Air • Magic Ntd1200 Neutral Temperature Dehumidifier Air • Magic

   EMBED


Share

Transcript

Air • magic NTD1200 Neutral Temperature Dehumidifier Air • magic HRV1200/HRV1200HP Heat Recovery Ventilation (passive/active) designed for radiant cooling applications User’s Manual CONTENTS 2 Chapter 1 GENERAL INFORMATION page 5 Chapter 2 TECHNICAL SPECIFICATIONS [NTD1200] page 8 Chapter 3 DEHUMIDIFICATION PERFORMANCE TABLE [NTD1200] page 9 Chapter 4 SUPPLY (ASP) AVAILABLE STATIC PRESSURE (ASP) [NTD1200] page 10 Chapter 5 DRAWINGS [NTD1200] page 11 Chapter 6 SCHEMATIC DIAGRAM AND OPERATING PRINCIPLE [NTD1200] page 13 Chapter 7 ROOM AIR DISTRIBUTION [DEHUMIDIFICATION ONLY] page 14 Chapter 8 HYDRAULIC DIAGRAM page 16 Chapter 9 WIRING DIAGRAM [NTD1200] page 17 Chapter 10 TECHNICAL SPECIFICATIONS [HRV1200] page 18 Chapter 11 EXHAUST (ASP) AVAILABLE STATIC PRESSURE [HRV1200] page 19 Chapter 12 DRAWINGS [HRV1200] page 20 Chapter 13 WIRING DIAGRAM [HRV1200] page 22 Chapter 14 ELECTRICAL CONNECTIONS BETWEEN NTD1200 AND HRV1200 page 23 air • magic 1200 air unit range User's Manual CONTENTS 3 Chapter 15 SCHEMATIC AND OPERATING PRINCIPLE [NTD1200 WITH HRV1200] page 24 Chapter 16 OPERATING MODES [NTD1200 AND NTD1200+HRV1200/HRV1200HP] page 25 Chapter 17 BASICS OF ROOM AIR DISTRIBUTION page 27 Chapter 18 GENERAL AIRFLOW DIAGRAMS page 28 Chapter 19 SUPPLY AVAILABLE STATIC PRESSURE [NTD1200 WITH HRV1200] 19.1 DAMPER IN RECIRCULATION POSITION [NTD1200 WITH HRV1200] 19.2 DAMPER IN HRV POSITION [NTD1200 WITH HRV1200] page 30 page 31 Chapter 20 TECHNICAL SPECIFICATIONS [HRV1200HP] page 32 Chapter 21 DRAWINGS [HRV1200HP] page 33 Chapter 22 WIRING DIAGRAM [HRV1200HP] page 35 Chapter 23 OPERATING MODES [NTD1200 WITH HRV1200 OR HRV1200HP] page 36 Chapter 24 DRAWINGS 24.1 NTD1200 WITH HRV1200 24.2 NTD1200 WITH HRV1200HP page 37 page 39 air • magic 1200 air unit range User's Manual CONTENTS Chapter 25 Chapter 26 4 ACCESSORIES 25.1 FAN1200 25.2 HYDRONIC HEATING AND COOLING COIL FOR FAN1200 25.3 INLET ADAPTER page 41 page 43 page 44 INSTALLATION CLEARANCES page 45 air • magic 1200 air unit range User's Manual Chapter 1 DESCRIPTION 5 air • magic 1200 air unit range User's Manual Chapter 1 GENERAL INFORMATION Radiant Cooling And Heating Systems provides a range of air treatment unit for the HVACR industry. This user’s manual pertains to the neutral temperature (isothermal) dehumidifi- er air • magic NTD1200. The air • magic range of dehumidification and ventilation systems has been specifically designed and manufactured for use in the commercial buildings. Its main functions are to control the relative humidity level, provide ventilation (HRV module require) and increase the Indoor Air Quality (IAQ) and comfort of the occupants. The unit is specifically designed to work in combination with radiant cooling and heating systems. The air • magic 1200 range of units integrates with the control • magic climate control platform offered by . The air • magic NTD1200 differs from traditional dehumidifiers because is able to control the relative humidity maintaining the temperature of the supplied air neutral with the room (isothermal). The air • magic NTD1200 also features an exclusive convective integration function that, when necessary, integrates the cooling and heating effect of the radiant panels, by supplying cooler air (in cooling mode) or warmer air (in heating mode), in order to rapidly obtain the desired thermal and hygrometric conditions. In addition, the air • magic NTD1200 units feature a free-cooling function that makes it possible to mitigate the overheating effect due to solar radiation during the winter. During the design of the air • magic NTD1200 neutral temperature dehumidification units, particular attention was paid to reduce the power consumption and ambient noise levels. air • magic devices can be ducted making it possible to be installed inside of buildings: in plenum ceilings or in mechanical rooms. IMPORTANT NOTE: The air • magic NTD1200 units may not be installed outdoors or in places exposed to the elements! The air • magic NTD1200 unit can be combined with the HRV module (optional), air • magic HRV1200 or air • magic HRV1200HP (with integrated air-to-air Heat Pump) to create a complete air handling system for radiant cooling application. The additional HRV module is equipped with built-in motorized damper and exhaust blower that enable total or partial ventilation: from total air renewal (100% ventilation) with heat recovery to full recirculation (0% ventilation). The efficiency of the cross flow heat exchanger (passive) can easily exceeds 60%, especially during partial recirculation 6 When ventilation need are high, the air • magic NTD1200, combined with the active heat recovery ventilation unit, air • magic NTD1200HP, is the preferred solution An integrated air-to-air heat pump extract the residual energy of the air before his expulsion bringing the efficiency of the heat recovery much more than 100%. In addition to the enormous energy savings, the active heat recovery ventilation allows ventilation of the building even when the external conditions are prohibitive and the traditional system would be forced to be set in a partial recirculation and therefore wouldn’t meet the ventilation requirement. The air • magic 1200 device features several operating functions: • Dehumidification (at neutral temperature) • Convective integration function (heating and cooling) • Heat recovery ventilation (HRV module air magic HRV1200 or HRV1200HP required) • Free-cooling (HRV module air HRV1200 or HRV1200HP required) For more information read Chapter 16 air • magic 1200 air unit range User's Manual • • magic Chapter 1 7 GENERAL INFORMATION IMPORTANT NOTE: The correct model should be selected based on the number of people occupying the conditioned environment rather than its dimensions, as listed in the technical specifications table, calculated at specified