200W 12V 1x32
8kVA 178
10kVA 140
15kVA 88
Note! The specifications are subject to change without a notice. The battery backup tables are given with end voltage 1.70 VPC and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles.