Transcript
Models BMPlus 3000/5000/7000 Rev. B Leave this bulletin on the job site for future reference! The BMPlus Zone Control System allows you to easily upgrade an inefficient single zone HVAC system, into a Multi-zone, Energy savings, Comfort producing, HVAC system. The Superior Design, Intuitive Firmware, Simple Setup Options, Easy to Understand wiring and Backwards Compatibility, makes the BMPlus Zoning system the Contractors dream. Combined with EWC Motorized Dampers and Any off-the-shelf Thermostats, EWC Controls sets a another high standard in the residential & light commercial Forced Air Zoning Industry. The main module controls three zones Zone using motorized dampers and may be Capacity expanded up to 5, or 7 zones, using 1 or 2 XM2 Expansion Modules. Compatible Controls 2 stage conventional or dual fuel heat pumps, without the need for dual fuel HVAC kits. Also single or two-stage gas, oil, & Systems hydronic heating systems, with single or two stage air conditioning. Constant or variable speed fan systems. Not compatible with 2 speed / 2 stage compressor heat pumps. (3 stage heat pumps).
Compatible Compatible with any off the shelf Thermostats H e a t P u m p T h e r m o s t a t (2heat/1cool). You may also use any regular Heat/Cool thermostat (1heat/1cool). You may still use regular Heat/Cool thermostats to control a Heat Pump system.
Automatic Heat/Cool Changeover
The BMPlus Zone system features automatic changeover from any thermostat allowing for individual zone comfort from the HVAC system.
Status LED
The STATUS LED pulses as a steady heart beat to indicate active Microprocessor status.
System LEDs
On board LED’s illuminate to indicate HVAC system mode, system status, active and inactive zone identification. See page 10 for details.
Damper LEDs
LEDs labeled Zone 1 thru Zone 7 indicate which dampers are energized open.
Operating Power
All modules operate on 24vac power supplied from a separate transformer. A single 40va transformer can power up to 7 zones with a total of 7 ND/URD dampers directly connected. See page 9 for details.
TB-228
J1
CONTROL SYSTEM 14
ZONE3 MOTOR
43
40
28
34
42
OFF
46
52
2 ND STAGE TIMER OAS R2
19
26
40
R 36 R 37 R 38 R 39 R 41
47
C15
SAS
R 43
U3
R14
SAS
R 42
DIFFERENTIAL
R4
C7 C8
R15 R16
D10 D11 D12 D13
33
2 ND STAGE HEAT
HIGH TEMP LIMIT R3
C5
K1
150
160 12 170 5
110
LOW TEMP LIMIT
R1
140
130
49 120
35 37
7
M6 M4 M2 M1
D 21
OAS
R 40 R 82
OAS
R 81
ZONE2 MOTOR
D1
R44
U2
U1
R45
K2
M6 M4 M2 M1
C10
RESET
ZONE3 T STAT
C W/E O/B Y R G
R 46
U4
R 47
C11 D2
R 48
R13
R 49
K3
C12 R 50
ZONE1 MOTOR
U9
M6 M4 M2 M1
F1
D4
+
D3
R 51 C13
C14
Y1
R 52 R 53
U5
+
R 79
ZONE3 T STAT
C W/E O/B Y R G
R 78 C1
C2
SW 3
K4
24 VAC T’FORMER
R D5
C
K5
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
R 54 R 55 R 66 C9
R 22
K 6 R 23
R 59 R 60
LED 1
STATUS
LED 2
OAS
LED 3
SAS
LED 4
ZONE 3
LED 5
ZONE 2
LED 6
ZONE 1
R 24 R 25 D7
W1 B W2 E RH RC C
K7
R 26 R 27 R 28 R 29
D8
K8
R 30
R 33
EWC
D9
LED 7
FAN
LED 8
Y2
LED 9
Y1
R 31 R 32
RC RH LINK
R 57 R 58
R 35
R 21 D6
R 56
U6
Z1
R 19 R 20
SYSTEM
G Y2 Y1 O
ZONE1 T STAT
R 62
U7
R 63 R 71 R 64 R 65 R 68
C W/E O/B Y R G ONE ZONE
R 67
U8
R 69
EM
R 70 R 73
LED 10
W1
B
LED 11
W2
EM
R 34
R 61
BMPlus3000B
R 72 R 77
NORM
R 76
SW 4
Figure 1
Contents
* BMPlus 3000 Control Panel * Supply Air Sensor * Technical Bulletin TB228 * Mounting Hardware
Thermal Circuit Breaker
The BMPlus module has a Thermal circuit breaker that protects the module(s) from shorts in the damper and thermostat field wiring. It will not protect against shorts in the HVAC system wiring.
