Preview only show first 10 pages with watermark. For full document please download

Ac Input High Current Transmitters Series T26

   EMBED


Share

Transcript

ACInputHighCurrentTransmitters Precision,LoopPowered SeriesT26 Series T26 represents a new concept for high AC current measurements. The new units combine the reliability of high precision high capacity current-transformers with the proven performance of Mescon's AC input 2-wire transmitters. The T26 offer a coherent industrial solution to current measurement problems of up to 1000A. The output is a linear current loop, 4-20mA which is proportional to the electrical current flowing through the T26 core. A test terminal provides a 40-200mV signal proportional to the 4-20mA output for monitoring and verification of the output without breaking the current loop. An optional integral digital LCD indicator is available for many input ranges to directly display the actual current flow through the T26. SPECIFICATIONS: Input Ranges ............. 0-20A min., 0-50, 0-100, 0-200, 0-500, 0-1000A max. 50/60/ 400Hz Output ....................... 4-20mA loop powered transmitter Zero Suppression ...... to 50% of input range Adjustments .............. > ± 20% for both zero and span Power Supply Range ... 10-40 VDC, reverse polarity protected Supply Load Effect .... Negligible I/O Isolation ............... > 4000 VDC or peak AC Linearity (BSLF) ........ Better than ±0.25% of full range Conversion Method ... AC averaging Stability ..................... Better than 0.01% of full range/°C Operating Temperature -20°C to 70°C Size HxWxD .............. 95x115x68 mm OPTIONS: • LCD Digital Indicator Core Opening Size .... 31x61x68 mm Mounting ................... 2 stand-off screws 4 mm Dia. Weight ....................... 0.9Kg. (2 lb.) max. All specifications are subject to change without notice. 9318 Gulfstream Road • Suite A • Frankfort, IL. 60423 • Telephone: 815-464-5004 • Fax: 815-464-5003 E-Mail Address: [email protected] • Web Site: www.mescontec.com ACInputHighCurrentTransmitters Precision,LoopPowered SeriesT26 1.75 (44) 0.81 (20) 3.19 (81) 4.12 (105) 3.75 (95) 2.91 (74) Display Optional DISPLAY Test Output MESCON T ECHNOLOGIES 2.37 (68) AC CURRENT TRANSMITTER T26 (0-100) A Tst TST 1.75 (44) 4-20mA – 9408253 Current Monitor – + Power Supply + ZERO SPAN 1.25 (32) Wiring Instructions: 0.87 (22) Dimensions are in inches (mm) 1.Connect the positive supply lead to terminal +. 2.Connect the negative supply lead to terminal -. 3.Route the Input current cable through the T26 orifice. ORDERING INFORMATION T26 - D - (0-75) A Calibrating and Adjustments: It is assumed that the unit undergoing calibration has been properly ranged at the factory or workshop. 1.Connect a digital current monitor to the T26 output terminals. Observe for proper polarity. 2.Connect the power supply leads to the digital current monitor and terminal. 3.Set the input to the desired minimum signal and adjust the Zero pot until the output minimum signal is set. 4.Set the input to the desired maximum signal and adjust the Span pot until the output maximum signal is set. 5.Repeat steps 3 & 4 until no further adjustment is needed, until the output maximum signal is set. Model Display (optional) Input ranges: 0-20A 0-50 0-100 0-200 0-500 0-1000 Please request our ordering and calibration diskette describing the rest of Mescon's products. Distributed By: Tel: 815-464-5004 • Fax: 815-464-5003 E-Mail Address: [email protected] Web Site: www.mescontec.com T-26 11.97