Transcript
AQUA Link
TM
Advanced hydronic module
The cover image is based on AQUA Link LN version.
General
Quick facts
AQUA Link is a pioneering hydronic module designed to optimise connection between the chiller and the users in plants featuring both an air handling unit (for air ventilation and humidity control) and chilled beams (for ambient temperature control).
►► One single interlocutor for the entire plant eliminates possible inconveniences relating to identification of responsibilities and difficult communications with the various parties involved;
AQUA Link always produces and distributes the exact right amount of water at the exact required temperature to both cooling coils and for example chilled beams. AQUA Link contains all you need in a water circuit between a Swegon chiller and GOLD air handling unit. The former time-consuming and expensive process is now replaced with Plug and Play!
►► The system only requires hydronic and electrical connection between the chiller, the users and the AQUA Link to operate. ►► All equipment and components are condensed in one unique volume and AQUA Link can be placed outdoor. ►► Energy efficient through demand controlled operation and energy efficient pumps.
AQUA Link
Contents Features and operating principle Technical characteristics Technical data Operating limits Energy analysis Overall dimensions, weights and hydronic connections Single-line hydronic diagram Installation tips Summary of unique selling points
2
3 4 6 7 10 18 26 28 29
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link
Features and operating principle The hydronic module AQUA Link is designed to optimise connection between the chiller and the users in plants featuring both an air handling unit (for air ventilation and humidity control) and chilled beams for ambient temperature control (or other elements like fan coils for example). The control algorithm gives high benefits in terms of energy consumption, which is minimised through the control of several parameters at a time. These parameters are: temperature setpoint of chilled water produced by the chiller, pump rotation (both in primary and secondary circuits, if any), opening of the water flow control valves. Some additional benefits are granted at installation: the module, in fact, already features all the required elements, which consequently do not need to be provided for separately and are governed by one single controller. Temperature setpoint modulation The temperature at which chilled water is produced to the chiller (mix of water and glycol for glycol version and pure water for “No Glycol” version), that is directly connected to the refrigerant evaporation temperature, is essential for the determination of the energy efficiency coefficient of the chiller (EER or ESEER when considered in seasonal terms). In traditional plants where one chiller feeds both the air handling units and the chilled beams, the cold fluid is supplied at one temperature only (typically 7°C) and is blended with the fluid returning from the chilled beams so that the correct water supply temperature is guaranteed. Actually, the production of fluid at such low temperature is not always required. Consider, for instance, that the correct water supply temperature to the chilled beams is normally around 14°C: forced dehumidification is not always necessary in air handling units, especially in climate conditions such as those in Northern European countries, and free cooling may be adopted frequently.
increase in the chiller energy efficiency. The variable chiller setpoint and continuous transfer of operating parameter data between the controllers on the users’ side and the chiller keep the fluid production temperature as high as possible and, in any case, such as to fully meet the users’ requirements. This operating logic offers a substantial benefit in terms of energy consumption minimisation thanks to enhanced chiller operating efficiency. Water flow rate modulation The amount of energy used to pump the fluid is linked to the flow rate required by the users. A decrease in the amount of pumped water causes a proportional reduction of the energy spent for this purpose. The water flow rate required to the users basically depends on the water load to be supplied. This is substantially variable according to, for instance, the number of chilled beams to be fed against the total number of chilled beams installed, which need to be served in full load conditions. The water flow rate is modulated, and energy consumption for pumping is consequently reduced, thanks to inverters and variable pumps which are operated by a pressure signal detected by a probe fitted in the hydronic piping. 2-way valve opening modulation The primary circuit features two 2-way valves that control the destined flow to the AHU and to the plate heat exchanger (or mix manifold for “No Glycol” version) respectively. This arrangement allows for the use of one single pump in the primary circuit, which leads to a reduction in both installation and plant management costs. The valves are modulated according to the actual requirements of each user. The modulation speed of these valves is such as to provide a quick and accurate response to the users’ requirements.
This enables feeding the users with water at a temperature that is often above 7°C, which consequently leads to a direct
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
3
AQUA Link
AQUA Link An evolved hydraulic module designed to optimise the energy specifications of chilled water production and distribution systems requiring the simultaneous presence of a primary air treatment unit and internal end elements for the treatment of secondary air. The module is available in two main configurations suitable for operation: --with a percentage of Glycol between 20% and 40% in the primary circuit --without Glycol in the primary circuit (AQUA Link NG; the secondary circuit never contains Glycol) The range of power available to the various utilities (UTA and Chilled Beams) varies based on the version that is being examined, as the two configurations (with and without Glycol) are suitable for operation in different climatic conditions where the powers intended for fresh air and secondary air treatment differ greatly. For further information on this topic please refer to the data provided in the attached tables.
STRUCTURE
Indoor version structure The load bearing frame is built with polished, pickled sheet steel with textured epoxy-polyester powder coating (Colour RAL 7035). Stainless steel screws Outdoor version structure The load-bearing frame is built with galvanised sheet metal, painted with textured polyester powders RAL 7035 at 180°C, which confer high resistance to atmospheric agents. Stainless steel screws. Panelling Built from sheet metal coated with textured RAL 7035. The removable doors are fitted with handles to make them easier to take out.
HYDRONIC CIRCUIT Common standard parts include: primary circuit pump, 2-way regulation valve on the primary circuit to regulate the temperature to the secondary circuit, gate valves, expansion vessel, relief valve. The version with Glycol also includes: inertial tank, plate exchanger The NO Glycol version also includes: mixing manifold
HEAT EXCHANGER
(only for the version with Glycol) AISI 316 stainless-steel braze-welded plate evaporator, housed inside a closed-cell insulating casing. The exchanger can be single or double. Double exchangers are already supplied complete with manifold to guarantee a single hydraulic fitting.
MIXING MANIFOLD
(only for the NO Glycol version) It has an adequate diameter to ensure the water flows are mixed correctly and is supplied with a relief valve and drainage valve to promote drainage.
PRIMARY CIRCUIT ELECTRIC CIRCULATION PUMP
(Gold supply + plate exchanger or mixing manifold) One-piece impeller pump with direct motor-pump coupling using a single shaft in chrome-plated steel. Cast iron body and impeller, mechanical seal, two-pole three-phase electric motor with electric protection IP 54. Variable-operatinon pump controlled by external inverter. It is possible to choose the single or double-circulation pump version managed with rotation logic and assistance in case of failure. The pumping unit in the version with Glycol is suitable for operation with elevated glycol percentages, between (20% and 40%).
SECONDARY CIRCUIT ELECTRIC CIRCULATION PUMP (Chilled Beams supply, optional)
One-piece impeller pump with direct motor-pump coupling using a single shaft in chrome-plated steel. Cast iron body and impeller, mechanical seal, two-pole three-phase electric motor with electric protection IP 54. Variable-operating pump controlled by external inverter. It is possible to choose the single or double-circulation pump version managed with rotation logic and assistance in case of failure.
CIRCULATION PUMP ROTATION SPEED REGULATION INVERTER Each pump (or pair of pumps) is governed by a dedicated inverter controlled by customised regulating logic. The inverters are contained inside the electric control panel which is accordingly cooled by installed fans and shutters for air circulation.