conditions. Target number of people (NTD1200): 70 Outdoor air: 90°F - 50% R.H. As a reference, required ventilation per person following the ASHRAE standard 62-89 (ventilation guidance): schools 15 CFM per person offices 20 CFM per person hospital 25 CFM per person offices 20 CFM Metabolic activity: Average Body weight: Clothing: Average radiant temperature: Air speed: 1.2 met 154 lbs 0.6 clo 74.3F < 0.34 f/s air • magic 1200 air unit range User's Manual Chapter 2 TECHNICAL SPECIFICATIONS 8 Coil water temperature in cooling mode Min water temp: Max water temp: 50 °F 100°F 20 % 80 % 45 °F 75 °F Coil water temperature in heating mode Min water temp: 75 °F Max water temp: 130 °F pints/day 440 Thermal cooling input* (for Neutral Dehumidification function) Btu/h 37,530 Sensible cooling capacity* (Convective Integration) Btu/h 20,470 Nominal Airflow CFM 1,200 Max. supply available static pressure (S3 - High Speed) @120CFM inch of w.c. 0.64 Max supply available static pressure (S2 - Medium Speed) @1200CFM inch of w.c. 0.37 Max supply available static pressure (S1 - Low Speed) @1200CFM inch of w.c. 0 Nominal water flow (60°F) GPM 6.6 Water circuit loss of head ft. of head 6.7 oz. 53 Sound power level dB(A) 55 Sound pressure level (at 3.28 ft.) dB(A) 45 Rated power consumption* KW 2.5 Max. power consumption (Compressor ON and blower S3 high speed ) KW 2.8 W 430 Rated Amps absorbed* Amps 12.4 Max. Amps. absorbed Amps 14.6 Refrigerant gas quantity (R410a) ELECTRICAL SPECIFICATIONS Min temperature: Max temperature: Min relative humidity: Max relative humidity: WEIGHTS AND DIMENSIONS The following ambient conditions in indoor environments are required for proper operation of the air • magic NTD1200 unit dehumidifier: MECHANICAL SPECIFICATIONS Water removal* Supply Blower Max. power consumption (S3 - High Speed) Dust and water protection rating Power supply IP 44 VAC / Ph / Hz 220 / 1+N / 60 Height inch 19 1/4 Width inch 32 1/4 Depth inch 40 1/2 Weight lbs. 242 *At the following conditions: room supply air at 80°F / 65% R.H., coil supply water temperature 60F air • magic 1200 air unit range User's Manual DEHUMIDIFICATION PERFORMANCE TABLE The performances indicated in the chart refer to the following conditions: Airflow: Water flow: 1,200 CFM 6.6 GPM Maximum sensitive heat output in winter seasons based on indoor temperature and coil water supply temperature Max sensible heat output (in heating mode) by the pre-heating water coil of the dehumidifier module in function of the indoor temperature to maintain neutral air output (same indoor temperature). Outside temperature: 32 °F Coil supply water temperature: 104 °F Airflow: 1200 CFM RELATIVE HUMIDITY WATER TEMPERATURE 55% 65% AMBIENT TEMPERATURE 78°F Dehumidifier performance is a function of: - ambient temperature - relative humidity - refrigerated water temperature 9 65°F 240 pints/day 289 pints/day 60°F 300 pints/day 367 pints/day 55°F 356 pints/day 440 pints/day AMBIENT TEMPERATURE 75°F Chapter 3 65°F 179 pints/day 216 pints/day 60°F 225 pints/day 276 pints/day 55°F 266 pints/day 329 pints/day INDOOR TEMPERATURE WATER TEMP. 68°F 72°F 75°F 82°F 95°F 22,100 Btu/h 19,100 Btu/h 16,300 Btu/h 10,200 Btu/h 104°F 29,600 Btu/h 26,600 Btu/h 23,500 Btu/h 17,700 Btu/h 113°F 40,600 Btu/h 34,100 Btu/h 31,000 Btu/h 24,900 Btu/h 122°F 44,700 Btu/h 41,600 Btu/h 38,500 Btu/h 32,400 Btu/h 131°F 52,200 Btu/h 49,100 Btu/h 46,000 Btu/h 39,900 Btu/h 68°F 72 75°F 82°F NA Btu/h NA Btu/h NA Btu/h NA Btu/h INDOOR TEMPERATURE Sensible heat output (HRV damper set 100% in ventilation) air • magic 1200 air unit range User's Manual Chapter 4 SUPPLY (ASP) AVAILABLE STATIC PRESSURE [NTD1200] 10 1.6 AVAILABLE STATIC PRESSURE* (Inch w.c.) 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0 100 200 300 400 500 600 700 800 AIRFLOW (CFM) 900 1000 1100 1200 1300 S1 - LOW SPEED S2 - MEDIUM SPEED *ASP is the amount of external static loss (of the ducting) that the unit can overcome at a specific CFM. ASP = ESP of the internal supply blower - DPL internal device losses (e.g. coil) S3 - HIGH SPEED air • magic 1200 air unit range User's Manual Chapter 5 DRAWINGS [NTD1200] 11 anchoring brackets anchoring brackets supply outlet return inlet water coil return outlet air relief valve anchoring brackets RJ45 connector cable feedthroughs water coil supply inlet supply outlet return inlet moisture discharge outlet cable feedthroughs SUPPLY SIDE AND CONNECTIONS SIDE electric board cover CONNECTION SIDE AND RETURN SIDE air • magic 1200 air unit range User's Manual Chapter 5 DRAWINGS [NTD1200] 12 ROOM AIR RETURN 718 983 ROOM AIR SUPPLY TOP VIEW 487 421 819 387 1024 696 552 951 SUPPLY SIDE VIEW CONNECTIONS SIDE VIEW RETURN SIDE VIEW air • magic 1200 air unit range User's Manual Chapter 6 SCHEMATIC DIAGRAM AND OPERATING PRINCIPLE [NTD1200] The refrigeration system of the air • magic NTD1200 dehumidifier’s includes two high efficiency rotary compressors with two different size. This technology ensures the maximum extraction with the lowest consumption of electrical energy (up to 50%) activating only one compressor, or their combination, to satisfy the actual sensible heat load. The humid air extracted from the room, through a high-efficiency blower [5] crosses the air filter [1] where the suspended dust particles are separated and eliminated from the air. The air continues through a finned pre-treatment coil [2] that is supplied with the same water circulating in the radiant panel closed loop [10]. This cause a preliminary air temperature drop in order to induce high relative humidity (air saturation). In the next step, the air passes through the evaporator [3] to further lower the air temperature below the dew point. This intense cooling cycle causes the condensation of the water vapor of the air. The resulting water is collected in a specific tank and expelled through the drain. After passing through the evaporator, the air has a low water content and its