Transcript
Premolded screened separable cable connectors CSE-A 12–24 kV, 250 A CSS-A 12–24 kV, 250 A
Fits standard bushings of outer cone type according to EN 50181. Connector with rated current: − 250 A: Interface A with plug-in Ø 7.9 mm. CSE-A 12250 CSE-A 24250
Standard Meets the requirements of: − CENELEC, HD 629.1 S2
CSS-A 12250 CSS-A 24250
Dimensions in mm.
Design CSE-A and CSS-A are manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer, that are vulcanized together for the best possible interface between the layers.
Ø 63
C-C 70 min
124
29
Ø 58 211
The cable connectors include both a capacitive test point with protection and an integrated earthing wire. − Delivered in 3-phase kits, complete with cable lugs, bolt connection and stress grading adapter, designed to ensure a reliable installation.
CSE-A 250 A, 12–24 kV C-C 80 min
Note: − For 3-core cable with common copper screen wires, a screen separation kit or a branch seal kit must be used. To be ordered separately.
66
Ø 65 263
Always select products by cable insulation diameter. Voltage
Insulation diameter
kV
mm
Conductor Designation cross section mm²
Weight
CSS-A 250 A, 12–24 kV
kg/unit
Elbow cable connector
C 2x45°
10–16
CSE-A 12250-01
2.2
12
13–22
25–95
CSE-A 12250-02
2.2
24
13–22
10–16
CSE-A 24250-01
2.2
24
17–25.5
25–95
CSE-A 24250-02
2.2
48
9
Straight cable connector 12
10–12
10–16
CSS-A 12250-01
2.2
12
13–22
25–95
CSS-A 12250-02
2.2
24
13–22
10–16
CSS-A 24250 01
2.2
24
17–25.5
25–95
CSS-A 24250 02
2.2
Elbow cable connector complete with screen separation kit 12
10–12
10–16
CSE-A 12250-01 P
5.5
12
13–22
25–95
CSE-A 12250-02 P
5.5
24
13–22
10–16
CSE-A 24250-01 P
5.5
24
17–25,5
50–95
CSE-A 24250-02 P
6.1
2/19 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
R3
R1
Ø 31 Ø 32.5
10–12
Ø 90 Ø 48.5
12
1
2
Application areas Premolded screened separable connectors for XLPEand EPR-insulated 1- or 3-core cables with Al- or Cuconductors for 12–24 kV. Can be installed both indoors and outdoors.
3.5 Bail holder
Ø4 Standard bushing EN 50181 Interface A, 250 A Contact type: Plug-in approx. Ø 7.9 mm
Premolded screened separable connector for cables with Cu-tape screen CSE-A 12–24 kV, 250 A Application areas Premolded screened separable connectors for XLPE- and EPR-insulated 1- or 3-core 12–24 kV cables with Al- or Cu-conductors with copper tape screens, with or without aluminium or steel wire armouring. Can be installed both indoors and outdoors.
2
Fits standard bushings of outer cone type according to EN 50181. Connector with rated current: − 250 A: Interface A with plug-in Ø 7.9 mm. CSE-A 12250 CSE-A 24250
Standard Meets the requirements of: − CENELEC, HD 629.1 S2
Dimensions in mm.
Design CSE-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer, that are vulcanized together for the best possible interface between the layers. The cable connectors include both a capacitive test point with protection and an integrated earthing wire.
Ø 63
C-C 70 min
124
29
Ø 58 211
Delivered in 3-phase kits, complete with cable lugs, bolt connection, earthing kit and stress grading adapters. The adapters are designed to ensure a reliable installation.
CSE-A 250 A, 12–24 kV
For 3-core cables, a branch seal kit is included.
