Preview only show first 10 pages with watermark. For full document please download

Acx 700 Installation Guide

   EMBED


Share

Transcript

ACX 700 Installation Guide ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com i Version E Reproduction or distribution forbidden. Copyright  1997 by Andover Controls. Subject to change without notice. Order No. 30-3001-204 Copyright  1997 Andover Controls Corporation 300 Brickstone Square Andover, Massachusetts 01810 All Rights Reserved. Published by the Engineering Department at Andover Controls Corporation. IMPORTANT NOTICE This product is subject to change without notice. This document does not constitute any warranty, express or implied. Andover Controls Corporation reserves the right to alter capabilities, performance, and presentation of this product at any time. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com ii Preface The Andover Controls ACX 700 Installation Guide presents instructions for installing the ACX 700 access controller on an Infinet network. It first presents site preparation information and then step-bystep installation instructions. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com iii ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com iv Contents Setting Up the ACX 700 Controller and Infinet Site/System Setup Requirements ..........................................................2 Controller Dimensions and Weight .................................................3 Power Requirements ........................................................................3 Cable Limitations.............................................................................4 Lightning Protection ........................................................................4 Building Ground Requirements .......................................................5 Inspecting the Ground......................................................................6 Environmental Requirements ..........................................................6 Enclosure Requirements ..................................................................6 Special Wire for Card Reader Inputs...............................................6 Special Wire for Keypad Inputs ......................................................7 Output Requirements .......................................................................7 Input Requirements..........................................................................8 Laying Out the Site Setup................................................................9 Installing the ACX 700 ........................................................................10 Parts Required................................................................................10 Mounting........................................................................................10 Connecting the AC Power .............................................................15 Selecting the AC Input Voltage .....................................................16 Connecting the UPS Power Supply ...............................................17 Connecting the Power Indicating LED..........................................18 Wiring the Infinet to the ACX 700 .................................................21 Wiring the Infinet to the Infinity CX 9000 or 9200........................22 Wiring Inputs ......................................................................................24 Supervisory Input Circuits.............................................................26 Wiring Door Switches ...................................................................28 Andover Controls Corporation Technical Manuals Online! - http://www.tech-man.com v Wiring Motion Sensors/Exit Push Buttons....................................30 Wiring Other Two-Wire Inputs .....................................................32 Wiring Card Reader Inputs ............................................................32 Wiring Keypad Inputs....................................................................39 Wiring Outputs ...................................................................................40 Wiring Door Outputs .....................................................................40 Connecting Modules to the Expansion Port ..................................42 Wiring Power Supply for Modules................................................45 Powering Up the ACX 700..................................................................47 Reset Button...................................................................................48 Connecting the Battery ..................................................................48 Connecting the Andover Controls Service Tool............................49 Appendix A—Underwriters Laboratories Requirements Appendix B—Setting the Card Type Jumpers Locating the Card Type Jumpers ......................................................B-2 Setting Jumpers for ABA Cards ..................................................B-3 Setting Jumpers for Wiegand Cards ............................................B-4 vi Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Figures 1. Dimensions and Location of Mounting Holes in Cabinet Provided, in inches (mm) ..................................................................11 2. Dimensions and Location of Mounting Holes in Backplate, in inches (mm).......................................................................................12 3. Dimensions of ACX 700 on Backplate with EMX 190s, in inches (mm)...................................................................................13 4. Cover Plate of the ACX 700 ..............................................................14 5. Metal Plate and Screw for Power Supply Wire ................................16 6. Location of Power Indicating LED on Front Door of Cabinet Provided ............................................................................................19 7. Power Indicating LED and Its Parts..................................................20 8. Inserting the External LED through Drilled Hole.............................20 9. Infinet Cable Wiring..........................................................................21 10. Attaching the Infinet Cable to Infinity CX 9000 or 9200 ..................22 11. Normally Closed Supervisory Inputs................................................26 12. Normally Open Supervisory Inputs ..................................................27 13. Wiring Ordinary Switch to DoorSwitch Input .................................28 14. Wiring Switch with Built-in Resistor to DoorSwitch Input .............29 15. Functioning of DoorSwitch Input Wired to Supervisory Input ........30 16. Functioning of Passive Infrared (PIR) Motion Detector Switch Wired to Supervisory Input ...............................................................31 17. Wiring Diagram for Counter or Digital Input...................................32 18. Connections Between Card Reader and Controller ..........................33 19. Wiring Wiegand Card Reader (Sensor Engineering) to Controller ........34 20. Connections Between Card Reader and Controller ..........................35 21. Wiring Proximity Wiegand Card Reader to Controller, with 12 VDC Power Supply......................................................................36 22. Connections Between Card Reader and Controller ..........................37 23. Wiring Dorado ABA Card Reader to Controller ..............................38 Andover Controls Corporation Technical Manuals Online! - http://www.tech-man.com vii 24. Wiring Diagram for DOOR and AUX Form C Outputs if Normally Open..................................................................................41 25. Wiring Diagram for DOOR and AUX Form C Outputs if Normally Closed ...............................................................................42 26. Wiring External and AC Power to Controller and Modules.............46 B-1. Location of Card Type Jumpers.....................................................B-2 B-2. Jumpers for ABA Cards.................................................................B-3 B-3. Jumpers for Wiegand Cards...........................................................B-4 viii Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Tables 1. Maximum Length Wire for Card Readers ............................................7 2. Connecting Jumpers for AC Input Voltages .......................................16 Andover Controls Corporation Technical Manuals Online! - http://www.tech-man.com ix x Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Setting Up the ACX 700 Controller and Infinet The ACX 700 is a building access controller that can control access to two doors. You can use it to control access through up to four doors by attaching two EMX 190 modules to the ACX 700. You may set up access through either Wiegand or ABA card readers, which read access cards, or security keypads, which accept access codes. You may also use both the card reader and the security keypad together, for extra tight security. This manual covers the following: • Site/System Setup Requirements • Installing the ACX 700 • Powering Up the ACX 700 Warranty Registration Your warranty is effective for 18 months starting on the date the system is shipped. Warning All wiring and installations must comply with local, state, and national electrical codes. