Preview only show first 10 pages with watermark. For full document please download

Al300x220 Series Power Supply/charger Installation Guide • Al300x220

   EMBED


Share

Transcript

AL300X220 Series Power Supply/Charger Installation Guide Models Include: • AL300X220 - Single Output • AL300PD4220 • AL300PD4CB220 - Four (4) Fused Outputs - Four (4) PTC Outputs • AL300PD8220 • AL300PD8CB220 - Eight (8) Fused Outputs - Eight (8) PTC Outputs • AL300XPD16220 • AL300XPD16CB220 - Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs For a red enclosure add an “R” suffix to the part # e.g. AL300PD8R220 For a larger enclosure add an “X” suffix to the part # e.g. AL300XPD8220 Rev. 062206 Overview: The AL300X220 is a power supply that converts a nominal 220VAC (working range 198VAC - 256VAC) 50/60Hz input to a 12VDC or 24VDC regulating output (see specifications below). The AL300X220 is a base power supply unit for multi-output power supply/charger series: AL300PD4220, AL300PD4CB220, AL300PD8220, AL300PD8CB220, AL300XPD16220, AL300XPD16CB220 (Refer to AL300X220 Series Power Supply Configuration Reference Chart below). 13.5” x 13” x 3.25” AL300X220 ----- 1 ----- ----- 2.5 AL300XX220 AL300PD4220 5A/ 15A/ (342.99mm x 330.2mm x 82.55mm) 2.5 250V 32V 15.5” x 12” x 4.5” x ----- 2.5 5A/ 15A/ 3.5 250V 32V PD4CB ----- x 2.5 5A/ 15A/ 2.5 250V 32V PD8 x ----- 2.5 5A/ 15A/ 3.5 250V 32V ----- x 2.5 5A/ 15A/ 2.5 250V 32V Two (2) x ----PD8 16 Two (2) ----- x PD8CB 2.5 5A/ 3.5 250V 5A/ 2.5 250V PD4 AL300XPD4220 4 AL300PD4CB220 AL300XPD4CB220 AL300PD8220 AL300XPD8220 8 AL300PD8CB220 PD8CB AL300XPD8CB220 AL300XPD16220 AL300XPD16CB220 Input: Enclosure Dimensions 2.5 15A/ 32V 15A/ 32V (393.7mm x 304.8mm x 114.3mm) 13.5” x 13” x 3.25” (342.99mm x 330.2mm x 82.55mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 13.5” x 13” x 3.25” (342.99mm x 330.2mm x 82.55mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 13.5” x 13” x 3.25” (342.99mm x 330.2mm x 82.55mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 13.5” x 13” x 3.25” (342.99mm x 330.2mm x 82.55mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) Accomodates Stand-by Batteries Power Supply Output Fuse Rating Power Supply Input Fuse Rating Output Rating (amp) per Output Total Output Rating (amp) PTC Outputs Fused Outputs Number of Outputs Altronix Model Number Accessory Power Distribution Module(s) AL300X220 Series Power Supply Configuration Reference Chart: Two (2) 12VDC/7AH Two (2) 12VDC/12AH Two (2) 12VDC/7AH Two (2) 12VDC/12AH Two (2) 12VDC/7AH Two (2) 12VDC/12AH Two (2) 12VDC/7AH Two (2) 12VDC/12AH Two (2) 12VDC/7AH Two (2) 12VDC/12AH Two (2) 12VDC/12AH Two (2) 12VDC/12AH Specifications: Battery Backup (cont’d): • Nominal 220VAC (working range 198VAC - 256VAC) • Zero voltage drop when switched over to 50/60Hz, 1.7 amp. battery backup. • AC input and DC output LED indicators. Supervision: Output: • AC fail supervision (form “C” contacts). • 12VDC or 24VDC selectable output(s). • Low battery supervision (form “C” contacts). • 2.5 amp total supply current. • Battery presence supervision (form “C” contacts). • Filtered and electronically regulated output(s). Additional Features: • Short circuit and thermal overload protection. • Power supply, enclosure, cam lock and battery leads. Battery Backup: • All models are available in red enclosure • Built-in charger for sealed lead acid or gel type batteries. (add an “R” suffix to the part # e.g. AL300PD8R220). • Automatic switch over to stand-by battery when AC fails. • Maximum charge current 0.7 amp. - 2 -­ AL300220series Power Supply Output Specifications: Switch Position SW1 - ON SW1 - OFF ON Output 12VDC 24VDC OFF - 24V ON - 12V Stand-by