Always select products by cable insulation diameter.
mm mm² connector, 3 x 1-core 13–22 25–95 19–25.5 35–95 connector, 3-core 13–22 25–50 13–22 70–95 19–25.5 35–95
Designation
CSE-A 12250-02 R CSE-A 24250-02 S
Outer sheath diameter
Weight
mm
kg/unit
– –
2.7 2.7
C 2x45°
CSE-A 12250-02 RA CSE-A 12250-02 RB CSE-A 24250-02 SB
31–50 44–70 47–70
R3
R1
2.9 2.9 2.9
Ø 31 Ø 32.5
kV Elbow cable 12 24 Elbow cable 12 12 24
Conductor cross section
Ø 90 Ø 48.5
Insulation diameter
9 1
Voltage
48 3.5 Bail holder
Ø4 Standard bushing EN 50181 Interface A, 250 A Contact type: Plug-in approx. Ø 7,9 mm
| Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/20
Accessories, to be ordered separately CSE-A and CSS-A 12–24 kV, 250 A
2
IH-A 24250 Insulating hood of flexible rubber with outer conductive layer and a preinstalled insulating rod. To be mounted on the bushing in a switchgear or a transformer 250 A to insulate it when a cable is temporarily disconnected but other cables are energized.
PSSK Screen separation kit to achieve a metallic screen on each core for 3-core cables.
JP 250 Earth circuit connector for short-circuit protective earthing. For mounting on the disconnected connector CSE-A for 250 A.
IP 250 Screened insulating plug for installation in the connector so that the cable can be energized even when disconnected from the switchgear or transformer 250 A.
TSH Branch seal kit to achieve a sealing on each core for 3-core cables.
CU 250 Coupling piece to connect two connectors.
PC 630/250 Parallel coupling piece. Replaces the plug in CSE-A 630 A when making a parallel connection to CSE-A 250 A. Delivered in 3-phase kits and hex bit socket.
MA 250 Measurement adapter used for mega ohm Ω measurements and to perform different measurements up to 5 kV DC, for example determination of phases, 250 A.
Designation Description
Qty. per kit
Weight
See page
kg/kit
IH-A 24250
Insulating hood, 12–24 kV, 250 A
3
2.3
2/21
IP 250
Screened insulating plug, 250 A
1
0,8
2/21
PSSK
Screen separation kit, heat-shrink for 3-core cable
1
1.0–1.1
2/47
TSH
Branch seal kit
1
0.3–1.0
2/48
PC 630/250
Parallel coupling piece
3
3.0
2/21
JP 250
Earthing device, 250 A
1
2.7
2/21
CU 250
Coupling piece between two cable connectors, 250 A
1
0.2
2/21
MA 250
Measurement adapter, 250 A
1
0.3
2/21
2/21 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
Premolded screened separable cable connector CSE-A 12–42 kV, 400 A
Application areas Premolded screened separable connector for XLPEand EPR-insulated 1- or 3-core cables with Al- or Cuconductors for 12–42 kV. Can be installed both indoors and outdoors.
2
Fits standard bushings of outer cone type according to EN 50181. Connector with rated current: − 400 A: series 400 interface type B with plug-in Ø 14 mm. CSE-A 12400
CSE-A 24400
Standard Meets the requirements of: − CENELEC, HD 629.1 S2
Dimensions in mm.
Ø 80
Design CSE-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer, that are vulcanized together for the best possible interface between the layers.
C-C 85 min
173
34
Ø 72 256
The cable connector includes both a capacitive test point with protection and an integrated earthing wire. − Delivered in 3-phase kits complete with cable lugs, bolt connection and stress grading adapter, designed to ensure a reliable installation.
CSE-A 400 A, 12–24 kV
Note: − For 3-core cables with common Cu-screen wires, a screen separation kit or a branch seal kit must be used. To be ordered separately.
Ø 80
C-C 85 min
195
34
Ø 74 284
Always select products by cable insulation diameter.