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 1 Hardware Installation Site/System Setup Requirements Before you proceed to install the system, you should map out where you plan to install each controller, terminal/workstation, and modem. When planning the sites, be aware of any electrical interference that may occur. You also need to be aware of cabinet dimensions, power requirements, cable limitations, and environmental requirements. Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Note This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Avis Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada. 2 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Controller Dimensions and Weight Each ACX 700 is 19 × 15 × 4.56 in. (483 × 381 × 116) and weighs 17 lbs. (7.73 kg). Power Requirements Caution The ACX 700 should receive power from its own independent, unswitched circuit. You can choose to connect AC power or a 12 VDC uninterrupted power supply (UPS), but not both. Instructions for how to connect the 12 VDC UPS are included later, with the installation instructions. To maintain the UL listing of your system, you should use a power supply listed by UL under APHV. If you choose AC power, you can select an AC power supply voltage of 24 V, 115 V, or 230 V. You receive it set to 115 V. Instructions for selecting the power supply you want are included later, with the installation instructions. AC voltages you can select are as follows (each uses a 3 A slow blow fuse): • 24 VAC 50/60 Hz • 115 VAC 50/60 Hz • 230 VAC 50/60 Hz The ACX 700 consumes 20 VA of power at 115/230 VAC and consumes 50 VA of power at 12 VDC/24 VAC. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 3 Hardware Installation Cable Limitations The maximum cable length for all buses is 4,000 ft. (1,200 m) at 19,200 baud (up to 32 Infinet controllers). You can extend buses beyond 4,000 ft. or put more than 32 Infinet controllers on less than 4,000 ft. by using the InfiLink 200 amplification module. Note You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to provide reliable communications. Cables that form Infinet are 24-gauge (0.25 mm), single-twisted-pair, tinned, shielded copper wire. Use the following cables1 or their equivalents: • Brand Rex # H 9002 (single-pair) • Anixter # 9J2401021 (single-pair plenum cable) The cable should have a nominal impedance of 100 Ohms and a nominal velocity of propagation of 78%. Capacitance of Infinet cable should be nominal, below 12.5 pF/ft (41 pF/m) between conductors and below 22 pF/ft (72 pF/m) between the conductor connected to ground and the next conductor. Lightning Protection Lightning Arrestors are required at each point where an Infinet or other wiring (such as for a card reader) enters or exits a building. Use the following arrestor: Two pair combination gas tube/silicon avalanche arrestor, Andover Controls # 01-2100-299. 1. You can also use any cables you may already have in place for ACNET or LBUS. 4 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Building Ground Requirements Warning Be sure that all Infinity products from Andover Controls Corporation are grounded to true earth ground. This kind of ground protects the equipment from transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented unless you properly ground all controllers. Warning Grounding should be in accordance with article 240 of the National Electrical Code. Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not and often have substandard electrical grounds. An example of a substandard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 5 Hardware Installation Inspecting the Ground You can check your ground as follows: 1. Check your ground by first inspecting the building power distribution panel for earth ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: • Does not exist. • Is connected to a corroded or galvanized pipe. • Is connected using a small gauge wire thinner than 14 AWG (16 or 18 AWG, for example, or less than 2.5 mm2). 2. Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel. Environmental Requirements The ACX 700 operates in rooms with temperatures ranging from 32 to 120°F (0° to 49°C) and with humidity between 10 and 95%, noncondensing. Enclosure Requirements If you did not purchase the Andover Controls cabinet, you purchased the open class controller. The open class controller must be in an Underwriters Laboratories listed enclosure that is a minimum of 12.75 × 30 × 2.75 in. (324 × 762 × 70 mm). Special Wire for Card Reader Inputs We recommend a five-conductor, 22-gauge (0.35 mm2) shielded wire for wiring card reader inputs. Table 1 shows the various card brands and the maximum length for #18 gauge wire (1.0 mm2), then for #22 gauge (0.35 mm2) wire. 6 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Table 1. Maximum Length Wire for Card Readers Card Reader Type Sensor Engineering* #18 Gauge (1.0 mm2) #22 Gauge (0.35 mm2) 500 ft (152 m) 200 ft (60 m) 250 ft (76 m) 100 ft (30 m) Proximity (12V at Reader) 500 ft (152 m) 350 ft (106 m) Dorado ABA Card Reader 500 ft (152 m) 200 ft (76 m) Proximity (12V at ACX 700) * Model number 30387 for UL listed systems. Special Wiring for Keypad Inputs We recommend eight-conductor, 18-gauge shielded wire for wiring keypad inputs except for the Essex unit, which requires two extra wires bringing its total to ten conductors. 8-conductor, shielded 10-conductor, shielded for Essex Touch Pads You can extend the length of this cable up to 500 ft. Output Requirements Two of the outputs are door outputs that control a door through a card reader or keypad access. Each output is a Form C relay rated at 24 VAC, 5 A. You wire these outputs just as you would a digital/pulsed output. Resolution of the output is 0.1 sec. You may choose to manually override the output by setting the OVERRIDE switch to ON or OFF. Or you can set it to AUTO to have the card reader control access through the door. The OVERRIDE LED indicates at least one of the door outputs is on manual control; the DOOR OPEN LED indicates the door is open. The third output is an auxiliary output, also a Form C relay rated at 24 VAC, 5 A. You may want to use this output for a bell or other audio alarm indicator. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 7 Hardware Installation Input Requirements Caution Andover Controls inputs are designed to be used with the specified card readers, two-wire door switches, two-wire motion sensors, and other two-wire input devices; they do not provide sufficient power to operate sensors requiring an external power supply of 12 or 24 VAC/DC. Each ACX 700 controller has the following inputs: • Two card reader inputs that receive either the Wiegand format or the standard ABA format. You set the switch next to each reader to indicate Wiegand or ABA. You may also have additional card readers by attaching one or two EMX 190 modules to the ACX 700. The card reader may have an LED, but does not have to. (UL listed systems must use model 30387 Sensor Engineering card readers.) Maximum data rate for the card reader—1 ms between bits with a 50 µs bit width. Maximum power available to each card reader is 35 mA at 5 VDC. If the card reader requires 12 ± 2 or 24 ± 2 VCD, it requires an external power supply. • Eight supervisory inputs (1 through 8) that you can use for any of the following types of inputs: — Door switch that indicates the status of the door—open or closed. Must have a 10 KΩ resistor in series if normally closed or in parallel if normally open. The resistor allows the input to detect tampering. Refer to the Infinity CX Programmer’s Guide for details. Required. — An exit request input, usually a motion sensor that determines someone is approaching the door or a push button that you must press to leave the area. Must have a 10 KΩ resistor in series if 8 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation normally closed or in parallel if normally open. The resistor allows the input to detect tampering. Refer to the Infinity CX Programmer’s Guide for details. Optional. — Two keypads, each a single input (inputs 9 and 10), that you place near the door as an alternative to a card reader. The person punches in an access code that the controller recognizes before allowing the person access. You may have up to two keypads and/or two card readers. Each keypad has eight connections. • One built-in tamper switch that indicates when the cabinet door has been forced open. The switch is actually a button that reacts when someone opens the cabinet door. You may also wire another switch to the input if you install the unit in another cabinet. When the switch is open, the cabinet tamper is ON. Laying Out the Site Setup You may want to draw a map of where you plan to put each controller and store it in a notebook. Find the tag attached to each controller that gives the number of the controller. Before you remove any tags, be sure the tag has all of the following information on it: • Location of the controller. • Serial number. • Model name and number. • Communications port the Infinet connects to on the ACX 700 controller. Then collect the tags. You will need to know where your controllers are located when you later assign a name to each controller and each input and output. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 9 Hardware Installation Installing the ACX 700 Parts Required To install a single controller you start with the following parts: • • • • • • • • • • • ACX 700 Controller (with or without cabinet) AC Power Cable or 12 VDC UPS Power Supply and Cable Input and Output Wires Up to Two Card Readers and/or Two Keypads Up to Two Door Switches Up to Two Motion Sensors or Two Exit Buttons (or One of Each) LED with Wires Attached and Screws/Washers Included (if you purchased the open class controller, without the Andover Controls cabinet) (optional) One Cabinet Door Tamper Switch (optional) Infinet Cable (twisted pair) InfiLink 200s as Hubs, Repeaters, or Cable Switching Boxes as required Up to two EMX 190 Modules (optional) Mounting Caution You must keep the ACX 700 in the UL listed enclosure provided or insert it in a UL listed enclosure. 1. Before you begin, if you have the enclosed unit, open the front door of the ACX 700 cabinet. Figure 1 shows the dimensions of the UL listed cabinet provided by Andover Controls and the location of the mounting screw holes. Figure 2 shows the dimensions of the open class UL listed unit and the dimensions of the backplate for mounting. 10 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 1. Dimensions and Location of Mounting Holes in Cabinet Provided, in inches (mm) 15.00 (381) 12.35 (314) 1.33 (34) 1.00 (25) AC INPUT USE COPPER CONDUCTORS ONLY GND AC INPUT VOLTAGE SELECTION 115V 230V 24V FROM TO FROM TO FROM TO E6 E7 E6 E5 --E4 E3 E4 E2 E4 E5 P1 E1 P1 E1 P1 E2 NEU HOT ACX700 F1 3A,250V SLOW BLOW + PWR ON +12VDC -INPUT 19.00 (483) B1 IN1 RET1 IN2 RET2 IN3 RET3 IN4 RET4 3.6V 1.8AHr LITHIUM - KEYPAD 1 SUPERVISORY INPUTS IN5 RET5 IN6 RET6 IN7 RET7 IN8 RET8 KEYPAD 2 TAMPER SWITCH 9 RESET EXT TAMPER ABA SWITCH +5V LED I/DATA O/CLK GND 17.00 (432) C1 C2 C3 R1 R2 R3 R4 RET OVERRIDE AUTO/OFF/ON WIEGAND READER 1 +5V LED I/DATA O/CLK GND READER 2 DOOR 1 OUTPUT CPU TD AUTO/OFF/ON DOOR OUTPUT ABA RD + – SHLD C1 C2 C3 R1 R2 R3 R4 RET OUTPUT 3 WIEGAND INFINET +24VDC CLASS 11 160 mA SERVICE EXPANSION PORT PORT AUTO/OFF/ON OVERRIDE Caution Never drill holes in the ACX 700 cover or boards. A metal shaving could easily short circuit the electronics. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 11 Hardware Installation 2. Position two standard No. 8 screws for the pre-cut eyelets in the cabinet or backplate, and hang the cabinet or backplate on the screws. Figure 2. Dimensions and Location of Mounting Holes in Backplate, in inches (mm) 12.54 (318) 11.72 (298) R .117 (3) AC INPUT .45 (11) AC INPUT VOLTAGE SELECTION 24V 115V 230V FROM TO FROM TO FROM TO E6 E7 E6 E5 --E4 E3 E4 E2 E4 E5 P1 E1 P1 E1 P1 E2 NEU HOT R .195 (5) USE COPPER CONDUCTORS ONLY GND ACX700 F1 3A,250V SLOW BLOW + PWR ON +12VDC -INPUT B1 IN1 RET1 IN2 RET2 IN3 RET3 IN4 RET4 3.6V 1.8AHr LITHIUM - KEYPAD 1 SUPERVISORY INPUTS IN5 RET5 IN6 RET6 IN7 RET7 IN8 RET8 KEYPAD 2 TAMPER SWITCH 9 RESET EXT TAMPER SWITCH +5V LED I/DATA O/CLK GND ABA C1 C2 C3 R1 R2 R3 R4 RET 14.25 (362) 11.50 (292) OVERRIDE AUTO/OFF/ON WIEGAND READER 1 +5V LED I/DATA O/CLK GND READER 2 DOOR 1 OUTPUT CPU TD AUTO/OFF/ON DOOR OUTPUT ABA RD + – SHLD C1 C2 C3 R1 R2 R3 R4 RET OUTPUT 3 WIEGAND INFINET +24VDC CLASS 11 160 mA SERVICE EXPANSION PORT PORT AUTO/OFF/ON 1.45 (37) OVERRIDE Figure 3 shows the dimensions of the ACX 700 with an EMX 190. When you attach modules, they must be enclosed in the same UL listed enclosure as the controller. For additional modules, you require a larger cabinet. You can find the exact dimensions of each module in the installation instructions included with that module. 12 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 3. Dimensions of ACX 700 on Backplate with EMX 190s, in inches (mm) 12.54 (318) 11.72 (298) R .117 (3) AC USE COPPER INPUT CONDUCTORS ONLY .45 (11) GND NEU HOT AC INPUT VOLTAGE SEL 24V 115V 230V FROM TOFROMTOFROMTO E6 E7 E6 E5 -- -E4 E3 E4 E2 E4 E5 P1 E1 P1 E1 P1 E2 ACX700 F1 3A,250V SLOW BLOW R .195 (5) + PWR ON +12VDC -INPUT B1 3.6V 1.8AHr LITHIUM IN1 RET1 IN2 RET2 IN3 RET3 IN4 RET4 IN5 RET5 IN6 RET6 IN7 RET7 IN8 RET8 R3 R4 RET DOOR 1 OUTPUT CPU DOOR TD OUTPUT AUTO/OFF/ON ABA RD SERVICE PORT OUTPUT 3 +24VDC CLASS 11 AUTO/OFF/ON 160mA EXPANSION PORT BOARD 1 2 OVERRIDE 1.45 (37) EMX190 DOOR SWITCH RTN EXIT REQUEST RTN RTN CARD 0-CLK READER 1/DATA INPUT LED +5V DOOR NC C OUTPUTNO OVERRIDE OFF 24VDC CLASS ON AUTO II WIEGAND ABAOVERRIDE CARD READER BOARD 1 2 6.72 (171) 4.95 (126) 14.25 (362) 11.50 (292) OVERRIDE AUTO/OFF/ON READER 2 WIEGAND + – INFINET SHLD 6.72 (171) 4.95 (126) R3 R4 RET C1 C2 C3 READER 1 +5V LED I/DATA O/CLK GND KEYPAD 1R1 R2 KEYPAD 2R1 R2 TAMPER SWITCH 9 RESET EXT TAMPER ABA SWITCH +5V LED WIEGAND I/DATA O/CLK GND C1 C2 C3 - SUPERVISORY INPUTS EMX190 DOOR SWITCH RTN EXIT REQUEST RTN RTN CARD 0-CLK READER 1/DATA INPUT LED +5V DOOR NC C OUTPUTNO OVERRIDE OFF 24VDC CLASS AUTO ON II WIEGAND ABAOVERRIDE CARD READER 5.38 (137) 6.13 (156) ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 13 Hardware Installation Figure 4. Cover Plate of the ACX 700 AC INPUT USE COPPER CONDUCTORS ONLY GND AC INPUT VOLTAGE SELECTION 24V 115V 230V FROM TO FROM TO FROM TO E6 E7 E6 E5 --E4 E3 E4 E2 E4 E5 P1 E1 P1 E1 P1 E2 NEU HOT ACX700 F1 3A,250V SLOW BLOW +12VDC -INPUT – POWER + LED PWR ON + B1 3.6V IN1 RET1 IN2 RET2 IN3 RET3 IN4 RET4 1.8AHr LITHIUM KEYPAD 1 C1 C2 C3 R1 R2 R3 R4 RET KEYPAD 2 C1 C2 C3 R1 R2 R3 R4 RET - SUPERVISORY INPUTS IN5 RET5 IN6 RET6 IN7 RET7 IN8 RET8 TAMPER SWITCH 9 RESET EXT ABA TAMPER OVERRIDE SWITCH +5V LED I/DATA O/CLK GND +5V LED I/DATA O/CLK GND AUTO/OFF/ON DOOR 1 OUTPUT WIEGAND READER 1 READER 2 CPU TD AUTO/OFF/ON ABA RD + – SHLD DOOR 2 OUTPUT OUTPUT 3 WIEGAND INFINET +24VDC CLASS 11 160 A m SERVICE PORT EXPANSION PORT 14 Technical Manuals Online! - http://www.tech-man.com AUTO/OFF/ON OVERRIDE ACX 700 Installation Guide Hardware Installation Figure 4 shows the location of various parts inside the ACX 700, labeled on the cover plate. Note the parts of the controller labeled here. You may want to refer to this figure to locate parts during the installation process. Connecting the AC Power Warning Be sure the AC power cable is not connected to an electrical power source while you are wiring the controller, or you could receive an electrical shock that is life-threatening. If you choose to use a 12 VDC UPS power supply, skip these instructions and go to the section called Connecting the UPS Power Supply. The AC power connection is in the upper left corner of the controller. You must wire the AC cable to the three screws on the far left. Caution Be sure to connect all three wires, HOT, NEUTRAL, and GROUND. Otherwise, the controller could malfunction. The three screws are labeled GND, NEU, HOT. 1. Place the ground wire under the metal plate behind the screw labeled GND. 2. Tighten the screw with a flathead screw driver. Figure 5 shows the position of the plate, where to place the wire, and how the screw fits on the plate. You can see how the screw holds the plate in place once you tighten it. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 15 Hardware Installation Figure 5. Metal Plate and Screw for Power Supply Wire Metal Plate Insert Wire Here 3. Place the neutral wire under the metal plate behind the screw labeled NEU. 4. Tighten the screw with a flathead screw driver. 5. Place the hot wire under the metal plate behind the screw labeled HOT. 6. Tighten the screw with a flathead screw driver. Selecting the AC Input Voltage The voltage is set to 115 V when shipped. To change the voltage, you must reset the jumpers to the right of the AC power cord connection. Table 2 shows jumper settings for the three voltages. Table 2. Connecting Jumpers for AC Input Voltages 24V Jumpers 115V Jumpers 230V Jumpers From To From To From To E6 E7 E6 E5 — — E4 E3 E4 E2 E4 E5 P1 E1 P1 E1 P1 E2 To change the voltage from 115 V to 24 V, proceed as follows: 1. Disconnect the jumper end from E5 and move it to E7 so it jumpers E6 to E7. 16 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation 2. Disconnect the jumper end from E2 and move it to E3 so it jumpers E4 to E3. 3. Leave the other jumper as it is. To change the voltage from 115 V to 230 V, proceed as follows: 1. Disconnect the jumper from E6 to E5 and remove it. 2. Disconnect the jumper from E5 and connect it to E2, so it jumpers E4 to E2. 3. Disconnect the jumper from E1 and connect it to E2, so it jumpers P1 to E2. Connecting the UPS Power Supply If you choose to connect the controller to a UPS power supply, you may not also connect it to AC power. Note Be sure to size the power supply to provide 1.6 A for each ACX 700 controller. If the supply also provides power to motion sensors, card readers, or other auxiliary devices, be sure to size the power supply accordingly. Wire the UPS power supply to the terminal block connector below the AC input labeled +12VDC INPUT. The connector is immediately to the left of the power indicator light labeled PWR ON. You wire the power supply as follows: 1. Slip the hot wire under the screw labeled + and tighten the screw down on the wire. 2. Slip the ground wire under the screw labeled – and tighten the screw down on the wire. Once the power supply is connected, the PWR ON light should light up. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 17 Hardware Installation Connecting the Power Indicating LED Caution If you purchased the ACX 700 enclosed in the Andover Controls cabinet, skip this section and proceed with the next section, Wiring the Infinet to the ACX 700. If you purchased the ACX 700 without the cabinet (open class), included with it is an LED that you can wire to the printed circuit board and mount on the front of the UL listed enclosure. This LED lights up to indicate that the unit is receiving power. Mounting the LED If you had the cabinet provided by Andover Controls, you would see the LED on the front door of the cabinet, approximately 1--4- -in. (6 mm) to the left of and below the logo/product name. Figure 6 shows where the LED would be located. You should position the LED in an approximately equivalent location. 18 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 6. Location of Power Indicating LED on Front Door of Cabinet Provided Location of Power Indicating LED on Front Door of Cabinet Provided To mount the LED on the front of the UL enclosure for the open class controller, proceed as follows: 1. If you have an open class controller, drill a 3--8- -in. (9.5 mm) hole in the front of the enclosure for it. Drill the hole approximately in front of where the controller is labeled EXTERNAL LED on the cover plate. 2. Find the LED included with the controller. It should have two wires on the back end. Figure 7 shows the LED with the three nuts and one washer on it. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 19 Hardware Installation Figure 7. Power Indicating LED and Its Parts LED Red Wire (+) Black Wire (–) 3/16-in. (4.7 mm) Front Nut 1/16-in. (1.5 mm) Front Nut Washer Hexagonal Nut 3. Remove the two front nuts from the LED assembly. 4. Insert the LED through the drilled hole. Figure 8 shows how to insert the LED through the drilled hole. Figure 8. Inserting the External LED through Drilled Hole Cabinet Door Outside Cabinet or Enclosure Inside Cabinet or Enclosure 1 1 --5. Screw the ----16 -in. (1.5 mm) front nut approximately 4 in. (6 mm) onto the threaded area. 6. Screw the 3 ------ -in. 16 7. Unscrew the (4.7 mm) front nut on as far as you can. 1 ------ -in. 16 (1.5 mm) nut until it is tight against the 3 ------ -in. 16 (4.7 mm) frontmost nut and secures it. 8. Tighten the hexagonal nut from the rear until it is tight against the inside of the enclosure. 20 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Now, you are ready to wire the LED to the controller. Wiring the Power Indicating LED You wire the LED to the screws labeled +/– POWER LED as follows: 1. Slip the red wire for the sensor under the screw labeled + next to POWER LED and tighten the screw down on it. 2. Slip the black wire under the screw labeled – next to POWER LED and tighten the screw down on it. Wiring the Infinet to the ACX 700 Note You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to ensure reliable communications. Figure 9 illustrates how to wire the Infinet cable to the removable terminal block connector in the lower left corner of the ACX 700. Figure 9. Infinet Cable Wiring Infinet Connection + – SHLD 1. Trim back the shield over the wires. 2. Take the first wire for the incoming Infinet and the first wire for the outgoing Infinet and slip both in the hole beneath the screw labeled with a plus sign. 3. Tighten the screw down on them until the screw holds the wires in place. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 21 Hardware Installation 4. Slip the second (usually black) wire from each Infinet cable under the screw labeled with a minus sign and tighten the screw down on them. 5. Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD and tighten the screw down on them. Wiring the Infinet to the Infinity CX 9000 or 9200 You connect the last piece of Infinet cabling to the Infinity CX 9000 or 9200, as described below (refer to the illustration): 1. Open the front of the Infinity CX 9000 controller cabinet. Notice that to the left are three ports labeled COMM1, COMM2, and COMM3. Two RS-485 ports, one above the three comm ports and one below, are in the same area. Notice that the end of the Infinet cable has two wires and a shield. You wire them to the terminal block connector on the RS-485 port. Figure 10 illustrates how to wire the Infinet cable to the Infinity CX 9000 or 9200. Figure 10. Attaching the Infinet Cable to Infinity CX 9000 or 9200 +IN –IN SHLD +OUT –OUT 2. Run the cable through the knockout on the left side of the controller. 3. Select the port to wire the cable to—on a 9000, either the RS-485 port just above the three RS-232 ports (COMM2) or the RS-485 port just below the three RS-232 ports (COMM1). Once you use either of 22 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation these ports for COMM1 or COMM2, the RS-232 port for COMM1 or COMM2 is disabled. On a 9200, you can also select COMM4. 4. Trim back the shield over the wires. 5. Slip the first wire through the hole under the screw labeled +IN and jumper it to the screw labeled +OUT. 6. Tighten both screws to hold the wire there. 