Transcript
Effective: March 2008
AlarmLine™
Addressable Linear Heat Detector
P/N 73-100001-003
TM
K-73-02
FEATURES • • • • •
• • • • • • • • • • •
UL Listed FM Approved CSFM MEA (pending) Low-cost interface between AlarmLine™ sensor cable and control panel accepting SmartOne™ addressable devices Up to 255 Addressable AlarmLine Modules (AAM) per addressable loop Real-time monitoring Software adjustable alarm set point Optional pre-alarm and overheat output configuration selections Three cable styles (standard, nylon, bronze braided) Sensor cable restorable up to 257°F Full supervision for short and open circuits Two-color status-LED display for alarm and trouble conditions Intrinsically safe option Flexibility in zoning Enhanced response time
DESCRIPTION The AlarmLine Addressable Linear Heat Detector provides early detection of fire or overheat condition in protected areas or equipment. It is especially suited for confined areas or environments where adverse ambient conditions cause other detection devices to be unreliable or difficult to use. The detector consists of two major components: A sensor cable and an Addressable AlarmLine Module (AAM). The AAM is used with any intelligent control panel that accepts SmartOne devices.
APPLICATIONS • • • • • • • • • • • • • •
Open-area protection Cable trays Rack storage Freezer warehouses Belt conveyers Floating roof fuel tanks Cooling towers Dust collectors Waste fuel drum storage Power distribution apparatus Escalators Tunnels Mines Hangars
BENEFITS
NEGATIVE TEMPERATURE COEFFICIENT MATERIAL
Application Flexibility: Allows installation at point of risk. Programmable pre-alarm, alarm, and overheat levels for differing ambient conditions.
SENSOR CONDUCTOR WIRE
Durability: Extrusion and braiding options to satisfy environmental conditions and project risks.
CABLE SENSOR
Reliability: Fault signaling of open and short circuit conditions, pre-alarm, alarm, and overheat reporting. Recoverability: Cable does not need to be replaced after an alarm event as high as 257º F (125º C). Sensitivity: Proven measurement.
superiority
over
point-type
ANALOG HEAT SENSING AlarmLine’s analog heat sensing characteristics offer several distinct advantages: Field Adjustability of pre-alarm, alarm, and overheat setpoints: Pre-alarm, alarm, and overheat thresholds may be programmed to meet specific system requirements. Integrating: It is not necessary to reduce sensor spacing with increased ceiling height per NFPA 72-2007 Section 5.6.5.5.1, Exception (1). System sensitivity remains constant as ceiling height increases without reducing spacing. Short Circuit Discrimination: The system will produce a trouble condition instead of a false alarm in the event of a conductor to conductor short due to damage or electrical faults.
SENSOR CABLE The AlarmLine sensor cable consists of four 26 AWG copper conductors, each color-coded in an insulated sheath containing a negative temperature coefficient polymer (where an increase in temperature decreases the resistance of the sensor). Two of the conductors are enameled and provide loop continuity supervision, but not temperature sensing. The conductors are twisted at thirty turns per foot (90 turns per meter) and protected by a flame-retardant outer extrusion or metallic braid (See Figure 1). The color coding of the four inner conductors is repetitively marked on the outer coating every three feet as an aid installation. Cable is sold in standard coils of 656 feet (200 meters) and 3280 ft. (1000 m). Note:
The maximum length of sensor cable per zone depends on the maximum ambient temperature defined on the nomogram(s) (See Figures 2 and 3). Regardless of ambient temperature, however, the maximum length of cable is 3280 feet (1000 meters) per zone for Type “T” cable.
PROTECTIVE INSULATION HIGH TEMPERATURE PVC
Figure 1. Standard Sensor Cable
PART NUMBERS Sensor cable is available with the following part numbers: Standard Sensor Cable 73-117068-013 (656 ft./200 m) 73-117068-113 (3280 ft./1000 m) Recommended for environments ranging from clean and dry to moderate dust and moisture. Nylon Coated Sensor Cable 73-117068-016 (656 ft./200 m) 73-117068-116 (3280 ft./1000 m) Recommended for use in wet, oily, or corrosive environments or outdoors. Use in freezer warehouses. Phosphor Bronze Braided Sensor 73-117068-019 (656 ft./200 m) 73-117068-119 (3280 ft./1000 m) Recommended for applications requiring superior abrasion protection and/or increased tensile strength.