TWO-WAY MODULATED VALVE INSTALLED ON THE PRIMARY CIRCUIT TO REGULATE THE TEMPERATURE OF THE SECONDARY CIRCUIT Motorised automatic regulation valve to control the flow of water to the plate exchanger or to the mixing manifold. The valve is regulated by a temperature signal sent by a probe on the water flow pipe downstream of the plate exchanger. The temperature probe is installed on the secondary branch when the unit is configured with circulation pumps on the secondary branch. Alternatively, the probe is supplied and must be installed according to the instructions provided in the user and maintenance manual.
ELECTRIC CONTROL BOARD The board includes: • main isolating switch • thermal magnetic circuit breakers for the pumps
4
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link • pump relays • three-phase inverter rpm regulator for each hydraulic circuit • protective thermal magnetic circuit breakers for the inverter/s • IQnomic module to manage I/O signals from the utilities • cut-off transformer • cooling fan Electrical power supply 400V/3~/50Hz.
CHECKS AND SAFETY DEVICES • temperature probe in the flow water to the Chilled Beams circuit • pressure probe to control the rate of pump operation on the primary circuit (if there are pumps on the circuit a pressure probe will also be installed on the secondary circuit). • motorised two-way infeed valve to the heat exchanger or the mixing manifold. • the standard version for outdoor installation is equipped with frost-protection heating elements for the plate exchanger, when included (version with Glycol), and for the main parts when the temperatures make it necessary.
INSPECTION The units are inspected in factory to check the hydraulic seal and correct electrical cabling of the parts.
VERSIONS and ACCESSORIES Single circulation pump for primary circuit (standardAQUA Link 1P) The design includes only one circulation pump on the primary circuit. The same pump supplies the thermal exchange coil inside the air treatment unit, as well as the plate exchanger or the mixing manifold on the Chilled Beams circuit. The circulation pump is controlled by an inverter that regulates the speed of rotation based on the real request from the utilities. There are two types of useful pump head: “standard head” and “increased head”. Double circulation pump on the primary circuit (optional – AQUA Link 2P) The design includes 2 circulation pumps on the primary circuit. The operating logic controls timed operation of the 2 pumps and the automatic intervention of the operating pump if one of the two breaks down. It is possible to choose between two types of useful pump head: “standard head” and “increased head”. Circulation pumps to the secondary circuit on the Chilled Beams circuit (optional – AQUA Link 1P-1P/2P-2P) The standard unit does not require the use of circulation pumps to supply the Chilled Beams. It is possible to select either a single or double circulation pump accessory for the secondary circuit. It is possible to choose between two types of useful pump head: “standard head” and “increased head”.
only, are therefore: 1 pump to the primary
(AQUA Link 1P)
1 pump to the primary and one pump to the secondary (AQUA Link 1P-1P) 2 Pumps to the primary
(AQUA Link 2P)
2 pumps to the primary and 2 pumps to the secondary ( AQUA Link 2P-2P)
Version for indoor installation (standard – AQUA Link IN) This version does not have closing panels along its perimeter or a cover on top (supplied separately as an option). Any electrical resistance is provided to protect the components, regardless of the percentage of glycol. Version with Glycol for outdoor installation (optional – AQUA Link OD) This version is designed with closing panels around the entire perimeter and cover on top. The structural work is built with galvanised sheet steel painted with textured polyester powders in RAL 7035. The electrical control panel is designed to provide protection IP 55. Plate exchanger and circulation pumps (if included) on the Chilled Beams circuit will always be protected from low temperatures by a heating cable. The installer must be careful to protect sections of pipes that send supply water for the secondary circuit to the AQUA link unit inside the building from frost. For glycol percentages up to 30%, at a minimum outdoor temperature of -10°C, no other additional form of protection is required. With glycol percentages between 30% and 40% heating cables are added to protect the pumps, the servo-control for the 2-way valve and the electric control panel. No Glycol version NG (optional- AQUA Link NG) The No Glycol version requires both primary and secondary pumps to operate on pure water, without the addition of ethylene Glycol. This version is therefore suitable for operation in mild climatic conditions where the temperatures never subject the system to the risk of frost (for example: completely indoor installation). The last two digits of the machine’s alphanumeric identification code indicate the percentage of Glycol required for the primary circuit. In the No Glycol version, these two digits are replaced by the acronym “NG”. If this version is used for outdoor installation, a series of heating cables will need to be set up accordingly to protect: pump volutes, mixing manifolds, pipes inside the machine. WARNING: it is the installer’s responsibility to protect the sections of machine infeed and outfeed pipes that lead to the chilled beam circuit and chiller, including the inertial tank.
The double pump to the secondary circuit can only be selected if there is a double pump to the primary circuit. The possible versions, with reference to the number of pumps Swegon reserves the right to alter specifications. 20120904
www.swegon.com
5
AQUA Link
Technical data AQUALink with glycol
AQUA Link size 110
STANDARD PRIMARY PUMP*
OVERSIZED PRIMARY PUMP*
STANDARD SECONDARY PUMP*
OVERSIZED SECONDARY PUMP*
DIMENSIONS AND WEIGHT
WATER GLYCOL MIXTURE TANK VOLUME
(1) (2)
140
220
300
Chiller reference capacity
[kW]
da 90 a 110
da 111 a 143 da 144 a 224 da 225 a 293
Nominal absorbed power
[kW]
2,2
2,2
4
5,5
Maximum absorbed power permitted (4)
[kW]
2,21
2,37
4,06
5,52
Nominal absorbed current
[A]
4,7
4,7
7,9
10,6
Nominal absorbed power
[kW]
3
3
5,5
7,5
Maximum absorbed power permitted (4)
[kW]
3,2
3,02
5,52
7,57
Nominal absorbed current
[A]
6,2
6,2
10,6
14,7
Nominal absorbed power
[kW]
2,2
2,2
4
5,5
Maximum absorbed power permitted (4)
[kW]
2,37
2,37
4,06
5,52
Nominal absorbed current
[A]
4,7
4,7
7,9
10,6
Nominal absorbed power
[kW]
3
4
5,5
7,5
Maximum absorbed power permitted (4)
[kW]
3,02
4,06
5,52
7,57
Nominal absorbed current
[A]
6,2
7,9
10,6
14,7
Length
[mm]
3304
3304
3304
3304
Height
[mm]
1773
1773
1773
1773
Depth
[mm]
872
872
872
872
Weight
[kg]
512
522
572
602
[l]
500
500
500
500
(3)
* The values in the table are valid for primary loop glycol percentages from 20% to 40% * The values in the table are valid for every allowed pwer distribution between AHU and Chilled Beams (20%-80%; 30%-70%; 40%-60%) (1) (2) The weight values are valid for standard version AQUA Link IN 1P (3) The chiller combined to AQUA Link has to be selected wit pump (s) + storage tank accessory (4) The nominal absorbed power overcoming, within the indicated range, is allowed by the pump manifacturer and it has not to be considered as an overcoming of the limit values.
Technical data AQUALink no glycol
AQUA Link size 110
STANDARD PRIMARY PUMP*
DIMENSIONS AND WEIGHT
VOLUME PLANT
[kW]
da 90 a 110
[kW]
1,5
1,5
2,2
3
1,52
1,59
2,37
3,01
3,2
3,2
4,7
6,2
Nominal absorbed current
[A]
Nominal absorbed power
[kW]
(3)
2,2
2,2
3
4
2,21
2,37
3,01
4,06
[A]
4,7
4,7
6,2
7,9
Nominal absorbed power
[kW]
0,75
1,1
1,5
1,5
0,815
1,1
1,58
1,59
Nominal absorbed current
[A]
1,7
2,4
3,2
3,2
Nominal absorbed power
[kW]
1,5
1,5
1,85
2,2
Maximum absorbed power permitted (4)
(1) (2)
da 111 a 143 da 144 a 224 da 225 a 293
Nominal absorbed current Maximum absorbed power permitted (4)
OVERSIZED SECONDARY PUMP FOR AHU-CB POWER DISTRIBUTION: 50%-50%
300
Nominal absorbed power
Maximum absorbed power permitted (4)
STANDARD SECONDARY PUMP FOR AHU-CB POWER DISTRIBUTION: 20%-80%; 30%-70%; 40%-60%
220
Chiller reference capacity Maximum absorbed power permitted (4)
OVERSIZED PRIMARY PUMP*
140
1,5
1,5
2,07
2,37
Nominal absorbed current
[A]
3,2
3,2
4,65
4,7
Length
[mm]
1986
1986
1986
1986
Height
[mm]
1773
1773
1773
1773
Depth
[mm]
872
872
872
872
Weight
[kg]
281
287
297
310
[l]
(3)
(3)
(3)
(3)
* The values in the table are valid for every allowed pwer distribution between AHU and Chilled Beams (80%-20%; 70%-30%; 60%-40%) (1) (2) The weight values are valid for standard version AQUA Link IN 1P NG (3) The minimum water volume content of the combined pant has to be identified in the manual of the combined chiller and depends on the tipe and on the size of the chiller. This volume has to be available in the primary circuit (in the calculation the water volume in the secondary -Chilled Beams- circuit has not to be considered) (4) The nominal absorbed power overcoming, within the indicated range, is allowed by the pump manifacturer and it has not to be considered as an overcoming of the limit values.
6
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link
OPERATING LIMITS UNITS WITH GLYCOL INDOOR VERSION Units containing Glycol in the primary circuit and made for indoor installation are built to operate at outdoor temperatures between +3°C and +45°C. They therefore do not provide the installation of heating cables to protect the internal components. For operation at temperatures outside of the aforementioned range, it is necessary to contact our Technical Office. OUTDOOR VERSION Units containing Glycol in the primary circuit and made for outdoor installation are built to operate within the following limits, whose values depend on the percentage of glycol in the primary circuit. • With a 20% concentration of ethylene glycol, the minimum admissible temperature is -5°C • With a 30% concentration of ethylene glycol, the minimum admissible temperature is -10°C • With a 40% concentration of ethylene glycol, the minimum admissible temperature is -20°C The overall maximum admissible temperature is 45°C The plate exchanger is always protected by a protective heating cable on the secondary circuit that contains water. If there are pumps installed on the secondary circuit, the volutes are always protected by a heating cable as well as preinstalled pipes. The installer must protect any connecting pipe sections between the indoor system and AQUA Link For temperatures below -15°C (i.e. for glycol percentages between 30% and 40%) a series of heating elements designed to protect the main parts (pump motors, valve bodies...) and the electrical control board must be set up For operation at temperatures outside of the aforementioned range, it is necessary to contact our Technical Office.
UNITS WITHOUT GLYCOL Units without Glycol in the primary circuit are designed and built to operate at outdoor air temperatures between +3°C and +45°C. For operation at temperatures outside of the aforementioned range, it is necessary to contact our Technical Office. For outdoor installation it will nevertheless be necessary to set up a series of heating elements against accidental low temperatures to protect: pump volutes, mixing manifolds, pipes inside the machine. WARNING: it is the installer’s responsibility to protect the sections of machine infeed and outfeed pipes that lead to the chilled beam circuit and chiller, including the inertial tank.
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
7
AQUA Link
Capacities data AQUALink with glycol
AQUA Link size
Maximum cooling capacity of combined chiller 100% capacity (12/7°C) - 40% ethylen glycol STANDARD PRIMARY PUMP
100% capacity (12/7°C) - 30% ethylen glycol 100% capacity (12/7°C) - 20% ethylen glycol
OVERSIZED PRIMARY PUMP
300
[kW]
110,7
143,5
224,5
293,1
Maximum head pressure
(1) (2)
[kPa]
118,9
98,3
96,6
117,8
Power consumption at the maximum available pressure
(3)
[kW]
1,7
1,78
3,47
4,39
Maximum head pressure
(1) (2)
[kPa]
132,7
106,8
119,7
131,8
Power consumption at the maximum available pressure
(3)
[kW]
1,65
1,72
3,38
4,22
Maximum head pressure
(1) (2)
[kPa]
144,1
113,8
128,2
143,1
Power consumption at the maximum available pressure
(3)
[kW]
1,59
1,65
3,28
4,07
(1) (2)
[kPa]
186,6
154,9
175,2
168,9
Power consumption at the maximum available pressure
(3)
[kW]
2,41
2,59
4,02
5,98
100% capacity (12/7°C) - 30% ethylen glycol
Maximum head pressure
(1) (2)
[kPa]
201,3
163,5
182,4
185,6
Power consumption at the maximum available pressure
(3)
[kW]
2,33
2,49
3,86
5,76
100% capacity (12/7°C) - 20% ethylen glycol
Maximum head pressure
(1) (2)
[kPa]
213,7
170,6
188,2
199,1
Power consumption at the maximum available pressure
(3)
[kW]
2,24
2,4
3,7
5,55
70% capacity (14/17°C) - Water
60% capacity (14/17°C) - Water 70% capacity (14/17°C) - Water 80% capacity (14/17°C) - Water
INTERMEDIATE HEAT EXCHANGER WATER PRESSURE DROP
220
Maximum head pressure
80% capacity (14/17°C) - Water
OVERSIZED SECONDARY PUMP
140
100% capacity (12/7°C) - 40% ethylen glycol
60% capacity (14/17°C) - Water STANDARD SECONDARY PUMP
110
Maximum head pressure
(1) (4)
[kPa]
185,3
161,1
161,4
200,5
Power consumption at the maximum available pressure
(5)
[kW]
1,98
2,14
3,37
5,07
Maximum head pressure
(1) (4)
[kPa]
163,7
131,3
132,2
151,8
Power consumption at the maximum available pressure
(5)
[kW]
2,08
2,23
3,57
5,3
Maximum head pressure
(1) (4)
[kPa]
139,1
97,1
96,1
93,4
Power consumption at the maximum available pressure
(5)
[kW]
2,16
2,3
3,74
5,44
Maximum head pressure
(1) (4)
[kPa]
251,4
293,9
231,2
283,4
Power consumption at the maximum available pressure
(5)
[kW]
2,47
3,44
4,59
6,5
Maximum head pressure
(1) (4)
[kPa]
228,9
261,9
196,7
237,3
Power consumption at the maximum available pressure
(5)
[kW]
2,61
3,64
4,88
6,87
Maximum head pressure
(1) (4)
[kPa]
202,8
224,6
155,8
181,5
Power consumption at the maximum available pressure
(5)
[kW]
2,73
3,79
5,11
7,17
24,3
23,7
36,9
24,6
32,6
31,9
49,9
33,2
42,1
41,2
64,7
42,9
60% capacity (14/17°C) 70% capacity (14/17°C)
Pressure drop on Chilled Beams side exchanger
[kPa]
