ALTV244UL3 Series CCTV Power Supplies Installation Guide Models Include:
• ALTV244UL3 - - -
• ALTV244ULCB3
24VAC @ 3.5A (85VA) - or 28VAC @ 3A (85VA). Four (4) Fuse Protected Outputs. - Factory installed 3-wire line cord. -
24VAC @ 3.5A (85VA) or 28VAC @ 3A (85VA). Four (4) PTC Protected Outputs. Factory installed 3-wire line cord.
• ALTV244ULX3 - - -
24VAC @ 3.5A (85VA) or 28VAC @ 3A (85VA). Four (4) Fuse Protected Outputs. Factory installed 3-wire line cord.
• ALTV244175UL3 - - -
• ALTV244175ULCB3
24VAC @ 7A (175VA) - or 28VAC @ 6.25A (175VA). Four (4) Fuse Protected Outputs. - Factory installed 3-wire line cord. -
24VAC @ 7A (175VA) or 28VAC @ 6.25A (175VA). Four (4) PTC Protected Outputs. Factory installed 3-wire line cord.
Rev. 040406
Overview: ALTV244UL3 Series CCTV Power Supplies provide 24VAC or 28VAC distributed via four (4) fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories.
ALTV244175UL3 ALTV244175ULCB3
Agency Listings:
28VAC
3A
24VAC
3.5A
28VAC
3A
24VAC
3.5A
28VAC
3A
24VAC
7A
28VAC
6.25A
24VAC
7A
28VAC
6.25A
5A/ 250V
3.5A/ 0.9A 250V
4
---
P
3.5A 3.5A
5A/ 250V
3.5A/ 0.9A 250V
4
P
---
2.5A
5A/ 250V
3.5A/ 0.9A 250V
4
---
P
3.5A 3.5A
10A/ 250V
3.5A/ 1.76A 250V
4
P
---
2.5A
10A/ 250V
3.5A/ 1.76A 250V
---
---
115VAC 60Hz Input Current
3.5A 3.5A
Primary In-line Fuse Ratings
P
Main Fuse Ratings
---
Fuse Ratings
4
Agency Listings
Individual Output Current (max per output, not to exceed total output current)
Fuse Protected Class 1 Outputs
ALTV244ULCB3
3.5A
PTC Protected Outputs (Class 2 power-limited for Dry locations Class 3 for Wet locations)
ALTV244ULX3
24VAC
Number of Outputs
ALTV244UL3
Total Output Current (Power)
Altronix Model Number
Output Voltage
Four (4) Output ALTV244UL3 Reference Chart:
Specifications: Features (cont’d):
• UL Listed for Commercial CCTV Equipment (UL 2044). CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment. • CE European Conformity.
• Illuminated power disconnect circuit breaker with manual reset (ALTV244175UL3, ALTV244175ULCB3). • Unit maintains camera synchronization. • Ease of installation saves time and eliminates costly labor. Input: • Spare fuses included (on fuse protected models). • 115VAC, 50/60Hz. • Factory installed 3-wire line cord. Output: Enclosure Dimensions (H x W x D): • Four (4) fuse or PTC protected outputs. • ALTV244UL3, ALTV244ULCB3: • 24VAC or 28VAC output. 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm). • Outputs are rated @ 3.5A (fused) or 2.5A (PTC). • ALTV244175UL3, ALTV24175ULCB3: • Surge suppression. 12” x 7.5” x 4.5” (304.8mm x 190.5mm x 114.3mm). Features: • Power ON/OFF switch (ALTV244UL3, ALTV244ULX3 • ALTV244ULX3: 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm). or ALTV244ULCB3).
Installation Instructions: 1. - 2 -
Mount unit in a desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 7, 8). Secure enclosure to earth ground. ALTV244UL3 Series
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3, ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4, 5). 3. All units are factory set for 24VAC operation. For 28VAC operation adjust unit prior to applying power as follows: Remove wires marked [24V] and [28V] from terminals marked [P] and [S]. Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S]. Note: ALTV244ULCB3 set for 28VAC operation is not Class 2 Rated, not power-limited. 4. Plug in 3-wire line cord (Figs. 1-5, pgs. 4-6). Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. Minimum 0.25” spacing must be provided. Use separate knockouts. 5. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3, ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4, 5). 6. Measure output voltage before connecting devices. This helps avoid potential damage. Terminals marked [1P - 4P] are of the same polarity. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. 7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3, ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4, 5). UnPlug 3-wire line cord for all other models (Figs. 1-5, pgs. 4-6). 8. Connect devices to terminals marked [1P - 1N] through [4P - 4N] on PD4 or PD4CB board (Figs. 1-5, pgs. 4-6), carefully observing polarity. 9. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3, ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4, 5). Plug in 3-wire line cord (Figs. 1-5, pgs. 4-6). 10. Green LED will illuminate when power is present. 11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional. Caution: Equipment to be installed/serviced by authorized/trained personnel only. Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes. Use 75˚ C or higher rated UL insulated wiring for connecting the unit to the mains. Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL3 Reference Chart, pg. 2) PD4 - Power Distribution Module 1P - 4P 1N - 4N
Terminal Identification:
AC output AC output
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock. The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
ALTV244UL3 Series
-3-
Fig. 1
3.5A 250V
3.5A 250V
MAIN FUSE
ALTV244UL3
3.5A 250V
ON
OFF
SW1
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 4P & N outputs 2 through 4)
LED
1P
1N
2P
2N
3P
3N
4P
4N
INPUT
N
P
S
Class 1 Outputs
non powerlimited Black Lead
non-power limited
Primary In-line Fuse
Black Lead
XFMR
Back Panel of Enclosure
White Lead
Green Lead (Ground)
115VAC Input 50/60 Hz.
