Appliance and Controller Electrical Installation Guide.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Telephone 0845 6448802 Fax 0845 6448803 Email
[email protected] www.mhgheating.co.uk 01/01/12
MHG Heating Ltd ©
Content Appliances
Page
ProCon 16 – 77 Wall Mounted Condensing Boilers (LMU64)
3
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVA47 Controlled to 01/01/2011
5
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVS43 Controlled from 01/01/2011
6
ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVA47 Controlled to 01/01/2011
8
ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVS43 Controlled from 01/01/2011
9
Boiler Controller Mounted Options AGU2.511 BMS Run & Fault Output & 0-10V or 0-20mA Input Clip
11
AGU2.500 Heating Zone 2 Pump & Mixing Valve Clip
13
OCI420 LPB Cascade & System Controller Communication Clip
14
Cascade, System & Room Controls RVA47 Cascade Manager Without Optional Housing
15
RVA47 Cascade Manager With Optional Housing
16
RVA63 Boiler and Zone Controller Without Optional Housing
18
RVA63 Boiler and Zone Controller With Optional Housing
20
RVA46 Zone Controller Without Optional Housing
23
RVA46 Zone Controller With Optional Housing
24
RVS63 Cascade and Zone Control Manager With/Without Housing
25
QAA73 Single Boiler Opentherm Room Unit
27
QAA70/50/10 PPS Cascade or System Controller Room Unit
28
QAA55 BSB Cascade or System Controller Room Unit
29
QAA75 BSB Cascade or System Controller Room Unit
30
QAA78 Wireless Cascade or System Controller Room Unit
31
Please note that this document is intended as a quick reference guide. Further detailed guidance should be sought from the respective boiler/controller technical manuals.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
2
MHG Heating Ltd ©
ProCon 16 – 77 Wall Mounted Condensing Boilers. Boiler Wiring Terminals
Boiler Controller Mounted Terminals
Terminal Designation Tag RU
Terminal #s
Voltage
1&2
< 25V
(Not Polarity Sensitive)
Screened Cable
Description/Operation/Function
(Earthed Screening)
Yes
QAA73 Opentherm Room Unit or Link to enable second heating zone time switch. (AGU2.500 Communication Clip required to control second heating zone pump/valve.)
3&4
RT
(Not Polarity Sensitive)
5&6
AT
(Not Polarity Sensitive)
7&8
BW
(Not Polarity Sensitive)
< 25V
Yes
< 25V
Yes
< 25V
Yes
(Via Time Switch/Room Thermostat/BMS)
Outside Air Sensor. (QAC34) (Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)
Hot Water Sensor (QAZ36) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)
10 Perm Live 11 Neutral 12 Switched Live
230V
K2
13 Switched Live 14 Neutral
230V
-
K1
16 Neutral 17 Switched Live
230V
-
BW/K3
Heating Volt Free Enable.
-
Hot Water Charging Pump or 3 way Valve Output. (Max 1 Amp) (Parameter alteration required if charging pump used with 16 & 31 and if 3 way valve used with 47 & 75.)
Models 16 & 31 External Heating Pump. (Max 1 Amp)
Models 47 & 75 Internal Boiler Pump. (Max 1 Amp) Models 16 & 31 Internal Boiler Pump. (Max 1 Amp) Models 47 & 75 External Heating Pump. (Max 1 Amp)
-
-
Common Permanent Earth
N L
9, 15 & 18 19 20
230V 230V
-
Permanent Neutral Permanent Live (Max 5 Amp)
X10-03
-
<25V
Yes
Safety Interlock Volt Free Enable
E
(For use with ventilation interlocks/gas pressure switch etc.)
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13/14 for additional guidance.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
3
MHG Heating Ltd ©
Generic Single Boiler Hydraulic Configuration
For BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Options.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
4
MHG Heating Ltd ©
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVA47 (Grey) Controlled. Produced to 01/01/2012
Additional Wiring Terminals (This terminal rail is in addition to the standard rail.)