Conductor cross section
kV
mm
mm²
Designation
Rated current
Weight
A
kg/unit 6.1
12
13–20
25–70
CSE-A 12400-01
400
12
18.5–30.5
95–300
CSE-A 12400-02
400
6.6
24
17–24
25–70
CSE-A 24400-01
400
6.1
24
22.5–35
95–300
CSE-A 24400-02
400
6.6
36
24.5–34
50-95
CSE-A 36400-01
400
6.1
36
27.5–42
95-300
CSE-A 36400-02
400
6.6
42
24.5–34
50–70
CSE-A 42400-01
400
6.1
42
27.5–42
95–300
CSE-A 42400-02
400
6.6
R3 R3
40
R3 Ø 46 Ø 56
Insulation diameter
Ø 102 Ø 70
Voltage
CSE-A 400 A, 36–42 kV
90 5.5 Bail holder
11
Standard bushing EN 50181 Interface B, 400 A Contact type: Plug-in Ø14
| Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/22
Accessories, to be ordered separately CSE-A 12–42 kV, 400 A
2
IH-A 24400, 42400 Insulating hood, of flexible rubber with outer conductive layer and a preinstalled insulating rod. To be mounted on the bushing in a switchgear or a transformer 400 A to insulate it when a cable is temporarily disconnected but other cables are energized.
IP 400 Screened insulating plug for installation in the connector so that the cable can be energized even when disconnected from the switchgear or transformer 400 A.
PSSK Screen separation kit to achieve a metallic screen on each core for 3-core cable.
TSH Branch seal kit to achieve a sealing on each core for 3-core cable.
Designation Description
Qty. per kit
Weight
See page
kg/kit
IH-A 24400
Insulating hood, 12–24 kV, 400 A
3
5.2
2/23
IH-A 42400
Insulating hood, 36-42 kV, 400 A
3
5.5
2/23
IP 400
Screened insulating plug, 400 A
1
2.2
2/23
PSSK
Screen separation kit, heat-shrink for 3-core cable
1
1.0–1.1
2/47
TSH
Branch seal
1
0.3–1.0
2/48
2/23 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
Premolded screened separable cable connector CSE-A 12–42 kV, 630 A
Application areas Premolded screened separable connector for XLPEand EPR-insulated 1- or 3-core cables with Al- or Cu-conductors for 12–42 kV. Can be installed both indoors and outdoors.
2
Fits standard bushings of outer cone type according to EN 50181. Connector with rated current: − 630 A: Interface C1 with bolt M16. − 1250 A: Interface C2 with bolt M16. CSE-A 12630, CSE-A 24630
Standard Meets the requirements of: − CENELEC, HD 629.1 S2
CSE-A 36630, CSE-A 42630 Ø 81
Dimensions in mm.
C-C 85 min
172
Design CSE-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer, that are vulcanized together for the best possible interface between the layers.
Ø 72 256
29 1.5
Ø 70
− Delivered in 3-phase kits, complete with cable lugs, bolt connection and stress grading adapter, designed to ensure a reliable installation.
CSE-A 630 A, 12–24 kV, sizes 1–2 R3 Ø 46 Ø 56
R3 R3
The cable connector includes both a capacitive test point with protection and an integrated earthing wire.
11
Ø 85
90 314
CSE-A 630 A, 12–24 kV, size 3
Ø 81
Conductor cross section
Designation
kV mm mm² 12 13–20 25–70 CSE-A 12630-01 12 18.5–30.5 95–300 CSE-A 12630-02 12 30.5–45 400–630 CSE-A 12630-03 24 17–24 25–70 CSE-A 24630-01 24 22.5–35 95–300 CSE-A 24630-02 24 30.5–45 400–630 CSE-A 24630-03 36 24.5–34 50-95 CSE-A 36630-01 36 27.5–42 95-300 CSE-A 36630-02 36 38.0–55 400-630 CSE-A 36630-03 42 24.5–34 50–70 CSE-A 42630-01 42 27.5–42 95–300 CSE-A 42630-02 42 38–55 400–630 CSE-A 42630-03 Cable connector complete with screen separation kit 12 13–20 25–70 CSE-A 12630-01 12 18.5–30.5 95–300 CSE-A 12630-02 24 17-24 50–70 CSE-A 24630-01 24 22.5–35 95–300 CSE-A 24630-02 36 23–34 50–95 CSE-A 36630-01 36 27.5–42 95–300 CSE-A 36630-02
9
180
90
Always select products by cable insulation diameter. Insulation diameter
C-C 90 min
Standard bushing EN 50181 Interface: C1, 630 A Interface: C2, 1250 A Contact type: Bolt M16
Note: − For 3-core cables with common Cu-screen wires, a screen separation kit or a branch seal kit must be used. To be ordered separately.