(1) Maximum allowable frequency: 50 Hz (2) Available pressure that can be obtained if the pump should transfer to the users the maximum permissible power for that size with water temperature in / out from the chiller 12 / 7 ° C (3) Power absorbed by the pump if it should transfer to the users the maximum permissible power for that size with water temperature in / out from the chiller 12 / 7 ° C and the maximum static pressure under the same conditions (4) Static pressure that can be obtained if the pump should transfer to the Chilled Beams the indicated percent capacity with water temperature in / out 14/17 ° C from Chilled Beams (5) Power absorbed by the pump if it should transfer to the Chilled Beams the indicated percent capacity with water temperature in / out 14/17 ° C from Chilled Beams and the maximum static pressure under the same conditions
8
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link
Capacities data AQUALink no glycol
AQUA Link size
Maximum cooling capacity of combined chiller STANDARD PRIMARY PUMP
100% capacity (12/7°C)
OVERSIZED PRIMARY PUMP
100% capacity (12/7°C) 20% capacity (14/17°C) - CB
STANDARD SECONDARY PUMP
30% capacity (14/17°C) - CB 40% capacity (14/17°C) - CB 20% capacity (14/17°C) - CB
OVERSIZED SECONDARY PUMP
30% capacity (14/17°C) - CB 40% capacity (14/17°C) - CB
110
140
220
300
[kW]
110,7
143,5
224,5
293,1
Maximum head pressure
(1) (2)
[kPa]
156
122
123
115
Power consumption at the maximum available pressure
(3)
[kW]
1,47
1,48
2,35
2,9
Maximum head pressure
(1) (2)
[kPa]
239
184
174
164
Power consumption at the maximum available pressure
(3)
[kW]
2,06
2,14
3,01
3,71
Maximum head pressure
(1) (4)
[kPa]
149,0
172,0
169,0
152,0
Power consumption at the maximum available pressure
(5)
[kW]
0,53
0,77
1,08
1,27
Maximum head pressure
(1) (4)
[kPa]
134
149
140
121
Power consumption at the maximum available pressure
(5)
[kW]
0,63
0,94
1,34
1,49
Maximum head pressure
(1) (4)
[kPa]
110
114
97
78
Power consumption at the maximum available pressure
(5)
[kW]
0,72
1,06
1,51
1,57
Maximum head pressure
(1) (4)
[kPa]
231,0
223,0
207,0
212,0
Power consumption at the maximum available pressure
(5)
[kW]
0,85
0,98
1,34
1,91
Maximum head pressure
(1) (4)
[kPa]
216
198
179
183
Power consumption at the maximum available pressure
(5)
[kW]
1,06
1,21
1,62
2,15
Maximum head pressure
(1) (4)
[kPa]
195
161
139
143
Power consumption at the maximum available pressure
(5)
[kW]
1,23
1,39
1,87
2,31
(1) Maximum allowable frequency: 50 Hz (2) Available pressure that can be obtained if the pump should transfer to the users the maximum permissible power for that size with water temperature in / out from the chiller 12 / 7 ° C (3) Power absorbed by the pump if it should transfer to the users the maximum permissible power for that size with water temperature in / out from the chiller 12 / 7 ° C and the maximum static pressure under the same conditions (4) Static pressure that can be obtained if the pump should transfer to the Chilled Beams the indicated percent capacity with water temperature in / out 14/17 ° C from Chilled Beams (5) Power absorbed by the pump if it should transfer to the Chilled Beams the indicated percent capacity with water temperature in / out 14/17 ° C from Chilled Beams and the maximum static pressure under the same conditions
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
9
AQUA Link
ENERGY ANALYSIS Introducing AQUA link combined with chiller set point variable and the SMART Link of advanced management of set point allows to obtain significant benefits in terms of reduced fuel consumption. As evidence of this below shows the results
of simulations made for both energy systems with glycol for Northern European climates for both systems without glycol for southern European climates.
NO GLYCOL SYSTEM, LOCATION IN NORD EUROPE (STOCKHOLM) 1. TRADITIONAL SYSTEM: (see diagram below) GOLD air handling unit
Extract air
Outdoor air
Supply air
Regulating 2-way valve
On/off 2-way valve
Air cooler
Exhaust air
On/off 2-way valve
Bypass valve
i Heat exchanger
i = Inverters
i
Regulating 2-way valve
i
Climate beams
Collector 40% water/glycol primary circuit
Chiller Integrator inertial tank
Inertial tank
This system consists of the following components: 1. A fixed setpoint chiller with a known total power. The chiller is supplied with a water-glycol blend circulation pump and a small capacity inertial tank complete with an expansion vessel. In addition, the chiller features multiple compressors giving the possibility to reduce the supplied power according to the required power, still producing water at the same temperature; 2. An inertial tank complete with an expansion vessel to achieve the min. volume required in the plant proportionally to the chiller capacity and number of steps; 3. A manifold used to mismatch the users’ feeding circuits;
6. An inspectable plate heat exchanger to mismatch the section working with a blend of water and glycol from the section fed with pure water; 7. A variable feed pump to the chilled beams; 8. A complete air handling unit with a rotary heat exchanger (enthalpy rotor) and a air cooler complete with a 2-way modulating control valve; 9. A chilled beam system equipped with a 2-way valve to shut off the water supply; 10. Taps, valves and hydronic piping to connect the various components.
4. A variable pump feeding the air handling unit coil; 5. A variable feed pump on the glycol side of the plate heat exchanger;
10
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link 2. AQUA Link SYSTEM: (see diagram below)
GOLD air handling unit
Exhaust air Air cooler
Supply air
On/off 2-way valve
Outdoor air
Regulating 2-way valve
AQUA Link
i
Inertial tank
Bypass valve
Heat exchanger
Regulating 2-way valve
Chiller
On/off 2-way valve
Extract air
Climate beams
40% water/glycol primary circuit
Integrator inertial tank
This system consists of the following components: 1. A variable setpoint chiller with a known total power. The chiller is supplied with a circulation pump for water-glycol blending and a small capacity inertial tank. In addition, the chiller features multiple compressors giving the possibility to reduce the supplied power according to the required power. The temperature of the output chilled water is connected to the user’s requirements and may vary continuously between two setpoints. 2. The AQUA Link module, which comprises: --An additional inertial tank complete with an expansion vessel to achieve the min. volume required in the plant proportionally to the chiller capacity and number of capacity steps; --A variable circulation pump feeding the primary circuit; --Pressure probes for pump rotation speed control;
i = Inverters
i
--A plate heat exchanger to mismatch the section working with a blend of water and glycol from the section fed with pure water; --A 2-way motor-driven modulating valve designed to control the flow rate to the users; --Taps, valves and hydronic piping to connect the various components; 3. A complete air handling unit with a rotary heat exchanger (enthalpy rotor) and an air cooler complete with a 2-way modulating control valve; 4. A variable feed pump to the chilled beams; 5. Pressure probes to control rotation speed of the pump; 6. A chilled beam system equipped with a 2-way valve to shut off the water supply.
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
11
AQUA Link The simulation was made keeping the same operating conditions in both systems. Below is a list of operating conditions
that are fundamental to identify the test context.