Terminal Designation Tag
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
BW HK / ZB
230V 230V
-
H1
< 25V
Yes
RL
< 25V
Yes
Return Sensor (QAD21)
Yes
Flow Sensor (QAD21)
VL BW
< 25V < 25V
Yes
Hot Water Charging Pump Output. (Max 2 Amp) Heating Circuit Pump Output. (Max 2 Amp) Enabling Input Volt Free Enable or 0-10Volt or Operation Changeover (M = Ground & H1 = Positive) (M = Ground & B70/B4 Positive) (M = Ground & B10 Positive)
Hot Water Sensor (QAZ21) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)
(M = Ground & B3 Positive)
Outside Air Sensor. (QAC31/32) (620Ω Substitute Resistor = -1 C) 0
AF
< 25V
Yes
(Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)
(M = Ground & B9 Positive)
RU
< 25V
Yes
Room Unit QAA70/50/10
LPB
< 25V
Yes
LPB Cascade Communication. (Loom Mounted Plug.)
(M = Ground & A6 Positive) (MB = Ground & DB = Data Bus)
Each boiler within the cascade including the master will have an OCI420 Communication Clip fitted. The LPB communication wiring must be wired (X41) between each OCI420 Communication Clip in parallel. MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
5
MHG Heating Ltd ©
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVS43 Controlled. Produced from 01/01/2012
Additional Wiring Terminals Located on the RVS43 Controller.
Tag
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
LEN
230V
-
P
230V
-
Q
230V
-
R S
230V 230V
-
T
230V
-
U
230V
-
X30
< 25V
Ribbon
a
< 25V
Yes
b
< 25V
Yes
b
< 25V
Yes
f
< 25V
Yes
h
< 25V
Yes
k
< 25V
Yes
n
< 25V
Yes
p n n
< 25V < 25V < 25V
Yes Yes Yes
Permanent 230 Volt Power Supply From the LMU X1:02. Not Used in this configuration. Safety Interlock (SK1 & SK2) HWS Pump or Valve Output 230 Volts Max 1 Amp (Q3) Heating Circuit Pump Output 230 Volt Max 1 Amp (Q2) Heating Circuit Mixing Valve Output (Y1 Valve Open. Y2 Valve Close) Multifunctional Relay Output (QX1) Display Panel LPB Cascade Communication .
For connection to OCI clips in master and cascade boilers
DB Data MB Ground BSB Data Communication QAA75 Room Unit Communication CL+ Data CL- Ground G+ 12 Volt Power Supply Not Used in this configuration. Hot Water Sensor or Volt Free Enable QAZ36 Parameter change required if using volt free enabling.
Outside Air Sensor QAD34 Volt Free Enable or 0-10 Volt Drive input H1 +, M Ground Heating Circuit 1 Flow Senor. (Only used when a mixing valve is applied.) System Flow Senor QAZ36 System Return Sensor QAZ36
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
6
MHG Heating Ltd ©
Generic Multiple Boiler Hydraulic Configuration
For BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Options.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
7
MHG Heating Ltd ©
ProCon HT 150-225 Floor Standing Condensing Boilers. RVA47 (Grey) Controlled. (Produced to 01/01/2011)
Boiler Wiring Terminals
External Flow and return sensors (QAD21) are required for Cascade Manager Units only. The sensors must be wired to the terminal detailed below.
These terminals are located on the top left of the boiler frame when viewed from the front. (These terminals are pre-wired on Standalone FS units.)
Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)
Tag RU H1 BW AF BUS BW HK 230V
Terminal Designation Terminal Voltage #s A6 & MD (Not Polarity Sensitive)
H1 & M (Polarity Sensitive)
B3 & M (Not Polarity Sensitive)
B9 & M (Not Polarity Sensitive)
DB & MB (Polarity Sensitive)
N Neutral Q3 Switched Live 11 Switched Live N Neutral N Perm Neutral L Perm Live
Screened Cable
Description/Operation/Function
(Earthed Screening)
< 25V
Yes
<25V
Yes
< 25V
Yes
< 25V
Yes
< 25V
Yes
230V
-
230V
-
230V
-
VL
B10 & M
< 25V
Yes
RL
M & B70
< 25V
Yes
X10-03
-
<25V
Yes
QAA70/50/10 PPS Room Unit 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS Hot Water Sensor (QAZ21) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)
Outside Air Sensor.
(QAC31/32) or (620Ω Substitute Resistor = -1 C) 0
(Mounted on North Facing Wall)(Parameter alteration required if outside air sensor not connected)
Boiler Communication to Slave Boilers. (LPB DB Data & MB Ground)
Hot Water Charging Pump or 3 way Valve Output.