CAUTION: When the circuit breaker is tripped it will get quite hot. To reset the breaker: Shut off power to the panel. Find and repair the short. Restore the 24VAC power. Any zone can activate the indoor fan and only the dampers in zones calling for continuous fan operation will open. Continuous fan operation will only occur when there are no active or pending, heat or cool demands. A dip switch is provided to enable automatic fan operation in heat mode. Useful for straight electric heat or hydronic heat applications. Fan operation is seamless and occurs without interruption from Cool to Heat mode. 1 FAX 732-446-5362 E-Mail-
[email protected]
Indoor Fan Control
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 P/N 090375A0228 9 November 2007 REV. B
21
Copyright © 2007 EWC Controls All Rights Reserved
BMPlus 3000 FIRMWARE/HARDWARE FEATURES The panel has seven built-in Delay Timers that insure safe & reliable operation.
*Built-In Timer Settings
* Start-up Delay Timer = 3 minutes-fixed * Short Cycle Timer = 3 minutes-fixed * Change Over Timer = 4 minutes-fixed * Opposing Call Timer = 20minutes-fixed * 2nd Stage Timer = OFF, 7-42 min. -Adj. * Supply Air Limit Timer = 3minutes-fixed * Purge Delay Timer = 90 seconds-fixed
*Startup Delay Timer
The panel will not activate a cooling or heating operation until the startup delay has expired. This occurs after any initial power up, after any power failure or after pressing the Reset button for 7 seconds.
*Short Cycle Timer
When the system is satisfied, the panel will not resume the same mode for a minimum of 3 minutes.
*Changeover Timer
*Opposing Call Delay Timer
A 20 minute delay must expire, or the active zone(s) must satisfy, before the panel will honor a thermostat demand to changeover to the opposite mode of system operation.
*2nd Stage Timer / OAS
The 2nd STAGE TIMER sets the amount of continuous call time in 1st stage, before second stage heat or cool is energized. NOTE: The potentiometer also serves as the 2nd stage Heat Outside Air Changeover Setting.
14 7
21
28 35 42
OFF 2nd STAGE Timer / OAS
OFF, 7 to 42 minutes or 7 to 42 degrees F. Any setting below 7 is off! DO NOT set to off if using OAS
*Supply Air Limit Delay Timer
*Purge Delay Timer 2
A built-in timer prevents the system from rapidly switching between heating and cooling modes. At the end of a call, a 4 minute timer is started and the panel will not switch to the opposing mode until the timer has expired.
The BMPlus 3000 can inhibit 2nd stage heat based on a Timer or Outside Air Temperature. NOTE: An Optional OAS Sensor is required to use the OAS feature. NOTE: 2nd stage cool delay defaults to 15 minutes, if OAS is chosen to inhibit 2nd stage Heat. The time delay of 3 minutes must expire before the BMPlus 3000 will re-energize heat or cool mode. This occurs when the processor detects the supply air temperature is higher or lower than the High or Low temperature limit settings. The last Damper(s) will be held Open for 90 seconds at the end of every call allowing a system purge into the last zone that was calling.
Cooling and Heating Limit Controls 43
40
46 49
37
34 52 LOW TEMP LIMIT
130
140
150 160
120
170 110 HIGH TEMP LIMIT
19
26
33 40
12 5
47
2nd STAGE HEAT DIFFERENTIAL
Example: Hi Temp. Limit =130°F plus 2nd stg. DT= 40°F New Limit = 170°F.
Reset BUTTON
RESET Always reset the CPU anytime you make dip-switch changes to the BMP3000 panel! DO NOT use a sharp object to press the button! Your finger tip will work fine.
The Adjustable Cooling Limit potentiometer sets the supply air temperature at which the cooling is cycled off and the fan continues to run, allowing the coil to warm up. The Adjustable Heating Limit potentiometer sets the 1st stage heat supply air temperature, at which the heating is cycled off and the fan continues to run, allowing the heat exchanger or coil to cool down. The Adjustable 2nd stage heat differential potentiometer sets the 2nd stage heat supply air temperature, at which the heating is cycled off and the fan continues to run, allowing the heat exchanger or coil to cool down. NOTE: Allows the supply air sensor to be installed in the supply air plenum, regardless of the coil/heat exchanger configuration. Allows the installer to fine tune virtually any 2 stage heating system! The separate reset buttons on the old BMP3000 have been replaced by a single button with dual functions. Momentarily pressing the RESET button clears the built-in timers controlling the Startup delay timer, Short cycle timer, W2 timer, Supply air sensor timer and the Changeover timer. This enables you to test the installation faster. Caution should be observed when using this button.
