Preview only show first 10 pages with watermark. For full document please download

Aubur N University Jorda N-har E Stadium South Endzon E Score Boar

   EMBED


Share

Transcript

400A 5 150A/3P/WP ENCLOSED CIRCUIT BREAKER "T-ELVB8" 45 kVA 480-208Y/120 WEATHERPROOF SMART PANEL 6 7 2. THE ELECTRICAL WORK SHALL CONSIST OF ALL LABOR AND MATERIAL TO COMPLETELY INSTALL ALL ELECTRICAL WORKS AS SHOWN ON THESE DRAWINGS. 3. ELECTRICAL EQUIPMENT, AND EXPOSED CONDUIT IN PARTICULAR, TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER PER SECTION 110.112 OF THE NATIONAL ELECTRICAL CODE. INSTALLATION TO COMPLY WITH (ANSI/NEIS) NECA 1-2000 ON STANDARD FOR GOOD WORKMANSHIP IN ELECTRICAL CONTRACTING. ELECTRICAL EQUIPMENT TO BE SQUARE D, GENERAL ELECTRIC OR SIEMENS. 4. THE CONTRACTOR SHALL INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER AND ACCORDING TO GENERALLY ACCEPTED PRACTICES OF FIRST CLASS WORKMANSHIP. 5. ANY CONDUIT, SLEEVES, ETC. THAT PENETRATE RATED WALLS, CEILINGS AND FLOORS SHALL BE FIRE STOPPED PER IBC/NFPA (202, 221, ETC.) AND IN NO CASE LESS THAN FIRE-RATING OF EXISTING BUILDING SURFACE. 150A SPEAKER BOX LEVEL 1 1 8 1# 2 GND.,1"C. 600A 6. 600A/3P/NF/WP B. GIRT LEVEL 6 600A/3P/NF/WP 600A 600A 400A 7. 1 8. GIRT LEVEL 4 1 9. 100A EMERGENCY LIGHT FIXTURE 1 1 9 wall or structure MOUNTED LIGHT FIXTURE EXIT SIGN (PROVIDE FACES AND ARROWS AS SHOWN) WALL MOUNTED EXIT SIGN (PROVIDE FACES AND ARROWS AS SHOWN) CONDUIT RUN CONCEALED IN WALL OR CEILING UNDERGROUND SERVICE AND UNDERGROUND FEEDER - PVC SCHEDULE 40 ENCASED IN CONCRETE OR GRC MEETING CORROSION RESISTANT PROTECTION PER NEC 300.6. (SEE SECTION 16110-3.1(A)) C. WHEN PVC IS USED UNDERGROUND A TRANSITION TO METAL CONDUIT SHALL BE MADE BELOW GRADE USING GRC 90 DEGREE FITTING. D. ABOVE GROUND FEEDERS AND BRANCH CIRCUITS WITHIN THE VIDEOBOARD STRUCTURE SHALL BE GRC OR IMC. E. FEEDERS AND BRANCH CIRCUITS EXPOSED TO DAMAGE OR 8'-0" AFF OR LESS SHALL BE GRC OR IMC. F. EXPOSED TO WEATHER SHALL BE GRC OR IMC. G. CONCEALED SHALL BE EMT. H. EXPOSED ABOVE 8'-0" AFF IN A DRY AREA SHALL BE EMT (WITH COMPRESSION FITTINGS), GRC, OR IMC. I. EXPOSED WITHIN THE EXISTING MAIN CONCOURSE ABOVE 8'-0" AFF AND 10'-0" OR GREATER FROM THE EXTERIOR DRIP LEDGE SHALL BE EMT (WITH COMPRESSION FITTINGS), GRC, OR IMC. J. PROVIDE LONG SWEEP RADIUS ELBOWS FOR ALL LOW VOLTAGE CONDUITS. K. SEE SECTION 16110 FOR MORE INFORMATION. PANEL "HVB3" PANEL "LVB3" SMART PANEL SMART PANEL GIRT LEVEL 3 100A 600A No. CONDUIT RUN CONCEALED IN THE FLOOR, UNDERGROUND, OR UNDER THE ELEVATED SLAB UNDERGROUND BRANCH CIRCUITS - PVC SCHEDULE 80 OR GRC MEETING CORROSION RESISTANT PROTECTION PER NEC 300.6. (SEE SECTION 16110-3.1 (D)) CONDUIT RUN EXPOSED. ROUTE PARALLEL/PERPENDICULAR TO WALLS AND STRUCTURE. 1 NUMBER OF CONDUCTORS (GROUND NOT SHOWN) and DUPLEX AND QUAD RECEPTACLE - WALL MOUNTED 18" and GFCI DUPLEX AND QUAD RECEPTACLE - WALL MOUNTED 18" WP WEATHER PROOF GFCI DUPLEX RECEPTACLE - WALL MOUNTED 18" VOICE AND DATA OUTLET - WALL MOUNTED FOR EQUIPMENT THAT IS TO BE WIRED BY ELECTRICAL CONTRACTOR AND FURNISHED BY OTHERS, ELECTRICAL CONTRACTOR SHALL REVIEW ALL SPECIFICATION SECTIONS, EQUIPMENT SCHEDULES, AND/OR DETAILS THROUGHOUT DOCUMENTS THAT PERTAIN TO THIS EQUIPMENT AND INCLUDE ALL WIRING AND DEVICES REFERENCED IN THEIR BIDS. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF THIS EQUIPMENT WITH RESPECTIVE CONTRACTOR PRIOR TO ROUGH-IN. ALL ABANDONED WIRE, CONDUIT, DISCONNECTS AND ASSOCIATED EQUIPMENT SHALL BE REMOVED. IN SITUATIONS WHERE ABANDONED CAN NOT BE REMOVED DISCONNECT FROM PANEL, PROVIDE PERMANENT CAP AT EACH END OF THE CONDUCTORS AND PROVIDE A PERMANENT LABEL AT END READING "ABANDONED." WHERE WORK BY THE GENERAL CONTRACTOR (WALL REMOVE, NEW OR RELATED WALL OPENING, ETC.) RESULTS IN THE REMOVALS, REFEEDING, OR RELOCATION OF LIGHTING FIXTURES OR ELECTRICAL DEVICES, THE ELECTRICAL CONTRACTOR SHALL DISCONNECT OR RECONNECT AS REQUIRED ALL ACTIVE DEVICES REMAINING ON THAT CIRCUIT SYSTEM. CONDUCTORS SHALL HAVE COLOR CODED JACKETS THE ENTIRE LENGTH FOR ALL SIZES. COLORS SHALL BE AS FOLLOWS 277/480 VOLT SYSTEM PHASE 'A' - BROWN PHASE 'B' - ORANGE PHASE 'C' - YELLOW FEEDER OR SHARED NEUTRAL - GRAY BRANCH PHASE A NEUTRAL - WHITE W/ BROWN STRIPE BRANCH PHASE B NEUTRAL - WHITE W/ ORANGE STRIPE BRANCH PHASE C NEUTRAL - WHITE W/ YELLOW STRIPE GROUND - GREEN 12. PROVIDE CONSPICUOUS AND PERMANENT LABEL ON NEW PANELBOARDS INDICATING AVAILABLE FAULT CURRENT PER NEC 110.24 13. FIELD IDENTIFY EXISTING PANELBOARDS THAT ARE MODIFIED PER NEC 408.4(B). J JUNCTION BOX J JUNCTION BOX - WALL MOUNTED S SPST SWITCH - WALL MOUNTED 48" S3 3-WAY SWITCH - WALL MOUNTED 48" ST TIMER SWITCH - WALL MOUNTED 48" S D DIMMER SWITCH - WALL MOUNTED (PROVIDE WATTAGE AND TYPE AS REQUIRED) 48" S M MOTOR RATED SWITCH 48" Pc PHOTOCELL PANELBOARD OR DISTRIBUTION PANEL DISCONNECT (FRAME AND POLES TO MATCH OCP OR AS NOTED) 48" AFF TO TOP OF BOX FIRE ALARM PULL STATION - WALL MOUNTED F FIRE ALARM ADA APPROVED AUDIO/VISUAL (110cd) 80" AFF TO BOTTOM OF VISUAL FIRE ALARM ADA APPROVED VISUAL ONLY (110cd) 80" AFF TO BOTTOM OF VISUAL FIRE ALARM PULL STATION AT 48" AFF TO TOP OF BOX AND AUDIO/VISUAL AT 80" AFF AT 80" AFF TO BOTTOM OF VISUAL F 600A SMOKE DETECTOR - CEILING MOUNTED DUCT MOUNTED SMOKE DETECTOR 100A sb-vb 1 2 GIRT LEVEL 2 6 SETS OF 4#600KCMIL, 1#350KCMIL G., 4"C. TO 'MSB-S' UTILIZE EXISTING SPARE 60A/3P BREAKER. PROVIDE NEW LABEL READING "VIDEOBOARD PANEL 'HVB3.'" PULLBOX 1 1 6 SETS OF 4#600KCMIL, 1#350KCMIL G., 4"C. TO 'MP-EM.' utilize EXISTING spare 70A/3P BREAKER. PROVIDE NEW LABEL rEADING "VIDEOBOARD PANEL 'EHVB3.'" TO BE CONNECTED TO WAY 3 1791 SWITCH. AU FACILITIES TO REPROGRAM OVERCURRENT PROTECTION TO 75A. EXISTING MEDIUM VOLTAGE SWITCHGEAR AND VAULT. 2500a/3p MAIN BREAKER 'MB-VB' - NEMA 3R WITH HINGED DOOR AND LATCHING HANDLE. 65,000 aic 1. ALL NEW FIRE ALARM DEVICES SHALL BE ADA APPROVED. 2. ALL AUDIO/VISUAL DEVICES SHALL MATCH EXISTING. 3. ALL FIRE ALARM DEVICES ARE TO BE CONNECTED TO THE BASE BUILDING FIRE ALARM SYSTEM BY A NICET LEVEL 3 LISCENSED INSTALLER AS APPROVED BY THE LANDLORD. 4. CONFIRM EXISTING A/V LOADS AND PROVIDE NEW POWER SUPPLIES WITHIN THIS TENANT SPACE AS REQUIRED. 5. ALL WORK ASSOCIATED WITH THE FIRE ALARM SHALL BE COORDINATED WITH THE BUILDING'S CHIEF ENGINEER. 6. ADDITIONS AND ALTERATIONS TO THE FIRE ALARM SYSTEM REQUIRE TESTING, A RECORD OF COMPLETION, AND RECERTIFICATION. ADDITIONALLY, THE WORK SHALL BE PERFORMED BY QUALIFIED PERSONNEL AS DEFINED IN NFPA 72 (2013), 10.4.2. 1 6 SETS OF 4#600KCMIL, 4"C. 7. M METER PAD MOUNTED UTILITY TRANSFORMER T-VB (2) 5"C. HEAT DETECTOR - CEILING MOUNTED, WALL MOUNTED FIRE ALARM NOTES 3 BOND NEUTRAL GROUND LEVEL 12" BELOW CEILING SYMBOL DESCRIPTION AC ABOVE COUNTER AFF ABOVE FINISHED FLOOR BFG BELOW FINISHED GRADE E/R EXISTING / RELOCATED FAA FIRE ALARM ANNUNCIATOR PANEL THE STATE OF ALABAMA CERTIFIED FIRE ALARM ACT REQUIRES THAT EVERY BUSINESS WHO INSTALLS FIRE ALARM SYSTEMS IN COMMERCIAL OCCUPANCIES MUST BE LICENSED AS A CERTIFIED FIRE ALARM CONTRACTOR. THE CONTRACTOR MUST HAVE A NICET LEVEL III TECHNICIAN IN A POSITION OF RESPONSIBILITY, AND THE LICENSE WILL BE ISSUED IN THE NAME OF THE CERTIFICATE HOLDER AND THE CONTRACTOR. THE CERTIFIED FIRE ALARM ACT ALSO REQUIRES THAT TECHNICIANS WORKING FOR THE CERTIFIED CONTRACTOR mUST HOLD A CURRENT NICET LEVEL II, OR EQUIVALENT, CERTIFICATION. THE FIRE ALARM SPECIFICATIONS SHALL REQUIRE CONTRACTORS WISHING TO BID ON FIRE ALARM WORK TO SHOW EVIDENCE AT THE PRE-BID CONFERENCE THAT HE/SHE MEETS THE CERTIFICATION REQUIREMENTS OF THE ACT AND HOLDS A PERMIT ISSUED BY THE STATE FIRE MARSHAL. FACP (2) 5" CONDUITS FOR FUTURE NORTH END ZONE PRIMARY. FIELD COORDINATE TERMINATION POINT WITH ENGINEER. FIRE ALARM CONTROL PANEL ELECTRICAL RISER DIAGRAM UNO UNLESS NOTED OTHERWISE WP WEATHER PROOF XFMR F 1 TRANSFORMER SPEAKER BOX LEVEL 1 NOT TO SCALE NOTE: ALL DISTRIBUTION EQUIPMENT SHALL BE NEMA 3R UNLESS NOTED OTHERWISE. GIRT LEVEL 8 GIRT LEVEL 7 LIGHTING FIXTURE SCHEDULE TYPE RISER DIAGRAM FEEDER SCHEDULE TAG NUMBER OF SETS CONFIG. PHASE/NEUTRAL SIZE PER SET EQUIP. GROUND PER SET CONDUIT SIZE PER SET 600A 2 3-PH, 4W+G 4 # 350 kcmil 1 # 1/0 3" 400A 1 3-PH, 4W+G 4 # 600 kcmil 1 # 1/0 4" 150A 1 3-PH, 4W+G 4 # 1/0 1#6 2" 100A 1 3-PH, 4W+G 4#2 1#8 1\" 40A 1 3-PH, 4W+G 4#8 1 # 10 1" 80A 3W 20A 3W 1 1 3-PH, 3W+G 3-PH, 3W+G 3#3 3 # 12 1#8 1 # 12 KEY NOTES (APPLIES TO THIS SHEET ONLY): NOTES 1 2 1|" [" 1 A CONTROL PANEL BY OTHERS. PROVIDE CONNECTION. COORDINATE WITH VIDEOBOARD MANUFACTURER. B EXTERNAL WEATHERPROOF SURGE PROTECTION DEVICE. LOCATE ADJACENT TO BREAKER IN 'SB-VB' AND NIPPLE CONNECTION TO MINIMIZE LEAD LENGTH. MAXIMUM CONDUCTOR LENGTH TO BE 2'-0". LOCATE BREAKER IN THE SWITCHBOARD NEAREST THE NEUTRAL/GROUND TERMINATIONS. PROVIDE BREAKER AND CONDUCTORS AS RECOMMENDED BY THE SPD MANUFACTURER. SEE SECTION 26 43 04. 3 DO NOT BOND THE NEUTRAL AT 'SB-VB'. 4 PROVIDE INTELLIGENT PANELBOARD PER SECTION 26 24 50. PROVIDE 1" CONDUIT TO JOHNSON CONTROLS AND CONTROL WIRING AS REQUIRED. PROVIDE NECESSARY INTERFACE WITH JCI. 5 GIRT LEVEL 6 GIRT LEVEL 5 C D1 GIRT LEVEL 4 D2 F G GIRT LEVEL 3 AUDIO CONTROL PANEL BY OTHERS FOR LIFE SAFETY AUDIO BROADCAST. COORDINATE WITH VIDEOBOARD MANUFACTURER. 6 EMERGENCY AUDIO CONTROL PANEL BY OTHERS FOR LIFE SAFETY AUDIO BROADCAST. COORDINATE WITH VIDEOBOARD MANUFACTURER. 7 provide a ground bar (erico egba14412bb) for audio equipment and tranformer 't-elvb8'. provide bond to structural steel using cadweld eXothermic connection with 1#3/0, 1|"pvc conduit. coordinate location with audio system installer. 8 bond transformer to structural steel. 9 provide 1" conduit for lighting control interface to johnson control panel on the main concourse level. Z GIRT LEVEL 2 GROUND LEVEL 2 TO LOCKER ROOM FIRE ALARM PANEL COORDINATE LOCATION WITH SIMPLEX. FIRE ALARM RISER NOT TO SCALE NOTE: 1. ALL CONDUIT SHALL BE 1" GRC 2. COORDINATE WIRING AND POWER SUPPLY REQUIREMENTS WITH SIMPLEX. pe# 20753 2-16-2015 ELECTRICAL ABBREVIATIONS SEE SPECIFICATIONS REUSE EXISTING PRIMARY CONDUCTORS REMOVED BY AUBURN facilities distrbution department (#2CU, 3~, 15KV CABLE). CONFIRM LENGTH OF EXISTING CABLE PRIOR TO ROUGH-IN OF NEW TRANSFORMER PAD, PRIMARY CONDUITS, AND SECONDARY CONDUITS. Date 02-11-15 02-17-15 CIRCUITS HOMERUN TO THE PANEL 14. PROVIDE ARC-FLASH WARNING LABELS ON ELECTRICAL EQUIPMENT THAT COMPLIES WITH NEC 110.16. 100A Revision BID SET Addendum 1 FLEXIBLE CONDUIT OR CORD 120/208 VOLT SYSTEM PHASE 'A' - Black PHASE 'B' - RED PHASE 'C' - BLUE FEEDER OR SHARED NEUTRAL - WHITE BRANCH PHASE A NEUTRAL - WHITE W/ BLACK STRIPE BRANCH PHASE B NEUTRAL - WHITE W/ RED STRIPE BRANCH PHASE C NEUTRAL - WHITE W/ BLUE STRIPE GROUND - GREEN 9 Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. CEILING MOUNTED LIGHT FIXTURE 10. WHERE DEMOLITION DISRUPTS ELECTRICAL CONTINUITY OF EXISTING RECEPTACLES/LIGHTS, AND NO RECONNECTION IS SHOWN, RECONNECT TO ITS EXISTING CIRCUIT. 11. DESCRIPTION CONDUIT APPLICATIONS (600V AND LESS) A. 1 SYMBOL 205-251-4500 PANEL "LVB8" MOUNTING HEIGHT ON CENTER (COORD WITH ARCH) LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 80A 3W ALL INSTALLED ELECTRICAL EQUIPMENT TO BE NEW, SPECIFICATION GRADE AND LISTED WITH UL (UNDERWRITERS LABORATORIES INC.). ELECTRICAL INSTALLATION TO COMPLY WITH NATIONAL, STATE, AND LOCAL CODES TO INCLUDE LATEST REVISION OF ANSI C2, (NATIONAL ELECTRICAL SAFETY CODE), NFPA 70 (NEC ART. 250 GROUNDING), AND NFPA 70E (WORKPLACE ELECTRICAL SAFETY.) LBYD Project No: 101-14-054.002 1. 100A/3P/NF/WP 9 DESCRIPTION LAMP WALL MOUNTED UTILITY VAPOR TIGHT FIXTURE. INCANDESCENT 100 WATT FIXTURE HOUSING USING AN LED MEDIUM BASE LAMP. GRAY EQUIVALENT LED FINISH. BULB, 5000K SAME AS TYPE 'A' EXCEPT CEILING MOUNTED 100 WATT EQUIVALENT LED BULB, 5000K SURFACE MOUNTED 4' LINEAR VAPOR TIGHT, LED, 5500 L840 - 4000K LUMEN, WIDE DISTRIBUTION LED WALL MOUNTED FULL CUTOFF LED WALL PACK, 2804 DELIVERED LUMENS. WALL MOUNTED FULL CUTOFF LED WALL PACK, 4409 DELIVERED LUMENS. SURFACE MOUNTED AREA LIGHT. TYPE FOUR FORWARD THROW DISTRIBUTION. GREY FINISH. 15,000 DELIVERED LUMENS, 5000K YOKE MOUNTED LED FLAG POLE, MEDIUM FLOOD LIGHT WITH HALF VISOR, GRAY FINISH. SURFACE MOUNTED WET LOCATION LED EMERGENCY LIGHT. MANUFACTURER LITHONIA #VW150IM12 OR EQUAL BY COOPER, HUBBELL LITHONIA #Vc150IM12 OR EQUAL BY COOPER, HUBBELL METALUX #VT-LD2-55-DR-W-UNV-L840-WL OR EQUAL BY LITHONIA, HUBBELL 26W LED 5000K LUMARK CROSSTOUR #XTOR3A OR APPROVED EQUAL 41W LED 5000K LUMARK CROSSTOUR mAXX #XTOR5A OR APPROVED EQUAL 157W LED 5000K MCFRAW EDISON GLEON #AE-03-LED-E1-T4FT-AP-7050 OR EQUAL BY LITHONIA, HUBBELL 55 WATT LED BEACON 4000K #CDT-24NB-55-4K-5X5-UNV-TKGYS-HV OR EQUAL BY BEGA, DESIGN PLAN LED LITHONIA #WLTU LED OR EQUAL BY SURE-LITE, EMERGI-LITE, DUAL-LITE NOTES AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 1 400A/3P/NF/WP ELECTRICAL LEGEND ELECTRICAL GENERAL NOTES: 150A SHEET TITLE: ELECTRICAL LEGEND, NOTES, AND SCHEDULES DRAWN BY: AFH CHECKED BY: CDC DATE: 2-11-2015 FILE NUMBER: PROJECT NUMBER: AU #14-286 SHEET NUMBER: E0.1 11.9 8.9 8 15 No. 7' - 1" 12.9 7 J J J J J LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO 400A/3P/NF/WP LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO. J J LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO 150A/3P/WP ENCLOSED BREAKER J J 1 J J J J J J J J J J J J 45KVA XFMR GIRT LEVEL 8 780' - 4 3/16" TO GND BAR 8' - 4 13/16" bond flag pole to structural steel GROUND BAR. BOND TO STEEL AND TO GROUND ADJACENT TO 'SB-VB' WITH 1#3/0, 1|"PVC CONDUIT. GENERAL NOTES (APPLIES TO THIS SHEET ONLY): 9' - 7 3/16" GIRT LEVEL 7 771' - 11 3/8" 600A/3P/NF/WP 1 9' - 7 3/16" GIRT LEVEL 6 762' - 4 3/16" J J J J J J J J 600A/3P/NF/WP 7 1 GIRT LEVEL 4 743' - 1 3/4" HVB3 & LVB3 TO AUDIO ROOM 2 GIRT LEVEL 2 723' - 11 3/8" GROUND BAR. BOND TO STEEL, 'SB-VB' GROUND BUS AND AUDIO ROOM GROUND BAR. J J J J J J PULLBOX - PROVIDE VERTICAL CABLE SUPPORTS IN THE PULLBOX 6 LEVEL 5 708' - 0 1/2" 6 LOW VOLTAGE/CONTROL/VERIZON CONDUITS. J J J 3. REFER TO SECTION 26 05 00 FOR MORE INFORMATION. pe# 20753 1 VIDEO CONTROL PANEL BY OTHERS. PROVIDE CONNECTION. COORDINATE WITH VIDEOBOARD MANUFACTURER. 2 EXTERNAL WEATHERPROOF SURGE PROTECTION DEVICE. LOCATE ADJACENT TO BREAKER IN 'SB-VB' AND NIPPLE CONNECTION TO MINIMIZE LEAD LENGTH. MAXIMUM CONDUCTOR LENGTH TO BE 2'-0". LOCATE BREAKER IN THE SWITCHBOARD NEAREST THE NEUTRAL/GROUND TERMINATIONS. PROVIDE BREAKER AND CONDUCTORS AS RECOMMENDED BY THE SPD MANUFACTURER. SEE SECTION 26 43 04. 3 PROVIDE NEW LIGHTNING PROTECTION GROUND ROD AND BOND THE BASE OF EVERY COLUMN (6) PER UL AND LPI STANDARDS. SEE SECTION 26 41 00. 4 REPLACE EXISTING GROUND ROD AND BOND AT EXISTING COLUMN. 5 BOND NEW 'MB-VB' SERVICE GROUNDING ELECTRODE TO THE NEAREST LIGHTNING PROTECTION GROUND ROD. 6 BOND NEW STRUCTURE TO EXISTING WITH 1#3/0 IN 1|" SCH 80 PVC CONDUIT. 7 PROVIDE ONE (1) PULLBOX PER CONDUIT. 8' - 6 11/16" J ALL LOW VOLTAGE CONDUITS 1\" AND LARGER SHALL BE GALVANIZED RIGID STEEL. WELDED TUBE FRAME SUPPORT. SEE DETAIL 2/E1.0 SWITCHBOARD 'SB-VB' (DO NOT BOND NEUTRAL TO GROUND) 17' - 3 1/8" GIRT LEVEL 1 716' - 7 3/16" 1 2. 7' - 4 3/16" 9' - 7 3/16" GIRT LEVEL 3 733' - 6 9/16" 181' - 8 3/8" PULLBOX - PROVIDE VERTICAL CABLE SUPPORTS IN THE PULLBOX (1) 4" FOR VIDEOBOARD CONTROL. 9' - 7 3/16" 1 ALL EXPOSED FEEDER CONDUITS SHALL BE GALVANIZED RIGID STEEL OR IMC. KEY NOTES (APPLIES TO THIS SHEET ONLY): J 9' - 7 3/16" GIRT LEVEL 5 752' - 9" J 1. 'SB-VB' FEEDERS SEE RISER DIAGRAM switchboard LEVEL 4 690' - 9 3/8" 17' - 3 1/8" steel fabricated frame with bottom plate (by others) to total enclose bottom of switchboard to prevent varment access. coordinate required dimensions with switchgear submittals and steel fabricator. see structural drawings. (2) 4" CONDUITS FROM SPEAKERBOX LEVEL 1 TO SOUTH MAIN CONCOURSE CABLE TRAY FOR SPARE. PROVIDE LONG SWEEP RADIUS ELBOWS. LEVEL 3 673' - 6 1/4" 6 (1) 4" CONDUIT FROM SPEAKERBOX LEVEL 1 TO SOUTHWEST CONTROL ROOM ON THE MAIN LEVEL FOR AUDIO. PROVIDE LONG SWEEP RADIUS ELBOWS. 6 17' - 3 1/8" SHEET TITLE: (1) 4" CONDUIT FROM GIRT LEVEL 2 TO SOUTHWEST CONTROL ROOM ON THE MAIN LEVEL FOR VIDEO. PROVIDE LONG SWEEP RADIUS ELBOWS. (1) 4" CONDUIT FROM SPEAKERBOX LEVEL 1 TO LEVEL 2 FOR VERIZON. OVERALL ELEVATION ELECTRICAL DISTRIBUTION 2 MAIN BREAKER "mb-vb" TO 'MSB-S' SEE RISER DIAGRAM TO 'MP-EM' SEE RISER DIAGRAM SWITCHBOARD HOUSEKEEPING FRAME NOT TO SCALE DRAWN BY: AFH MAIN BREAKER FEEDERS. SEE RISER DIAGRAM. 17' - 3 1/8" LEVEL 2 656' - 3 1/8" cut holes in bottom plate for conduits. seal penetrations. 2-16-2015 205-251-4500 J 100A/3P/NF/WP LVB8 LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 (1) 4"C FOR VERIZON & (2) 4" SPARE. LBYD Project No: 101-14-054.002 LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO 12' - 11 15/16" LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO 6' - 4 1/16" (1) 4"C., FOR SPEAKER SYSTEM. ROUTE TO STADIUM CONTROL ROOM LOCATED ON FRONT OF SPEAKER BOX FOR ILLUMINATED LETTERING/LOGO. Speaker BOX Level 1 787' - 8 7/8" 10.9 7' - 4 11/16" Speaker BOX 17 Level 3 807' - 0 7/8" 2'-0"lightning air terminal (2) at each location. bond to column (typical). Date 02-11-15 02-17-15 6' - 6 1/2" Speaker BOX Level 4 813' - 7 3/8" Speaker BOX Level 2 800' - 8 13/16" 1 Revision BID SET Addendum 1 AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 16 Speaker BOX Level 5 820' - 8 3/8" 11.1 Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. new utility transformer CHECKED BY: CDC DATE: 2-11-2015 FILE NUMBER: FOUNDATION PLAN 639' - 0" 3 4 3 4 3 3 5 3 4 3 4 PROJECT NUMBER: AU #14-286 SHEET NUMBER: 1 OVERALL ELEVATION - ELECTRICAL DISTRIBUTION 1/8" = 1'-0" (2) 5" CONDUIT FOR PRIMARY FEEDER TO 'T-VB'. REUSE EXISTING PRIMARY