(Max 2 Amp)
Heating Pump Output (Max 2 Amp) Permanent 240 Volt Supply
(Max 10 Amp)
System Flow Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)
System Return Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)
Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
8
MHG Heating Ltd ©
ProCon HT 150-225 Floor Standing Condensing Boilers. RVS43 Controlled. (Produced from 01/01/2011)
Boiler Wiring Terminals
Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
9
MHG Heating Ltd ©
Generic Single HT Boiler Hydraulic Configuration
Generic Multiple HT Boiler Hydraulic Configuration (Indicting the location of the system mounted Flow and Return Sensors)
For Module BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Option.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
10
MHG Heating Ltd ©
Boiler Controller Mounted Options. AGU2.511 BMS Run & Fault 230V Outputs & 0-10Volt/0-20mA Input Clip.
Terminal Designation Tag
Terminal #s
Voltage
Description/Operation/Function
Switched Output Power Input X52-01
1 Live 2 Neutral
230V
Power Supply from X01-02 for switched live outputs. Power Supply from BMS can replace power supply from X01-02 (<230V/0.5Amp)
(Max)
Programmable Output Output 1R X52-02
1 Live 2 Neutral
230V (Max)
Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV.(Safety Shut Off Valve) (Max 1 Amp) (Parameter amendment required)
Output 2R X52-03
1 Live 2 Neutral
Programmable Output 230V (Max)
Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp) (Parameter amendment required)
Programmable Output Output 3R X52-03
3 Live
230V (Max)
Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp) (Parameter amendment required)
Control Input X51-01
1 Control Input 2 Ground
0-10V Or 0-20mA
Programmable Control Input 0-10 Volt or 0-20mA Flow Temperature or % Power Control (Parameter amendment required)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
11
MHG Heating Ltd ©
Boiler Controller Mounted Options. AGU2.500 Heating Zone 2 Pump/Mixing Valve/Sensor Clip.
Terminal Designation Tag Switched Output Power Input X52-01 Pump Output X52-02 Mixing Valve X52-03 Flow Sensor Input X51-01
Terminal #s
Voltage
Description/Operation/Function
1 Live 2 Neutral
230V
Power Supply from X01-02 for switched live outputs.
1 Live 2 Neutral
230V
Heating Zone 2 Pump Outputs
1 Close 2 Neutral 3 Open
230V
1&2
<25V
(Not Polarity Sensitive)
(Max 1 Amp)
Heating Zone 2 Mixing Valve Outputs (Valve control is possible only when a zone flow sensor is connected) (Max 1 Amp)
Heating Zone 2 Flow Sensor Inputs. (QAD36)
*H552 must be set to 66 to ensure correct operation of mixing zone clip.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
12
MHG Heating Ltd ©
Generic Single Boiler (AGU2.500 Zoned) Hydraulic Configuration
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
13
MHG Heating Ltd ©
Boiler Controller Mounted Options. OCI420 LPB Cascade Communication Clip. For use when control is provided via a RVA47 Cascade Manager or RVA63 Controller.
Terminal Designation Tag
Terminal #s
LPB X41-01
1, DB LPB Data 2, MB LPB Ground (Polarity Sensitive)
Screened Cable
Description/Operation/Function
Yes
LPB Control Communication From RVA47 Cascade Manager or RVA63 Boiler and zone controller. (Parameter amendment required)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
14
MHG Heating Ltd ©
RVA47 Cascade Manager. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation Tag H1
Terminal #s
Voltage
6
<25V
(Polarity Sensitive)
Screened Cable
Description/Operation/Function
(Earthed Screening)
Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS (M terminal used to create circuit)
B70/ B4 B3
5 (Not Polarity Sensitive)
4 (Not Polarity Sensitive)
<25V
Yes
System Return Sensor (QAD21)
<25V
Yes
Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS
(To be positioned on boiler side of system Low Loss Header)
(Parameter alteration required if Volt Free Enable Used)
M B10 B9 MD A6 MB DB
M 2 (Not Polarity Sensitive)
1 (Not Polarity Sensitive)
M (Not Polarity Sensitive)
(Not Polarity Sensitive)
M (Polarity Sensitive)
(Polarity Sensitive)
<25V
Yes
<25V
Yes
Ground Connection for all Sensors/Inputs System Flow Sensor (QAD21)
<25V
Yes
Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
<25V
Yes
QAA70/50/10 Room Unit (PPS Ground)
<25V
Yes
QAA70/50/10 Room Unit (PPS Data)
<25V
Yes
Boiler Communication (LPB Ground connected in parallel to
<25V
Yes
Boiler Communication (LPB Data connected in parallel to
(To be positioned on system side of system Low Loss Header) 0
(Mounted on North Facing Wall)
boiler mounted OCI420 Clips) boiler mounted OCI420 Clips))
Q3
3
230V
-
Hot Water Charging Pump/3 Way Valve Output
Q1
2
230V
-
F1
F
230V
-
Heating Pump Output (Max 2 Amp) Power Input for Heating and Hot Water Pump Outputs
L N
L N
230V 230V
-
Permanent Live (Max 6 Amp) Permanent Neutral
(Max 2 Amp)
(To be linked to Live Input)
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
15
MHG Heating Ltd ©
RVA47 Cascade Manager. Manager Wiring Terminals.(Housing) (Housing designed for use with additional RVA46 Zone controller)
(RVA 46 Zone Controller wiring Information detailed later in document.)