7. Slip the ground wire through the hole under the screw labeled –IN and jumper it to the screw labeled –OUT. 8. Tighten both screws to hold the wire there. 9. Slip the shield in under the middle screw labeled SHLD and tighten the screw to hold it there. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 23 Hardware Installation Wiring Inputs Caution Do not remotely ground any part of the sensor wiring. Remote grounds connected to the ACX 700 return terminal could make the controller operate incorrectly or damage the equipment. The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. Do not externally ground sensor or switch terminals that return to the ACX 700. Caution Card readers require shielded wiring. Although two-wire inputs usually function properly with unshielded sensor wire, you may need shielded wire if you run the wire as follows: • In the same conduit with other noise-generating conductors such as 60 Hz AC power. • In long runs close to large power-consuming or power-generating equipment that can produce 60 Hz noise. We recommend you run input wiring in a conduit separate from AC power or output wiring and avoid long wiring runs. The “supervisory” inputs are on the upper left side of the ACX 700, just below the 12VDC UPS power connector. Input wires should enter from the left side. Notice that the inputs are labeled IN1, RET1, IN2, RET2, IN3, RET3, IN4, RET4, and so on, for up to eight inputs. The first return terminal goes to the first input, the second to the next input, and so on. 24 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Caution Follow the rules below when wiring inputs and outputs: • Never lay wires across the surface of the printed circuit board. You should bring input wires in from the left and output wires in from the right. • Bundle excess wires toward the back of the cabinet to avoid any contact with circuit boards. • Wires should never be within 1 in. (25 mm) of any component on the printed circuit board. • Keep cabinet free of foreign materials (extra power supplies, relays, and so on). • Be careful when stripping wire not to drop small pieces of wire inside the cabinet. If you violate any of these rules, the controller could malfunction. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 25 Hardware Installation Supervisory Input Circuits All 700/780 controller series inputs are supervisory inputs. The following drawings depict the six types of supervisory inputs that exist—three normally closed and three normally open types. After the drawings, there is an explanation of which types are recommended for access control installations. Figure 11 shows the three types of normally closed supervisory inputs. Figure 11. Normally Closed Supervisory Inputs NC Series Door Closed Door Open SW Closed SW Open SW Shorted Wire Cut 10K Infinite Zero K Infinite Door Open and Wire Cut conditions both result in an infinite reading. If the door was sensed open without a valid card swipe, a Door Violation should be triggered. NC Parallel Door Closed Door Open SW Closed SW Open SW Shorted Wire Cut Zero K 10K Zero K Infinite Not the best choice, the switch could be shorted and the door forced open, and the system would still think the door was closed. NC Series and Parallel Door Closed Door Open SW Closed 5K SW Open 10K SW Shorted Zero K Wire Cut Infinite This configuration is the best choice; the parallel and series resistors provide a redundant security feature. 26 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 12 shows the three types of normally open supervisory inputs. Figure 12. Normally Open Supervisory Inputs NO Series Door Closed Door Open SW Open SW Closed SW Shorted Wire Cut Infinite 10K Zero K Infinite This configuration is not the best choice. If the wire is cut and the door forced open, and the system senses that the door is still closed. NO Parallel Door Closed Door Open SW Open SW Closed SW Shorted Wire Cut 10K Zero K Zero K Infinite This configuration is defeated by shorting the switch. The systems senses this condition as a normal door open situation. However if the wire is cut, that is a unique resistance that can easily be identified as a tampering situation. NO Series and Parallel Door Closed Door Open SW Open 10K SW Closed 5K SW Shorted Zero K Wire Cut Infinite This configuration provides the most security. There are four unique resistance values associated with the four possible conditions. We recommend NO Parallel and NO Series and Parallel types for access control installations. The next sections explain how to wire these types of inputs for door switches and motion detectors. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 27 Hardware Installation Wiring Door Switches You may wire up to two of the eight supervisory inputs to door switches. The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2) or 200 ft of #22 gauge wire (60 m of 0.35 mm2). You wire the door switch as follows (switches may be either normally open or normally closed): 1. Slip the appropriate wire under the IN screw and tighten the screw down on it. Figure 13 shows the wiring diagram for the input if the door switch is an ordinary switch. This switch can detect either the switch position, or tampering if the switch has an open fault. If the switch is shorted, it appears closed. Figure 13. Wiring Ordinary Switch to DoorSwitch Input RET 10 KΩ IN1 28 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 14 shows the wiring diagram for the input if the door switch has a built-in series resistor. This switch can detect either the switch position, or tampering where the switch is shorted or grounded. We recommend this switch for situations requiring the greatest security. Figure 14. Wiring Switch with Built-in Resistor to DoorSwitch Input RET 10 KΩ IN1 Each switch requires a single parallel resistor to provide extra security should an intruder attempt to break in through the door by closing the contact. 2. Slip the ground wire under the RET screw that corresponds to the IN number and tighten the screw down on it. 3. Be sure you wire the 10 KΩ resistor in parallel as shown in each diagram. Figure 15 shows the how the door switch works if it is an ordinary switch (normally open). The switch remains open while the door is in a normal state (closed or not tampered with). If the switch detects the door is open or has been tampered with, it appears closed. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 29 Hardware Installation Figure 15. Functioning of DoorSwitch Input Wired to Supervisory Input Normally Open DoorSwitch Access Controller 10 KΩ Door Closed (Normal) Normally Open DoorSwitch Access Controller 10 KΩ Detects Door Open Wiring Motion Sensors/Exit Push Buttons You may wire up to two of the first four supervisory inputs to motion sensors or exit buttons. You wire them the same way you wire DoorSwitch inputs, only the motion sensor requires an external power supply of 12± 2 VDC or 24 ±2 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2) or 200 ft of #22 gauge wire (60 m of 0.35 mm2). Be sure that when you wire the motion detector, it is correctly set up, as illustrated in the next figure. 30 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 16 shows the how the motion detector works if it is an ordinary Passive Infrared (PIR) Motion Detector. The switch (normally open) remains open while it detects no motion or tampering If the switch detects motion, it appears closed. Figure 16. Functioning of Passive Infrared (PIR) Motion Detector Switch Wired to Supervisory Input Normally Open PIR Motion Detector Access Controller No Motion Detected 10 KΩ Normally Open PIR Motion Detector Access Controller 10 KΩ Motion Detected!!! ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 31 Hardware Installation Wiring Other Two-Wire Inputs Follow these steps to wire two-wire inputs: 1. Slip the first wire for the sensor under the screw labeled IN5 and tighten the screw down on it. 2. Slip the ground wire under the RET5 screw and tighten the screw down on them. 3. Repeat the steps for each pair of inputs. Figure 17 shows a counter wired to an input point. Figure 17. Wiring Diagram for Counter or Digital Input 1 (input point 1) RET (return) Wiring Card Reader Inputs Be sure you wire all card readers with shielded wiring. The maximum length of wire you may use depends on the card reader brand name and the type of wiring/cable you use. Refer to the earlier sections in this manual. In the case of Proximity card readers, you may connect the required 12 ± 2 VDC power supply at the ACX 700 or at the card reader. 