Voltage
9
C-C 85 min
194
9
Weight kg/unit 5.1 5.5 7.7 5.1 5.5 7.7 6.1 6.6 8.7 6.1 6.6 8.7 P P P P P P
8.4 9.4 9 9.4 10 1.4
Ø 74 283
CSE-A 630 A, 36–42 kV sizes 1–2.
Ø 85
C-C 90 min
202
9
90 314
CSE-A 630 A, 36–42 kV size 3. | Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/24
Premolded screened separable cable connector for cables with copper tape screen CSE-A 12–36 kV, 630 A
2
Application areas Premolded screened separable connector for XLPE- and EPR-insulated 1- or 3-core 12–36 kV cables, with Al- or Cuconductors with Cu-tape screens, with or without aluminium or steel wire armouring. Can be installed both indoors and outdoors. Fits standard bushings of outer cone type according to EN 50181. Connectors with rated current: − 630 A: Interface type C1 with bolt M16. − 1250 A: Interface type C2 with bolt M16.
CSE-A 12630 / CSE-A 24630
Standard Meets the requirements of: − CENELEC, HD 629.1 S2
CSE-A 36630
Dimensions in mm. Ø 81
Design CSE-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer, that are vulcanized together for the best possible interface between the layers. The cable connector includes both a capacitive test point with protection and an integrated earthing wire.
C-C 85 min
172
9
Ø 72 256
CSE-A 630 A, 12–24 kV, sizes 1–2
− Delivered in 3-phase kits, complete with cable lugs, bolt connection, earthing kit and stress grading adapters. The adapters are designed to ensure a reliable installation. For 3-core cables, a branch seal kit is included.
Ø 85
C-C 90 min
9
180
90 314
Always select products by cable insulation diameter. Voltage
Insulation diameter
Conductor cross section
kV
mm
mm²
Outer sheath Designation diameter
Elbow cble connectors, 3 x 1-core cables 12 13–20 25–70 12 19–29 95–300 12 30.5–37 400 24 19–24 35–70 24 25–35 95–300 24 30.5–37 400 36 19–29 50–70 36 27.5–37 95–300 36 38–50 400
Weight
mm – – – – – – – – –
Elbow cable connectors, 3-core cables 12 13–20 25–70 31–50 12 19–29 95–185 47–70 12 25–30.5 240–300 58–94 12 30.5–37 400 58–94 24 19–24 35–70 47–70 24 25–35 95–300 58–94 24 30.5–37 400 65–110 36 19–29 50–95 58–94 36 27.5–37 95–300 65–110
kg/unit CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A
12630-01 R 12630-02 S 12630-03 T 24630-01 S 24630-02 T 24630-03 T 36630-01 S 36630-02 T 36630-03 U
5.6 6.0 8.2 5.6 6.0 8.2 6.8 7.3 9.4
CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A CSE-A
12630-01 12630-02 12630-02 12630-03 24630-01 24630-02 24630-03 36630-01 36630-02
5.8 6.2 6.2 8.4 5.8 6.2 8.4 6.8 7.3
2/25 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
RA SB TB TB SB TB TB SB TB
CSE-A 630 A, 12–24 kV, size 3
Ø 81
C-C 85 min
194
9
Ø 74 283
CSE-A 630 A, 36–42 kV sizes 1–2.
Ø 85
C-C 90 min
202
9
90 314
CSE-A 630 A, 36–42 kV size 3.
Accessories, to be ordered separately CSE-A 12–42 kV, 630 A
2
IH-A 24630, IH 42630 Insulating hood, of flexible rubber with outer conductive layer and a preinstalled insulating rod. To be mounted on the bushing in a switchgear or a transformer 630 A to insulate it when a cable is temporarily disconnected but other cables are energized.
