Transcript
GENERALINFORMATION: The No. 655 provides feet. All
8 zones
models have the following *
High precision,
*
Dual element
*
Precision die-cast optical alignment.
*
Pre-declined
l
* l
of wide-angle important
parabolic
optical
Wall/corner
fast
and,easy
not observable mounting
system.
head for maximum RF1 protection
plate
when cover
for
fast
and accurate
installation.
Separate pan and tilt control for convenient achieve desired coverage or avoid hazards. Zone direction
range of up to 30
sensor.
optical
zones for
with
features:
computer-designed pyro-electric
coverage
pattern
adjustment
to
is in place.
and easy installation.
The No. 655 requires power from either a 6V.DC or 12V.DC source that 4omA and at least 4 hrs. of standby power.
can provide
The detector will operate at all times, regardless of whether the control which it is connected is ARMED or DISARMED. Whenever (and while) motion detected, the unit's LED will light and its relay contacts will transfer.
to is
PRINCIPLE OF OPERATION: The optical system divides the area into a series of protective zones. A special When an intruder sensor measures the level of far infrared energy in each zone. crosses or enters any zone the resulting change in infrared energy is detected and an alarm condition will exist. The sensor does not respond to visible perature of the room.
light
Because a passive infrared device employs number of units may be used in the same area.
or changes in the background no transmission
of any kind,
Far infrared energy does not penetrate most building materials glass) so the unit responds only to motion inside the room.
temany
(even window
COVERAGECONSIDERATIONSAND TYPICAL IAYDDTS: The pattern of protection provided by the 655 includes five main zones which span an angle of 75"; and three downward zones as shown in Diagrams 1 and 3. The entire
pattern
may be'panned
left
or right 1114
www.PDF-Zoo.com
up to 20°.
The optical system has been designed to give proper coverage'based upon a typical mounting height of 7'. However,.the unit may be mounted at any height between 7' and 9' to achieve a proper 30' pattern. If the unit is to be mounted higher than 9', perhaps as high as 12', or it it is desired to obtain a range of less than 30' for a particular installation, the optical head may be tilted downward. Combinations of mounting height and "tilt" can be used to obtain coverages as shown in Diagram 3. To adjust the tilt of the optical head, grasp the metal casting firmly between thumb and index finger at both sides (where a ridge is provided): pull gently forward until assembly is free, then set the tabs on the casting into the desired notches on the bracket and release. See Diagram 2. IMPORTANT: Do not touch the reflector or sensor surfaces.
:c--J ‘.
,I
"Dead" Zone Caution: Note in Diagram 3 that for several tilt position/mounting height combinations there are indicated "dead zones" within which a person could be moving and not be detected by any of the unit's coverage zones. In general, these dead zones are apt to be present as the unit's mounting height is increased and its coverage pattern is tilted downward. SELECTIN A MOUNTIN LOCATION: The No. 655 Passive Infrared Motion Detector responds to changes in energy which occur when an intruder moves into or out of a zone. Best coverage will be obtained if the mounting site is selected such that the likely direction of intruder motion is ACROSSthe pattern. See Diagram 4a, b and c. ItlSTALLATlOM AND YIRIWG: Passiwe.1.R. units are following recommendations Avoid ducts
remarkably resistant should be observed:
locating unit could be within
where central the protective
Avoid locating of heat.
the unit
Avoid
locating
unit
Avoid
running
in direct
on unstable
alarm wiring
close
heating zones. sunlight
to
false
alarm
radiators, or directly
live
hazards fires
but the
or outlet
above strong
sources
surfaces. to heavy duty electrical
After wiring is complete, the wire entry opening to prevent entry of air movement and drafts into
in the case the PIR unit.
cables. should
be sealed
muNTIN6: IMPORTANT: Be careful during installation DR SENSORSURFACES. WHEN POSITIONING BODY ONLY, AS SHOWNIN DIAGRAM 2. 1.
or adjustment NOTTO TOUCHTHE REFLECTOR THE HEAD ASSEMBLY, GRIP THE DIE-CAST
Mount the wall plate to a firm and vertical surface (flat on wall or in corner) at the recommended height (see previous section). Orient the plate -so that its unit mounting hooks are at the bottom; If wiring is provided from a hole in the mounting surface, center the mounting plate This will align the with the bottom of the pl.ate just above the hole. See. wires with the wiring entry in the case when the unit is secured. Diagram 5.
www.PDF-Zoo.com
'
r
2.
Remove front
cover
by loosening,.the
retaining
screw.
3.
Push the two special hex head screws provided type mounting holes at rear of,the plastic case, been done.
4.