Terminal Designation Tag
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
DB
<25V
Yes
Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clips))
MB
<25V
Yes
Boiler Communication (LPB Ground connected in parallel to boiler
A6 MD
<25V <25V
Yes Yes
B9
<25V
Yes
QAA70/50/10 Room Unit (PPS Data) QAA70/50/10 Room Unit (PPS Ground) Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
M
<25V
Yes
B10
<25V
Yes
Ground Connection for all Sensors/Inputs System Flow Sensor (QAD21)
Yes
Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS
B3
<25V
mounted OCI420 Clips)
0
(Mounted on North Facing Wall)
(To be positioned on system side of system Low Loss Header)
(Parameter alteration required if Volt Free Enable Used)
B70/ B4
<25V
Yes
System Return Sensor (QAD21)
H1
<25V
Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS
Q1 Q3 N PE L
230V 230V 230V 230V
(To be positioned on boiler side of system Low Loss Header)
Heating Pump Output (Max 2 Amp) Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) Permanent Neutral Permanent Earth Permanent Live (Max 6 Amp) (All ‘M’ Terminals are Internally Linked)
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
16
MHG Heating Ltd ©
Generic Multiple Boiler RVA47 Controlled Hydraulic Configuration
Outside Air Sensor QAC32
Up to 12 ProCon Boilers In Cascade
RVA47 Cascade Controller
Heating Zone
LPB Communication to each boiler via an OCI clip module.
QAA70/50/10
Zone Pump Hot Water Primary Pump
Hot Water Sensor QAZ21 Flow Sensor QAD21
Return Sensor QAD21
Component Control Capability of RVA47
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
17
MHG Heating Ltd ©
RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation (Low Voltage Terminals) Tag MD
Terminal #s (Not Polarity Sensitive)
-
A7
(Not Polarity Sensitive)
B12
3 (Not Polarity Sensitive)
M
M
(Not Polarity Sensitive)
1
B8
(Not Polarity Sensitive)
B31/ H2/ B41
4 (Polarity Sensitive)
3
B1
(Not Polarity Sensitive)
6
H1
(Polarity Sensitive)
5
B2
(Not Polarity Sensitive)
4
B3
(Not Polarity Sensitive)
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
<25V
Yes
Zone 2 QAA70/50/10 Room Unit (PPS Ground)
<25V
Yes
Zone 2 QAA70/50/10 Room Unit (PPS Data)
<25V
Yes
Zone 2 Flow Sensor (QAD21/26)
<25V
Yes
Ground Connection for all Sensors/Inputs
<25V
Yes
Flue Gas Sensor (Not Used)
<25V
Yes
Volt Free Enable via Room Thermostat/BMS
<25V
Yes
Zone 1 Flow Sensor (QAD21/26)
<25V
Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS
<25V
Yes
Boiler Sensor (Not Used)
<25V
Yes
Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS
<25V
Yes
Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
<25V
Yes
Zone 1 QAA70/50/10 Room Unit (PPS Ground)
<25V
Yes
Zone 1 QAA70/50/10 Room Unit (PPS Data)
<25V
Yes
Boiler Communication (LPB Ground connected in parallel to
Yes
Boiler Communication (LPB Data connected in parallel to
(To be positioned on Zone side of 3 way mixing valve)
(To be positioned on Zone side of 3 way mixing valve)
(Parameter alteration required if Volt Free Enable Used)
1
B9
(Not Polarity Sensitive)
MD
-
A6
(Not Polarity Sensitive)
MB DB
M (Not Polarity Sensitive)
M (Polarity Sensitive)
(Polarity Sensitive)
<25V
0
(Mounted on North Facing Wall)
boiler mounted OCI420 Clip or RVA47 Manager) boiler mounted OCI420 Clip or RVA47 Manager)
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
18
MHG Heating Ltd ©
RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation (230 Volt Terminals)
Y6 Y5
Terminal #s -
F3
-
230V
Q6 Q2
3 2
230V 230V
F6
F
230V
Y2 Y1
3 2
230V 230V
F2
F
230V