ADDRESSABLE ALARMLINE MODULE (AAM) The AAM permits an AlarmLine sensor cable to be directly interfaced to any control panel that accepts SmartOne addressable loop devices. This interface will allow for pre-alarm, alarm, and trouble conditions to be transmitted to the control panel via the Signaling Line Circuit (SLC). The AAM monitors the resistance of the sensor cable and generates a pre-alarm (if enabled), alarm, or overheat output (if enabled) when the resistance drops below the programmed threshold. The module also supervises the AlarmLine cable for opens and shorts, which will generate a fault condition. All of the pre-alarm, alarm, overheat, and trouble conditions will be displayed on the control panel. Up to 255 AAM modules can be connected to a single SLC loop. Use of multiple AAMs allows flexibility in zoning larger installations for location of alarm and zone output control; the control panel acts as a central display and control interface. The AAM receives power directly from the SLC loop which eliminates the need for additional wiring and external power supplies.
-2-
For further information on installation and configuration of the AAM, please refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation, and Maintenance Manual, P/N 06-235820-003.
Standard Sensor
Nylon Coated Sensor
Bronze Braided Sensor
Service Life
Up to 212ºF (100ºC) = 30 years @ 257ºF (125ºC) = 24 hours. Self Restores below 257ºF (125ºC) Above 374ºF (190ºC) is the destructive temperature.
Up to 212ºF (100ºC) = 30 years @ 257ºF (125ºC) = 24 hours. Self Restores below 257ºF (125ºC) Above 374ºF (190ºC) is the destructive temperature.
Up to 212ºF (100ºC) = 30 years @ 257ºF (125ºC) = 24 hours. Self Restores below 257ºF (125ºC) Above 374ºF (190ºC) is the destructive temperature.
Approved Spacing (between parallel runs)
30 ft. (9 m)
30 ft. (9 m)
30 ft. (9 m)
Description
The Addressable AlarmLine Module is available using the following part numbers: 73-100001-003 Module with operating temperature range of -40º Fº to 140º F (-40º C to 60º C). Mounted on a 4-inch square faceplate. AAM mounts in a 4-inch square backbox, 2-1/8-inches deep. 73-100003-001 NEMA-4 sealed, protective polycarbonate enclosure used to mount AAM in wet or dusty environments.
CABLE SPECIFICATIONS
SENSOR MOUNTING HARDWARE
Standard Sensor
Nylon Coated Sensor
Bronze Braided Sensor
Part Number : Length: Weight:
73-117068-013 656 ft. (200 m) 7 lbs. (3.2 kg)
73-117068-016 656 ft. (200 m) 7 lbs. (3.2 kg)
73-117068-019 656 ft. (200 m) 7 lbs. (3.2 kg)
Part Number : Length: Weight:
73-117068-113 3280 ft. (1000 m) 35 lbs. (14.5 kg)
73-117068-116 3280 ft. (1000 m) 35 lbs. (14.5 kg)
73-117068-119 3280 ft. (1000 m) 35 lbs. (14.5 kg)
Jacket Construction
Blue PVC
Black nylon extrusion over blue PVC
Phosphor bronze braid over blue PVC
External Diameter
0.117 in. (3 mm)
0.153 in. (3.9 mm)
0.153 in. (3.9 mm)
Tensile Strength
100 N
100 N
1000N
1 = Orange 2 = White 3 = Red 4 = Blue
1 = Orange 2 = White 3 = Red 4 = Blue
1 = Orange 2 = White 3 = Red 4 = Blue
Description
Conductor Insulation Costs Conductor Material
26 AWG Solid Copper
26 AWG Solid Copper
26 AWG Solid Copper
Conductor Diameter
0.018 in. (0.460 mm)
0.018 in. (0.460 mm)
0.018 in. (0.460 mm)
Twist of Inner Conductors
30 per ft. (90 per m)
30 per ft. (90 per m)
30 per ft. (90 per m)
Specially Doped Polymer
Specially Doped Polymer
Specially Doped Polymer
Standard Outer Jacket Material
High Temperature PVC
High Temperature PVC
High Temperature PVC
Voltage Proof Between PVC Jacket and a Conductor
10 KV
10 KV‘
10 KV
Dielectric Material
Three types of standard mounting hardware (master clamp, flange clamp, nylon cable tie) for AlarmLine permit safe, secure sensor cable installation in most applications. Other mounting means may be used as required by the specific application. The sensor should be supported at a minimum of ten foot intervals on straight runs when under tension, and more as conditions dictate at corners and transition points to provide suitable strain relief. Local codes or conditions may also require the sensor to be supported at closer intervals. Refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation, and Maintenance Manual, P/N 06-235820-003 for specific mounting information.