Engage lower hooks on wall plate Attach unit to wall plate, as follows: into case bottom (see Diagram 5) and secure unit to wall plate with the Move detector head left or right two hex'head screws provided; Note: Do not remove detector, head from unit as damage to gain access to screws. to mirror may result.
through if this
the two retainer has not already
Use only the wiring entry at the lower rear of the case and carefully feed the wires along the underside of the printed circuit board. Avoid contact between bare conductors, screws or metal parts likely to contact the printed circuit. Avoid unnecessary carefully. See Diagram 6.
1. 2.
splices
and loops
Connections
should
within
the
be made in this
unit.
Check all
connections
order:
Diagram 6 shows how to connect a closed circuit protective Alarm Terminals: loop. Connect these terminals to a 6V.DC or 12V.DC source that DC 'Terminals: Observe polarity! Continuous auxiliary can provide 40 mA continuously. 6V.DC controls are: capacities for some typical No. No. No. No.
1022: 1023: 1024: 1025:
150 350 200 220
JnA InA mA InA
For 12V.DC operation
it
Continuous
capacity
auxiliary
No. No. No. No.
Nos. 330R-25, Nos. 332R-50,
is necessary
34OR-25: 342Rk50: No. 4080:
250 mA 750 mA 500 InA
to cut the BLUE jumper provided.
of some typical 650 300 220 500
1022-12: 1023-12: 1025-12: 4080-12:
lEV.DC controls
are:
mA. mA mA mA
ADJUSTHENTand TESTING: IMPORTANT:
Wait at least two minutes to walk-test unit.
dfter
connecting
power before
attemptinq
Ali gmnent: The adjustment - and-- testing of the detector should be conducted with the protected area cleared of all people. In some business establishments it will be more convenient to do this after hours. The protective system's control should be OFF during the procedure to prevent unwanted. alarms from being sounded. Remove the front cover. Using a DC Voltmeter (or volt or equivalent) cpnnect the positive test lead located at the extreme left edge of the printed circuit 137 131
www.PDF-Zoo.com
Multimeter, to the Test board.
20K Ohms per Point post,
The meter's negative lead should block (input ground). The meter should
be connected
to
terminal
2 on the
connector
be set to the 2.5V.DC range.
Mask the detector's optics so that motion cannot be detected. The meter should Remove the mask covering the optics, remain indicate approximately 1.6VDC. Motion into any,of the motionless and allow time for the meter to settle. detector's 8 zones will cause the meter to deflect above or below the 1.6V nominal DC level. Meter variations oft 0.5VDC will trigger the unit causing the LED to illuminate and the alarm relay to transfer. Final
Test:
Double-check all connections. Replace the front cover and secure the holding Test operation by walking through screw. Walk-test unit with cover in place. the protective zones and observing walk-test LED. Note: The absolute range of all Passive I.R. units is subject to variation because of different types of clothing, backgrounds, and ambient temperature ensure that the most likely intruder routes are changes. For this reason, well within the protective zones and that walk-testing is carried out. along these routes. MINTAIWIWG PROPEROPERATIONAND COVERAGE: In order to maintain the detector in proper that the following be observed by the user. 1.
Power should
be provided
at all
working
condition,
it
is
important
times.
The unit's DC source should have standby power at least 4 hrs of operation during emergencies. Units should never be re-aimed or relocated assistance of the alarm service company.
3.
The physical surroundings of the protected area should not be changed. or additional If furniture or stock is moved, or air-conditioning the system may have to be readjusted by the heating is installed, alarm service company.
4.
Walk-tests should be conducted proper coverage by each detector.
TROUBLE 1:
monthly
the advice
for
2.
at least
without
available
to confirm
or
continued
UNIT GOES INTO ALARM INTERNITTENTLY FOR NO APPARENTREASONAND WALK-TEST LIGHT 60ES DN WHENALARM CONDITION EXISTS. REHEDY
CAUSE A.
Rapid chanqe in IR level in one of the zones. Check for electric or gas heaters, open flames, electric arcs, or any objects which may be partially in a which can,change temperature raPidly. 138 132
www.PDF-Zoo.com
Identify source of IR or temperature chanqe, Use test meter (see "Alignment") to confirm and Inspect zone locations. Re-position zones so that source of problems is no longer in a zone.
B.
Drafts are creating motion in drapes, display material or overhead lighting fixtures.
Locate source of motion. Eliminate motion or aim zones away from Walk-test unit source. after adjustment to confirm coverage.'
c.
Birds or other small animals are entering area (particularly in warehouses).
Check for and eliminate all possible entry points for birds, cats, dogs, rodents, etc.. Contact exterminator if necessary.
