Preview only show first 10 pages with watermark. For full document please download

Application Note - Dmp.com - Digital Monitoring Products

   EMBED


Share

Transcript

APPLICATION NOTE Contents Introduction....................................... 1 What are the Possibilities?.................. 1 Circuit Power Options......................... 1 Conventional Large Fire/ Small Burglary ................................ 2 Installation Notes:...................... 2 Conventional Large Burglary/ Small Fire ...................................... 3 Installation Notes:...................... 3 Distributed Power Notification Circuit .. 4 Installation Notes:...................... 4 Separate Horn and Strobe Circuits ...... 6 Installation Notes:...................... 6 Model 867 Style W LX-Bus™ Notification Module.......................... 7 Model 866 Style W Notification Module........................................... 7 Model 865 Style Y or Z Notification Module........................................... 8 Product Compliance Certifications........ 8 Introduction To meet today’s demanding installation requirements, an alarm installer needs a control panel that provides a wide variety of fire notification and local burglary alarm circuit configurations. The DMP XR500 Series, XR2500F, XR100 Series, and XR200 Command Processor™ Panels meet and exceed those needs with a unique blend of industryleading UL listed hardware and software operations. This application note provides technical information needed to apply one of many flexible solutions to your installation, whether the application is a stand-alone fire system, a burglary system, or a cost-effective combination system. What are the Possibilities? Typical fire and burglary alarm control panels offer single or multiple notification outputs directly powered by the panel. This type of design requires all notification circuits be wired from the most remote points of the system directly to the panel. Increasing the wire gauge and limiting the number of notification appliances are typical strategies required to maintain voltage levels at the end of a circuit. The UL listed XR500 Series, XR2500F, XR100 Series, and XR200 Panels provide a single output, or zoned outputs that allow power supplies to be distributed throughout the facility. Supervised power supplies can be located anywhere along the panel LX-Bus™ placing the notification circuit power near the notification appliances where it is needed. Circuit Power Options The system can be configured to provide a traditional 12 VDC burglary output, a 24 VDC fire output, or a combination of both outputs. A 12 VDC, 1.5 Amp output is standard on the XR500 Series, XR2500F, XR100 Series, and XR200 panels and can be used for burglary or fire appliances. Easily add 12 or 24 VDC power supplies to the system by employing any of the available notification modules. Expand a panel to support independently supervised, fully programmable circuits for customized applications: • XR500 Series or XR2500F panels support up to 574 circuits • XR100 Series panels support up to 142 cirucits • XR200 panel supports up to 242 circuits This application note illustrates several different system configurations. NOTIFICATION CIRCUIT OPTIONS FOR COMBINATION SYSTEMS APPLICATION NOTE Conventional Large Fire/Small Burglary Command Processor Panel This application provides a 12 VDC, 1.5 Amp burglary output, and a 12 VDC, 5 Amp fire output. This would be useful in a facility where the major objective is fire notification, but a local burglary alarm is also desired. The XR500 Series, XR2500F, XR100 Series, and XR200 Panel 12 VDC, 1.5 Amp output is used to power all burglary alarm appliances and the auxiliary outputs are used to activate the DMP 866 Fire Notification Module. The 866 module switches the power supply to power the fire notification appliances. Because DMP supports 12 or 24 VDC configurations the fire notification appliances can be 12 or 24 VDC to meet local requirements. Bell Output Output 1 DMP Notification Module Notification Device Polarized Burglary Alarm 12 VDC or 24 VDC Power Supply Installation Notes: 1. The Model 865 Style Y/Z Notification Circuit Module may be substituted for the Model 866 to provide Class A notification. 