Location of installation
Stockholm
Max. total required power
200 kW
Power distribution to 2 users: Air handling unit
60 kW (30%)
Chilled Beams
140 kW (70%)
Temperature below which the chilled beams do not require feeding with chilled water
0°C
Temperature below which the air handling unit can operate in free cooling conditions
16°C
Air delivery temperature to chilled beams
16°C
Outdoor temperature
from weather file covering 8760 hours
Outdoor enthalpy
from weather file covering 8760 hours
Outdoor air volume treated by the AHU
3,6 m3/s (13 000 m3/h)
No. of chilled beams
241
An iterative method was used to calculate the following values for each hour of operation of the chiller serving the plant: • The hourly COP values; • The power absorbed on an hourly basis and the absorbed energy, as a consequence. The analysis has enabled identification of: • The energy consumed by the variable setpoint system (supposing that the water temperature delivered by the chiller varies according to the chill request);
• The energy consumed by the same system, but with a fixed setpoint, producing water at a constant temperature of 7°C for the GOLD air handling unit and chilled beams regardless of fluctuations in the required power. The trends of the COP value measured every hour throughout the annual 8760 hours is illustrated below.
EER 8,00
Fixed set point Variable set point
7,00 6,00
EER
5,00 4,00 3,00 2,00 1,00 0,00 0
5
10
15
20
25
30
35
40
Temperature °C
12
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link The analysis was conducted considering real chiller operating conditions and the actual energy consumption of the axial fans
serving the condensing section.
Absorbed energy
70,00
Fixed set point Variable set point
Absorbed energy (hourly) kW
60,00
50,00
40,00
30,00
20,00
10,00
0,00 0
5
10
15
20
25
30
35
40
Temperature °C
Reduction coefficient fans
Fixed set point chiller
Variable set point chiller
Absorbed energy (annual)
[kWh]
81,913
71,027
Consumption reduction
[kWh]
0
10.886
Consumption reduction
%
0,0%
13,3%
[€/kWh]
0,07
0,07
[€]
0
805,5
Electricity rata Economic Saving
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
13
AQUA Link NO GLYCOL SYSTEM, LOCATION IN CENTRAL ITALY (ROME) 1. TRADITIONAL SYSTEM: (see diagram below)
GOLD air handling unit
Exit air Cold Coil exchanger
Exhaust air
Primary air On/off 2-way valve
Outdoor air
On/off 2-way valve
Regulating 2-way valve
i i = Inverters Regulating 3-way valve
i
Climate beams Collector No glycol primary circuit
Chiller Integrator inertial tank
The system is assumed to be composed of the following parts:
4. supply pump with variable flow rate for the AHU coil
1. a chiller with a known overall power and fixed set point. The chiller is equipped with a water circulation pump. The chiller is built in a multi compressor version, with the possibility of lowering the power supply based on the power request, to always produce water at the same temperature.
5. chilled beams circuit supply pump with variable flow rate
2. outdoor inertial tank complete with expansion vessel, used to obtain the minimum volume of the system in proportion with the capacity and number of steps in the chiller 3. decoupling manifold supplying the utilities
14
6. AHU equipped with heat recovery system (enthalpy wheel) and finned-coil thermal exchanger complete with 2-way modulating regulation valve 7. chilled beam system equipped with two-way water supply shut-off valve 8. taps, valves and hydraulic connecting pipes for the various components.
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link 2. AQUA Link SYSTEM: (see diagram below)
GOLD air handling unit
Exhaust air Cold Coil exchanger
Exit air
Outdoor air
Primary air
i
Regulating 2-way valve
On/off 2-way valve
i
Bypass valve
On/off 2-way valve
Regulating 2-way valve
Chiller
Vertical collector
AQUA Link
No glycol primary circuit
Climate beams
Integrator inertial tank
The system is assumed to be composed of the following parts: 1. a chiller with a known overall power and variable set point. The chiller is equipped with a water circulation pump. The chiller is built in a multi compressor version, with the possibility, therefore, of lowering the power supply based on the power request. The temperature of the chilled water being produced depends on the request from the utilities and varies continuously between the two set values. 2. The AQUA Link module, in turn, is composed of: --variable flow-rate circulation pump to supply the primary circuit --pressure probe to control pump rotation speed --decoupling and mixing manifold to supply the chilled beams
--motorised modulating two-way valve to control the manifold supply flow rate --taps, valves and hydraulic connecting pipes for the various components 3. AHU equipped with heat recovery system (enthalpy wheel) and finned-coil thermal exchanger complete with 2-way modulating regulation valve 4. chilled beams supply pump with variable operating rate and relative pressure probe 5. chilled beam system equipped with two-way water supply shut-off valve.
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
15
AQUA Link Simulation is obviously achieved by maintaining the same operating conditions for the two systems. The basic conditions to
identify this trial context are provided below.
Location of installation
Rome
Max. total required power
200 kW
Power distribution to 2 users: Air handling unit
140 kW (70%)
Chilled Beams
60 kW (30%)
Temperature below which the chilled beams do not require feeding with chilled water
0°C
Temperature below which the air handling unit can operate in free cooling conditions
16°C
Air delivery temperature to chilled beams
16°C
Outdoor temperature
from weather file covering 8760 hours
Outdoor enthalpy
from weather file covering 8760 hours
Outdoor air volume treated by the AHU
(11 000 m3/h)
No. of chilled beams
70
In terms of the previous analysis carried out on Stockholm, the overall chiller power therefore remained unchanged. Accordingly, the two analyses refer to buildings of different sizes. The distribution of powers between AHU and chilled beams changes due to the different climatic conditions in southern European areas with a high dehumifidying requirement. Through an interactive procedure for each single hour of chiller operation serving the system, the following were evaluated: --the hourly EER values --the hourly rate of power absorption and consequently the absorbed energy
The analysis determined: • the energy consumed by the system with a variable set (assuming that the water supply temperature from the chiller varies based on the request for cold). • the energy consumed by the system, at a fixed set however, that produces water at a constant temperature of 7°C for Gold and chilled beams, regardless of the change in required power. The progress of the EER value read at an hourly rate for 8760 hours per annum is provided below.
EER 8,00
Fixed set point Variable set point
7,00 6,00
EER
5,00 4,00 3,00 2,00 1,00 0,00 0
5
10
15
20
25
30
35
40
Temperature °C
16
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link The analysis took into account real chiller operation and therefore also the energy consumption of the axial fans serving the
condensing unit.
Absorbed energy 80,00
Fixed set point Variable set point
Absorbed energy (hourly) kW
70,00 60,00 50,00 40,00 30,00 20,00 10,00 0,00 0
5
10
15
Reduction coefficient fans
20
Temperature °C
25
30
35
Fixed set point chiller
Variable set point chiller
Absorbed energy (annual)
[kWh]
104,260
93.674
Consumption reduction
[kWh]
0
10.586
Consumption reduction
%
0,0%
10,2%
[€/kWh]
0,15
0,15
[€]
0
1587,8
Electricity rata Economic Saving
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
40
17
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link 100/140
A4E027-C
3304 689 530 870
Gold in Chiller in
192 1250 331
1773
W out
160
Gold out
256 375
W.in
359
Ep
312
461 162
470
W out
A
*
Chiller out
1187
872
1682 2992
Rp
800
800
Es
800
800
800
800
Lh
A CLEARANCES Ep
ELECTRICAL PANEL
Es
ELECTRICAL SUPPLY INLET
Lh
LIFTING HOLES
Rp
REMOVABLE PANEL
C 19/07/12 R.Crivellaro B 14/02/12 R.Crivellaro Rev. Data-Date Dis.-Draftsman Denominazione-Denomination
Chiller.in Chiller.out
*
OPTIONAL
F.Cappon F.Cappon Visto-Checked by
A OPTIONAL WATER PUMP
Height reduced Modified water connections Descrizione revisione-Revision description Codice-Code
18 DIMENSIONAL DRAWING Swegon reserves the right to alter specifications. 20120904 AQUALINK 110-140
G 2"1/2 F G 3"F
W.in
G 2"1/2 F
W.out
G 2"1/2 F
Gold.in
G 3"F
Gold.out
G 2"1/2 F
Disegno-Drawing
Rev.