UNIT GOESINTO ALARM INTERMITTENTLY OR CONTINUDUSLYFORNO APPARENT REASON AND WALK-TEST LIGHT DOES NOT COMEON WHENALARM CONDITION
TROUBLE 2:
EXISTS. REMEDY
CAUSE DC voltaqe supply to detector. from panel or power supply inadequate or absent. PROPER SERVED.
a TROUBLE 3:
Check for proper DC voltage at terminals of detector. If absent, check for proper voltage at panel or power suppiy terminals with wiring disconnected. If present, wiring to detector is faulted. Check for open and shorted conditions in wiring. If proper DC voltage is absent, consult instructions for panel or power supply.
RELAY OPERATESNORMALLYBUT UALK-TEST LIGHT DOES NOT OPERATE. REMEDY
CAUSE LED malfunction. broken or shorted
Return Unit to Ademco for service (obtain, Return Authorization Number from Ademco before returning).
Check for leads.
AREA OF COVERAGECHANGES.
TROUBLE4:
CAUSE
REMEDY
A.
Customer has repositioned furniture or equipment in premises.
Caution customer that changes in layout .can affect coverage. Re-aim or relocate the unit according to' installation instructions. Be certain that unit has not been tampered with.
B.
Mountinq surface is unstable. A few degrees vertical shift can change range substantially.
Mount on secure
139
133
www.PDF-Zoo.com
surface.
TROUBLE 5:
UNIT DOES NOT APPEAR TO BE OPERATING. CAUSE Unit
IMPORTANTNOTE:
REMEDY
is not receiving
power.
Check for presence of appropriate input voltage at terminals of unit.
Before any equipment is returned to Ademco for service, a Return Authorization Number should first be obtained from the nearest Ademco Distribution'center. If it becomes necessary to return a unit for repair, the optical head and reflector assembly within the unit should be cushioned by surrounding it with soft packing material (such as tissue, newspaper, foam or plastic bubbles) to protect it from undue stress during shipment. Take care not to touch the reflector or sensor surfaces.
6EHERAL SPECIFICAT.HlIlS: Physical:
Llectrlcal:
Uidth: Height: Depth:
4-l/16" 5-11/16" 2-7/8"
(10.3 cm) (14.5 cm) ( 7.3 cm)
Voltage:
6V.DC or lEV.DC
Current:
40 mA
Standby:
None built-in. be able to provide power.
Power source used should at least 4 hrs. of standby
TO THE INSTALLER
Regularmaintenanceandinspection(atleastannually) bytheinstallerand user is vital tocontinuoussatisfactoryoperationofanyalarn7 system.
frequenttesting bythe
The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting,the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least annually) to insure the system’s proper operation at all times.
140 134
www.PDF-Zoo.com
I?
Selecting a Mounting Location:
30
20
10
0
1C
2c
3c
1 20’ Diagram 1: PkOTECTlON
50’
ZONES 141 135
www.PDF-Zoo.com
IMPORTANT ! DO NOT TOUCH REFLECTOR OR SENSOR SURFACES. GRIP ONLY DIE CAST BODY OF
FLUX MID
DOWNWARD’ POSITION
RMAL
Diagram 2: TILT POSITIONS
www.PDF-Zoo.com
POSITION
Caution: Make tab js placed ‘same slbt on sides of unit.
/
sure in both -
3a
No. 655 DETECTOR NORMAL TILT POSITION
3b
MID TILT POSITION
APPROX. 6 FT “DEAD” ZONE
3d
MAIN
FULLY
ZONE RANGE (MAX)
!
TILT POSlTlON
APPROX. 10 FT. “DEAD” ZONE
0 Diagram
3: RANGES AT VARIOUS MOUNTING HEIGHTS AND TILT POSITIONS 143
137
www.PDF-Zoo.com
I
DOOR
,
4a
FiOT” IDEAL
I DOOR - - __.
1 I
I DISPLAY WINDOW
4b
BETTER
’ DOOR
1 1
I DISPLAY WINDOW
I RR
//
4c
BEST
I L
Diagram 4: TYPICAL LAYOUTS
www.PDF-Zoo.com
DISPLAY WINDOW
\ 1
WALL
HEX
Diagram 5: MOUNTING DETAILS
www.PDF-Zoo.com
PLATE
SCREW
TEST POST
OZY
f-3
.
( ) g-&~(-jOO@@@
2’
I
WALK-TEST’ LED (BUILT- IN) (+I
t-1
FROM DC SOURCE (40 mA MIN.) 6V.DC (LEAVE BLUE JUMPER INTACT) W.D&UT
OTHER CONTACTS 1
71
v
BLUE JUMPER)
CLOSED CIRCUIT PROTECTIVE LOOP
Diagram 6: CONNECTIONS. TERMINALS, JUMPER, ETC.
I’8998
www.PDF-Zoo.com
9/82
146 140
Copyright
8 198 2 PIllWAY
CORPORATlON
.