Specifications (total current shown): Output 12VDC / 40AH Battery 4 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 2.5 amp Alarm = 2.5 amp 24VDC / 12AH Battery -------- 24VDC / 40AH Battery Stand-by = 2.5 amp Alarm = 2.5 amp Fig. 1 60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.5 amp -------Stand-by = 300mA Alarm = 2.5 amp CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture. G Wire Strap (from Enclosure to Door) N Risk of Fire, Replace Fuses As Marked NC C L C NO Door Switch Position: 24VDC = SW1 OFF 12VDC = SW1 ON 5A 250V Ground Lug Fig. 1a NC 24 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 1.0 amp Alarm = 2.5 amp Stand-by = 200mA Alarm = 2.5 amp Stand-by = 1.0 amp Alarm = 2.5 amp NO AC 220VAC power mains DC Bat Battery and AC Supervision Circuit Bat Fail NC C NO NC C Battery and AC Supervision Circuit NO AC Fail OFF - 24V ON - 12V J1 15A 250V AC Delay ON 15 1 SW1 + BAT --- + DC --- Fig. 1b DC Output to devices 1 ON Battery connection OFF - 24V ON - 12V SW1 12VDC Rechargeable Battery (optional) For 12VDC Operation use hook-up in the inset on the right 12VDC Rechargeable Battery (optional) CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. AL300220series - 3 -­ Installation Instructions: 5A 250V CAUTION: Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI De-energize and with all local unit p codes and authorities having jurisdiction. Product is intended for indoor use only. shock and fire hazard replace f 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7,8). Secure enclosure to earth ground. 2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1b, pg. 3) to the appropriate position Ground (Power Supply Voltage Output Selections Chart, pg. 3). Lug Door (safety) ground lug . 3. Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth Line and Neutral to the connector on power supply board marked [L, N] respectively (Fig. Wire 1, pg. 3). Strap Use 14 AWG or larger for all power connections (Battery, DC output, AC input). (from Enclosure Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). to Door) Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. NC C NO NC C NO 220VAC CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. Battery and AC power mains SupervisiontoCircuit There are no user serviceable parts inside. Refer installation and servicing qualified service personnel. 4. Measure output voltage before connecting devices. This helps avoiding potential damage. When servicing the unit, AC mains should be removed. 5. Connect devices to be powered: Battery and AC a. For AL300X220 Power Supply: connect devices to the terminals marked [- DC +] (Fig. 1, pg. 3). Supervision b. For other Power Distribution Models: connect devices to be powered to the terminal pairsCircuit 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 2a & 2b, pg. 6) or 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6), carefully observing correct polarity. 6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [+ BAT -] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation. 7. Connect appropriate signaling notification devices to the terminals marked [AC FAIL & BAT FAIL] (Fig. 1a, pg. 3) supervisory relay outputs. Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to provide a visual indication of AC power on. 8. Please ensure that the cover is secured with the provided Key Lock. L G N Replace Fuses As Marked AC DC Bat Bat Fail NC C NO NC C 1 ON NO AC Fail OFF - 24V ON - 12V SW1 12VDC Rech (o For 12VD use h inse CAUTION: the power su Keep power Use minimu - 4 -­ AL300220series LED Diagnostics: AL300XB220 - Power Supply Board Red (DC) ON ON OFF OFF Green (AC) ON OFF ON OFF Power Supply Status Normal operating condition. Loss of AC. Stand-by battery supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output. Red (Bat) ON OFF Battery Status Normal operating condition. Battery fail/low battery. AL300XB220 - Power Supply Board Terminal Identification: Terminal Legend Function/Description L, G, N Connect 220VAC 50/60Hz to these terminals: L to hot, N to Neutral. Do not use the [G] terminal. + DC --12VDC or 24VDC @ 2.5 amp continuous power-limited output. Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC Fail condition will report approximately AC Fail within one (1) minute after loss of AC. To delay report for 6 hours, cut jumper J1 on the Power Supply NC, C, NO Board (AC trouble output delay option). If this mode is selected, the Power Supply Board must be reset by removing all power to it for 30 seconds. Bat Fail NC, C, NO + BAT --- Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 28VDC. Low battery conditions will report approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting). Battery presence detection will report approximately 1 minute after battery remains undetected (missing or removed). Stand-by battery connections. Maximum charge current 0.7 amp. LED Diagnostics: PD4/PD4CB/PD8/PD8CB - Power Distribution Module Green ON OFF Power Distribution Module Status Normal operating condition. No Power Output. Terminal Identification: PD4/PD4CB/PD8/PD8CB - Power Distribution Module Terminal Legend PD4/PD4CB PD8/PDCB 1P to 4P 1P to 8P 1N to 4N 1N to 8N AL300220series Function/Description Positive DC power outputs. Negative DC power outputs. - 5 -­ Power Distribution Module(s): Fig. 2b BROOKLYN, NY 11220 F2 F3 MADE IN USA F1 ALTRONIX CORP. Fig. 2a 1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS F4 F1 F2 F3 F4 PD4 POWER DISTRIBUTING UNIT LED LED 2P 1N 1P COMMON 2N POWER 3P 3N 4P ( 1 2 ) 3 4 5 6 7 P 8 OUTPUTS PD8 LED INPUT POWER OUTPUTS Non Power-Limited DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs ( - 6 -­ ) 4P 3N ( 4N INPUT From Power Supply Board (Factory Installed) ) 1 2 From Power Supply Board (Factory Installed) 3 4 5 6 7 P N 8 D1 FUSED COMMON 3P Fig. 3b R1 N 2N Class 2 Rated Power-Limited DC Output to devices 1P-4P Power Outputs, 1N-4N Common Outputs From Power Supply Board (Factory Installed) D1 POWER 2P POWER OUTPUTS POWER DISTRIBUTING UNIT FUSED 1N 1P INPUT OUTPUTS Non Power-Limited DC Output to devices 1P-4P Power Outputs, 1N-4N Common Outputs Fig. 3a 4N COMMON POWER POWER OUTPUTS R1 INPUT OUTPUTS Class 2 Rated Power-Limited DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs ( LED ) From Power Supply Board (Factory Installed) AL300220series Wiring: USE 14 AWG or larger for all power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level (Power Supply Voltage Output Specifications Chart, pg. 3). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the battery terminal and at the board terminals marked [+ BAT -] to ensure that there is no break in the battery connection wires. Note: Maximum charging current under discharges is 0.7 amp. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. Enclosure Dimensions: • AL300X220 • AL300PD4220 • AL300PD4CB220 • AL300PD8220 • AL300PD8CB220 13.5” x 13” x 3.25” (342.99mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 1.0” (25mm) AL300220series 10.5” (267mm) 1.0” (25mm) - 7 -­ Enclosure Dimensions: • AL300XX220 • AL300XPD4220 • AL300XPD8220 • AL300XPD4CB220 • AL300XPD8CB220 • AL300XPD16220 • AL300XPD16CB220 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.79” (20.06mm) 1.25” (31.75mm) 1.75” (44.45mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected]. Lifetime Warranty, Made in U.S.A. IIAL300X220 series - 8 -­ J28O MEMBER AL300220series