CONDUCTORS. SEE ELECTRICAL SITE PLAN AND RISER DIAGRAM (2) 5" CONDUIT FOR FUTURE NORTH END ZONE PRIMARY, SEE ELECTRICAL SITE PLAN AND RISER DIAGRAM. E1.0 16 KEY PLAN: SOUTHWEST CONTROL ROOM SCOREBOARD & UTILITY YARD 1 PANEL "EHMS" 15 LIGHTNING GROUND rod, BOND TO COLUMN with #3/0 stranded copper north SWITCHBOARD 'MSB-S', PANELS 'MP-EM', & 'PPA' n Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. No. LIGHTNING GROUND rod, BOND TO COLUMN with #3/0 stranded copper 1 EXISTING SWITCHBOARD 'MSB-S' LOCATED IN MECHANICAL ROOM 0455 EXISTING "TRN-669" EXISTING SOUTH MAIN switchboard Revision BID SET Addendum 1 Date 02-11-15 02-17-15 EXISTING PANEL 'MP-EM' LOCATED IN MECHANICAL ROOM 0455 e 12.9 e EXISTING 'TC4' e e-c EXISTING 'TC3' EXISTING PANEL 'PPA' LOCATED IN MECHANICAL ROOM 0455 EXISTING "TC1" EXISTING EAST STAND LIGHTING DUCT BANK EXISTING DISCONNECT SERVING OUTLETS UNDERNEATH SOUTH WEST STANDS. REMOVE DISCONNECT, CONDUIT, AND WIRE (ENTIRE LENGTH). e e-t NOT TO SCALE r 11.9 SECTION OF EXISTING GATE CARD READER REMOVED DURING DEMOLITION. REMOVE CONDUIT & REFEED CONTROL WIRING TO OPERATE AS EXISTING. LIGHTNING GROUND, BOND TO COLUMN AND EXISTING south MAIN SWITCHboard GROUND EXISTING WATER VAULT 11.1 // e e // EXISTING 'TC2' LIGHTNING GROUND rod, BOND TO COLUMN with #3/0 stranded copper " -0 ) AL // // // // // 6' 0" PIC NOT TO SCALE NEW bollard TO MATCH EXISTING (typical) B 4' D BE NEW 2-WAY 5" DUCT BANK J EXISTING UNDERGROUND AND NEW MAIN BREAKER LOCATION e2.0 NEW XFMR 'T-XB' e2.0 (TY EXISTING VAULT EXISTING 'VS' 2 3 EXISTING PRIMARY DUCTBANK TO EAST STAND LIGHTS 4' 0" PIC (TY EXISTING PRIMARY TO EAST STANDS // north TRANSFORMER SCHEDULE TAG T-VB KVA SIZE 750 PRIMARY & SECONDARY VOLTAGE 7.2/12.47 KV 120/208V 3` 4W Y-Y ENCLOSURE REMARKS PADMOUNT 65E S&C SMZ-4-STD FUSE LIGHTNING GROUND rod, BOND TO COLUMN with #3/0 stranded copper SITE PLAN - ELECTRICAL 1/8" = 1'-0" NOTE: ROUTING OF EXISTING PRIMARY DISTRIBUTION IS SHOWN FOR INFORMATION ONLY. CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS. #4 REBAR ON 12"x12" MAX. CENTERS 4. 5. 6. 7. SECONDARY COMPT. 12 10 13 8 2 1-1/2" CLEAR #2 COPPER TIED TO REBAR TO GROUND BUS 6 7 15 11 14 6" 16 GRADE #4 BARS CONTINUOUS (TYPICAL) #4 BARS CONTINUOUS (TYPICAL) 6" GROUND ROD INSTALLATION 76" GROUND ROD INSTALLATION TOP VIEW 1 METER CONDUIT 6 2-WAY DUCT SECTION NOT TO SCALE SIDE VIEW 4" SECONDARY CONDUITS: (10) 3.5" PVC C. WITH 90^ LONG SWEEP TRANSFORMER PAD DETAIL NOTE: 1. PAD FOR 225 KVA 3 TRANSFORMER. VERIFY WITH MANUFACTURER'S DIMENSIONS. 5 TRANSFORMER PAD DETAIL NOT TO SCALE DEAD FRONT TRANSFORMERS METERING-CURRENT TRANSFORMERS SECURED TO SECONDARY SPADES. BY OWNER 3 KW/KWH METER IN WEATHER PROOF METER SOCKET WITH SHUNT BLOCKS. BY OWNER 4 METERING WIRING SHALL BE NEATLY LACED & SECURED TO TRANSFORMER CASE. BY OWNER 5 GROUNDING BUS 2" 2-way DUCT BANK SECTION NOTES: 1. DUCT BANK SHALL HAVE MINIMUM 2'. CLEARANCE AROUND DUCT BANK, AND BACKFILL OF NOT MORE THAN 12" SAND, THE REMAINDER IN CLAY. 2. THIS CONTRACTOR SHALL PROVIDE A PROTECTIVE BARRIER BENEATH ANY WATER PIPING. EXTEND 10' EITHER SIDE. 3. THIS CONTRACTOR SHALL VERIFY ALL UTILITY DEPTHS PRIOR TO DUCT BANK CONSTRUCTION. 4. DUCT BANK SHALL NOT CROSS WATER MAIN AT JOINT LOCATION. NOTES: SECONDARY SPADES. 2 4" 4-way duct bank section notes NOTES: 1. DUCT BANK SHALL HAVE MINIMUM 2'. CLEARANCE AROUND DUCT BANK, AND BACKFILL OF NOT MORE THAN 12" SAND, THE REMAINDER IN CLAY. 2. THIS CONTRACTOR SHALL PROVIDE A PROTECTIVE BARRIER BENEATH ANY WATER PIPING. EXTEND 10' EITHER SIDE. 3. THIS CONTRACTOR SHALL VERIFY ALL UTILITY DEPTHS PRIOR TO DUCT BANK CONSTRUCTION. 4. DUCT BANK SHALL NOT CROSS WATER MAIN AT JOINT LOCATION. 4-WAY DUCT SECTION 8" DRAWN BY: AFH 9 1' - 8" 1'-7-1/2" 4" #3 BARS (TYPICAL) 6" ELECTRICAL SITE PLAN 4 11 DSW 8" 6" 6" 1'-7-1/2" 6" 7-1/2" 6" 7-1/2" NOT TO SCALE 65" SHEET TITLE: 1 (TYP) #2 CU 15KV ABLE SELECT BACKFILL 4-5" PVC CONDUITS #3 BARS (TYPICAL) 6" 7 SECONDARY CONDUITS: (10) 3.5" PVC C. WITH 90^ LONG SWEEP 12" 48" THE CONTRACTOR SHALL SCHEDULE AND PERFORM THE WORK IN SUCH A MANNER THAT THE EXISTING ELECTRICAL DISTRIBUTION SYSTEM SHALL REMAIN IN SERVICE UNTIL THE NEW ADDITIONS & MODIFICATIONS TO THE ELECTRICAL DISTRIBUTION SYSTEM HAVE BEEN COMPLETED. iN GENERAL THIS MEANS THAT THE EXISTING FEEDERS SHALL FEED NORMALLY AND REMAIN IN SERVICE UNTIL THE NEW FEEDERS ARE INSTALLED. THE CONTRACTOR SHALL INSURE THAT ALL POWER INTERRUPTIONS, NECESSARY