A4E027
C
www.swegon.com
AQUA Link A4E027-C
G1
G1
G2
G2
G4
G4
G3
G3
745 60
865
60
Overall dimensions, weights and hydronic connections AQUA Link 100/140
508
240
1480
508
240
2976
MODELLO MODEL
Fh G..
PESO (kg) PESO IN FUNZIONE(kg) WEIGHT(kg) OPERATING WEIGHT(kg) G1 (kg) G2 (kg) G3 (kg) G4 (kg)
AQUALINK 110 2P2P
654
1154
65
218
226
68
AQUALINK 140 2P2P
666
1166
68
217
227
71
AQUALINK 110 2P2P_LN
840
1340
85
256
247
82
AQUALINK 140 2P2P_LN
854
1354
88
255
248
86
AQUALINK 110 1P
512
1012
54
188
205
59
AQUALINK 140 1P
522
1022
56
187
206
62
AQUALINK 110 1P_LN
700
1200
74
226
226
74
AQUALINK 140 1P_LN
710
1210
76
225
227
77
AQUALINK 110 1P1P
568
1068
58
211
208
57
AQUALINK 140 1P1P
580
1080
59
205
214
62
AQUALINK 110 1P1P_LN
756
1256
78
249
229
72
AQUALINK 140 1P1P_LN
770
1270
80
243
235
77
AQUALINK 110 2P
554
1054
61
196
206
64
AQUALINK 140 2P
564
1064
63
195
207
67
AQUALINK 110 2P_LN
740
1240
81
234
227
78
AQUALINK 140 2P_LN
754
1254
84
233
228
82
FORI DI FISSAGGIO FIXING HOLES
Ø16
PUNTI DI APPOGGIO ANTIVIBRANTI VIBRATION DAMPER FOOT HOLDS
C 19/07/12 R.Crivellaro B 14/02/12 R.Crivellaro Rev. Data-Date Dis.-Draftsman Denominazione-Denomination
F.Cappon F.Cappon Visto-Checked by
DIMENSIONAL DRAWING AQUALINK 110-140
Height reduced Modified water connections Descrizione revisione-Revision description Codice-Code
-
Swegon reserves Scala-Scale the right to alter specifications. 20120904 Data-Date Dis.-Draftsman Visto-Checked by 1:40
12/12/11
Crivellaro
G.Morosin
www.swegon.com Foglio di 2 N. 2 Sheet of
Disegno-Drawing
Rev
A4E027
C
19
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link 220/300
A4E024-C
3304 2992
312 1804
871
1310
756
Gold out
626
870 *
Gold in
331 300
Chiller in
W.out
950
178 838
W.out
256
1773
340
192
160
W.in
Chiller out
-AQUALINK 220-
Ep
3304
Rp
2992
312 1804 1310
790
Gold out
434
192
262
*
Gold in
331 300
256
Chiller in
W.out
674
837
W.out
870
229
189
W.in
950
Es
Chiller out
-AQUALINK 300-
800
800
Lh
CLEARANCES
Es
ELECTRICAL SUPPLY INLET
Lh
LIFTING HOLES
Rp REMOVABLE PANEL
C 19/07/12 R.Crivellaro B 27/02/12 R.Crivellaro Rev. Data-Date Dis.-Draftsman Denominazione-Denomination
*
800
ELECTRICAL PANEL
800
Ep
800
OPTIONAL WATER PUMP
F.Cappon F.Cappon Visto-Checked by
Reduced height Modified water connections Descrizione revisione-Revision description Codice-Code
20 SCHEMA DIMENSIONALE Swegon reserves the right to alter specifications. 20120904 AQUALINK 220-300
Chiller.in
G 2"1/2 F
Chiller.out
G 3"F
W.in
G 3" F
W.out
G 3"F
Gold.in
G 3"F
Gold.out
G 3"F
Disegno-Drawing
Rev.
A4E024
C
www.swegon.com
AQUA Link A4E024-C
G1
G1
G2
G2
G4
G4
G3
G3
745 60
865
60
Overall dimensions, weights and hydronic connections AQUA Link 220/300
240
1480
508
508
240
2976
MODELLO MODEL
Fh G..
PESO (kg) WEIGHT(kg)
PESO IN FUNZIONE(kg) OPERATING WEIGHT(kg) G1 (kg) G2 (kg) G3 (kg) G4 (kg)
AQUALINK 220 1P
572
AQUALINK 300 1P
602
1102
85
209
183
74
AQUALINK 220 1P_LN
762
1262
100
235
208
88
AQUALINK 300 1P_LN
792
1292
112
241
200
93
AQUALINK 220 2P2P
762
1262
92
223
224
92
AQUALINK 300 2P2P
844
1344
107
239
225
101
AQUALINK 220 2P2P_LN
948
1448
118
255
240
111
AQUALINK 300 2P2P_LN
1032
1532
134
271
242
119
AQUALINK 220 1P1P
644
1144
72
212
215
73
AQUALINK 300 1P1P
698
1198
86
216
213
84
AQUALINK 220 1P1P_LN
832
1332
98
244
231
93
AQUALINK 300 1P1P_LN
884
1384
112
248
229
103
AQUALINK 220 2P
626
1126
84
194
199
86
AQUALINK 300 2P
668
1168
99
200
191
94
AQUALINK 220 2P_LN
814
1314
111
226
215
105
AQUALINK 300 2P_LN
862
1362
126
232
209
114
FORI DI FISSAGGIO FIXING HOLES
1072
73
203
191
69
Ø16
PUNTI DI APPOGGIO ANTIVIBRANTI VIBRATION DAMPER FOOT HOLDS
C 19/07/12 R.Crivellaro B 27/02/12 R.Crivellaro Rev. Data-Date Dis.-Draftsman Denominazione-Denomination
F.Cappon F.Cappon Visto-Checked by
SCHEMA DIMENSIONALE AQUALINK 220-300
Reduced height Modified water connections Descrizione revisione-Revision description Codice-Code
-
Swegon reserves Scala-Scale the right to alter specifications. 20120904 Data-Date Dis.-Draftsman Visto-Checked by 1:40
10/04/12
Crivellaro
G.Morosin
www.swegon.com Foglio di 2 N. 2 Sheet of
Disegno-Drawing
Rev
A4E024
C
21
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link No Glicole 100/140
A4E302-A
1986 1322 540
Gold out
Ep
Gold in
228
Chiller in
232
872
*
Chiller out
260
1005
1773
W.out
A W.out
1023
139 401
215 275
232
W.in
853 1026 1432
800
800
Es
800
800
800
800
Rp
Rp
Lh
Rp
Rp
SPAZI DI INSTALLAZIONE CLEARANCES Ep
QUADRO ELETTRICO ELECTRICAL PANEL
Es
INGRESSO ALIMENTAZIONE ELETTRICA ELECTRICAL SUPPLY INLET
Lh
FORI DI SOLLEVAMENTO LIFTING HOLES
Rp
PANNELLO ASPORTABILE REMOVABLE PANEL
*
OPTIONAL
A
POMPE CIRCUITO SECONDARIO SECONDARY CIRCUIT PUMP
Rev. Visto-Checked by Descrizione revisione-Revision description 22Data-Date Dis.-Draftsman Swegon reserves the right to alter specifications. 20120904 Denominazione-Denomination Codice-Code
SCHEMA DIMENSIONALE
Chiller.in
G 2"1/2 F
Chiller.out
G 2"F
W.in
G 3"F
W.out *
G 2"F
W.out
G 3"F
Gold.in
G 2"1/2F
Gold.out 110
G 2"F
Gold.out 140
G 2"1/2F
www.swegon.com Disegno-Drawing
Rev.