PSSK Screen separation kit to achieve a metallic screen on each core for 3-core cable.
CSAP-A Surge arrestor, 630 A.
CSEP-A Parallel cable connector.
JPB 630 Universal earthing device with two fields of application for 630 A and 12-42 kV: − As earthing-for-work device mounted at the back of a connected cable connector CSE-A for 630 A. − As short-circuit protective earthing mounted in front of a disconnected cable connector CSE-A for 630 A.
IP 630 Screened insulating plug for installation in the connector so that the cable can be energized even when disconnected from the switchgear or transformer 630 A.
TSH Branch seal kit to achieve a sealing on each core for 3-core cable.
PG 630 Bushing for voltage testing.
PC 630/250 Parallel coupling piece. Replaces the plug in CSE-A 630 A when making a parallel connection to CSE-A 250 A. Delivered in 3-phase kits and hex bit socket.
MA-A 630 Measurement adapter used for mega ohm Ω measurements and to perform different measurements up to 5 kV DC, for example determination of phases, 630 A.
PG-A 630 Bushing for voltage testing, 36–42 kV.
Designation Description IH-A 24630 IH-A 42630 IP 630 PC 630/250 PSSK TSH MA-A 630 CSAP-A PG 630 PG-A 630 CSEP-A JPB 630 JPA V
Insulating hood, 12–24 kV, 630 A Insulating hood, 36-42 kV, 630 A Screened insulating plug, 630 A Parallel coupling piece Screen separation kit, heat-shrink for 3-core cable Branch seal Measurement adapter, 630 A Surge arrestor, 630 A, 12–24 kV Bushing for voltage testing, 630 A, 12–24 kV Bushing for voltage testing, 630 A, 36–42 kV Parallel cable connector Earthing device, 630 A Tool for earthing-for-work device, JPB 630
Qty. per kit 3 3 1 3 1 1 3 1 1 1 1 1 1
Weight
See page
kg/kit 5.2 5,5 2.2 3.0 1.0–1.1 0.3–1.0 0.2 3.6–5.0 1.5 2.0 5.7–9.8 5.0 1.8
2/26 2/26 2/26 2/26 2/47 2/48 2/26 2/28 2/26 2/26 2/27 2/26 2/26
JPA V Tool for earthing device, JPB 630.
| Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/26
Parallel separable connector for 630 A cable connector CSEP-A 12–42 kV
2
Application area CSEP-A is a screened separable parallel cable connector designed to be connected to a screened separable cable connector type CSE-A 630. Used with XLPE- och EPRinsulated 1- or 3-core cables with Al- or Cu-conductor for 12–42 kV. Standard − Fulfills the requirements of CENELEC HD 629.1 S2. Design CSEP-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer that are vulcanized together for the best possible interface between the layers.
Dimensions in mm. 100
9
When installing CSEP-A on the CSE-A the plug and the protective cap must be moved from CSE-A to parallel connector CSEP-A. In that way the capacitive test point is re-established.
72
− Delivered in 3-phase kits complete with cable lugs, bolt connections, stress grading adapters and also an integrated earthing wire.
CSEP-A, 12–24 kV sizes 1–2
Always select products by cable insulation diameter.