Zone 1 Mixing Valve Closing Output (Max 2 Amp) Zone 1 Mixing Valve Opening Output (Max 2 Amp) Power Input for Zone 1 Valve Outputs
Q3/Y 3
3
230V
Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)
F1
F
230V
Power Input for Hot Water Pump/Valve Output
K5 F5 K4 F4 L N
4 F 2 F L N
230V 230V 230V 230V 230V 230V
Burner Enable Output Stage 2 (Not Used) Power Input Burner Enable Stage 2 (Not Used) Burner Enable Stage 1 (Not Used) Power Input Burner Enable Stage 1 (Not Used) Permanent Live (Max 6 Amp) Permanent Neutral
Tag
Voltage
Description/Operation/Function
230V 230V
Zone 2 Mixing Valve Closing Output (Max 2 Amp) Zone 2 Mixing Valve Opening Output (Max 2 Amp) Power Input for Zone 2 Valve Outputs (To be linked to Live Input)
Zone 2 Pump Output (Max 2 Amp) Zone 1 Pump Output (Max 2 Amp) Power Input for Zone Pumps Output (To be linked to Live Input)
(To be linked to Live Input)
(To be linked to Live Input)
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
19
MHG Heating Ltd ©
RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)
Terminal Designation (Low Voltage Terminals) Tag
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
DB
<25V
Yes
Boiler Communication (LPB Ground connected in parallel to boiler
M
<25V
Yes
Boiler Communication (LPB Data connected in parallel to boiler mounted
A6 M
<25V <25V
Yes Yes
B9
<25V
Yes
Zone 1 QAA70/50/10 Room Unit (PPS Data) Zone 1 QAA70/50/10 Room Unit (PPS Ground) Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
M
<25V
Yes
B3
<25V
Yes
B2
<25V
Yes
H1
<25V
Yes
B7
-
-
B1
<25V
Yes
Boiler Sensor (Not Used) 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS Not Used with RVA63 Zone 1 Flow Sensor (QAD21)
<25V
Yes
Volt Free Enable via Room Thermostat/BMS
<25V
Yes
B12
<25V
Yes
Flue Gas Sensor (Not Used) Zone 2 Flow Sensor (QAD21)
B4 M M A7
<25V <25V <25V
Yes Yes Yes
Not Used with RVA63 Ground Connection for all Sensors/Inputs Zone 2 QAA70/50/10 Room Unit (PPS Ground) Zone 2 QAA70/50/10 Room Unit (PPS Data)
mounted OCI420 Clip or RVA47 Manager) OCI420 Clip or RVA47 Manager)
0
(Mounted on North Facing Wall)
Ground Connection for all Sensors/Inputs Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used)
B31/ H2/ B41 B8
(To be positioned on Zone side of 3 way mixing valve)
(To be positioned on Zone side of 3 way mixing valve)
(All ‘M’ Terminals are Internally Linked)
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
20
MHG Heating Ltd ©
RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)
Terminal Designation (230 Volt Terminals) Tag K6 Y6 Y5 N Q6 Q2 N Y2 Y1 Q3/Y 3 PE N L1 K5 F5 K4
Voltage 230V 230V 230V 230V 230V 230V 230V 230V
Description/Operation/Function Not Used with RVA63 Zone 2 Mixing Valve Closing Output (Max 2 Amp) Zone 2 Mixing Valve Opening Output (Max 2 Amp) Permanent Neutral Zone 2 Pump Output (Max 2 Amp) Zone 1 Pump Output (Max 2 Amp) Permanent Neutral Zone 1 Mixing Valve Closing Output (Max 2 Amp) Zone 1 Mixing Valve Opening Output (Max 2 Amp)
230V
Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)
230V 230V 230V 230V 230V
Permanent Earth Permanent Neutral Permanent Live (Max 6 Amp) Burner Enable Output Stage 2 (Not Used) Power Input Burner Enable Stage 2 (Not Used) Burner Enable Stage 1 (Not Used)
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
21
MHG Heating Ltd ©
Generic Single Boiler RVA63 Controlled Hydraulic Configuration
RVA47 Cascade Controller
Outside Air Sensor QAC32
LPB Communication to each boiler via OCI Clip Modules RVA63 Controller
LPB Single Boiler Control with OCI420 Clip
Heating Zone 1
Heating Zone 2
QAA70/50/10
QAA70/50/10