Fig. 2
F1
F2
F3
MAIN FUSE
ALTV244ULCB3
F4
Primary In-line Fuse
ON
OFF
SW1
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 4P & N outputs 2 through 4)
LED
1P
1N
2P
2N
3P
3N
4P
4N
INPUT
N
P
S
24VAC configuration Class 2 Not Wet/Class 3 Wet 28VAC configuration Class 1
non powerlimited
non-power limited
Black Lead Black Lead
XFMR
Back Panel of Enclosure
White Lead
Green Lead (Ground)
115VAC Input 50/60 Hz.
- 4 -
ALTV244UL3 Series
ALTV244ULX3
24VAC or 28VAC fused ( Follow same procedure using terminals 2P & N thru 4P & N outputs 2 thru 4).
1P 1N
Door
3.5A 250V
2P 2N
Class 1 outputs
3.5A 250V
3P 3N 4P 4N
3.5A 250V
N LED
P S
SW1
INPUT
Fig. 3
ON
OFF
MAIN FUSE
Primary In-line Fuse
non power-limited
Black Lead White Lead
XFMR
115VAC 50/60Hz Input, 0.9 amp
ALTV244UL3 Series
AC Input and protected outputs must leave cabinet through separate knockouts. 0.25" spacing must be provided between AC Input and low voltage wiring. For supply connection use wire rate for at least 90˚C.
-5-
Fig. 4
ALTV244175UL3
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 4P & N outputs 2 through 4)
Fig. 4a Class 1 Outputs
non-power limited
Illuminated Power Disconnect Circuit Breaker with manual reset
Black Lead
XFMR
White Lead
Green Lead (Ground)
115VAC Input 50/60 Hz.
Fig. 5
MAIN FUSE
ALTV244175ULCB3
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 4P & N outputs 2 through 4)
Fig. 5a
INPUT N
P
S
24VAC configuration Class 2 Not Wet/Class 3 Wet
non-power limited
Illuminated Power Disconnect Circuit Breaker with manual reset
Black Lead
XFMR
White Lead
Green Lead (Ground)
115VAC Input 50/60 Hz.
- 6 -
ALTV244UL3 Series
Enclosure Dimensions (H x W x D) for: • ALTV244UL3 • ALTV244ULCB3
7.25” (184.15mm) 3.625” (184.15mm) 1.25” (31.75mm)
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)
3.5” (88.9mm)
1.25” (31.75mm)
2” (50.8mm)
0.6” (15.24mm)
0.6” (15.24mm)
6.05” (153.67mm)
1.125” (28.575mm)
1.125” (28.575mm)
2” (50.8mm)
8.125” (206.375mm)
1” (25.4mm)
1” (25.4mm) 6.05” (153.67mm)
0.6” (15.24mm)
0.6” (15.24mm)
1.25” (31.75mm)
3.5” (88.9mm) 1” (25.4mm) 1” (25.4mm)
5.25” (133.35mm)
Enclosure Dimensions (H x W x D) for: • ALTV244175UL3 • ALTV244175ULCB3
1” (25.4mm) 7.5” (190.5mm)
4.5” (114.3mm)
12” x 7.5” x 4.5” (304.8mm x 190.5mm x 114.3mm) 1.25” (31.75mm) 1.5” (12.7mm)
0.5” (12.7mm)
0.5” (12.7mm)
1.11” (28.19mm)
1.11” (28.19mm)
1.25” (31.75mm) 1.5” (12.7mm)
3.5” (88.9mm)
3.5” (88.9mm)
12” (304.8mm)
12” (304.8mm)
2.5” (63.5mm)
5.88” (149.35mm) 3.5” (88.9mm)
1.13” (28.7mm)
1” (25.4mm) 7.5” (190.5mm)
4.5” (114.3mm)
4.5” (114.3mm)
4.5” (114.3mm)
1” (25.4mm) 0.88” (22.35mm)
ALTV244UL3 Series
1” (25.4mm) 5.75” (146.05mm)
0.88” (22.35mm)
-7-
Enclosure Dimensions (H x W x D) for: • ALTV244ULX3 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm)
4.85” (123mm)
4.85” (123mm)
1.40” (36mm)
1.20” (31mm) 3.25” (83mm)
1.20” (31mm)
0.75” (19mm)
12.5” (318mm) 11.0” (279mm)
1.20” (31mm)
0.75” (19mm) 0.9375” (24mm)
1.40” (36mm)
1.40” (36mm)
5.10” (130mm)
5.10” (130mm)
13.0” (330mm)
5.10” (130mm) 6.5625” (167mm)
0.9375” (24mm)
3.25” (83mm)
3.25” (83mm) 3.25” (83mm)
1.0” (25mm)
1.0” (25mm)
1.0” (25mm)
10.5” (267mm)
1.0” (25mm)