TO CUT OVER FROM THE EXISTING CIRCUIT TO THE NEW CIRCUIT, ARE KEPT TO A MINIMUM. ALL DUCT BANKS & CONCRETE PADS. INDICATED ON THE DRAWINGS SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR UNLESS SHOWN AND LABELED AS EXISTING ON THE DRAWINGS. ALL TRANSFORMERS TO BE FURNISHED AND INSTALLED BY AU FACILITIES. PRIMARY CONNECTIONS BY AU FACILITIES DISTRIBUTION DEPARTMENT. CONTRACTOR SHALL VERIFY EXACT LOCATIONS OF ALL MANHOLES, PRIMARY SWITCHES, TRANSFORMER PADS, PANELS, METERS, SURFACE MOUNTED CONDUITS AND ALL OTHER EXPOSED EQUIPMENT WITH THE UNIVERSITY ENGINEER BEFORE BEGINNING WORK. WHERE MATERIAL AND EQUIPMENT IS INDICATED TO BE REMOVED, THE CONTRACTOR SHALL DISPOSE OF SUCH REJECTED MATERIAL AND EQUIPMENT OFF THE OWNER'S PREMISES. THE SPECIFICATIONS REQUIRE THAT THE PRIMARY CABLE INSTALLATIONS BE GIVEN A HIGH POTENTIAL TEST PRIOR TO ACCEPTANCE BY THE OWNER. (SEE SPECS). THIS CONTRACTOR SHALL INSTALL DUCT BANK, PADMOUNT SWITCH PAD, AND TRANSFORMER PAD. COORDINATE WITH AU FACILITIES DISTRIBUTION DEPARTMENT BEFORE CONCRETE POURS. FOR OTHER UTILITIES SEE THE CIVIL SITE DRAWINGS. 3 PRIMARY CONDUIT 1" CHAMFER 2 @ 5" PVC CONDUITS GENERAL NOTES (applies to this sheet only): 3. PRIMARY COMPARTMENT 200A ELBOW GROUND LEVEL 2. A A.5 NOTES: 1. AU FACILITIES DISTRIBUTION DEPARTMENT TO FURNISH T-vb, AND MAKE CABLE CONNECTIONS TO TRANSFORMER. 2. CONTRACTOR TO PROVIDE CONCRETE PAD. 3. CONTRACTOR TO INSTALL AND TEST PRIMARY CABLES REMOVED BY AV FACILITIES DISTRIBUTION DEPARTMENT FROM PREVIOUS VIDEO BOARD SERVICES. 1. 8 ) AL NEW 2-WAY 5" DUCTBANK FOR FUTURE NORTH END PRIMARY. CAP AND MARK BELOW FINISHED GRADE. 1 8.9 0" LIGHTNING GROUND rod, BOND TO COLUMN with #3/0 stranded copper PPA-12,14,16 20A/3P provide ELECTRICAL CONNECTIONS FOR MOTORIZED ENTRY GATE as alternate. COORDINATE EXACT LOCATIOn AND EXACT REQUIREMENTS PRIOR TO ROUGH-IN H 5' 1 NEW SECONDARY wp e // 1 // 3#10,1#10g., 1"c PROVIDE NEW BREAKER IN AVAILABLE SPACE. NEW BREAKER TO MATCH EXISTING IN ALL ASPECTS, 10,000 AIC. E1.0 EXISTING 'VS' switch to type 'd2' lights. see 1/e2.1. EXISTING 'VS' 2-16-2015 205-251-4500 // e // EXISTING MISCELLANEOUS CONDUITS RUNNING EAST-WEST 3 NEW MAIN BREAKER 'MB-VB' // EXISTING CONTROL WIRING TO SOUTH MAIN ELECTRICAL ROOM pe# 20753 LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 // // 10.9 EXISTING PRIMARY conductors removed by auburn utilities to be reused UNDER THIS CONTRACT to feed TRANSFORMER 'T-VB'. see riser diagram EXISTING SWITCHGEAR EXISTING CONTROL WIRING. CONDUITS FOR 'VS' CABINETS. COORDINATE SECONDARY CONDUITS WITH EXISTING CONDUITS BELOW GRADE. RE-ROUTE CONTROL CONDUITS AS NECESSARY TO A ACCOMMODATE NEW SECONDARY. LBYD Project No: 101-14-054.002 LIGHTNING GROUND rod, BOND TO COLUMN with # 3/0 stranded copper LIGHTNING GROUND, BOND TO COLUMN, FENCE, AND 'MB-Vb' SERVICE GROUND. EXISTING XFMR "TRN-215"and switchboard DEMOLISHED by others. e // // // 1 AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 2 e 4 6 LOAD BREAK ELBOW PARKING STANDS. 7 9KV, MOV LIGHTING ARRESTER/ LOAD ELBOW. 8 PRIMARY FUSING. 9 TRANSFORMER GROUND ROD - 3/4" x 10'-0". 10 PRIMARY TAP CHANGER. DATE: 2-11-2015 11 GROUND PAD. FILE NUMBER: 12 OIL COVER GAUGE. 13 THERMOMETER-DIM TYPE. 14 OIL DRAIN. 15 GROUND WIRE. 16 CONCRETE PAD, 8" THICK, 4" ABOVE GRADE WITH TWO (2) LAYERS 8x8 WIREWAY REINFORCING. PADMOUNT TRANSFORMER DETAIL NOT TO SCALE CHECKED BY: CDC PROJECT NUMBER: AU #14-286 SHEET NUMBER: E2.0 A.5 A.5 7 Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. 7 A A A J 7 A.5 No. (2) 1"c A 8 A (2) 1"c 8.9 8.9 J 8.9 Date 02-11-15 02-17-15 8 J 8 1 Revision BID SET Addendum 1 H B BE H D B BE H D B BE D (2) 1"c WP B VIDEOBOARD CONTROL PANEL (2) 1"c 'SB-VB' CONDUITS (2) 1"c to panel 'hvb3' for future use 1 PULLBOX for conduit routed to 100a/3p/nf/wp disconnect 11.1 (2) 1"c C 11.1 UP DN C 'SB-VB' CONDUITS J 11.1 for stair lights. route vertical portion of branch circuit up column c-11.9 (typical all levels). 