-3-
AAM SPECIFICATIONS Specification
Value
Part Number
73-100001-003
Supply Voltage
P.C. Line, 16.5 to 27.5 Vdc
Current Consumption, Standby
425 µAmps
Current Consumption, Alarm
440 µAmps
Current Consumption,Fault
425 µAmps
Noise Performance
Withstands 5% RMS 60 Hz supply noise or 1 Vrms 60 Hz sensor noise with negligible performance range. RFI immunity at 10 V/meter field strength over the band of 20 to 900 MHz
Operating Temperature Range
-4ºF (-20ºC) to 140ºF (60ºC)
Humidity
5 -95% R.H.
Terminals
Will accept up to #12 AWG
Working Voltage
6V
Maximum Voltage
7.5V
Fuse Rating
100 mA
Leakage Current
1 mA maximum at 6V
End-To-End Resistance
145 ohm maximum 90 ohm minimum
Enclosures
73-117068-732 holds 2 barriers 73-117068-733 holds 5 barriers 73-117068-734 holds 12 barriers 73-117068-735 holds 24 barriers
When determining the alarm temperature setting, the designer must take into account environmental factors that may affect the overall response of the system. By accounting for these factors, the designer minimizes unwanted alarms. Below is a step by step procedure which instructs the designer in selection of the proper alarm trip points.
Pre-Alarm: Slow flash RED every nine (9) seconds Alarm: Fast flash RED every two (2) seconds
The required alarm temperature and the correct alarm configuration setting for the AAM are determined using the AlarmLine nomogram(s).
Trouble: Off Operating Temperature Range
Class I, Division I, Groups A, B, C, D Class II, Division I, Groups E, F, G: Class III, Division I
SETTING THE ALARM TEMPERATURE
Normal: Slow flash GREEN every nine (9) seconds
LED Pulse Modes
UL Listed and FM Approvals
-40°F to 140°F (-40°C to 60°C)
Measurements centigrade.
are
in
feet/fahrenheit
or
meters/
INTRINSIC SAFETY BARRIERS
The use of the nomogram requires two known factors:
In classified hazardous areas where potentially explosive vapors, dust, or fibers exist, AlarmLine cable must installed using an intrinsic safety barrier. The barrier (P/N 73-117068-031) is a shunt diode safety barrier which limits the current and voltage in the sensor cable to safe levels. Each barrier handles two conductors, so two barriers are needed for each sensor cable. The barriers are designed to mount in separate weathertight enclosures. The intrinsic safety barrier’s specifications are as follows:
•
Maximum ambient temperature of the alarm zone. (Scale A). • The total length of the sensor cable to be used. (Scale L). The resistance change required to create an alarm can be a result of either a predetermined minimal increase in temperature over the entire length of the sensor, or a significant increase on a shorter section of cable. The alarm temperature in either case is determined only after the alarm trip switch position for the entire sensor length is known. A shorter section of sensor cable exposed to an overheat condition will require a higher temperature to achieve an alarm than a longer length of sensor cable exposed to the same overheat condition. The maximum length of sensor cable per zone depends on the maximum ambient temperature defined on the nomogram. Regardless of ambient, however, the maximum length of cable connected to a single AAM is 3280 ft. (1000 m). If cable length exceeds 3280 ft., the
-4-
alarm condition could be reached at room temperature (70º F (20º C)) for most switch settings. Refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation, and Maintenance Manual, P/N 06-235820-003 for more information.
KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721
PRODUCT MUST BE INSTALLED AND OPERATED IN ACCORDANCE WITH KIDDE-FENWAL INSTALLATION MANUAL 73.04 AND JURISDICTION OF LOCAL AUTHORITY.