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link No Glicole 100/140
A4E302-A
G2
G4
G3
705
G1
80
865
80
Fh
240
1179
240
1659
MODELLO PESO (kg) PESO IN FUNZIONE(kg) MODEL WEIGHT(kg) OPERATING WEIGHT(kg) G1 (kg) G2 (kg) G3 (kg) G4 (kg) AQUALINK NG 110 2P2P 383 415 137 50 38 102 AQUALINK NG 140 2P2P 386 418 138 51 38 102 AQUALINK NG 110 2P2P_LN 475 507 172 56 44 135 AQUALINK NG 140 2P2P_LN 482 514 173 58 45 135 AQUALINK NG 110 1P 281 309 119 37 22 72 AQUALINK NG 140 1P 287 315 121 37 23 74 AQUALINK NG 110 1P_LN 375 403 154 43 29 105 AQUALINK NG 140 1P_LN 381 409 156 43 30 107 AQUALINK NG 110 1P1P 306 336 119 42 28 77 AQUALINK NG 140 1P1P 320 350 121 44 30 81 AQUALINK NG 110 1P1P_LN 400 430 154 48 35 110 AQUALINK NG 140 1P1P_LN 414 444 156 50 37 114 AQUALINK NG 110 2P 331 361 135 37 27 98 AQUALINK NG 140 2P 331 361 135 37 27 98 AQUALINK NG 110 2P_LN 425 455 170 43 34 131 AQUALINK NG 140 2P_LN 425 455 170 43 34 131
Fh G..
FORI DI FISSAGGIO FIXING HOLES
Ø16
PUNTI DI APPOGGIO ANTIVIBRANTI VIBRATION DAMPER FOOT HOLDS
Rev. Data-Date 23 Dis.-Draftsman Visto-Checked by Descrizione revisione-Revision description Swegon reserves the right to alter specifications. 20120904 www.swegon.com Disegno-Drawing Codice-Code Denominazione-Denomination
Rev
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link No Glicole 220/300
A4E306-A
1986 1290 549
Gold out
257219
W.out
*
1002 295
Chiller in
1025
Gold in
208
1773
W.out
140 400
W.in Ep
-VERSIONE 220-
232
Chiller out
865
872
1038 1432
1986 1213 549
Gold out
Chiller in
W.out
*
1232
140 400 1025
Gold in
208
W.out
246
232
W.in
295
Es
-VERSIONE 300-
Chiller out
875 1048 1432
Rp
SPAZI DI INSTALLAZIONE CLEARANCES Ep
QUADRO ELETTRICO ELECTRICAL PANEL
Es
INGRESSO ALIMENTAZIONE ELETTRICA ELECTRICAL SUPPLY INLET
Lh
FORI DI SOLLEVAMENTO LIFTING HOLES
Rp
PANNELLO ASPORTABILE REMOVABLE PANEL
800
Rp
800
800
800
Lh
800
Rp
800
Rp
*
CON POMPE LATO ACQUA OPTIONAL WATER PUMP
Rev. Visto-Checked by Descrizione revisione-Revision description 24Data-Date Dis.-Draftsman Swegon reserves the right to alter specifications. 20120904 Denominazione-Denomination Codice-Code
SCHEMA DIMENSIONALE
Chiller.in
G 2"1/2 F
Chiller.out
G 3" F
W.in
G 3" F
W.out
G 3"F
Gold.in
G 2"1/2 F
Gold.out
G 3"F
www.swegon.com Disegno-Drawing
Rev.
AQUA Link
Overall dimensions, weights and hydronic connections AQUA Link No Glicole 220/300
A4E306-A
G1
G2
G4
G3
705 80
865
80
Fh
240
1179
240
1659
MODELLO MODEL
Fh G..
PESO (kg) PESO IN FUNZIONE(kg) WEIGHT(kg) OPERATING WEIGHT(kg) G1 (kg) G2 (kg) G3 (kg) G4 (kg)
AQUALINK NG 220 2P2P
407
444
141
55
42
109
AQUALINK NG 300 2P2P
463
500
150
66
51
116
AQUALINK NG 220 2P2P_LN
501
526
172
60
48
138
AQUALINK NG 300 2P2P_LN
557
594
185
72
58
149
AQUALINK NG 220 1P
297
330
121
40
26
77
AQUALINK NG 300 1P
310
343
127
41
26
82
AQUALINK NG 220 1P_LN
390
423
157
46
32
110
AQUALINK NG 300 1P_LN
404
437
162
47
33
115
AQUALINK NG 220 1P1P
323
358
121
46
31
83
AQUALINK NG 300 1P1P
363
398
126
52
38
92
AQUALINK NG 220 1P1P_LN
417
452
157
52
38
115
AQUALINK NG 300 1P1P_LN
457
492
161
58
45
125
AQUALINK NG 220 2P
346
381
138
40
30
103
AQUALINK NG 300 2P
360
395
143
41
31
108
AQUALINK NG 220 2P_LN
442
477
172
47
37
137
AQUALINK NG 300 2P_LN
458
493
179
47
38
144
FORI DI FISSAGGIO FIXING HOLES
Ø16
PUNTI DI APPOGGIO ANTIVIBRANTI VIBRATION DAMPER FOOT HOLDS
Rev. Data-Date 25 Dis.-Draftsman Visto-Checked by Descrizione revisione-Revision description Swegon reserves the right to alter specifications. 20120904 www.swegon.com Disegno-Drawing Codice-Code Denominazione-Denomination
Rev
26
INLET FROM CHILLER
OUTLET TO CHILLER
INLET FROM GOLD
RB
SB
SF
RB
ØA
ØC
RB
Swegon reserves the right to alter specifications. 20120904 BPW1
EL
VR
VR
ØM
ØM
Dis.-Draftman
www.swegon.com Sost. il dis.-Replace draw. /
Scala-Scale /
CR
ØC
B
ØA
BPW2 BP
03
PA(BT13)
RB
ØC
RB
VR
VR
Foglio di 1 N. 1 Sheet of - Proprietà riservata, riproduzione vietata a termini di legge.Copyright. - Reserved property, reproduction prohibited accordin to existent laws.Copyright.
Visto-Checked by F.Cappon
Aggiunte sonde antigelo,sigle pompe,trasduttori di pressione Convert to solid edge format
ØA
ØC
MTE 56 rev. 04 date: 07/04/11
C A4D921
3"
3"
2"1/2
2"1/2
Rev.