temperature is below that of the ambient. The air then travels through the condenser coil [4] and is heated until reaching isothermal (neutral temperature air) conditions. The air • magic NTD1200 features an unique operation mode: CONVECTIVE INTEGRATION. The radiant cooling (or heating) effect of the radiant 5 ROOM AIR SUPPLY 4 3 8 13 1 2 ROOM AIR RETURN 7 6A 9A 6B 9B 10 11 1. AIR FILTER 5. BLOWER 9A. PRE-TREATMENT SOLENOID VALVE 2. AIR PRE-TREATMENT COIL 6. COMPRESSOR (A:60% B:40%) 9B. WATER CONDENSER SOLENOID VALVE 3. EVAPORATOR 7. THERMAL EXPANSION VALVE 10. WATER SUPPLY 4. AIR CONDENSER 8. WATER CONDENSER 11. WATER RETURN ceiling system is “integrated” by a supplemental convective cooling effect (or heating). The radiant circuit water is pumped through the dehumidification unit and its water flow is modulated by controlling the solenoid valves [9A]. This allows to shift from an isothermal condition to an additional air cooling (or air heating) convective integration. In cooling mode (only), the DEHUMIDIFICATION function can also be combined with CONVECTIVE INTEGRATION (cooling). In this case the heat produced in the refrigeration cycle is largely dissipated by the cold water flowing through the additional condenser [8] connected in series with the air condensed [4]. The solenoid valve [9B], controlled by the climate control system (control • mag- ic), opens to allow the cold water from the hydronic radiant ceiling system to circulate through the water condenser [8]. By controlling the water flow, the supply air temperature can be regulated at a temperature a few degree below the room temperature (below neutral temperature). In heating mode (only) with the FREECOOLING function, the valves [9A] and [9B] are shut to supply fresh external air into the environment, while the CONVECTIVE INTEGRATION function fully opens the valves [9A] and [9B] to intake hot water and heat the room return air and supply air a few degrees above the room temperature (above neutral temperature). air • magic 1200 air unit range User's Manual Chapter 7 ROOM AIR DISTRIBUTION [DEHUMIDIFICATION ONLY] SUPPLY FROM DUCTS AND/OR CEILING PLENUM The unit air • magic NTD1200, unless combined with the HRV module air • magic HRV1200 or HRV1200HP works only as a dehumidifier at neutral temperature or below ambient temperature when set in CONVECTIVE INTEGRATION mode. The unit can be installed ceiling mounted or floor freestanding. The air • magic NTD1200 units, are able to overcome the air pressure losses of suspended ceiling plenum and supply/return ducts. Air distribution through plenum or ducts are the most appropriate and may also coexist as shown in the examples to the side. Figure 1 - NEUTRAL TEMPERATURE DISPLACEMENT DISTRIBUTION “A” Since the dehumidifier is designed only for the extraction of ambient humidity, there are no particular requirements for air distribution. Humidity, in fact, is a pressure and tends to self balancing among various zones, without any ducting. Air naturally moves from areas of higher pressure to areas of lower pressure and the only condition necessary for the migration of moisture between zones is the presence of natural flow opening (e.g. door gaps). Figure 2 - NEUTRAL TEMPERATURE DISPLACEMENT DISTRIBUTION “B” air • magic 1200 air unit range User's Manual 14 Chapter 7 ROOM AIR DISTRIBUTION [DEHUMIDIFICATION ONLY] The air • magic NTD1200 units can be ducted allowing installation also in dedicated areas as well as in mechanical rooms external to the conditioned space for easier maintenance. IMPORTANT NOTE: INSTALLATION MUST ALWAYS BE INDOORS WITH THE UNIT PROTECTED FROM THE ELEMENTS. Figure 3 - MIXED AIR DISTRIBUTION air • magic 1200 air unit range User's Manual 15 Chapter 8 HYDRAULIC DIAGRAM 16 The water supply line for the air • magic NTD1200 model must be independent, separate from the manifolds, and sized for the specific water flow required (6.6 GPM). It can be branched both upstream or downstream form the mixing valve of the secondary loop and, if necessary, equipped with a pump that can be controlled by the control • magic radiant cooling and heating electronic control unit. No motorized valves are needed because they are already built into the units (water flow regulation). ray • magic THERMALCOOLING GENERATION ray • magic ray • magic air • magic NTD1200 air • magic 1200 air unit range User's Manual Chapter 9 WIRING DIAGRAM 17 TE POWER SUPPLY N 208-230V/60Hz/1Ph L1 HRV BLOWER HRV MOTORIZED DAMPER SUPPLY WATER PROBE CONDENSER PROBE EVAPORATOR PROBE SUPPLY AIR PROBE + HUMIDITY DEHUMIDIFICATION VENTILATION CONVECTIVE INTEGRATION HRV HEATING/COOLING BLOWER SPEED FREECOOLING ECONOMY G G0 + GND B1 B2 B3 GND B4 B5 VG VG0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 GND + - C1 NO1 NO2 NO3 C1 RS485 SERIAL BUS USER CONFIGURATION C4 NO4 NO5 NO6 C4 C7 NO7 C7 NO8 C8 NO8 NO C NO C NO C NO C A2 NC NO COM NC NC NO NO COM COM NC A1 A2 A1 NC NO COM A1 A2 A2 NO NC A1 A2 A1 COM NO COM 24V TRANSFORMER 110-230V PRE-TREATMENT SOLENOID VALVE INTEGRATION SOLENOID VALVE SUPPLY BLOWER COMPRESSOR 151 COMPRESSOR 222 TE N L1 TE N Vmin Vmed VmAX Y3 G G0 TE N L1 Y4 G G0 IDC1 ID1 IDC1 ID2 IDC1 ID3 IDC1 ID4 IDC1 ID5 IDC1 ID6 IDC1 ID7 IDC1 ID8 G G0 B1 B2 G0 B3 G0 B4 G0 B5 TE N C1 N C2 N Vmin Vmed Vmax Y1 G G0 Y2 G G0 G G0 N L1-Fus.1A TE A1 A2 A1 A2 A1 A2 air • magic 1200 air unit range User's Manual Chapter 10 TECHNICAL SPECIFICATIONS [HRV1200] 18 Technical specifications of the Heat Recovery Ventilation (HRV) module air • magic HRV1200 MODEL air • magic HRV1200 Maximum heat recovery efficiency % 75 Heat recovery efficiency with primary / exhaust ratio 1/1 % 58 Heat recovery efficiency with primary / exhaust ratio 0.75/1 % 67 Maximum heat recovered* Btu/h 40,000 Nominal airflow CFM 1,200 Max. exhaust available static pressure (S3 - High speed) @1200CFM inch of w.c. 0.58 Ventilation head loss inch of w.c. 0.4 Recirculation head loss inch of w.c. 0.24 W (HP) 300 (1/3) Max. power consumption (S3 - High Speed) We 430 Rated Amps absorbed* A 1.7 Max. Amps. absorbed A 2.2 Vac / Ph / Hz 220 / 1 / 60 Rated power consumption* Power supply Dust and water protection rating IP 44 Height inch 19 1/4 Width inch 37 1/4 Depth inch 53 1/2 Weight Lbs 180 *At the following conditions: external temperature 32°F room supply air at 68°F and outlet air flow equal to inlet air • magic 1200 air unit range User's Manual Chapter 11 EXHAUST (ASP) AVAILABLE STATIC PRESSURE [HRV1200] 19 1.6 1.4 AVAILABLE STATIC PRESSURE* (inc of w.c.) 