32 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Wiring Wiegand Card Reader (Sensor Engineering) Wire the Sensor Engineering Wiegand card reader to the READER 1 and READER 2 inputs on the lower left side of the ACX 700 as follows: 1. Look at the wire connection on your Wiegand card reader. Notice that you have five connection points: • • • • • + 5VDC DATA1 DATA0 LED GND 2. Wire the first end of each wire to the appropriate connection point on the card reader. Figure 18 shows where to connect the various wires on the card reader and the ACX 700. Figure 18. Connections Between Card Reader and Controller Card Reader ACX 700 Controller +5VDC +5V DATA1 LED DATA0 1/DATA LED 0/CLK GND GND 3. Slip the other end of the +5VDC wire under the +5 V screw on the controller and tighten the screw down on it. 4. Slip the other end of the DATA1 wire under the 1/DATA screw on the controller and tighten the screw down on it. 5. Slip the other end of the DATA0 wire under the 0/CLK screw on the controller and tighten the screw down on it. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 33 Hardware Installation 6. Slip the other end of the LED wire under the LED screw and tighten the screw down on it. Figure 19 illustrates where you connect the various wires. Figure 19. Wiring Wiegand Card Reader (Sensor Engineering) to Controller ACX 700 Card Reader +5VDC +5V DATA1 LED DATA0 1/DATA 0/CLK LED Shield GND GND 7. Slip the GND wire and the shield under the GND screw and tighten the screw down on it. 8. Tie back the shield at the card reader end and any wires you do not use. 9. Set the switch on the ACX 700 cover plate (to the right of the wiring) to WIEGAND. 34 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Wiring Proximity PR-10/PR-12 Card Reader The Proximity card reader requires a 12 ± 2 VDC power supply. You wire the card reader inputs as follows: 1. Look at the wire connections on your Wiegand card reader: • • • • • 0 1 LED +12 GND 2. Wire the first end of five wires to the appropriate connection point. Figure 20 shows where to connect the various wires on the card reader and the ACX 700. Figure 20. Connections Between Card Reader and Controller Card Reader ACX 700 Controller 0 +5V 1 LED LED 1/DATA +12* 0/CLK GND GND* * see next illustration 3. Tie back the shield at the card reader end. 4. Slip the other end of the 0 wire under the 0/CLK screw on the controller and tighten the screw down on it. 5. Slip the other end of the 1 wire under the 1/DATA screw on the controller and tighten the screw down on it. 6. If the controller has an LED, slip the other end of the LED wire under the LED screw on the controller and tighten the screw down on it. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 35 Hardware Installation Figure 21 illustrates where you connect the various wires, including the shield and the 12 ± 2 V power supply. Figure 21. Wiring Proximity Wiegand Card Reader to Controller, with 12 VDC Power Supply 0 +5V 1 LED LED 1/DATA +12 0/CLK SHIELD GND +12 wire from reader GND ACX 700 Card Reader extension wire (Two wires and shield go to GND) + GND +12 +/-2 VDC Power Supply 7. Wire the other end of the +12 wire to the positive terminal of a 12 ± 2 VDC power supply. 8. Attach an extension wire to the GND terminal of the 12± 2 VDC power supply. 9. Take the other end of the extension wire from the 12V power supply, the other end of the cable GND wire, and the end of the shield. Slip all of them under the GND screw on the module; tighten the screw down on them. 10. Set the switch on the ACX 700 cover plate (to the right of the wiring) to WIEGAND. 36 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Caution The power supply for the Proximity card reader must have the following specifications: • Be nonswitching and fully regulated. • Ripple must be less than 2 mV. • Size the output for the amperage plus 25%. The PR-10 or PR-12 draws 150 mA, the PR-20 or PR-22 draws 250 mA. We recommend you use a UL listed power supply. Wiring the Dorado ABA Card Reader You wire the Dorado ABA card reader inputs as follows: 1. Look at the wire connections on your ABA card reader: • • • • • +5 LED DATA CLK COMMON 2. Wire the first end of each wire to the appropriate connection point on the card reader. Figure 22 shows where to connect the various wires on the card reader and the ACX 700. Figure 22. Connections Between Card Reader and Controller Card Reader ACX 700 Controller +5V +5V LED LED DATA CLK COMMON ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 1/DATA 0/CLK GND 37 Hardware Installation 3. Slip the other end of the +5 wire under the +5 V screw on the controller and tighten the screw down on it. 4. Slip the other end of the LED wire under the LED screw and tighten the screw down on it. 5. Slip the other end of the DATA wire under the 1/DATA screw on the controller and tighten the screw down on it. 6. Slip the other end of the CLK wire under the 0/CLK screw on the controller and tighten the screw down on it. 7. Slip the other end of the COMMON wire under the GND screw and tighten the screw down on it. Figure 23 illustrates where you connect the various wires. Figure 23. Wiring Dorado ABA Card Reader to Controller +5V +5V LED LED DATA 1/DATA CLK 0/CLK COMMON GND Card Reader ACX 700 8. Tie back the shield as well as any wires you do not use. 9. Set the switch on the ACX 700 cover plate (to the right of the wiring) to ABA. If you would like to connect a different card reader, contact your Andover Controls representative. For information on how to assign and program the inputs and outputs, see the Infinity CX Programmer’s Guide. 38 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Wiring Keypad Inputs You wire the keypads to the keypad inputs on the right side of the controller, near the middle. The maximum length of wire to the keypad is 200 ft of #22 gauge wire (152 m of 1.0 mm2) and 500 ft of #18 gauge wire (60 m of 0.35 mm2). Wire the keypad inputs to the input terminals marked C1, C2, C3, R1, R2, R3, R4 and RET as follows: 1. Slip the wire marked COL1 on the keypad under the screw marked C1 and tighten the screw down on it. 2. Slip the wire marked COL2 on the keypad under the screw marked C2 and tighten the screw down on it. 3. Repeat the previous step for COL3, connecting them to C3. 4. Slip the wire marked ROW1 on the keypad under the screw marked R1 and tighten the screw down on it. 5. Slip the wire marked ROW2 on the keypad under the screw marked R2 and tighten the screw down on it. 6. Repeat the previous step for ROW3 and ROW4, connecting them to R3 and R4. 7. Slip the shield under the screw marked RET and tighten the screw down on it. 8. Repeat the entire process for the second keypad. The remaining two wires for the Essex Keypad are connected as follows: 1. Connect the wire labeled 5VDC POWER (red) to the appropriate +5V Reader terminal. 2. Connect the wire labeled LED (white) to the appropriate LED Reader terminal. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 39 Hardware Installation Wiring Outputs The outputs are on the lower right side of the ACX 700, labeled DOOR1, DOOR2, and AUX. All output wires should enter from the right. Wiring Door Outputs Wire the door and auxiliary outputs as follows: You wire the door outputs like any other Form C output, as follows: 1. Slip the appropriate wire under the NC screw and tighten the screw down on it. 2. Slip the appropriate wire under the C screw and tighten the screw down on it. 3. Slip the appropriate wire under the NO screw and tighten the screw down on it. 4. We recommend you install a metal oxide varistor (Andover part # 01-2020-095, purchased separately) across the door strike or lock being switched. 