kV 12 12 12 24 24 24 36 36 36 42 42 42 Parallel 12 12 24 24 36 36
Conductor Insulation cross section diameter mm² mm 25–70 13–20 95–300 18.5–30.5 400–630 30.5–45 25–70 17–24 95–300 22.5–35 400–630 30.5–45 50–95 24.5–34 95–300 27.5–42 400–630 38–55 50–70 24.5–34 95–300 27.5–42 400–630 38–55 connector complete with screen 13–20 25–70 18.5–30.5 95–300 17–24 50–70 22.5–35 95–300 23–34 50–95 27.5–42 95–300
Designation
CSEP-A 12630-01 CSEP-A 12630-02 CSEP-A 12630-03 CSEP-A 24630-01 CSEP-A 24630-02 CSEP-A 24630-03 CSEP-A 36630-01 CSEP-A 36630-02 CSEP-A 36630-03 CSEP-A 42630-01 CSEP-A 42630-02 CSEP-A 42630-03 separation kit CSEP-A 12630-01P CSEP-A 12630-02P CSEP-A 24630-01P CSEP-A 24630-02P CSEP-A 36630-01P CSEP-A 36630-02P
2/27 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
min 85
256
Note: − For 3-core cables with common Cu-screen wires, a screen separation kit or a branch seal kit must be used. For screen separation kit see table at page 3/45.
Voltage
85
114
9
85
min 90
90 314
CSEP-A, 12–24 kV size 3
Weight kg/kit 5.7 6.1 8.6 5.7 6.1 8.6 6.7 7.1 9.8 6.7 7.1 9.8
122
81
9
74 283
CSEP-A, 36–42 kV sizes 1–2 136 9
85
90
9 10 9.6 10 10.6 11.9
min 85
314
CSEP-A, 36–42 kV size 3
min 90
Parallel screened separable connector for cable with copper tape screen, 630 A CSEP-A 12–42 kV Application area CSEP-A is a screened separable parallel connector designed to be connected to a screened separable connector type CSE-A 630. Used with XLPE- and EPR-insulated 1- or 3-core 12–36 kV cables, with Al- or Cu-conductors with copper tape screens, with or without aluminium or steel wire armouring.
2
Standard − Fulfills the requirements of CENELEC HD 629.1 S2. Design CSEP-A is manufactured in rubber with three layers; a conductive inner layer, an insulation layer and a conductive outer layer that are vulcanized together for the best possible interface between the layers. When installing CSEP-A on the CSE-A, the plug and the protective cap must be moved from CSE-A to the parallel connector CSEP-A. In that way the capacitive test point is re-established.
Dimensions in mm. 100
9
81
min 85
72 256
− Delivered in 3-phase kits complete with cable lugs, bolt connections, stress grading adapters and also an integrated earthing wire.
CSEP-A, 12–24 kV sizes 1–2 114
Note: − For 3-core cables with common Cu-tape screen, a screen separation kit or a branch seal kit must be used. See table at page 3/45.
9
85
min 90
90 314
Always select products by cable insulation diameter. CSEP-A, 12–24 kV size 3
Voltage kV Parallel 12 12 12 24 24 24 36 36 36 Parallel 12 12 12 12 24 24 24 36 36
Insulation Conductor diameter cross section mm mm² connector for 3 x 1-core cables 13–20 25–70 18.5–30.5 95–300 30.5–45 400 17–24 35–70 22.5–35 95–300 30.5–45 400 24.5–34 50–70 27.5–42 95–300 38–55 400 connector for 3-core cables 13–20 25–70 18.5–30.5 95–185 18.5–30.5 240–300 30.5–45 400 17–24 35–70 22.5–35 95–300 30.5–45 400 24.5–34 50–95 27.5–42 95–300
Designation
Weight
122
81
9
min 85
kg/kit CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A
12630-01 12630-02 12630-03 24630-01 24630-02 24630-03 36630-01 36630-02 36630-03
R S T S T T S T U
5.8 6.2 8.7 5.8 6.2 8.7 6.8 7.2 9.9
CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A CSEP-A
12630-01 12630-02 12630-02 12630-03 24630-01 24630-02 24630-03 36630-01 36630-02
RA SB TB TB SB TB TB SB TB
5.8 6.2 6.2 8.7 5.8 6.2 8.7 6.8 7.2
74 283
CSEP-A, 36–42 kV sizes 1–2 136 9
85
min 90
90 314
CSEP-A, 36–42 kV size 3
| Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/28
Dimensional drawings – Parallel connection of CSE-A and CSEP-A 12–42 kV – Parallel connection of two CSE-A 12–42 kV Connection of parallel connector type CSEP-A to cable connector type CSE-A meets the requirements according to the standard CENELEC HD 629.1 S2.