1 11.9 11.9 C locate switch adjacent to door from stadium 2#10,1#10G., ["C. (ENTIRE CIRCUIT) 3 WP 11.9 EMHS-8 CONNECT TO EXISTING 20A/1P BREAKER. C J DN UP WP 2-16-2015 205-251-4500 2#10,1#10G., ["C. (ENTIRE CIRCUIT) pe# 20753 10.9 LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 10.9 LBYD Project No: 101-14-054.002 SPD (WEATHERPROOF) GROUND BAR B UP 10.9 'SB-VB' (DISTRIBUTION SECTION) FRONT LVB3- 4 J PULLBOX 'SB-VB' (PULL SECTION) 12.9 12.9 A 12.9 CONTROLS/VERIZON CONDUITS CONTROLS/VERIZON CONDUITS J CONTROLS/VERIZON CONDUITS WP A J (2) 1"c AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 (2) 1"c (2) 1"c 15 15 A 15 J SHEET TITLE: LEVEL 5 & GIRT LEVEL 1 & 2 ELECTRICAL PLANS (2) 1"c 16 16 A 16 J DRAWN BY: AFH CHECKED BY: CDC located at girt level 1 for future accent up lighting for rear facade. see e1.0 (typical 10 locations) DATE: 2-11-2015 FILE NUMBER: PROJECT NUMBER: AU #14-286 17 3 NORTH 17 GIRT LEVEL 2 2 1/8" = 1'-0" NORTH 17 GIRT LEVEL 1 1 1/8" = 1'-0" NORTH LEVEL 5 1/8" = 1'-0" SHEET NUMBER: E2.2 A.5 A.5 7 A.5 7 7 A J A Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. A No. (2) 1"C. 1 8 8 A 8 A Date 02-11-15 02-17-15 J A Revision BID SET Addendum 1 (2) 1"C. TO HVB3 A A 8.9 A 8.9 J 8.9 H B BE H D B BE H D B BE A (2) 1"C. WP WP 9KVA XFMR SUPPORT FROM STRUCTURE WP B D B 1 2#10,1#10G., ["C. (ENTIRE CIRCUIT) CONTROL PANEL BY OTHERS. J 600A/3P/NF/WP LVB3- 2 B 11.1 UP (2) 1"C. TO HVB3 C 11.9 WP A 11.9 WP UP 1 DN J DN UP 11.9 (2) 1"C. A 1 C C 1 C 12.9 A 12.9 WP CONTROLS/VERIZON CONDUITS 12.9 C WP CONTROLS/VERIZON CONDUITS WP J WP CONTROLS/VERIZON CONDUITS (2) 1"C. TO HVB3 LVB3- 1 2#10,1#10G., ["C. (ENTIRE CIRCUIT) (2) 1"C. WP WP A WP A J A 15 15 A 15 A AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 2#10,1#10G., ["C. (ENTIRE CIRCUIT) 205-251-4500 2#10,1#10G., ["C. (ENTIRE CIRCUIT) DN C 2-16-2015 LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 2#10,1#10G., ["C. (ENTIRE CIRCUIT) 11.1 LVB3- 9 pe# 20753 10.9 LBYD Project No: 101-14-054.002 10.9 J 11.1 HVB3 LVB3- 8 (2) 1"C. TO HVB3 A 10.9 LVB3 B LVB3- 6 A (2) 1"C. TO HVB3 J SHEET TITLE: GIRT LEVEL 3-5 ELECTRICAL PLAN (2) 1"C. 16 16 A 16 A A DRAWN BY: AFH CHECKED BY: CDC J DATE: 2-11-2015 FILE NUMBER: PROJECT NUMBER: AU #14-286 17 3 NORTH 17 GIRT LEVEL 5 2 1/8" = 1'-0" NORTH 17 GIRT LEVEL 4 1 1/8" = 1'-0" NORTH GIRT LEVEL 3 1/8" = 1'-0" SHEET NUMBER: E2.3 A.5 A.5 A.5 7 7 7 A J A Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. A No. (2) 1"c 1 8 A 8 8.9 A 8.9 J 8 Revision BID SET Addendum 1 Date 02-11-15 02-17-15 A (2) 1"c A J 8.9 H B BE H D B BE D H B BE A (2) 1"c WP D WP B CONTROL PANEL BY OTHERS. J LVB8- 7 (2) 1"c 600A/3P/NF/WP B 2#10,1#10G., ["C. (ENTIRE CIRCUIT) 11.1 J 11.1 11.1 UP DN C UP DN C DN UP 11.9 11.9 1 A C 11.9 2-16-2015 LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 (2) 1"c to panel 'hvb3' for future use pe# 20753 10.9 A 2#10,1#10G., ["C. (ENTIRE CIRCUIT) LBYD Project No: 101-14-054.002 10.9 10.9 205-251-4500 LVB8- 6 WP J (2) 1"c (2) 1"c 1 12.9 12.9 WP 12.9 C A CONTROLS/VERIZON CONDUITS CONTROLS/VERIZON CONDUITS J CONTROLS/VERIZON CONDUITS WP WP A A J (2) 1"c AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 C UP TO SPEAKER BOX LEVEL 1 (2) 1"c 15 15 15 A A J SHEET TITLE: GIRT LEVEL 6-8 ELECTRICAL PLAN (2) 1"c 16 16 16 A A J DRAWN BY: AFH CHECKED BY: CDC located JUST BELOW SPEAKER BOX LEVEL 1 FOR future accent DOWN lighting for rear facade. see e1.0 (typical 10 locations) DATE: 2-11-2015 FILE NUMBER: 17 17 3 NORTH GIRT LEVEL 8 2 1/8" = 1'-0" NORTH 17 GIRT LEVEL 7 1 1/8" = 1'-0" NORTH GIRT LEVEL 6 1/8" = 1'-0" PROJECT NUMBER: AU #14-286 SHEET NUMBER: E2.4 NEW PANEL: LVB8 VOLTAGE: 120/208 Wye PHASES: 3 BUS SIZE: 100 A CKT FAULT DUTY: CIRCUIT DESCRIPTION TRIP NOTE POLE 1 CAMERA OUTLET 20 A 2 1 3 CAMERA OUTLET 20 A 2 1 5 SpkBOX EGRESS LIGHTING 20 A 2 1 7 GIRT LVL 6 LTG 20 A 1 1 9 Spare 20 A 1 1 11 SPKBOX LVL 2 LIGHTING 20 A 1 1 13 SPKBOX LVL 3 LIGHTING 20 A 1 1 15 FLAG POLE LIGHTS 20 A 1 1 17 Spare 20 A 2 1 19 Spare 20 A 2 1 21 Spare 20 A 2 1 23 Spare 20 A 2 1 Connected Load 10,000 4 B 1.0 C POLE 1.0 1.0 1.0 0.0 0.8 0.8 1.0 0.0 0.8 1.2 1.2 1.2 1.0 0.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.0 kVA MLO 3.0 kVA 0.0 NOTE CIRCUIT DESCRIPTION 125.00% 9.0 kVA Miscellaneous 5.0 kVA 100.00% 5.0 kVA VOLTAGE: 120/208 Wye BUSSING 2500 A CKT 1 2 20 A FIREWORKS OUTLET 2 2 20 A FIREWORKS OUTLET 4 CKT POLE FRAME # TRIP 3 PHASE 4 WIRE MAIN: FAULT DUTY NOTE 2500 A / 3P MLO 65,000 AIC dESCRIPTION LTG REC 10.4 2.2 1 1 20 A GIRT LVL 7 LTG 6 1 1 20 A SPKBOX LVL 1 LIGHTING 8 1 3 100 100 PANEL LVb3 & lvb8 10 2 3 600 600 GIRT LEVEL 4 DISCONNECT MTR A/C HTG KIT MISC Load 5.0 17.3 200.0 200.0 1 1 20 A SPKBOX LVL 1 LIGHTING 1 1 20 A SPKBOX LVL 4 LIGHTING 12 3 3 600 600 GIRT LEVEL 6 DISCONNECT 200.0 200.0 1 2 20 A SPKBOX REC 14 4 3 600 600 VIDEO CONTROL PANEL 200.0 200.0 1 1 20 A Spare 16 5 3 400 400 SPEAKER BOX 1 DISCONNECT 1 1 20 A Spare 