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0 100 200 300 400 500 600 700 AIRFLOW (CFM) *ASP is the amount of external static loss (of the ducting) that the unit can overcome at a specific CFM. ASP = ESP of the internal exhaust blower - DPL internal device losses (heat exchanger) 800 900 1000 1100 1200 1300 S1 - LOW SPEED S2 - MEDIUM SPEED S3 - HIGH SPEED air • magic 1200 air unit range User's Manual Chapter 12 DRAWINGS [HRV1200] room air return inlet 20 anchoring bracket anchoring bracket anchoring bracket outside air inlet anchoring bracket anchoring bracket Optional exhaust air outlet anchoring bracket exhaust air outlet anchoring bracket moisture drainage air supply plenum for connection with dehumidifier moisture drainage electric board cover room air return inlet outside air inlet cable passthroughs Optional electric board cover SUPPLY SIDE AND EXHAUST / CONNECTION SIDE OUTSIDE AIR SIDE AND ROOM AIR RETURN SIDE air • magic 1200 air unit range User's Manual Chapter 12 DRAWINGS [HRV1200] OUTSIDE AIR 21 1238 570 x 398 EXHAUST AIR 1354 398 811 852 570 x 398 ROOM AIR RETURN 1304 402 487 1354 398 945 ROOM AIR RETURN SIDE VIEW EXTERNAL AIR SIDE VIEW ROOM AIR SUPPLY SUPPLY SIDE VIEW 387 TOP VIEW EXHAUST AIR SIDE VIEW air • magic 1200 air unit range User's Manual Chapter 13 WIRING DIAGRAM [HRV1200] 22 The heat recovery unit air • magic HRV1200 is powered and controlled by the electronic board on the dehumidifier air • magic NTD1200. DAMPER HRV DAMPER Vmin Vmed Vmax BLOWER TE N TE N V1 V2 V3 Y3 G G0 TE IMPORTANT NOTE: Excessive air output could cause a pressure drop in the zones and give rise to a number of problems, which decrease the efficiency of the units. HRV BLOWER Electrical connections entail wiring the seven lines exiting the dehumidifier terminal board to that of the recovery unit, taking care to connect the wires according to their names. The recovery unit is already set to supply an airflow less to or equal to intake volume. air • magic 1200 air unit range User's Manual NC COM NO NC COM NO A2 A1 A1 NC COM NO A2 A2 A1 A1 NC COM NO A2 A2 A1 A1 C C NO NO NC COM NO A2 A1 A2 A2 C C NO NO VG VG0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 B5 B4 B1 B2 B3 GND + - GND A1 RS485 SERIAL BUS G G0 23 NO8 C8 NO8 C7 NO7 C7 C1 NO1 NO2 NO3 C1 GND C4 NO4 NO5 NO6 C4 ELECTRICAL CONNECTIONS BETWEEN NTD1200 AND HRV1200 + Chapter 14 NC COM NO DAMPER BLOWER TE N V1 V2 V3 Y3 G G0 TE 208-230 Vac Y3 G G0 THIS CONNECTION MUST BE MADE BY THE INSTALLER air•magic HRV1200 ELECTRIC BOARD TE N Vmin Vmed Vmax Y3 G G0 RS485 SERIAL BUS air•magic NTD1200 ELECTRIC BOARD TE N Vmin Vmed Vmax TE N L1 TE N Vmin Vmed VmAX Y3 G G0 TE N L1 Y4 G G0 IDC1 ID1 IDC1 ID2 IDC1 ID3 IDC1 ID4 IDC1 ID5 IDC1 ID6 IDC1 ID7 IDC1 ID8 G G0 B1 B2 G0 B3 G0 B4 G0 B5 TE N C1 N C2 N Vmin Vmed Vmax Y1 G G0 Y2 G G0 G G0 N L1-Fus.1A TE 208-230 Vac POWER SUPPLY 208V-230 - 60Hz TE N L1 air • magic 1200 air unit range User's Manual Chapter 15 SCHEMATIC AND OPERATING PRINCIPLE [NTD1200 WITH HRV1200] Adding the heat recovery ventilation air • magic HRV1200 module create a truly compact air treatment unit with extra features described hereafter. 24 RECIRCULATION FUNCTION ROOM AIR RETURN ROOM AIR SUPPLY 1 5 4 3 2 Operating mode diagrams to the side. 1 8 7 13 6A 9A 12 6B 14 9B 10 11 HRV FUNCTION ROOM AIR SUPPLY ROOM AIR RETURN 1 5 4 3 2 1 OUTSIDE AIR 1. AIR FILTER 2. PRE-TREATMENT COIL 3. EVAPORATOR 8 7 4. AIR CONDENSER) 5. BLOWER 13 6A 9A 6. COMPRESSOR(A:60% B:40%) 12 7. THERMAL EXPANSION VALVE 6B 14 9B 10 8. WATER CONDENSER 9A. PRE-TREATMENT SOLENOID VALVE 9A. WATER CONDENSER SOLENOID VALVE 11 EXHAUST AIR 10. WATER SUPPLY 11. WATER RETURN 12. TWO-WAY MOTORIZED DAMPER 13. CROSS-FLOW HEAT EXCHANGER 14. EXHAUST BLOWER air • magic 1200 air unit range User's Manual Chapter 16 OPERATING MODES [NTD1200 AND NTD1200+HRV1200/HRV1200HP] DEHUMIDIFICATION FUNCTION (air • magic NTD1200 or air • magic NTD1200 + HRV1200/HRV1200HP) This function is used exclusively during the summer. Dehumidification is activated by a specific bus command (Monobus) with RS485 serial connection. Alternatively, the function can be activated by closing the dry contact [DEHUMIDIFICATION] indicated in the wiring diagram (see Chapter 9 and 14). At reception of command, the blower is started followed by the compressor after two minutes. Dehumidification is performed by activating the internal refrigeration circuit that, in tandem with the hydronic circuit, possesses high dehumidification efficiency, thus ensuring neutral temperature room air supply regulated by the modulating valve of the per-treatment coil. The hydronic circuit uses the same cooling water of the radiant panels. Dehumidification is controlled on the basis of set humidity levels or dew point threshold. This action guarantees comfortable hygrometric conditions and high cooling efficiency of the panels. Please keep in mind that panel surface temperature is variable and it is controlled in function of the room dew point; therefore, panel efficiency is highest if humidity levels are kept in check. The table below contains optimal relative humidity values and dew point temperature in function of the type of building. BUILDING TYPE RELATIVE HUMIDITY DEW POINT TEMP. RESIDENTIAL 55% ÷ 65% 60°F ÷ 62.5°F HOTELS 55% ÷ 60% 59°F ÷ 61°F OFFICES 50% ÷ 55% 57°F ÷ 60°F STORES 55% ÷ 60% 57°F ÷ 59°F HOSPITALS 55% ÷ 60% 59°F ÷ 61°F