Preview only show first 10 pages with watermark. For full document please download

Al168 Series Multi-output Power Supplies Installation Guide Al168cb

   EMBED


Share

Transcript

AL168 Series Multi-Output Power Supplies Installation Guide Models Include: AL168CB - 16VAC @ 6 amp (100VA) or 18VAC @ 5.5 amp (100VA). - Eight (8) PTC protected outputs. AL168175CB - 16VAC @ 10 amp (175VA). - Eight (8) PTC protected outputs. AL168300CB - 16VAC @ 18 amp (350VA) or 18VAC @ 16 amp (350VA). - Eight (8) PTC protected outputs. AL168300CBM - 16VAC @ 18 amp (350VA) or 18VAC @ 16 amp (350VA). - Eight (8) PTC protected outputs. AL168600CB - 16VAC @ 40 amp (700VA) or 18VAC @ 36 amp (700VA). - Eight (8) PTC protected outputs. Rev. 070109 Overview: These AL168CB Series Multi-Output Power Supplies provide 16VAC/18VAC distributed via eight (8) PTC protected outputs for powering multiple security system or access control panels. Eight (8) Output AL168 Reference Chart: Altronix Model Number AL168CB AL168175CB AL168300CB AL168300CBM AL168600CB Output Voltage Total ­Output Current (Power) 16VAC 6 amp 18VAC 5.5 amp 16VAC 10 amp 16VAC 18 amp 18VAC 16 amp 16VAC 18 amp 18VAC 16 amp 16VAC 40 amp 18VAC 36 amp Output Current (max per output) Main Fuse Ratings on Board 115VAC 50/60Hz Input Current Number of Outputs PTC Protected Outputs Fuse Protected Outputs 8 x - 2.5 amp 10 amp/250V 0.9 amp 8 x - 2.5 amp 15 amp/250V 1.45 amp 8 x - 2.5 amp 15 amp/32V 2.7 amp 8 x - 2.5 amp 15 amp/32V 2.7 amp 8 x - 6 amp Two (2) 15 amp/32V 5.4 amp Specifications: Enclosure Dimensions (H x W x D): • Surge suppression. • AC power LED indicator. • Illuminated power disconnect circuit breaker with manual reset (except AL168CB). • Unit maintains camera synchronization. • Ease of installation saves time & eliminates costly labor. • Spare fuses included. AL168CB: 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm) AL168175CB and AL168300CBM: 8.5” x 7.5” x 3.75” (215.9mm x 190.5mm x 95.25mm) AL168300CB and AL168600CB: 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) Installation Instructions: 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7). Secure enclosure to earth ground. 2. Turn OFF main switch (except AL168CB) (Figs. 2-5, pgs. 4-6). 3. All units are factory set for 16VAC operation. For 18VAC operation, adjust unit prior to mounting and applying power as follows: Change the wire position so that the black wire [18V] is connected to the terminal marked [P] and the yellow wire [16V] is connected to the terminal marked [S]. 4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-5, pgs. 4-6). Use 18 AWG or larger for all power connections. 5. Measure output voltage before connecting devices. This helps avoiding potential damage. Terminals marked [1P - 8P] are positive of the same polarity. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. 6. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board (Figs. 3 & 5, pgs. 5-6) or terminals marked [1P - 1N through 8P - 8N] on PD8/PD8CB board (Figs. 1, 2 & 4, pgs. 4-5), carefully observing polarity. 7. Turn main switch to the “RESET” (ON) position (except AL168CB) (Figs. 3-5, pgs. 5-6). - 2 - AL168 Series 8. Green LED will illuminate when unit is powered. 