2. Bell Action programming must activate for burglary zones. 3. Zones 1 and 2 must be programmed as supervisory type zones with appropriate names. 4. Fire Bell Output programming must activate output 1. 5. For UL burglary systems where the bell is tested daily at closing, circuit supervision is not required. 6. See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions. 7. See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or XR200 Programming Guide (LT-0196) for complete programming instructions. XR500 Series/XR2500F XR100 Series Command Processor™ Panel J a per J one e in J6 Interface Card Expansion Connector J P J odel XR200 tp t eader J ra J tp t J J C J C E E J 6 ra C I ones one r ar ones see notes and tp t J 6 eset tp t E ran e 6 6 E ire e ee note t C C ire t J atter tart 6 a e tead e C o ari ed r ar otification pp iance pe tp t ps E o er 6 E a e ire otification pe per isor ee note pp per isor ee note t e ode 66 ee note otification Circ it e od E x r ro e contacts E C or C o er pp o er C E pp Co on C po r e inp t ar inp t C o tp t eries s p ro e contacts ire otification orns 12 VDC @ 1.5 Amp Bell Output from the Panel 12 VDC @ 5 Amps Fire Output from a DMP 505 Series 12 VDC Power Supply Notification Circuit Application Note 2 Digital Monitoring Products APPLICATION NOTE Conventional Large Burglary/Small Fire Command Processor Panel This application is appropriate for a large burglary system which requires only a small amount of fire notification, such as central station water flow. The complete system is a 12 VDC design with the fire notification appliances powered by the XR500 Series, XR2500F, XR100 Series, or XR200 Command Processor™ Panel. The addition of the DMP 866 Fire Notification Module provides the panel with the circuit supervision required for fire notification. A separate, auxiliary power supply can also be added to sound burglary alarm appliances. This power supply is switched by a second 866 module that is controlled by the panel Burglary Bell Output programming option. Bell Output Output 1 866 NAC Module 866 NAC Module Polarized Burglary Alarm Fire Notification Device 12 VDC Power Supply Installation Notes: 1. The Model 865 Style Y/Z Notification Circuit Module may be substituted for the Model 866 to provide Class A notification. 2. Bell Action programming for fire zones may be steady, pulse, or temporal to meet local requirements. 3. Zones 1, 2, and 3 must be programmed as a supervisory type with appropriate names. 4. Burglary Bell Output programming must activate output one. The Model 866 is needed to switch more than 1 Amp. 5. For UL burglary systems where the bell is tested daily at closing, circuit supervision is not required. 6. See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions. 7. See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or XR200 Programming Guide (LT-0196) for complete programming instructions. XR500 Series/XR2500F XR100 Series Command Processor™ Panel J a per J one e in J6 Interface Card Expansion Connector J P J odel XR200 tp t eader J tp t ra J J J C t J atter tart ra J C C E E tp t E C I ones se or e pora r ar one one ee notes and a e E 6 E ire otification pe per isor ee note x r Co on ar inp t C po r e ro contacts t e J 6 eset 6 ptiona E a e r ar pe per isor ee notes and tar Circ i E E E Co C or C o er pp ire otification orns ar inp t ro e contacts E e on C po r e inp t ro e contacts ptiona E a e o er pp eries pe per isor o er pp ee note C ps e ode 66 ee note otification Circ it od e ran 6 6 E ire J 6 t C t e ode 66 ee note otification Circ it od o ari ed r ar otification pp iance e 12 VDC @ 1.5 Amp Bell Output from the Panel