CONVECTIVE INTEGRATION FUNCTION (air • magic NTD1200 or air • magic NTD1200 + HRV1200/HRV1200HP) This function consist in the convective integration of the radiant effect of the ceiling panels with air that is gently supplied from the dehumidifier at temperature slightly above (heating) or below (cooling) the room air temperature. The convective integration function is activated by a specific bus command (Monobus) with RS485 serial connection. In alternative, the function can also be activated by closing the dry contact [CONVECTIVE INTEGRATION] indicated in the wir- 25 ing diagram (see Chapter 9 and 14). COOLING MODE CONVECTIVE INTEGRATION + DEHUMIDIFICATION This operation engages and opens the internal solenoid valves that regulates the supply water flus into the water condenser and the pre-treatment coils. A large portion of the heat produced by the refrigeration circuit during dehumidification is transferred to the cold water of the radiant system, thus allowing to supply air at a temperature lower that the room temperature. CONVECTIVE INTEGRATION + HRV The convective integration function can also be set for the HRV function. As in the previous case, the valve connected to the pre-treatment coils is opened, thus increasing cold water intake to cool down the incoming air at temperatures lower than room air temperature. HEATING MODE CONVECTIVE INTEGRATION OR CONVECTIVE INTEGRATION + HRV The convective integration function in heating mode acts on the unit's internal valves, opening them to full hot water intake capacity, thus providing an air output with temperatures above room air temperature. air • magic 1200 air unit range User's Manual Chapter 16 OPERATING MODES [NTD1200 AND NTD1200+HRV1200/HRV1200HP] HRV FUNCTION (only: air • magic NTD1200 + HRV1200/ HRV1200HP) The HRV function is related to the combination of the air • magic HRV1200/HRV1200HP with the air • magic NTD1200. Connecting the HRV module upstream from the dehumidifier air return, creates a compact air treatment station with heat recovery from the exhaust air. The dehumidifier itself reduces internal air moisture, but this add-on module also allows a supply of make-up clean outside air. The air can also be pre-treated (convective integration function) and its level of humidity reduced (dehumidification function) to ensure maximum comfort. Air ventilation can be total or partial (with recirculation) by manually adjusting the damper to the appropriate opening. HRV function is activated by specific bus command (Monobus) with RS485 serial connection. In alternative, the HRV function may also be activated by closing the dry contact [HRV] indicated in the wiring diagram (see Chapter 9 and 14). HEATING AND COOLING MODES HRV The exhaust and supply air blowers are activated and the two way damper mechanism (recirculation and ventilation) built into the air • magic HRV1200/HRV1200HP unit is activated to close the recirculation bypass and open the ventilation damper. In addition, the internal solenoid valves modulates in order to obtain neutral supply air. COOLING MODE HRV + CONVECTIVE INTEGRATION During particular conditions, the HRV function can be used with the cold convective integration feature. The valves of the plate heat exchanger and of the pre-treatment coil are opened to allow an increase of cold water intake, thus allowing incoming air supply at temperatures below neutral air temperature. 26 FREECOOLING FUNCTION (only: air • magic NTD1200 + HRV1200/ HRV1200HP) Freecooling is activated by a specific bus command (Monobus) and serial connection RS485. This is mostly a winter function when solar radiation overheats environments despite the relatively mild outside temperatures. This function, according to a temperature differential that can be set in regards to set of zones, shut-off hot water intake to the unit by means of its internal valves. The output temperature is no longer adjusted to maintain neutral air but, by intake of cool outside air through the crossflow heat exchanger, allows a supply of cooler room incoming air (in compatibility with outside temperature) to decrease thermal loads inside zones treated. HEATING MODE HRV+ CONVECTIVE INTEGRATION During particular environmental conditions, the HRV function can be used with the hot convective integration feature. The valves of the plate heat exchanger and of the pre-treatment coil are opened to allow an increase of hot water intake, thus allowing incoming air supply at temperatures above neutral air temperature. air • magic 1200 air unit range User's Manual Chapter 17 BASICS OF ROOM AIR DISTRIBUTION 27 Inside a closed space, occupants and operating electrical equipment, produce heat and airborne pollutant particles that are released into the air. Therefore, both people and equipment can be considered heat sources able to activate natural hot air movements, which can be compared to virtual ducts, that push pollutants upward. HVAC systems based on displacement ventilation use these vertical natural convection flows as a mechanism for transporting ambient air, thus obtaining maximum performance with significant energy savings. Incoming air is released at low speeds (~ 100 FPM) from air outlets set near the flooring, and naturally pushes ambient air full of volatile pollutants towards the ceiling vents. Mixed distribution induces re-mixing of the pollutants present in zones, thus employing - to properly clean air - double the amount of airflow used by a displacement ventilation system. Displacement obtains maximum performance during all seasons in air conditioning systems combined with air treatment, as proposed by the technology Radiant Cooling And Heating Systems. In this mode, air is output at neutral tempera- ture, equal to that of comfort, exclusively with HRV and DEHUMIDIFICATION functions enabled, given that the control of thermal loads is performed by the radiant panels. Hence, air can be supplied at lower speeds