Zone 1 Pump
Zone 2 Pump
Hot Water Primary Pump
Mixing Valve Hot Water Sensor QAZ21
Mixing Valve
Zone 1 Flow Sensor QAD26
Zone 2 Flow Sensor QAD26
Component Control Capability of RVA63
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
22
MHG Heating Ltd ©
RVA46 Zone Controller. Controller Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation Tag H1 M B1 B9 MD A6 MB DB
Terminal #s 6 (Not Polarity Sensitive)
M 2 (Not Polarity Sensitive)
1 (Not Polarity Sensitive)
M (Not Polarity Sensitive)
(Not Polarity Sensitive)
M (Polarity Sensitive)
(Polarity Sensitive)
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
<25V
Yes
Volt Free Enable via Room Thermostat/BMS
<25V
Yes
<25V
Yes
Ground Connection for all Sensors/Inputs Zone Flow Sensor (QAD21)
<25V
Yes
Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
<25V
Yes
Zone QAA70/50/10 Room Unit (PPS Ground)
<25V
Yes
Zone QAA70/50/10 Room Unit (PPS Data)
<25V
Yes
RVA47/63 Communication (LPB Ground connected in parallel to
<25V
Yes
RVA47/63 Communication (LPB Data connected in parallel to RVA47 Mixing Valve Closing Output (Max 2 Amp) Mixing Valve Opening Output (Max 2 Amp) Power Input for Zone Valve Outputs
(To be positioned on Zone side of 3 way mixing valve) 0
(Mounted on North Facing Wall) (Not required if using RVA47 O/S Sensor)
RVA47 Manager or RVA63 Zone controller) Manager or RVA63 Zone controller)
Y2 Y1
3 2
230V 230V
-
F2
1
230V
-
Q2
2
230V
-
F6
F
230V
-
Zone Pump Output (Max 2 Amp) Power Input for Zone Pump Output
L N
L N
230V 230V
-
Permanent Live (Max 6 Amp) Permanent Neutral
(To be linked to Live Input)
(To be linked to Live Input)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
23
MHG Heating Ltd ©
RVA46 Zone Controller. Controller Wiring Terminals.(Housing) (Housing designed for use with primary RVA47 Cascade Manager.)
(RVA 47 Cascade Manager wiring Information detailed earlier in document.)
Terminal Designation Tag
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
A6 MD
<25V <25V
Yes Yes
Zone QAA70/50/10 Room Unit (PPS Data) Zone QAA70/50/10 Room Unit (PPS Ground) Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -1 C)
B9
<25V
Yes
M
<25V
Yes
B1
<25V
Yes
Ground Connection for all Sensors/Inputs Zone Flow Sensor (QAD21)
H1
<25V
Yes
Volt Free Enable via Room Thermostat/BMS
Q2 Y1 Y2
240V 240V 240V
Zone Pump Output (Max 2 Amp) Mixing Valve Opening Output (Max 2 Amp) Mixing Valve Closing Output (Max 2 Amp) (All ‘M’ Terminals are Internally Linked)
0
(Mounted on North Facing Wall)(Not required if using RVA47 O/S Sensor)
(To be positioned on Zone side of 3 way mixing valve)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
24
MHG Heating Ltd ©
RVS63 Cascade and Zone Controller. Wiring Terminals Located on the RVS63 Controller. (Housing Available)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
25
MHG Heating Ltd ©
Terminal Legend. Tag Terminal #s Voltage QX4, QX4, FX4, EX2 Z 230 Volts U QX3, ‡, N 230 Volts U QX2, ‡, N 230 Volts
Screened Cable (Earthed Screening)
NA NA NA
T
Y6, ‡, N, Y5
230 Volts
NA
S U
Q6, ‡, N QX1, ‡, N
230 Volts 230 Volts
NA NA
T
Y2, ‡, N Y1
230 Volts
NA
S R Q P ~ ~ ~
Q2, ‡, N Q3, ‡, N SK2, SK1 4, S3, T2, T1, , L1
S3 L1 N, E, L
230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts 230 Volts
NA NA NA NA NA NA NA
Tag n n n
Terminal #s M, UX M, BX4 M, BX3
Voltage >24 Volts >24 Volts >24 Volts
Screened Cable