for NAC 12 VDC @ 5 Amps Burglary Output from a DMP 505 Series 12 VDC Power Supply Digital Monitoring Products Notification Circuit Application Note 3 APPLICATION NOTE Distributed Power Notification Circuit When a large number of fire notification and burglary alarm appliances are required, the DMP LX-Bus™ provides extremely flexible and expandable system design capabilities. Either 12 or 24 VDC power supplies can be installed at any point on the panel LX‑Bus to provide burglary or fire, 12 or 24 VDC, zoned or simultaneous operation. Each of the five XR500 Series/XR2500F panel LX‑Bus expansion ports can supervise 100 devices including power supplies for a total of 500. Up to 100 devices including power supplies can be supervised on the XR100 Series LX-Bus for a total of 100. Each of the two XR200 LX-Bus expansion ports can supervise up to 100 devices including power supplies for a total of 200. Command Processor Panel 481 Expansion Card LX-Bus 867 NAC Module 867 NAC Module Polarized Burglary or Fire Alarm Bell Fire Notification Horns 12 VDC Power Supply 24 VDC Power Supply The 505-12LX Power Supply includes a power supply and two 867 Notification Circuit Modules, and can be addressed for independent supervision to indicate auxiliary power supply or notification circuit troubles. All power supplies can operate from a common output, from separate burglary or fire outputs, or individual assignment by a panel zone. Installation Notes: 1. The Model 867 LX-Bus Notification Module provides a secondary set of address switches so that supervisory trouble on the notification circuit or 12 or 24 VDC power supply can be indicated by the panel via the LX-Bus. 2. By selecting different bell addresses on the burglary 867 module and fire 867 module, the panel’s Burglary Bell Output and Fire Bell Output programming controls the modules independently. See the 867 Installation Guide (LT-0178). 3. Multiple 867 modules may be set to the same bell address so that all sound at the same time, or independent addresses so that notification may be zoned for burglary or fire. See the 867 Installation Guide (LT-0178). 4. To add a second LX-Bus to an XR500 Series/XR2500F panel, install a 481 Zone Expansion Card, 462N Network Interface Card, or 462P Printer Interface Card into the J6 Interface Card Expansion Connector. To add multiple LX-Buses to an XR500 Series/XR2500F panel, use a Model 461 Interface Adaptor Card and additional Interface Cards, such as a 481 Zone Expansion Card, 462N Network Interface Card, or 462P Printer Interface Card. To add a second LX-Bus to an XR200 use a Model 460 Interface Adaptor Card and a second Interface Card, such as a 481 Zone Expansion Card, 462N Network Interface Card, or 462P Printer Interface Card. Note: The XR100 Series panel only supports one on-board LX-Bus. 5. See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions. 6. See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or XR200 Programming Guide (LT-0196) for complete programming instructions. Notification Circuit Application Note 4 Digital Monitoring Products APPLICATION NOTE 4 Tamper 3 Phone Line 1 DMP Model 481 L -Bus E pansion Card (See note 4) XR500 Series/XR2500F XR100 Series Command Processor™ Panel se on P XR200 1 2 3 2 L 22 L B - us K6 P AC AC +B 1 2 3 B BELL 4 5 ND 6 ED EL 7 8 8 O N BLK SMK 10 11 ND 12 13 2 Out 1 Out 2 0 1 Battery Start 1 1 K7 ND 14 2 3 ND 15 16 17 18 6 1 eset 4 5 1 ND 6 20 21 22 7 ND 23 8 + 24 25 10+ 10 26 27 10K EOL + - + 12 VDC or 24 VDC Power Supply DMP 505 Series Power Supply 12 VDC @ 5 Amps Trouble contacts 10K EOL + - NAC power input Polarized Burglary Notification Appliances (See notes 2 and 3) DMP Model 867 (See note 1) Style W Notification Circuit Module To other 867 modules for burglary or fire notification 28 + - NAC power input + - + 12 VDC or 24 VDC Power Supply DMP 505 Series Power Supply 12 VDC @ 5 Amps Trouble contacts - DMP Model 867 (See note 1) Style W Notification Circuit