to drastically reduce displacement (~ 80%) and achieve a correct ambient stratification with consequential exploitation of the “piston” effect across the full mass of air. air • magic 1200 air unit range User's Manual Chapter 18 GENERAL AIRFLOW DIAGRAM 28 DUCTS AND / OR CEILING PLENUM The dehumidifier air • magic NTD1200 [1], combined with the air • magic HRV1200 or HRV1200HP module [2], become a complete air treatment system that can provide neutral air dehumidification, cold and hot air convective integration and heat recovery ventilation. The room air distribution type recommended in conjunction with the use of radiant ceiling panels, is neutral air displacement [Figures 1, 2 and 3]. In many cases, the space above the ray • magic panels can act as a plenum for the exhaust air intake (when air-tightness and insulation conditions exist), with air slots possibly located in the perimeter above windows. This yields various advantages: • reduction of ducting costs and space • conceals exhaust grilles with air inlet slots (which may contain air filters) • directly intakes hot air produced by the windows to avoid its distribution into the environment • reduces the need of primary air due to greater ventilation efficiency (eV) Also in a mixed distribution [Figure 4] the space above the suspended ceiling can be used as exhaust air plenum as well as valuable space for ducting. 1 2 Figure 1 - NEUTRAL AIR DISPLACEMENT DISTRIBUTION “A” 1 2 Figure 2 - NEUTRAL AIR DISPLACEMENT DISTRIBUTION “B” air • magic 1200 air unit range User's Manual Chapter 18 GENERAL AIRFLOW DIAGRAM The best combination of limited ducting space, cost saving and overall efficiency can be seen in figure 3. This figure represents a neutral air displacement system with dropped ceiling plenum for exhaust air intake and return air through a raised-floor air plenum system (messana ayro) with fresh air supplied through a series of floor vents, distributed across the entire flooring surface. This type of distribution, ideal for offices, allows full exploitation of suspended ceilings and raised-floor for the passage of wires and allows a more capillary air distribution. This leads to less airflow per vent and decreases the airflow perception while increasing overall comfort. 29 1 2 Figure 3 - NEUTRAL AIR DISPLACEMENT DISTRIBUTION “C” 1 2 Figure 4 - MIXED AIR DISTRIBUTION air • magic 1200 air unit range User's Manual Chapter 19 SUPPLY AVAILABLE STATIC PRESSURE [NTD1200 + HRV1200] Chapter 19.1 SUPPLY ASP WITH DAMPER IN RECIRCULATION POSITION [NTD1200 + HRV1200] 1.6 AVAILABLE STATIC PRESSURE (inch of w.c.) 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 AIRFLOW (CFM) S1 - LOW SPEED) *ASP is the amount of external static loss (of the ducting) that the unit can overcome at a specific CFM. ASP = ESP of the internal supply blower - DPL internal device losses (e.g. coil) S2 - MEDIUM SPEED S3 - HIGH SPEED air • magic 1200 air unit range User's Manual 30 Chapter 19 SUPPLY AVAILABLE STATIC PRESSURE [NTD1200 + HRV1200] Chapter 19.2 SUPPLY ASP WITH DAMPER IN HRV POSITION [NTD1200 + HRV1200] 31 1.6 AVAILABLE STATIC PRESSURE (inch of w.c.) 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0 100 200 300 400 500 600 700 800 900 AIRFLOW (CFM) *ASP is the amount of external static loss (of the ducting) that the unit can overcome at a specific CFM. ASP = ESP of the internal supply blower - DPL internal device losses (e.g. coil) 1000 1100 1200 1300 S1 - LOW SPEED S2 - MEDIUM SPEED S3 - HIGH SPEED air • magic 1200 air unit range User's Manual Chapter 20 TECHNICAL SPECIFICATIONS [HRV1200HP] WEIGHTS AND DIMENSIONS ELECTRIC SPECS THERMAL SPECIFICATIONS Technical specifications of the Heat Recovery Ventilation (HRV) module air • magic HRV1200HP 32 Maximum heat recovery efficiency % 170 Heat recovery efficiency (winter)* % 100 Maximum heat recovered (winter)* Btu/h 47,000 Heat recovery efficiency (summer)** % 110 Maximum heat recovered (summer)** Btu/h 36,000 Nominal airflow CFM 1,200 Max. available static pressure (S3 - High speed) inch of w.c. 0.58 Ventilation head loss inch of w.c. 0.48 Recirculation head loss inch of w.c. 0.24 Refrigerant gas R410a oz. 63.5 Max. power consumption (S3 - High speed) W 1,700 Vac / Ph / Hz 220 / 1 / 60 Power supply Dust and water protection rating IP 44 Height inch 19 1/4 Width inch 40 Depth inch 57 Weight Lbs 255 * At the following conditions: external temperature 32°F room supply air at 68°F and outlet air flow equal to inlet ** At the following conditions: external temperature 95°F room supply air at 78.8°F and outlet air flow equal to inlet air • magic 1200 air unit range User's Manual Chapter 21 DRAWINGS [HRV1200HP] room air return inlet 33 anchoring bracket anchoring bracket anchoring bracket outside air inlet anchoring bracket anchoring bracket Optional exhaust air outlet anchoring bracket exhaust air outlet anchoring bracket air supply plenum for connection with dehumidifier moisture drainage electric board cover outside air inlet room air return inlet Optional electric board cover cable passthroughs SUPPLY SIDE AND EXHAUST / CONNECTION SIDE OUTSIDE AIR SIDE AND ROOM AIR RETURN SIDE air • magic 1200 air unit range User's Manual Chapter 21 34 DRAWINGS [HRV1200HP] OUTSIDE AIR 1328 570 x 398 EXHAUST AIR 871 570 x 398 912 ROOM AIR RETURN 1394 EXTERNAL AIR SIDE VIEW ROOM AIR SUPPLY 1005 ROOM AIR RETURN SIDE VIEW 402 487 398 1444 387 TOP VIEW 1444 SUPPLY SIDE VIEW EXHAUST AIR SIDE VIEW air • magic 1200 air unit range User's Manual WIRING DIAGRAM HRV1200HP A2 A1 C A1 G G0 NC COM B1 B2 B3 B4 GND A1 NC C1 NO1 NO2 NO3 C4 NO4 NO5 C5 COM NO A1 GND + - A2 NO RS485 SERIAL BUS Y1 Y2 Y3 GND ID1 ID2 ID3 ID4 ID5 ID6 IDC1 A2 NO DIGITAL INPUT EXHAUST EXCHANGER PROBE SUPPLY ECHANGER PROBE INLET PROBE SUPPLY PROBE HEAT PUMP PRESSURE SWITCH VENTILATION CONVECTIVE INTEGRATION HRV HEATING/COOLING BLOWER SPEED EXCHANGER C OUTPUT FOR FAN TE N L1 TE N L1 G0 G Y2 Y3 GND B1 B2 B3 B4 ID1 ID2 