18 6 3 600 -- SPACE 0.0 7 3 100 -- SPACE 0.0 8 3 400 -- SPACE 0.0 1 1 20 A Spare 20 1 1 20 A Spare 22 1 1 20 A Spare 24 3.2 kVA 7.2 kVA 0.00% TRIP 1 Demand Factor Estimated Demand 0.0 kVA SWITCHBOARD: SB-VB MOUNTING: Surface Lighting Other MAIN: 100 A AIC A TOTAL LOAD: Load Classification WIRES: Panel Totals 9 3 225 -- 10 3 100 100 Load Classification Lighting Total Connected kVA: 12.2 kVA 0.0 kVA Miscellaneous Total Estimated kVA: 14.0 kVA 100.0 SPACE 0.0 SPD 0.0 1 Connected Load Demand Factor Estimated Demand 10.4 kVA 125.00% 13.0 kVA 100.00% 705.0 kVA Total Conn. Load: 717.5 kVA Total Est. Demand: 720.1 kVA Other 0.0 kVA 0.00% 0.0 kVA Total Estimated Demand Amps: 39 A Power 0.0 kVA 0.00% 0.0 kVA 2.2 kVA 100.00% 2.2 kVA No. 1 Revision BID SET Addendum 1 Date 02-11-15 02-17-15 Panel Totals 705.0 kVA Total Connected Amps: 34 A Receptacle 100.0 Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-9450 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. Total Conn.: 1992 A Total Est. Demand: 1999 A Notes: Notes: 1. remote controlled breaker 2. non-controlled breaker 1. CONFIRM BREAKER SIZE WITH SURGE PROTECTION DEVICE MANUFACTURER. LOCATE BREAKER NEAREST NEUTRAL AND GROUND TERMINALS. nema 3r intelligent panelboard per section 26 24 50. provide interface with jci. nema 3r 1 NEW PANEL: HVB3 CIRCUIT DESCRIPTION TRIP NOTE POLE 1 spare 20 A 1 1 3 SPARE 20 A 1 1 5 SPARE 20 A 1 1 7 UTILITY YARD LIGHTING 20 A 2 1 9 illuminated lettering/logo 20 A 1 1 11 illuminated lettering/logo 20 A 1 1 13 illuminated lettering/logo 20 A 1 1 15 illuminated lettering/logo 20 A 1 1 17 illuminated lettering/logo 20 A 1 1 19 Spare 20 A 1 1 21 Spare 20 A 1 1 23 Spare 20 A 1 1 25 Space -- -- 27 Space -- -- 29 Space -- -- 0.0 Connected Load 4 MAIN: 100 A AIC A C POLE 0.0 0.0 0.0 0.7 0.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 0.0 3.0 3.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 12.7 kVA MLO MOUNTING: Surface B 0.0 TOTAL LOAD: Load Classification 14,000 12.0 kVA 0.0 NOTE TRIP CIRCUIT DESCRIPTION CKT 1 1 20 A SPARE 2 1 1 20 A SPARE 4 1 1 20 A SPARE 6 1 1 20 A illuminated lettering/logo 8 1 1 20 A illuminated lettering/logo 10 1 1 20 A illuminated lettering/logo 12 1 1 20 A illuminated lettering/logo 14 1 1 20 A illuminated lettering/logo 16 1 1 20 A illuminated lettering/logo 18 1 1 20 A illuminated lettering/logo 20 1 1 20 A Spare 22 1 1 20 A Spare 24 1 1 26 20 A Spare -- -- Space 28 -- -- Space 30 pe# 20753 12.0 kVA Demand Factor Estimated Demand Panel Totals Lighting 0.2 kVA 125.00% 0.3 kVA Miscellaneous 36.5 kVA 100.00% 36.5 kVA Total Connected kVA: 36.7 kVA Other 0.0 kVA 0.00% 0.0 kVA Total Estimated kVA: 36.8 kVA 2-16-2015 205-251-4500 CKT WIRES: FAULT DUTY: LBYD, Inc. 716 South 30th Street Birmingham, AL 35233 PHASES: 3 BUS SIZE: 100 A LBYD Project No: 101-14-054.002 VOLTAGE: 480/277 Wye Total Connected Amps: 44 A Total Estimated Demand Amps: 44 A Notes: 1. remote controlled breaker 2. non-controlled breaker intelligent panelboard per section 26 24 50. provide interface with jci. NEW PANEL: LVB3 VOLTAGE: 120/208 Wye PHASES: 3 BUS SIZE: 100 A CKT WIRES: FAULT DUTY: CIRCUIT DESCRIPTION TRIP NOTE POLE 1 WEATHERPROOF REC 20 A 2 1 3 spare 20 A 2 1 5 spare 20 A 2 1 7 spare 20 A 2 1 9 GIRT LVL 5 LTG 20 A 1 1 11 Spare 20 A 1 1 13 Spare 20 A 1 1 15 Spare 20 A 2 1 17 Spare 20 A 2 1 TOTAL LOAD: Load Classification 1 Connected Load Lighting Other Receptacle 22,000 4 MAIN: 100 A AIC A MOUNTING: Surface B 1.1 C 1.1 0.0 0.8 0.0 0.0 0.0 0.0 0.0 0.8 0.8 0.8 0.0 0.0 0.0 0.0 0.0 3.0 kVA MLO 1.6 kVA 3.2 kVA 125.00% 4.0 kVA 0.00% 0.0 kVA 2.2 kVA 100.00% 2.2 kVA POLE NOTE TRIP CIRCUIT DESCRIPTION CKT 1 2 20 A WEATHERPROOF REC 2 1 1 20 A GIRT LVL 2 LTG 4 1 1 20 A GIRT LVL 3 LTG 6 1 1 20 A GIRT LVL 4 LTG 8 1 1 20 A Spare 10 1 1 20 A Spare 12 1 1 20 A Spare 14 1 1 20 A Spare 16 1 1 20 A Spare 18 0.8 kVA Demand Factor Estimated Demand 0.0 kVA 0.0 FEED THRU LUGS to feed 'lvb8' Panel Totals Total Connected kVA: 5.4 kVA Total Estimated kVA: 6.2 kVA Total Connected Amps: 15 A AUBURN UNIVERSITY JORDAN-HARE STADIUM SOUTH ENDZONE SCOREBOARD REPLACEMENT A.U. #14-286 nema 3r Total Estimated Demand Amps: 17 A Notes: 1. remote controlled breaker 2. non-controlled breaker intelligent panelboard per section 26 24 50. provide interface with jci. nema 3r SHEET TITLE: ELECTRICAL SCHEDULES DRAWN BY: AFH CHECKED BY: CDC DATE: 2-11-2015 FILE NUMBER: PROJECT NUMBER: AU #14-286 SHEET NUMBER: E6.1