Module Fire Notification Appliances (See notes 2 and 3) To other 867 modules for burglary or fire notification Multiple distributed 12 VDC @ 5 Amps Fire and Burglary Outputs from a DMP 505 Series 12 VDC Power Supply Digital Monitoring Products Notification Circuit Application Note 5 APPLICATION NOTE Separate Horn and Strobe Circuits Command Processor Panel Some applications require that during a system reset, fire horns be silenced first, followed later by strobes. This type of operation allows the strobes to remain active after the initial fire notification horn silencing. The strobes deactivate only after the cause of the alarm is investigated and the system is reset. Bell Output Polarized Burglary Alarm The XR500 Series, XR2500F, XR100 Series, and XR200 panels provide this operation by the addition of an 866 Notification Module which supplies power to the strobe circuit. This second module is activated by the panel Fire Alarm Output, which does not deactivate until a Sensor Reset Command is performed at any Fire Command™ or other DMP keypad. Output 1 Output 2 866 NAC Module 866 NAC Module Fire Notification Horns Fire Notification Strobes Power Supply Power Supply This diagram illustrates how to accomplish separate horn/strobe deactivation. In addition, an optional combination local burglary alarm is included. Installation Notes: 1. The Model 865 Style Y/Z Notification Circuit Module can be substituted for the Model 866 to provide Class A notification. 2. Bell Action programming must activate steady for burglary zones. 3. Zones 1 and 2 must be programmed as supervisory type zones with appropriate names. 4. Fire Bell Output programming must activate output one. If no burglary alarm is needed, the panel Bell Output can activate the fire horn. 5. For UL burglary systems where the bell is tested daily at closing, supervision of the circuit is not required. 6. Fire Alarm Output programming must activate output two. 7. See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions. 8. See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or XR200 Programming Guide (LT-0196) for complete programming instructions. XR500 Series/XR2500F XR100 Series Command Processor™ Panel J a per J one e in J6 Interface Card Expansion Connector t e ode 66 ee note otification Circ it od J P J x odel XR200 tp t J Co eader J tp t J ran e t J 6 ra J ran e ee C C E E E ire 6 C I ones none ar ones stead ee notes E a e e C r ire otification orns on C po r e inp t E E ar inp t C o tp t ote ro e contacts I E ote 6 6 6 r I E J 6 eset t C ite ee J J atter tart ran e ran e tp t C e pe tp t ps E a e ire otification pe per isor ee note E o er pp s per isor ee note 6 E E Co ro e Contacts o ari ed r ar otification pp iance C on ar pp inp t C po r e inp t C or C o er pp o er ire otification tro se x r E C o tp t eries ro e contacts ps t e are ode 66 ee note otification Circ it od nc od e re ired if sstro e ocated in sa e roo e 12 VDC @ 1.5 Amp Burglary Output from the Panel 12 VDC @ 5 Amps Fire Output from a DMP 505 Series 12 VDC Power Supply Notification Circuit Application Note 6 Digital Monitoring Products APPLICATION NOTE Model 867 Style W LX-Bus™ Notification Module The Model 867 provides one supervised Style W notification circuit for system expansion and connects at any point on the panel LX-Bus. Two sets of rotary switches provide a unique addressing scheme which enables the module to respond to one address for supervision, yet operate the notification circuit on a second address. Having separate supervisory and notification addresses allows multiple modules to be activated in groups, while monitored by the XR500 Series, XR2500F, XR100 Series, or XR200 panel individual supervisory zone programming. A ring style jumper allows any one of four notification cadences to be selected: Steady, Pulse, Temporal, or California School Code. The 867 is also capable of switching 12 or 24 VDC up to 5 Amps from an auxiliary power supply. Mount the 867 Module in the power supply enclosure for supervised operation. 