3200 2900 2600 2300 2000 1650 1300
EARTH GROUND
1000 825
B
A
B
WHT
TB1
1
SENSOR CABLE
P.C. LINE A
ORN
Sensor Cable Length (Ft.)
4
3
2
1
4
3
2
1
WHITE
Specified Alarm Temp. (F)
P.C.LINE OUT
TB2
ORANGE
Maximum Ambient Temp. (F)
BLU
Alarm Configuration Setting
FM APPROVED
DEVICE ADDRESS # _ _ _ _
RED
L
BLUE
T
RED
A
R
CAT NO. 73-100001-003
DATE OF MANUFACTURE: ALL TERMINALS ARE POWER LIMITED
S
UL
TM
ADDRESSABLE ALARMLINE MODULE
INTERCONNECT CABLE 16 AWG, 4 CONNECTOR (IF REQUIRED)
P.C.LINE IN
650
2
500 3
95
75
105
4
85
115
5
95
6
105 115
7
120 8
130 140
9
150 160 165 175 185 195
10 11 12 13 14
120 130 140
35 25 20
10
15
5
16
3
Figure 2. Example for Type “T” Cable (Feet/Fahrenheit) S
A
T
L
Alarm Configuration Settng
Maximum Ambient Temp. (F)
Specified Alarm Temp. (F)
Sensor Cable Length (Ft.)
3200 2900 2600 2300 2000 1650 1300 1000 825 650 500 3 4
75
95
6
105 115
7
120 8 9 10 11 12 13 14 15 16
95 105
85
5
130 140 150 160 165 175 185 195
115 120 130 140 150 160 165 175 185 195 205 210 220 230 240 250 257
3
2
1
4
3
2
1
Figure 4. Wiring the AAM to a Panel
50
165 175 185 195 205 210 220 230 240 250 257
2
4
SENSOR CABLE
100 80 65
150 160
1
WEATHERPROOF JUNCTION BOX (IF REQUIRED)
300 265 230 200 165 130
300 265 230 200 165 130 100 80 65 50 35 25 20
10
5 3
Figure 3. Example for Type “T” Cable (Feet/Fahrenheit)
ADDRESSABLE ALARMLINE MODULE WIRING The Addressable AlarmLine Module (P/N 73-100001003) may connected to any fire control panel that accepts SmartOne addressable devices. The module is wired directly to the SLC loop of the panel as shown in Figure 4. Refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation, and Maintenance Manual, P/N 06-235820-003 for complete wiring information.
NEMA-4 ENCLOSURE The NEMA-4 polycarbonate enclosure (P/N 73-100003001) is designed to mount the Addressable AlarmLine Module in areas requiring additional protection from wet and/or dusty environments. This enclosure is rated as follows: TM
•
UL 508 Type 4, Type 4X, Type 6, Type 12, and Type 13 • NEMA Type 4, Type 4X, Type 6, Type 12, and Type 13 • CSA Type 4, Type 4X, Type 6, Type 12, and Type 13 • Flammability rating UL94-5V • IEC 529, IP66 The enclosure is equipped with a clear cover so that the AAM alarm/trouble status indicator LED can be viewed. The cover also provides a molded-in wire-lead hole for tamper resistant installation. Mounting holes for the enclosure are molded directly under the cover screws. A cover gasket assures watertight and dust-tight seals.
-5-
The impact-resistant, glass-filled, polycarbonate enclosure material is easily punched, drilled, or sawed to provide access for field wiring. For further installation information, refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation, and Maintenance Manual, P/N 06-235820-003.
ENCLOSURE 4.330
BRACKET
AAM 4.330
COVER TM
e Lin rm Ala
MOUNTING HOLE FOR #8 SCREW (TYP.)
TM
e On art Sm
SELF-TAPPING SCREWS
TINNERMAN CLIPS
#8-32 SCREWS
CROSS-POINT, CAPTIVE COVER SCREWS
Figure 5. NEMA-4 Enclosure with AAM
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. K-73-02 Rev BB
© 2008 Kidde-Fenwal Inc.
Printed in USA
TM
KIDDE-FENWAL INC. 400 MAIN STREET, ASHLAND, MA 01721 TEL: (508) 881-2000 FAX: (508) 881-8920 www.Kidde-Fenwal.com