ID3 ID4 ID5 ID6 N L1-Fus.1A G0 G G0 G Y1 TE N Vmin Vmed Vmax 4WV COM TE NO POWER SUPPLY TE 208-230V/60Hz/1Ph N L1 35 A2 Chapter 22 NC COM NO COMPRESSOR CHANGE OVER VALVE BLOWER DAMPER M TRANSFORMER 110-230V 24V air • magic 1200 air unit range User's Manual Chapter 23 SCHEMATIC AND OPERATING PRINCIPLE [NTD1200 WITH HRV1200HP] RECIRCULATION FUNCTION The air • magic NTD1200 unit can be combined with the HRV module (optional) air • magic HRV1200HP (with integrated air-to-air Heat Pump) to create a complete air handling system for radiant cooling application. ROOM AIR SUPPLY 5 4 ROOM AIR RETURN 1 2 17 1 13 8 When ventilation need are high, the air • magic NTD1200, combined with the active heat recovery ventilation unit, air • magic NTD1200HP, is the preferred solution The air • magic NTD1200HP features an air-toair heat pump to extract the residual energy of the air before his expulsion. This allow to increase the efficiency of the heat recovery much more than 100%. In addition to the enormous energy savings, the active heat recovery ventilation allows ventilation of the building even when the external conditions are prohibitive and the traditional system would be forced to be set in a partial recirculation and therefore wouldn’t meet the ventilation requirement. 3 36 7 6A 16 9A 12 6B 15 9B 14 6C 10 11 HRV FUNCTION ROOM AIR RETURN 1. AIR FILTER 2. PRE-TREATMENT COIL ROOM AIR SUPPLY 5 4 3 1 2 3. EVAPORATOR 4. AIR CONDENSER 17 5. BLOWER 1 6. COMPRESSOR(A:60% B:40%) 6C. HRV COMPRESSOR 8 7. THERMAL EXPANSION VALVE 7 13 6A 16 9A 6B OUTSIDE AIR 12 8. WATER CONDENSER 9A. PRE-TREATMENT SOLENOID VALVE 9A. WATER CONDENSER SOLENOID VALVE 10. WATER SUPPLY 15 11. WATER RETURN Operating mode diagrams to the side. 9B 6C 10 14 12. TWO-WAY MOTORIZED DAMPER 13. CROSS-FLOW HEAT EXCHANGER 11 EXHAUST AIR 14. EXHAUST BLOWER 15. CHANGE OVER VALVE 16. HEAT RECOVERY COIL 17. HEAT REINSTATEMENT COIL air • magic 1200 air unit range User's Manual Chapter 24 DRAWINGS (NTD1200 WHIT HRV1200) Chapter 24.1 air • magic NTD1200 + air • magic HRV1200 37 anchoring bracket room air return inlet outside air inlet anchoring bracket anchoring bracket anchoring bracket exhaust air outlet anchoring bracket room air supply outlet NTD1200 SUPPLY SIDE electric board cover air / magic RR 2000 electric board cover air / magic HI 2000 NTD1200 CONNECTION AND HRV1200 EXHAUST SIDE air • magic 1200 air unit range User's Manual Chapter 24 DRAWINGS (NTD1200 WITH HRV1200) Chapter 24.1 air • magic NTD1200 + air • magic HRV1200 38 OUTSIDE AIR 1364 EXHAUST AIR 1770 ROMM AIR RETURN HRV1200 NTD1200 ROOM AIR SUPPLY TOP VIEW air • magic 1200 air unit range User's Manual Chapter 24 DRAWINGS [NTD1200 WITH HRV1200HP] Chapter 24.2 air • magic NTD1200 + air • magic HRV1200HP 39 anchoring bracket room air return inlet outside air inlet anchoring bracket anchoring bracket anchoring bracket exhaust air outlet anchoring bracket room air supply outlet electric board cover air magic RRA 2000 electric board cover air magic HI 2000 NTD1200 SUPPLY SIDE NTD1200 CONNECTION AND HRV1200HP EXHAUST SIDE air • magic 1200 air unit range User's Manual Chapter 24 DRAWINGS [NTD1200 WITH HRV1200HP] Chapter 24.2 air • magic NTD1200 + air • magic HRV1200HP 40 OUTSIDE AIR 1454,5 EXHAUST AIR 1825,5 ROMM AIR RETURN HRV1200HP NTD1200 ROOM AIR SUPPLY TOP VIEW air • magic 1200 air unit range User's Manual air • magic FAN1200 The air • magic FAN1200 is an optional module to increase the available static pressure of the dehumidification blower (supply blower) when the dehumidifier is combined with the HRV module (air • magic HRV1200 or air • magic HRV1200HP) and the head loss of the ducting require additional static pressure This module can also be combined with an HRV module (air • magic HRV1200 or HRV1200HP) and work as the air supply blower to create a stand alone HRV unit without the dehumidification unit. THERMAL SPECS Capitolo 25.1 41 ELECTRICAL SPECS ACCESSORIES WEIGHTS AND DIMENSIONS Chapter 25 Airflow Max. available static pressure Max. power consumption Power supply CFM 1200 inch of w.c. 0.88 W 300 Vac / Ph / Hz 220 / 1 / 60 Dust and water protection rating IP 44 Height inch 19.17 Width inch 28.31 Depth inch 30.63 Weight lbs. 38.90 air • magic 1200 air unit range User's Manual Chapter 25 ACCESSORIES Chapter 25.1 air • magic FAN1200 487 anchoring bracket 42 anchoring bracket inlet anchoring bracket SUPPLY SIDE VIEW BACK SIDE VIEW 730 719 500 anchoring bracket supply electric board cover integration coil compartment (optional) 778 TOP VIEW air • magic 1200 air unit range User's Manual inlet(1/2”M) Chapter 25.2 43 ACCESSORIES Hydronic heating and cooling coil for air • magic FAN1200 The optional hydronic heating and cooling coil can be installed when the air • magic FAN1200 is combined with and an HRV module (air • magic HRV1200 or HRV1200HP) and works as supply air blower. THERMAL SPECS Chapter 25 moisture discharge output (3/4 inch) Heating output (water temperature 95°F) * Btu/h 24,200 Cooling output (water temperature 59°F) ** Btu/h 13,600 ft of head 5 foot of head 8.36 Water circuit loss of head Air loss of head * Air inlet temperature 50°F - 60%HR. ** Air inlet temperature 86°F - 50%HR. The unit is supplied with the water of the closed loop radiant system, and works as a pre-cooling (or pre-heating) coil to cool down (or heat up) the outside air before entering the HRV. This allows to introduce in the ambient cooler air (or hotter, depending on the season). 