10K EOL Normal/Silence Switch NAC Power Supply: Up to 5 Amps @ 12 VDC or 24 VDC Ground Fault LED Bell Trouble LED 1 2 867 Module Trouble Contacts 12 or 24 VDC 3 4 5 6 7 TENS 867 Style W LX-Bus Notification Module Steady Pulse Termporal California Schools 8 ONES Bell Relay Address TENS ONES Supervisory Address To optional auxiliary trouble indicator To additional LX-Bus Modules From Panel LX-Bus™ Wiring Model 866 Style W Notification Module The 866 module is suitable for use with 2-wire circuits and can switch up to 5 Amps at 12 or 24 VDC. Trouble contacts are included to indicate notification circuit trouble. The 866 module can be used in parallel or zoned applications. DMP Model 866 Normal NAC Power Supply: Up to 5 Amps @ 12 VDC or 24 VDC 10K EOL Bell Silence AUX PWR 1 GND 2 12 or 24 VDC Alarm In 3 Bell PWR In 4 Bell Out + 5 866 Style W Notification Module Bell Out – 6 Bell Trouble 7 Bell Trouble 8 Digital Monitoring Products Notification Circuit Application Note 7 Model 865 Style Y or Z Notification Module The 865 Module is suitable for use with 2-wire or 4-wire circuits and provides a trouble LED, ground fault LED, and a set of trouble contacts to indicate off normal conditions. The module can be used in parallel, activated by a single output, or activated independently by using zoned outputs from the panel. The 865 can switch up to 5 Amps at 12 or 24 VDC. Normal/Silence Switch NAC Power Supply: Up to 5 Amps @ 12 VDC or 24 VDC 865 Module AUX PWR 1 GND 2 Alarm In 3 Bell PWR In + 4 Bell PWR In – 5 Bell Out A + 6 Bell Out A – 7 Bell Trouble Out + 8 Bell Trouble Out – 9 N/C Trbl Contacts 10 N/C Trbl Contacts 11 865 Style Y or Z Notification Module Style Z + + + - - - 10K EOL Style Y Only Style Y For Style Y circuit, remove wires from terminals 8 and 9 and install the 10K EOL as shown. Product Compliance Certifications The products discussed in this Application Note are certified by the agencies listed in the table below. For complete compliance information see the specific listing cards from each agency and the following guides: XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899), XR200 Installation Guide (LT-0197), XR500 Series/XR2500F Programming Guide (LT‑0679), XR100 Series Programming Guide (LT-0896), or XR200 Programming Guide (LT‑0196). This information is also available at www.dmp.com. Model Description UL CSFM MEA 574-Zone Command Processor™ Panel S3598 7165-1157:123 168-93-E VOL. VI 574-Zone Fire Command Processor™ Panel S3598 7165-1157:124 168-93-E VOL. VI XR100 Series 142-Zone Command Processor™ Panel S3598 7165-1157:123 Future XR200 242-Zone Command Processor™ Panel S3598 7165-1157:105 168-93-E VOL. III 865 Style Y or Z Notification Circuit Module S3598 7165-1157:105 168-93-E VOL. III 866 Style W Notification Circuit Module S3598 7165-1157:105 168-93-E VOL. III 867 Style W LX-Bus™ Notification Circuit Module S3598 7165-1157:105 168-93-E VOL. III 461 XR500 Series/XR2500F Interface Adaptor Card S3598 7165-1157:123 168-93-E VOL. VI 460 XR500 Series XR2500F XR200 Interface Adaptor Card S3598 7165-1157:105 168-93-E VOL. III 462N Network Interface Card S3598 7165-1157:105 168-93-E VOL. III 462P Printer Interface Card S3598 7165-1157:105 168-93-E VOL. III 481 LX-Bus™ Expansion Card S3598 7165-1157:105 168-93-E VOL. III 505-12 12 VDC Power Supply S7400 7315-1157:114 168-93-E VOL. VI Power Supplies 505-12L 12 VDC Power Supply S7400 7315-1157:114 168-93-E VOL. VI 505-12LX 12 VDC Power Supply w/2 built-in NACs S7400 7315-1157:114 168-93-E VOL. VI 505-12A 12 VDC Power Supply S7400 7315-1157:114 168-93-E VOL. VI 800 - 641 - 4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.com 2500 North Partnership Boulevard Designed, Engineered and Assembled in U.S.A. S p r i n g fi e l d , M i s s o u r i 6 5 8 0 3 - 8 8 7 7 LT-2012 (12\06) © 2013 Digital Monitoring Products, Inc. Command Processor™ Panel Equipment