APC MGE Galaxy 3500 20kVA 400V 4 Battery Modules, Start-up 5X8
MPN:G35T20K3I4B4S
APC Part Number: G35T20K3I4B4S APC MGE Galaxy 3500,16 kW /20 kVA,Input 400V 3PH /Output 230V, Interface Port DB-9 RS-232, Extended runtime model Includes: Battery modules ship installed, Bolt dow n brackets, CD w ith softw are, Installation guide, Netw ork Management Card, Pow er modules ship installed, Smart UPS signalling RS232 cable, Start-Up Service, User Manual MGE Galaxy 3500 UPS offers compact 3 phase pow er protection w ith the reliability of the MGE product family. Ideal for commercial and technical facilities as w ell as industrial applications, the MGE Galaxy 3500 includes dual-mains input, automatic and maintenance bypasses, and scalable runtime w ith hot-sw appable batteries for increased availability. The parallel capability for redundancy and capacity, new optional bypass panels, and extended run battery frames provide increased flexibility. Low cost of ow nership is achieved through best-in-class efficiency and a reduction in rating of electrical infrastructure – w ires, transformers, and generators. The built in Netw ork Management Card w ith temperature monitoring provides remote UPS pow er monitoring and management through a simple Web/SNMP interface. Serviceability is greatly enhanced by user-replaceable batteries, front access servicing, and included start-up service for maximized configurabililty. All these features make the MGE Galaxy 3500 the easiest UPS in its class to deploy, manage and maintain.
Additional Information Output Pow er Capacity
16 kW / 20 kVA
Max Configurable Pow er
16 kW / 20 kVA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load
95.3%
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
47 – 53 Hz for 50 Hz nominal
Other Output Voltages
220, 240
Crest Factor
Unlimited
Topology
Double Conversion Online
Waveform Type
Sine w ave
Output Connections
(1) Hard Wire 3-w ire (H N + G) (1) Screw Terminals
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
Output Voltage THD
< 2% for 0 to 100% linear load and < 5% for full non linear load
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load
95.4%
Required Output Current Protection
100A
Bypass
Built-in Maintenance Bypass, Built-in Static Bypass
Nominal Input Voltage
400V 3PH
Input Frequency
40 – 70 Hz (auto sensing)
Input Connections
Hard Wire 5-w ire (3PH + N + G)
Input voltage range for main operations
304 – 477V
Input voltage adjustable range for mains operation
340 – 460 (400V)V
Other Input Voltages
380, 415
Maximum Input Current
27A
Input Breaker Capacity
35.0 A
Input Total Harmonic Distortion
Less than 5% for full load
Type of Input Protection Required
3-pole breaker
Battery Type
Maintenance-free sealed Lead-Acid battery w ith suspended electrolyte : leakproof
Included Battery Modules
4
Typical recharge time
5 hour(s)
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage
+/-154 V
Efficiency in Battery Operation
94.80%
End of Discharge Maximum Battery Current
109
Extended Run Options
MGE Galaxy 3500 20kVA 400V 3:1 w ith 4 Battery Modules, Start-up 5X8
Interface Port(s)
DB-9 RS-232
Pre-Installed SmartSlot™ Cards
AP9631
Control panel
Multifunction LCD status and control console
Audible Alarm
Alarm w hen on battery : distinctive low battery alarm : configurable delays
Emergency Pow er Off (EPO)
Yes
Operating Environment
0 – 40 °C
Operating Relative Humidity
0 – 95%
Operating Elevation
0-999.9 meters
Storage Temperature
-15 – 45 °C
Storage Relative Humidity
0 – 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
51.30 dBA
Online Thermal Dissipation
2730.00 BTU/hr
Protection Class
IP 51
Regulatory Approvals
CE, EN 50091-2, EN/IEC 62040-3, EN/IEC 62040-1-1, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-111
Standard Warranty
Weight
Length
Width
Height
1 year repair or replace 656kg
83.8cm
52.3cm
149.1cm