Transcript
ALTV2432UL Series CCTV Power Supplies Installation Guide Models Include: • ALTV2432UL
• ALTV2432ULCB
• ALTV2432300UL
• ALTV2432300ULCB
• ALTV2432600UL
• ALTV2432600ULCB
- 24VAC @ 7A (175VA) - 24VAC @ 7A (175VA) or 28VAC @ 6.25A (175VA). or 28VAC @ 6.25A (175VA). - Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs. - 24VAC @ 12.5A (300VA) - 24VAC @ 12.5A (300VA) or 28VAC @ 10A (280VA). or 28VAC @ 10A (280VA). - Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs. - 24VAC @ 25A (600VA) - 24VAC @ 25A (600VA) or 28VAC @ 20A (560VA). or 28VAC @ 20A (560VA). - Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
Rev. 040506
Overview: Altronix ALTV2432UL Series CCTV Power Supplies provide 24VAC/28VAC distributed via thirty-two (32) fuse or PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
ALTV2432600ULCB
Agency Listings:
-
P
3.5A
3.5A 250V
2.9A
32
P
-
2.5A
3.5A 250V
2.9A
32
-
P
3.5A
-
2.7A
32
P
-
2.5A
-
2.7A
32
-
P
3.5A
-
5.4A
32
P
-
2.5A
-
5.4A
Specifications: Features:
• UL Listed for Commercial CCTV Equipment (UL2044). CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment. • CE European Conformity.
Input: • 115VAC, 50/60Hz.
Output: • Thirty-two (32) fuse or PTC protected outputs. • 24VAC or 28VAC outputs. • Outputs are rated @ 3.5A (fused) or 2.5A (PTC). • Surge suppression.
- 2 -
Agency Listings
32
115VAC 50/60Hz Input Current
Main Fuse Ratings
ALTV2432600UL
Output Current (max per output)
ALTV2432300ULCB
Fuse Protected Outputs
ALTV2432300UL
7A 6.25A 7A 6.25A 12.5A 10A 12.5A 10A 25A 20A 25A 20A
PTC Protected Outputs (Class 2 power-limited)
ALTV2432ULCB
24VAC 28VAC 24VAC 28VAC 24VAC 28VAC 24VAC 28VAC 24VAC 28VAC 24VAC 28VAC
Number of Outputs
ALTV2432UL
Total Output Current (Power)
Altronix Model Number
Output Voltage
Thirty-two (32) Output ALTV2432UL Reference Chart:
• AC power LED indicator. • Illuminated power disconnect circuit breaker with manual reset (all other models). • Unit maintains camera synchronization. • Ease of installation saves time & eliminates costly labor. • Spare fuses included (on fuse protected models).
Enclosure Dimensions (H x W x D approx.): 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm).
ALTV2432ULseries
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7). Secure enclosure to earth ground. 2. Turn OFF main switch on the unit (Figs. 1 - 3, pgs. 4 - 6). 3. All units are factory set for 24VAC operation. For 28VAC operation (where available) adjust unit prior to mounting and applying power as follows: Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is connected to the terminal marked [S]. 4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1 - 3, pgs. 4 - 6), secure green lead to earth ground. Use 18 AWG or larger for all power connections. Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. Minimum 0.25” spacing must be provided. Use separate knockouts. 5. Measure output voltage before connecting devices. This helps avoid potential damage. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. 6. Connect devices to terminals marked [1P - 1N] through [16P - 16N] on PD16W/PD16WCB board (Figs. 1 - 3, pgs. 4 - 6), carefully observing polarity. Terminals marked [1P - 16P] are of the same polarity. 7. Turn main switch on unit to the ON (RESET) position (Figs. 1 - 3, pgs. 4 - 6). 8. Green LED(s) will illuminate when unit is powered. 9. Upon completion of the wiring secure enclosure door with screws (supplied). CAUTION: Equipment to be installed/serviced by authorized / trained personnel only. Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with the National Electrical Code. Use 75 C or higher rated UL insulated wiring for connecting the unit to the mains. Replace fuses only with the same type and rating (3.5A/250V). Terminal Identification: PD16W - Power Distribution Module 1P - 16P 1N - 16N
AC output. AC output.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock. The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
ALTV2432ULseries
- 3 -
Fig. 1
ALTV2432UL • ALTV2432ULCB
Used on PTC Models (example: ALTV2432ULCB)
Power Limited Class 2 N P
common outputs protected outputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N P
common outputs protected outputs
9 10 11 12 13 14 15 16
N P
N P
N S
S
S
XFMR Input
XFMR Input
P
P
P
P
XFMR Input
P
N
N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N
Connected to Door
common outputs protected outputs
N
1 2 3 4 5 6 7 8
PTC's
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
Power Supply Board
Power Switch
non-power limited Black Lead
Ground
non-power limited
XFMR
XFMR
115VAC input 50/60 Hz.
Black Lead White Lead
- 4 -
non-power limited
ALTV2432ULseries
Fig. 2
ALTV2432300UL • ALTV2432300ULCB
Used on PTC Models (example: ALTV2432300ULCB) Power Limited Class 2 N P
common outputs protected outputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N P
common outputs protected outputs
9 10 11 12 13 14 15 16
N P
N P
P
P
N P
P
S
S
S
XFMR Input
XFMR Input
XFMR Input
P
N
N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N
Connected to Door
common outputs protected outputs
N
1 2 3 4 5 6 7 8
PTC's
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
Power Supply Board Power Switch
non-power limited
Ground non-power limited
Black Lead
115VAC input 50/60 Hz White Lead
ALTV2432ULseries
XFMR*
- 5 -
Fig. 3
ALTV2432600UL • ALTV2432600ULCB Used on PTC Models (example: ALTV2432600ULCB) Power Limited Class 2 N P
common outputs protected outputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N P
common outputs protected outputs
9 10 11 12 13 14 15 16
N P
N P
P
P
N P
P
S
S
S
XFMR Input
XFMR Input
XFMR Input
P
N
N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N
Connected to Door
common outputs protected outputs
N
1 2 3 4 5 6 7 8
PTC's
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
3.5A 250V
For continuous protection against risk of fire replace fuses with same type and rating.
Power Supply Board
Power Switch
non-power limited non-power limited Ground
115VAC input 50/60 Hz.
XFMR*
XFMR*
Black Lead White Lead
- 6 -
non-power limited
ALTV2432ULseries
Enclosure Dimensions 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm)
4.85” (123mm)
4.85” (123mm)
1.40” (36mm)
1.20” (31mm) 3.25” (83mm)
1.20” (31mm)
0.75” (19mm)
12.5” (318mm) 11.0” (279mm)
1.20” (31mm)
0.75” (19mm) 0.9375” (24mm)
1.40” (36mm)
1.40” (36mm)
5.10” (130mm)
5.10” (130mm)
13.0” (330mm)
5.10” (130mm) 6.5625” (167mm)
0.9375” (24mm)
3.25” (83mm)
3.25” (83mm) 3.25” (83mm)
1.0” (25mm)
1.0” (25mm)
1.0” (25mm)
ALTV2432ULseries
10.5” (267mm)
1.0” (25mm)
- 7 -
Notes:
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail:
[email protected]. Lifetime Warranty, Made in U.S.A. IIALTV2432ULSeries D05P - 8 -
MEMBER ALTV2432ULseries