2"1/2
2"1/2
2"1/2
2"1/2
Disegno-Drawing
3"
3" 300
2"1/2
140 220
ØM 2"1/2
/MODEL
SECONDARY CIRCUIT
PA(BTT)
BEAMS
OUTLET TO CHILLED
PA(BTT)
110
MODELLO
RB
BP BPW20
INLET FROM CHILLED BEAMS
BP BPW20
WITH 1 PUMP ONLY VERSION
M15 EL
RB
EL
CR
CR
CR
M15
M16
EL
WITH 2 PUMPS VERSION
Descrizione revisione - Revision description
Dis.-Draftsman Crivellaro Sost. dal dis.-Replaced by draw. /
Data-Date 27/02/2012
F.Cappon F.Cappon
ØM
SC
PRIMARY CIRCUIT
Visto - Checked by
RB
A
A25
Single-Line hydronic diagram AQUALink
HYDRAULIC CIRCUIT AQUALINK 110-300
C 24/10/12 R.Crivellaro B 28/02/12 R.Crivellaro Denominazione-Denomination
Data-Date
BP BPW10
ØC
OUTLET TO GOLD
WITH 1 PUMP ONLY VERSION
M13
ØA
EL
CR
CR
EL
CR
M13
ØA
M14
ØA
WITH 2 PUMPS VERSION
OPTIONAL WITH SECONDARY LOOP PUMP
ØA
Rev.
VE
RB
CR
AQUA Link
A4D921 - C
INLET FROM CHILLER
OUTLET TO CHILLER
INLET FROM GOLD
MADE BY THE PLUMBER
RB
SB
SF
RB
ØA
ØC
Swegon reserves the right to alter specifications. 20120904 BPW1 BP
Data-Date
RB
ØA
EL
CR
EL
CR
M13
VR
M14
VR
ØM
ØM
Dis.-Draftman
www.swegon.com Scala-Scale /
B
ØC
ØA
BPW2 BP
HS
PA(BT13)
RB
ØC
EL
M15
RB
VR
M16
VR
300
Foglio di 1 N. 1 Sheet of - Proprietà riservata, riproduzione vietata a termini di legge.Copyright. - Reserved property, reproduction prohibited accordin to existent laws.Copyright.
Visto-Checked by F.Cappon
ØC
MTE 56 rev. 04 date: 07/04/11
B A4E512
3"
3"
2"1/2
2"1/2
Rev.
2"1/2
2"1/2
2"1/2
2"1/2
ØA
BEAMS
Disegno-Drawing
3"
3"
2"1/2 220
140
ØM 2"1/2
/MODEL 110
MODELLO
PA(BTT)
OUTLET TO CHILLED
PA(BTT)
INLET FROM CHILLED BEAMS
BP BPW20 RB
BP BPW20
WITH 1 PUMP ONLY VERSION
RB
CR
EL
CR
CR
EL
WITH 2 PUMPS VERSION
OPTIONAL WITH SECONDARY LOOP PUMP
ØM
SC
Aggiunte sigle pompe,sigle sonde,trasduttori di pressione
Dis.-Draftsman R.Crivellaro
F.Cappon
A
Descrizione revisione - Revision description
RB
Sost. dal dis.-Replaced by draw. /
Data-Date 30/07/12
HYDRAULIC CIRCUIT AQUALINK NG 110-300
BP BPW10
Visto - Checked by
OUTLET TO GOLD
WITH 1 PUMP ONLY VERSION
ØA
ØA
CR
EL
B 23/11/2012 R.Crivellaro Denominazione-Denomination
Rev.
VE
ØA
WITH 2 PUMPS VERSION
ØC
CR
Single-Line hydronic diagram AQUALink No Glycol
Sost. il dis.-Replace draw. /
RB
A25
AQUA Link
A4E512 - B
27
AQUA Link
Installation tips Check that the location where the unit is installed provides for easy connection of the hydronic piping coming from the chiller and the terminal units. Refer to the dimension drawings attached to this Technical Booklet to locate the connections. Place the unit so that a minimum distance is left, as shown in the dimension drawings. Place the unit in a manner that assures the lowest environmental impact (noise emissions, integration with nearby structures, etc.).
700 mm
700 mm
28
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
AQUA Link
Summary Advantages for the fitter The construction of a hydronic system serving the air conditioning unit in a building is undoubtedly a complex operation both hydronically and in terms of easy management and control, first of all because the main elements making up the system (chiller, UTA, chilled beams) must be selected and, secondly, because they must be networked. Besides the main parts mentioned above, a hydronic system also comprises a series of “accessory” components such as pumps, tanks, shut-off valves, control valves, filling units, manifolds for circuit mismatching, etc. that must be selected, installed in a dedicated compartment (distribution box) and interconnected. The operating logic at the design stage may be affected by the features of these components and their capacity to respond to control signals originating from the system constituting elements. AQUA Link was designed to simplify commissioning of the plant, thus reducing both installation and plant management costs. This is why it is complete with all the elements required for the hydronic circuit, which are normally excluded from the supply of the main units and must be procured from the fitter. Provision of these elements in one single shell, that is sized by the manufacturer at earlier stages, offers a number of advantages: • One single interlocutor for the entire plant eliminates possible inconveniences relating to identification of responsibilities and difficult communications with the various parties involved; • Accurate sizing that can be tested at any time against complete documentation; • Quick commissioning compared to other solutions: the system only requires hydronic and electrical connection between the chiller, the users and AQUA Link to operate; • One individual standardised communication protocol between the various elements; • Well-organised, compact and easy-to-find location of components; • No dedicated compartment required to contain all the featured elements (when the outdoor version is selected); • Operating options to adapt AQUA Link to the different plant engineering requirements (high heads, mismatching of primary and secondary circuits, installation outdoors or indoors, etc.); • A dedicated selection software to check the performances of the unit according to the features of the served plant.
Advantages for the end user After implementation, the system must operate smoothly without downtimes and with minimised energy consumption, yet meeting the users’ requirements. High chiller and terminal unit performances are no guarantee that the second objective above be achieved, especially if, as is the case with all traditional plants, the production temperature of chilled water is established univocally at the design stage and is determined according to the heaviest work conditions envisaged for system operation. As a matter of fact, the operating conditions of the system vary according to different parameters: --indoor temperature; --outdoor temperature; --outdoor air humidity; --number of people in the room(s); --exposure of various areas to sun radiation; --possibility to go for free cooling; --etc. This said, it is fundamental that the system responds to the users’ requirements in real time. Thanks to this option, for instance, the unit heavily consumes energy only when the operating conditions are heavy. This results into a decrease in global energy consumption that derives from improved energy efficiency for the chiller and reduced energy requirements for water-glycol blend pumping. The awareness of the end user on matters regarding energy consumption is undeniable and self-evident. AQUA Link can play a major role in this thanks to: • Reduced indirect consumption: the consumption of energy supplied to the chiller and used to produce chilled water is reduced through a setpoint that varies continuously and according to the users’ requirements; • Reduced direct consumption: the consumption of energy used to pump water to the primary and secondary circuits (version 1P-1P or 2P-2P) is reduced through inverter-controlled variable pumps that only absorb the min. amount of energy required by the plant; • Reduced indirect consumption: the consumption of energy required for water pumping is reduced through the use of one single pump to the primary circuit to serve both users. • Decreasing of footprint: all equipment and components are condensed in one unique volume, AQUA Link can be placed outdoor.
Swegon reserves the right to alter specifications. 20120904
www.swegon.com
29
60192000502_AQUALink