9. Upon completion of the wiring secure enclosure door with screws (supplied). Caution: Equipment to be installed/serviced by authorized/trained personnel only. Shut branch circuit power before installing/servicing equipment. WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes. Terminal Identification: PD4/PD4CB/PD8/PD8CB - Power Distribution Module Terminal Legend 1P - 4P, 1P - 8P 1N - 4N, 1N - 8N Function/Description AC output. AC output. LED Diagnostics: PD4/PD4CB/PD8/PD8CB - Power Distribution Module Green (AC) ON OFF Power Distribution Module Status Normal operating condition. No Power Output. The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock. The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel. AL168 Series -3- Fig. 1 - AL168CB N P S 16VAC or 18VAC circuit breakered output 1 (Follow same procedure using terminals 2P & N thru 8P & N circuit breakered outputs 2 thru 8) White Lead 115VAC input 50/60 Hz, XFMR Black Lead Back Panel of Enclosure F1 F2 F3 F4 F5 F6 F7 MAIN FUSE Fig. 2 - AL168175CB F8 P D1 FUSED POWER OUTPUTS LED R1 N INPUT COMMON POWER N OUTPUTS P S 16VAC fused output 1 (Follow same procedure using terminals 2P & N thru 8P & N fused outputs 2 thru 8) Power Switch Black Lead 115VAC input 50/60 Hz, 1.5 amps - 4 - White Lead XFMR AL168 Series S P 1N 2P N 1P 1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS INPUT Fig. 3 - AL168300CB 2N 3P 3N 4P 4N N P LED S INPUT Power Switch Voltage Selection Configuration 16VAC Output 18VAC Output N P S (Yellow) (Black) N S P (Black) 115VAC input, 50/60 Hz. XFMR* Black Lead White Lead Fig. 4 - AL168300CBM Power Switch (Yellow) F2 F3 F4 F5 F6 F7 F8 MAIN FUSE Transformer underneath power supply board Black Lead F1 White Lead AL168 Series -5- N P S INPUT Fig. 5 - AL168600CB N P S INPUT 115VAC input, 50/60 Hz. Power Switch XFMR* XFMR* Black Lead White Lead Voltage Selection Configuration 16VAC Output 18VAC Output N P (Yellow) (Black) N S P (Black) - 6 - S (Yellow) AL168 Series • AL168CB Enclosure Dimensions (H x W x D approximate): 7.25” (184.15mm) 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm) 3.625” (184.15mm) 1.25” (31.75mm) 3.5” (88.9mm) 1.25” (31.75mm) 0.6” (15.24mm) 0.6” (15.24mm) 6.05” (153.67mm) 1.125” (28.575mm) 1.125” (28.575mm) 2” (50.8mm) 2” (50.8mm) 8.125” (206.375mm) 1” (25.4mm) 1” (25.4mm) 6.05” (153.67mm) 0.6” (15.24mm) 0.6” (15.24mm) 1.25” (31.75mm) 3.5” (88.9mm) 1” (25.4mm) 1” (25.4mm) 5.25” (133.35mm) • AL168300CBM and AL168175CB 1” (25.4mm) 3.63” (92.2mm) 8.5” x 7.5” x 3.75” (215.9mm x 190.5mm x 95.25mm) 1.25” (31.75mm) 3.85” (97.79mm) 7.25” (184.15mm) 0.6” (15.24mm) 1.25” (31.75mm) 1.25” (31.75mm) 0.6” (15.24mm) 1” (25.4mm) 1” (25.4mm) 0.9” (22.86mm) 0.9” (22.86mm) 8.13” (206.5mm) 8.13” (206.5mm) 1.75” (44.45mm) 1” (25.4mm) 1” (25.4mm) 0.6” (15.24mm) 1.25” (31.75mm) 0.6” (15.24mm) 3.85” (97.79mm) 3.85” (97.79mm) 1” (25.4mm) 1” (25.4mm) AL168 Series 7.25” (184.15mm) 1” (25.4mm) -7- • AL168300CB and AL168600CB: 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 1.0” (25mm) 10.5” (267mm) 1.0” (25mm) Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A. IIAL168Series J28M - 8 - MEMBER AL168 Series