41 459 700 water outlet(1/2”M) SIDE VIEW water inlet(1/2”M) 73 moisture discharge output (3/4 inch) TOP VIEW 700 41 air • magic 1200 air unit range User's Manual Chapter 25 ACCESSORIES 44 Chapter 25.3 air • magic FAN1200 + air • magic HRV1200 (or HRV1200HP) 1454 anchoring bracket room air return inlet outside air inlet anchoring bracket optional outside air inlet anchoring bracket anchoring bracket 1731 anchoring bracket anchoring bracket exhaust air outlet anchoring bracket anchoring bracket HRV1200 - HRV1200HP moisture drenage room air supply outlet hydronic module electric board FAN1200 electric board Optional electric board AXIOMETRIC VIEW cable feedthroughs OVERHEAD VIEW air • magic 1200 air unit range User's Manual Chapter 26 DRAWINGS [NTD1200 WITH HRV1200HP] 45 ASSEMBLY: NTD1200 DEHUMIDIFIER WITH HRV1200HP (ACTIVE HRV MODULE) Glue the four gaskets [3] onto the dehumidifier air • magic NTD1200 [1] around the inlet vent, bring the recovery unit air • magic HRV1200HP [4] close to the dehumidifier while lining them up; use the bracket [2] with the 4 (dimensions 6x10 mm) to couple the two units; conclude the operation with the corner piece [5] and other 4 screws (dimensions 6x10 mm). The recovery unit is powered via the dehumidifier: connect the lines from the dehumidifier terminals with the recovery unit terminals having the same code. A second bracket [5] is supplied as replacement to bracket [2] for reverse coupling of the recovery unit: in this set-up the exhaust air is on the side opposite to the dehumidifier connection port. 3 4 2 1 5 air • magic 1200 air unit range User's Manual Chapter 26 INSTALLATION CLEARANCES The dehumidifiers air • magic NTD1200, which can be coupled to the HRV module air • magic HRV1200 or HRV1200HP, were designed for ceiling hanging and freestanding floor installation. 46 For proper machine operation and maintenance, both scheduled and extraordinary, the minimum clearance must be respected during installation, as shown in the figures below [Figures A and B]. Make sure that unit is installed with a slight tilt or is plumbed to facilitate the condensation tank drainage towards the discharge. air • magic NTD1200 with air • magic HRV1200 or HRV1200HP air • magic NTD1200 12” 12” ROOM AIR SUPPLY 4” 20” ROOM AIR SUPPLY 12” 20” ELECTRIC BOARD ACCESS 12” ELECTRIC BOARD ACCESS ROOM AIR RETURN AIR FILTER ROOM AIR RETURN EXHAUST AIR 12” AIR FILTERS OUTSIDE AIR Figure A - TOP VIEW Figure B - TOP VIEW air • magic 1200 air unit range User's Manual Chapter 26 INSTALLATION CEILING INSTALLATION [Figure C] Ceiling installation depicts bracketing the machine in a hanging position using the brackets supplied [1]. These must be connected to appropriate anti-vibration elements [2], selected in function of the type of ceiling anchors [3], and regularly installed. It is necessary to mount on the ceiling [4] an inspection hatch or panel [5] to carry out scheduled maintenance on the unit (air filter cleaning, checking the refrigeration circuit, access to the electrical panel, etc...). Whenever the structure allows, it is best that the ceiling opening be large enough for complete unit dismounting. The need to line the internal part of the dropped ceiling with soundproof cladding should be evaluated if installing the unit in a noise-sensitive zone. 47 FREESTANDING FLOOR INSTALLATION [Figure D] Freestanding floor installation entails positioning the unit on a flat surface [6] on supports. These last must be connected to appropriate anti-vibration brackets [7], selected by the installer and mounted professionally. Dehumidifier maintenance can be easily done from overhead. 3 2 1 2 1 ELECTRIC BOARD COVER 4 5 Figure C - CEILING INSTALLATION 7 7 ELECTRIC BOARD COVER 6 Figure D - FREESTANDING INSTALLATION air • magic 1200 air unit range User's Manual Chapter 26 INSTALLATION 48 MOISTURE DISCHARGE An appropriate siphon must be connected in the vicinity of the unit for each condensate discharge, both for the dehumidifier and the HRV module when the latter is part of the system. The siphon can be emptied when the unit is idle. At the start of each summer season, the siphon must be "reactivated" by pouring water into the condensation collection tank located beneath the treatment coil. This fills the siphon with water and avoids the situation where air intake through the siphon impedes regular condensation discharge. Ensure that all panels are correctly installed and secured with their screws before starting the unit. Important Note: Running the unit when panels are not properly mounted can cause serious unit malfunctions (low efficiency, condensate discharge difficulties with leaks from the unit, etc.). AIRTIGHT CONNECTION BETWEEN MOISTURE DISCHARGE OUTLET AND SIPHON Figure E - MOISTURE DISCHARGE: CEILING INSTALLATION AIRTIGHT CONNECTION BETWEEN MOISTURE DISCHARGE OUTLET AND SIPHON Figure E - MOISTURE DISCHARGE: FREESTANDING INSTALLATION air • magic 1200 air unit range User's Manual Chapter 26 INSTALLATION 49 FROST PROTECTION If the outside intake air is very cold and/or there is a chilled wind there is a risk that the pre- and post- treatment water coils may be damaged. In order to protect the unit from any possible damage when the machine is not in use it is best to adopt - as determined by the installer and/or designer - a frost protection system by means of: insertion of glycol into the refrigeration circuit, frost protection dampers or any other adequate measures. PRE AND POST TREATMENT COIL CAUTION: The coils may rupture if the water freezes. NTD1200 WATER SUPPLY AND RETURN HRV1200 or HRV1200HP air • magic 1200 air unit range User's Manual 50 Radiant Cooling And Heating Systems reserves the right to modify the machine specifications in this manual without advance notice. Radiant Cooling And Heating Systems declines any liabilities for any inexactness due to printing errors and / or entries contained therein. The instructions, drawings, tables and information generally included in this technical manual are confidential and may not be duplicated, neither in whole nor in part, or disclosed to third parties without written authorization of Radiant Cooling And Heating Systems who owns all exclusive intellectual rights thereof. air • magic 1200 air unit range User's Manual Messana Air-Ray Conditioning LLC 2224 Albert Ln, Capitola, CA, 95010 Phone/Fax: (855) RAY-MAGIC (729-6244) [email protected] www.raymagic.com