Submittal Data: GWH09KF-A3DNB4A Job Name Purchaser Submitted To Unit Designation
9,000 BTU/H Wall Mounted Heat- Pump System
Location Engineer Reference For Schedule No.
Date Approval
Construction
GENERAL FEATURES -Compact and Quiet Design -High Efficiency - 16 SEER -DC Inverter Technology -Wireless Remote with LCD Display -Low Ambient Cooling -Comfortable Sleep Mode -Intelligent Defrost -5 year Limited Parts Warranty
Indoor Unit Data
System Ratings Fan Motor
Cooling Rated Capacity Capacity Range Power Input (Max) SEER EER Heating at 47° F Rated Capacity Capacity Range Power Input (Max) HSPF COP Heating at 17° F Rated Capacity Capacity (Max) Power Input (Max) COP Operating Range Cooling Heating
9,000 BTU/H 3,500-11,000 BTU/H 1 ,1 0 0 W 16 1 2 .0 9,800 BTU/H 2,500-11,000 BTU/H 1 ,2 3 0 W 8 .6 . 12.0
5,400 BTU/H 8,517 BTU/H 1,069 W 7.2
(Max) (Min) (Max) (Min)
Power S upply Normal Operational Voltage Voltage Range Main Power Wire Size Interconnecting Cable Wire Size MCA MOCP/Breaker Size
113°F (45 C) 64°F (18 C) 75°F (24 C) 5°F (-15 C) 115 V, 1 Phase, 60 Hz 103- 127 V 12-2 AWG 14-4 AWG 1 3 .0 A 20 A
Output Power F LA
15 W 0 .4 A
Airflow Cooling Wet (Lo/Hi) 188/330 CFM 188/330 CFM Heating Dry (Lo/Hi) S ound Pres s ure L evel Cooling (Lo/Hi) 32/41 db(A) Heating (Lo/Hi) 32/41 db(A) Dimensions & Weights Unit Dimensions (LxHxD) 30.3 x 11.1 x 7.9-in Weight (Net/Shipping) 19/23 LBS Outdoor Unit Data Compressor DC Inverter Driven Rotary Refrigerant Type R410A Output Power Fan Motor 30 W F LA 0.2 A Sound Pressure Cooling 53 db(A) Heating 53 db(A) Dimensions & Weights Unit Dimensions (LxHxD) 33.4 x 21.3 x 12.6-in Weight (Net/Shipping) 69/73 LBS R efrigerant Piping Data Gas Pipe Size (OD) 3/8-in Liquid Pipe Size (OD) 1/4-in Connection Method Flared MAX Refrigerant Pipe Length 5 0 - ft MIN Refrigerant Pipe Length 1 0 - ft MAX Refrigerant Pipe Height Difference 33-ft
© C&H Corporation 2015
ALICE Series
Powered by
Submittal Data: GWH09KF-D3DNB4F
9,000 BTU/H Wall Mounted Heat- Pump System
EXTENDED RATINGS COOLING PERFORMANCE Outdoor Ambient Temperature (DB) 25 F 35 F 45 F 55 F 65 F 75 F 85 F 95 F 105 F 115 F
Indoor Entering Air Temperatures (DB) 62 F 67 F TC SHC TC SHC NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 9,569 7,434 10,520 7,985 9,179 7,176 9,910 7,614 8,810 7,013 9,445 7,289 8,370 6,688 9,000 7,191 7,912 6,436 8,532 6,809 7,458 6,166 7,911 6,423
50% RH 72 F TC SHC NA NA NA NA NA NA NA NA 11,165 8,152 10,642 7,859 10,266 7,666 9,846 7,394 9,274 7,115 8,450 6,629
HEATING PERFORMANCE Outdoor Ambient Temperature (DB) (80% RH) 5F 15 F 25 F 35 F 45 F 55 F 65 F
TC- Total Capacity ( BtuH) SHC- Sensible Capacity (BtuH)
65 F
TC 8,239 8,926 9,439 10,911 12,357 13,368 13,350
Indoor Entering Air Temperatures (DB) 70 F 75 F SHC TC SHC TC SHC 8,239 7,881 7,881 7,629 7,629 8,926 8,239 8,239 8,231 8,231 9,439 9,631 9,631 9,559 9,559 10,911 11,392 11,392 10,889 10,889 12,357 12,243 12,943 12,386 12,386 13,368 13,116 13,116 12,596 12,596 13,350 13,203 13,203 12,856 12,856
© C&H Corporation 2015
ALICE Series
Powered by
Submittal Data: GWH09KF-D3DNB4F
9,000 BTU/H Wall Mounted Heat- Pump System
MINIMUM SPACING REQUIREMENTS Units: inch (mm)
Units: inch (mm)
© C&H Corporation 2015
DIMENSIONAL SPECIFICATIONS INDOOR UNIT DIMENSIONS
GWH09KF-A3DNB4A Units: inch (mm)
Liquid Line Valve Gas Line Valve Drain Connector
OUTDOOR UNIT DIMENSIONS
1/4-in OD Flared 3/8-in OD Flared 5/8-in OD Units: inch (mm)
21.3
Liquid Line Valve Gas Line Valve
1/4-in OD Flared 3/8-in OD Flared
www.cooperandhunter.us © C&H Corporation 2015