Description/Operation/Function Multifunctional 4 Relay Output Multifunctional 3 Relay Output Multifunctional 2 Relay Output Heating Circuit 2 Mixing Valve Output Y5 Open, Y6 Close Heating Circuit 2 Pump Output Multifunctional 1 Relay Output Heating Circuit 1 Mixing Valve Output Y1 Open, Y2 Close Heating Circuit 1 Pump Output HWS Circuit Pump, Valve Output External Safety Interlock Circuit **Burner Outputs Not Used** **Burner Outputs Not Used** Permanent Live Output Permanent Supply Input
Description/Operation/Function Yes 0-10 Volt Output **Not Used** Yes Multifunctional 4 Sensor Input Yes Multifunctional 3 Sensor Input Volt Free Enable or 0-10 Volt Input n M, H3 >24 Volts Yes Heating Zone 2 Heating Circuit 2 Flow Sensor p M, B12 >24 Volts Yes QAD/Z36 n M, BX2 >24 Volts Yes Boiler Return Sensor QAD/Z36# n M, BX1 >24 Volts Yes System Flow Sensor QAD/Z36# Heating Circuit 1 Flow Sensor p M, B1 >24 Volts Yes QAD/Z36 Volt Free Enable or 0-10 Volt Input n M, H1 >24 Volts Yes Heating Zone 1 k M, B9 >24 Volts Yes Outside Air Sensor QAC34 HWS Sensor QAZ36 or Volt Free h M, B3 >24 Volts Yes Enable f M, B2 >24 Volts Yes Boiler Sensor **Not Used** G+ QAA75 Power Supply 12 Volts Heating Circuit 1 QAA55/75 b CL-, CL+ >24 Volts Yes -Ground, + Data Heating Circuit 2 QAA55/75 b CL-, CL+ >24 Volts Yes -Ground, + Data b CL-, CL+ >24 Volts Yes BSB Comms to second RVS Boiler Communication Connection a MB,DB >24 Volts Yes (OCI420 Clips mounted in Boilers Wiring in Parallel) X30 ~ >24 Volts Yes Display Panel Connection X60 ~ >24 Volts Yes Connection for QAA78 Sender # Parameter alterations may be required to configure these terminals. MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR 26 (Earthed Screening)
Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
MHG Heating Ltd ©
QAA73 Single Boiler Opentherm Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation Screened Cable
Terminal #s
Voltage
1&2
<25V
Yes
-
-
(Not Polarity Sensitive)
3&4 5&6
Description/Operation/Function
(Earthed Screening)
Opentherm communication to Single Boiler Installation Not Used Not Used
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
27
MHG Heating Ltd ©
QAA70/50/10 PPS Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation Screened Cable
Terminal #s
Voltage
D1 & D2
<25V
Yes
<25V
Yes
-
-
(Not Polarity Sensitive)
D 3 & D4 (Not Polarity Sensitive)
D5 & D6
Description/Operation/Function
(Earthed Screening)
PPS communication to RVA47/46/63 Controlled Installation Tamperproof QAW44 Remote Sensor or Volt Free Enable Not Used
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
28
MHG Heating Ltd ©
QAA55 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation Terminal #s 1 2
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
<25V <25V
Yes Yes
BSB Data CL+ BSB Ground CL-
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
29
MHG Heating Ltd ©
QAA75 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation Terminal #s 1 2 3
Voltage
Screened Cable
Description/Operation/Function
(Earthed Screening)
<25V <25V <25V
Yes Yes Yes
BSB Data CL+ BSB Ground CLPower Supply DC 12V G+
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
30
MHG Heating Ltd ©
QAA78 Wireless Cascade or System Controller Room Units Room Unit Mounting Plate and Receiver Module Mount the receiver module outside of the boiler/housing and connect the ribbon cable to X60 on the controller
Mount the cradle and insert the batteries into the rear of the QAA78 room unit.
**Follow synchronising instructions supplied with the QAA78 room unit.**
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12
31
MHG Heating Ltd ©
NOTES
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email
[email protected] Web www.mhgheating.co.uk 01/01/12