40 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Figure 24 shows the schematic for wiring a DOOR or AUX output if the circuit is normally open. Figure 24. Wiring Diagram for DOOR and AUX Form C Outputs if Normally Open Oxide Metal Varistor (Andover #01-2020-095) NC C NO C + – 12/24V Power Supply (UL listed power supply (APHV) for UL listed systems) Door Strike (UL listed burglaryresistant electric locking mechanism (CVXY) for UL listed systems) This configuration shows a normally deenergized lock (when secured) in a fail secure mode. Always be sure to use “panic” hardware that allows emergency exit from the secured area. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 41 Hardware Installation Figure 25 shows the schematic for wiring a DOOR or AUX output if the circuit is normally closed. Figure 25. Wiring Diagram for DOOR and AUX Form C Outputs if Normally Closed Oxide Metal Varistor (Andover #01-2020-095) NC C C NO 12/24V Electromagnetic Door Lock (UL listed burglaryresistant electric locking mechanism (CVXY) for UL listed systems) Power Supply (UL listed power supply (APHV) for UL listed systems) This configuration shows a normally deenergized lock (when secured) in a fail secure mode. If power loss occurs, the lock circuit opens. Connecting Modules to the Expansion Port The expansion port at the bottom center of the controller board allows you to connect modules to expand the capabilities of the controller. For details on installing the EMX 190, see the EMX 190 Installation Guide provided with the unit. 42 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Caution If you are wiring an ACX 700 rather than an ACX 710, disregard the Modules Configuration Guide included with the unit and follow the guidelines that follow. You can install multiple expansion modules, along with the EMX 190s, on the ACX 700, as long as you comply with the following: • Never attach more than two modules of the same model to the controller. • Do not exceed the maximum total number of inputs or outputs allowed on the controller. The maximum number of inputs/outputs allowed on the ACX 700 is as follows: Outputs • Maximum Base Outputs (already on controller)—3 • Maximum Expansion Module Outputs—4 • Maximum Total Outputs—7 Inputs • Maximum Base Supervisory Inputs (already on controller)—8 • Maximum Expansion Module Inputs—21 • Maximum Total Inputs—29 If the modules, however, consume a total greater than 166 mA, you must add an external power supply (more later). ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 43 Hardware Installation Caution Do not attach an output module, an input module, then another output module, as this later causes confusion when assigning input and output numbers. Attach Modules in Order You should first attach all output modules, then all input modules. Expansion Outputs Allowed Of the output modules available, you can have up to 4 expansion outputs on an ACX 700 controller. Expansion Inputs Allowed Before you add any input modules to the ACX 700, the first 4 inputs you define are the supervisory inputs on the EMX 190s. Of the input modules you can attach, you can always have a maximum of two EMX 160s and one EMX 170s for 17 more expansion inputs; the first 4 plus the 17 is a total of 21 expansion inputs. EMX 190 Modules EMX 190s must always be the first two expansion output modules on the chain. Other Output Modules After the EMX 190s, you can have one more and only one output module with up to two outputs—and it can be any of the following: • EMX 150 • EMX 151 • EMX 155 • EMX 140—If you attach an EMX 141 or 143, you must count the one output as two when numbering the outputs. 44 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation First Input Modules EMX 160s (or other digital/counter input modules with up to 16 inputs between them) must always be the first two expansion input modules on the chain. Place EMX 170 at End of Chain If you have an EMX 170 or expect to add one in the future, the EMX 170 must always be the last module on the entire chain. Setting Board Switches on Modules You must always set the first module of a particular model number to Board 1. So, we strongly advise that you attach the modules of the same model number one immediately after the other. You must set the first output module on the chain to Board 1, the second to Board 2, the third to Board 1, the fourth to Board 2, and so on—no matter which model number modules. When you start the input modules, start at again Board 1 and continue to alternate from 1 to 2. Wiring Power Supply for Modules After you have installed the modules, if you require an external power supply, refer to the Modules Configuration Guide for details regarding how much external power each module you attach requires. You must wire the power supply to ensure that the modules receive power at the same time that the controller does. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 45 Hardware Installation Figure 26 shows how to wire the power supply. You must wire it to the AC power source as shown. Figure 26. Wiring External and AC Power to Controller and Modules 120 VAC 700 Modules 24 VDC + 120 VAC – External Power Supply 46 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Powering Up the ACX 700 Warning Before powering up the controller, be sure the board is jumpered for the correct input voltage. Before you proceed, be sure the following are correct: 1. Be sure you have jumpered the proper input voltage. 2. Be sure the battery is connected. 3. Be sure the AC power or UPS 12 VDC power source is wired properly. For AC power, check to be sure all three wires have been connected. 4. Be sure the controller has a true earth ground. 5. Be sure you have used the proper cables/wires and the correct lengths. 6. Be sure you have properly labeled the tag with the name of the controller before removing the tag. 7. Be sure the Infinet cable has been properly wired. 8. Be sure the Infinet cable shields are properly connected. If you have completed all previous sections in this manual, you are now ready to power up the controller. Turn on the AC power source (or close the power connection) and the controller starts automatically. The following occurs (also occurs when you press RESET): 1. If the controller has been off, relays remain off. If you have pressed RESET, relays deenergize. 2. The CPU light begins flashing and flashes every.1 sec if all is normal. If the controller fails a ROM test, the CPU light flashes every .2 sec. If the controller fails a RAM test, the CPU light flashes ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 47 Hardware Installation every .025 sec. If the controller fails any other software test, it flashes every .05 seconds. 3. The POWER LED on the front of the cabinet turns on and remains on as long as the unit is receiving power. 4. The TD light may not flash at this time. Once you have set up the Infinet controller in the software and assigned the controller an ID, the TD light immediately starts flashing to show data is being transmitted. 5. The RD light begins flashing only if data is being received from other controllers on the network. This may not happen immediately. 6. If any of the three outputs is not set to AUTO, the OVERRIDE light remains steadily on. 7. The EXTERNAL +24V light turns on and remains steadily on. When the EXTERNAL +24V light goes out, it means no power is being supplied to the expansion port. You may have to replace the fuse. See the Andover Controls Infinet Controller Troubleshooting Guide. Reset Button The RESET button is the red square button to the left of the vertical center of the board. You press it to restart the controller without erasing memory. The same events occur as described above. Connecting the Battery When you have the controller mounted, find the AA battery. Remove the plastic tab below the clip on the battery to activate the battery. The battery is an 1.8 A 3.5 V primary lithium battery that runs the realtime clock and maintains RAM when AC power goes out. 48 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Hardware Installation Connecting the Andover Controls Service Tool The SERVICE PORT on the left side of the bottom of the controller is to connect the Andover Controls Service Tool to an ACX 700. The service tool accesses all ACX 700s and other Infinet controllers on the same network. For information on availability of the Andover Controls Service Tool, contact your Andover Controls representative. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com 49 Hardware Installation 50 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Appendix A Underwriters Laboratories Requirements This appendix explains all requirements for installing the ACX 700 in a UL listed system. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com A-1 The ACX 700 is listed by Underwriters Laboratories, Inc. for standard UL 294, Access Control System Units, as a stand-alone unit. A UL listed system must be set up in one of the following ways: • The ACX 700 enclosed class controller board residing in the ACX 700 enclosure. OR • The ACX 700 open class controller residing in a listed enclosure, with or without one or two EMX 190 modules. See the section called Installing the ACX 700. You must install the controller and accessories in accordance with the UL requirements stated in this manual to have a UL listed access control system. Failure to install the access control system in accordance with the UL requirements listed in this manual is a violation of the listing mark of Underwriters Laboratories. EMX 190 modules are UL listed for use with the ACX 700 in access control systems. These modules are designed for use with the open class ACX 700 for access control. Each ACX 700 is limited to two EMX 190 modules. UL has examined the ACX 700 controller with Sensor Engineering card reader model 30387. For other accessories (door switches, door locks, etc.) and specific two-wire inputs you should use in UL listed systems, consult the UL listings. The exit push button and its wiring must be installed inside the secured area. UL has not examined the operation of the door switch input, lightning arrestors, keypad input, or the Andover Controls metal oxide varistor with the ACX 700. (For varistors you should use in UL listed systems, consult the UL listings.) UL has not examined connection and operation with the Infinet. For UL listed systems, all wires connected to the panel should be in dedicated, grounded conduit. A-2 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide For a UL listed system, when wiring a fail secure door strike, you should use listed panic hardware to allow emergency exit from the secured area. For information on how to program the controller and modules, refer to the Infinity CX Programmer’s Guide, #30-3001-166 Version 1.4, © 1993 or the SX 8000 Programmer’s Guide # 30-3001-174 Version 1.4, © 1993. (Please note that the keypad option is not intended for UL listed systems.) ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com A-3 A-4 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Appendix B Setting the Card Type Jumpers This appendix shows how to switch required jumpers if you change card types from ABA to Wiegand or from Wiegand to ABA. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com B-1 Locating the Card Type Jumpers Located inside the ACX 700 cabinet to the right of the Card Type Switches are two sets of 0 Ω resistor jumpers. These jumpers are correctly set for ABA or Wiegand card types when shipped. If you choose to change the card type from ABA to Wiegand or from Wiegand to ABA you must reset the jumpers. Figure B-1 shows the location of the card type jumpers. Figure B-1. Location of Card Type Jumpers ABA Card Type Switch for READER 1 J1 J2 J3 J4 Card Type Jumpers for READER 1 WIEGAND CPU Card Type Jumpers for READER 2 TD ABA Card Type Switch for READER 2 RD WIEGAND J5 +24VDC CLASS 11 160 A J6 m J7 J8 B-2 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Setting Jumpers for ABA Cards Figure B-2 illustrates how the jumpers should look when set for ABA cards. Figure B-2. Jumpers for ABA Cards READER 1 J1 J2 J3 J4 READER 2 J5 J6 J7 J8 Set the READER 1 jumpers for ABA cards as follows: 1. Find the jumpers labeled J1, J2, J3, and J4 to the right of the Card Type Switch for READER1on the ACX 700. 2. Leave J1 jumpered. 3. Do not jumper J2. 4. Using pliers, remove the jumper from J3. 5. Insert the jumper into J4. Set the READER 2 jumpers for ABA cards as follows: 1. Find the jumpers labeled J5, J6, J7, and J8 to the right of the Card Type Switch for READER2 on the ACX 700. 2. Using pliers, remove the jumper from J6. 3. Insert the jumper into J5. 4. Leave J7 jumpered. 5. Do not jumper J8. ACX 700 Installation Guide Technical Manuals Online! - http://www.tech-man.com B-3 Setting Jumpers for Wiegand Cards Figure B-3 illustrates how the jumpers should look when set for Wiegand cards. Figure B-3. Jumpers for Wiegand Cards READER 1 J1 J2 J3 J4 READER 2 J5 J6 J7 J8 Set the READER 1 for Wiegand cards as follows: 1. Find the jumpers labeled J1, J2, J3, and J4 to the right of the Card Type Switch for READER 1 on the ACX 700. 2. Leave J1 jumpered. 3. Do not jumper J2. 4. Using pliers, remove the jumper from J4. 5. Insert the jumper into J3. Set the READER 2 for Wiegand cards as follows: 1. Find the jumpers labeled J5, J6, J7, and J8 to the right of the Card Type Switch for READER 2 on the ACX 700. 2. Using pliers, remove the jumper from J5. 3. Insert the jumper into J6. 4. Leave J7 jumpered. 5. Do not jumper J8. B-4 Technical Manuals Online! - http://www.tech-man.com ACX 700 Installation Guide Index A D AC power connecting 15 AC voltage setting 16 Andover Controls Service Tool using 49 auxiliary outputs wiring 40 dimensions cabinet 3 dimensions to knockouts 10 door outputs length of wire to 40 wiring 40 door switch inputs wiring 28 door switches length of wire to 28 B backup power connecting 48 battery connecting 48 C cabinet dimensions 3 weight 3 cable for Infinet 4 length 4 card reader ABA jumpers B-3 wiring 37 Wiegand jumpers B-4 wiring 33, 35 card readers length of wire to 6 Proximity power supply requirements 37 circuit requirements for power 3 configuration planning 9 counter inputs wiring 32 E enclosure Underwriters Laboratories requirements 6, 10 environments for operating 6 exit buttons length of wire to 30 expansion modules connecting 42 expansion port purpose 42 G ground correcting 6 inspecting 6 requirements 5 I Infinet lightning arrester for 4 selecting port for 22 wiring 23 Infinet cable connecting 21 Infinet cable numbers 4 ACX 780 Installation Guide Technical Manuals Online! - http://www.tech-man.com Index-1 inputs card reader wiring 33, 35, 37 door switch wiring 28 keypad wiring 39 motion sensor wiring 30 standard two wire wiring 32 wiring rules 25 J jumpers location of card reader jumpers B-2 setting for AC voltage 16 K keypad inputs length of wire to 39 wiring 39 knockouts dimensions 10 L LED power indicating mounting 18 lightning arrester for Infinet 4 M motion sensor inputs wiring 30 motion sensors length of wire to 30 mounting controller 10 mounting power indicating LED 18 N normally closed supervisory inputs 26 normally open supervisory inputs 27 O outputs wiring auxiliary 40 wiring door 40 wiring rules 25 P parts inside the controller 15 port selecting for Infinet 22 power battery backup 48 power indicating LED mounting 18 wiring 21 power requirements circuit 3 power supply requirements for Proximity card reader 37 power surges preventing 5 powering up preparations for 47 R RESET button 48 S screw holes locations for mounting 10 service port purpose of 49 shields for Infinet cable connecting 22 required for sensor wire 24 supervisory inputs circuit types 26 Index-2 Technical Manuals Online! - http://www.tech-man.com ACX 780 Installation Guide normally closed 26 normally open 27 recommended types 27 T temperatures for operating 6 two-wire inputs wiring 32 U Underwriters Laboratories enclosure requirements 6, 10 V voltage selecting for AC power 16 W weight cabinet 3 wiring AC power connection 15 card reader ABA 37 Wiegand 33, 35 connecting Infinet cable 21 correct wire gauge for ground 6 counter inputs 32 door outputs 40 door switch inputs 28 Infinet 23 inputs 24 keypad inputs 39 length to card readers 6 length to door outputs 40 length to door switches 28 length to exit buttons 30 length to keypad inputs 39 length to motion sensors 30 motion sensor inputs 30 rules for inputs and outputs 25 two-wire inputs 32 ACX 780 Installation Guide Technical Manuals Online! - http://www.tech-man.com Index-3 Index-4 Technical Manuals Online! - http://www.tech-man.com ACX 780 Installation Guide 30-3001-204 ACX 700 Installation Guide Rev E Technical Manuals Online! - http://www.tech-man.com