2
289
298
286
12–24 kV
278
Dimensions in mm.
97 CSEP-A size 1–2 + CSE-A size 1–2
CSEP-A size 3 + CSE-A size 1–2
CSEP-A size 1–2 + CSE-A size 3
330
324
CSEP-A size 3 + CSE-A size 3 339
36–42 kV
316
109
101
105
113 CSEP-A size 1–2 + CSE-A size 1–2
117
124 CSEP-A size 3 + CSE-A size 1–2
CSEP-A size 1–2 + CSE-A size 3
128 CSEP-A size 3 + CSE-A size 3
Parallel connection of two cable connectors type CSE-A with parallel coupling piece PC 630-3 / PC 630-3 L meets the requirements according to the standard CENELEC HD 629.1 S2. 353
369
397
413
172 194
180 Parallel connection of two CSE-A size 1–2, 12–24 kV
202
Parallel connection of two CSE-A size 1–2, 36 kV
Parallel connection of two CSE-A size 3, 12–24 kV
Accessories, to be ordered separately: Designation Description TSH, SSH Branch seal and additional hoses PSSK Screen separation kit
See page 2/48 2/47
2/29 | 2015 | ABB cable accessories 7.2–42 kV | Product range |
TSH
SSH
PSSK
Parallel connection of two CSE-A size 3, 36 kV
Surge arresters for 630 A separable connector CSAP-A 6–24 kV
Application area CSAP-A is a screened separable surge arrester designed to be connected in parallel with screened separable cable connector type CSE-A 630 A. − Protects electrical components against overvoltage and transients.
2
Standard − Fulfills the requirements of IEC 60099-4. − Parallel connection of surge arrester CSAP-A connected to cable connector CSE-A meets the requirements according to standard CENELEC HD 629.1 S2. Dimensions in mm.
Design CSAP-A includes a premolded body, manufactured in three layers; a conductive inner layer, an insulation layer and a conductive outer layer vulcanized together for the best possible interface between the layers. The surge arrester’s active part is made of metal oxide. The connected earth braid manages short circuit currents according to the standard.
CSAP-A CSAP-A CSAP-A CSAP-A CSAP-A CSAP-A
6/5 kA 6/10 kA 12 5 kA 12 10 kA 24 5 kA 24 10 kA
CSAP-A sizes 12/5 and 12/10
Weight kg/kit 3.6
114
9 mm
min 90
89.5
90
3.6 3.6 4.0 4.6 5.0
360
Explanation of symbols according to IEC 60099-4 Uc Ur Ures In Ihc Is
min 90
266
Delivered in 1-core kits complete with bolt connection, earth braid and also an integrated earthing wire. Designation
89.5
90
When installing CSAP-A on the CSE-A 630, the plug and the protective cap must be moved from CSE-A to the surge arrester CSAP-A. In that way the capacitive test point is re-established.
Voltage kV 6 6 12 12 24 24
9 mm
114
CSAP-A sizes 24/5 and 24/10
continuous operating voltage rms rated voltage rms residual voltage peak at 8/20 μs nominal discharge current 8/20 μs high current impulse 4/10 μs short circuit rating 50 Hz rms for 0.2 s
295
303
Technical data Designation CSAP-A CSAP-A CSAP-A CSAP-A CSAP-A CSAP-A
6/5 kA 6/10 kA 12 5 kA 12 10 kA 24 5 kA 24 10 kA
Uc [kV] 6 6 12 12 24 24
Ur [kV]
15 15 30 30
Ures [kV]
39.1 40 78.2 80
In [kA] 5 10 5 10 5 10
Ihc [kA]
65 100 65 100
Is [kA] 16 16 16 16 16 16
IEC line discharge class – 1 – 1 – 1
CSE-A sizes 1–2 + CSAP-A
CSE-A size 3 + CSAP-A
| Product range | ABB cable accessories 7.2–42 kV | 2015 | 2/30