Pressing the RESET button for 7 seconds will reset the CPU for the entire zone system.
Emergency Heat Switch
An On-Board Switch is provided that allows the Customer to set the system to the Emergency heat mode.
EM
This switch is shown in the NORMAL position.
NORM
This switch would be used for Heat Pump applications where the Customer chooses to use Regular Heat/Cool thermostats instead of Heat Pump thermostats.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
Selecting the Options Using the DIP Switches ***FS = Factory Settings
RECORD YOUR OWN DIP SWITCH SETTINGS HERE
ON
1
Programming and setting up the BMPlus 3000 to control your HVAC system is very easy! Look below for an explanation of each dip switch function and choose your settings. Some functions may not apply to your application. Then use a pencil to mark/record your settings. If the settings get changed later on, you will have a record of the original settings.
2 3 4 5 6 7 8
HP < SYSTEM > GAS FS DF < HP > CONV FS FS HC < TSTATS > HP FS O < RV > B OAS < 2nd STAGE > TIMER FS FS OFF < 50%RULE > ON FS OFF < SAS > ON FS GAS < FAN > HYDRONIC
HP < SYSTEM > GAS Choose the type of HVAC system you want to control. Select HP, if your system is any type of heat pump. Select GAS, if your system is a standard Gas or Oil furnace. Also applies to straight electric furnaces or hydronic (hot water coil) heating systems. NOTE: If HP is selected at dip switch 1, Y2 is not available. Y2 is only available in GAS mode.
DF < HP > CONV Choose the type of Heat Pump you want to control. Select DF, if your system is a dual fuel heat pump with gas or oil furnace backup heat. Select CONV, if your system is a conventional heat pump with electric resistance backup heat. Also applies to Ground source/Geothermal heat pumps.
HC < TSTATS > HP Select HC, if you want to use regular Heat/Cool thermostats on your job. Select HP, if you want to use Heat Pump thermostats on your job. Remember that you can use standard HC T-stats on a Heat Pump application. IMPORTANT NOTE: The BMPlus 3000 Zone Control System allows Heat Pump thermostats to be connected to all zones. When doing so, make sure you turn the 2nd stage timer to the “OFF” position. Using heat pump thermostats means that the zone panel will obey thermostatic demands and ignore Timer operations. This comfort over-ride feature provides a level of versatility to your zoning system and gives the homeowner comfort control over the system, instead of waiting for the adjustable timer to energize 2nd stage heat.
O < RV > B Select the correct Reversing Valve signal for your particular Heat Pump. Choose “O” for any heat pump that energizes the RV in the cooling mode. Choose “B” for any heat pump that energizes the RV in heating mode.
OAS < 2nd STAGE > TIMER Select OAS, if you want to delay 2nd stage heat based on the outside air temperature sensor. Select TIMER, if you want to delay 2nd stage heat & cool based on the adjustable on-board timer. NOTE: 2nd stage cool defaults to a 15 minute delay, when OAS is chosen. NOTE: An optional Outside Air Sensor (OAS) is required to use the OAS feature.
OFF < 50%RULE > ON Select OFF, if you do not want to inhibit 2nd stage heat/cool based on the total number of zones calling. Select ON, if you want to inhibit 2nd stage heat/cool based on the total number of zones calling. More than half the total zones must be calling for the same mode, or 2nd stage will not activate. If DF or OAS has been selected, the 50% rule will apply to cooling operations only. 2nd stage heat will not be affected. The 50% rule will always dominate the 2nd stage timer or thermostat demands unless Emergency mode is active.
OFF < SAS > ON
Select OFF, if you do not want to use the supply air sensor included with the BMPlus Zone Control system. Select ON, if you intend to use the included supply air sensor. Refer to the data sheet included with the supply air sensor for details.
GAS < FAN > HYDRONIC Select GAS, if your HVAC system is a gas or oil forced air furnace. Select HYDRONIC, if your HVAC system has a hot water coil, or straight electric heat with no indoor blower support. Useful when you need the indoor blower to run automatically in heat mode, just like it does in cool mode. NOTE: When you select HP on dip switch #1, the indoor fan mode is automatically set for you. There is no need to move this switch when setting up for Heat Pump operations. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
3
INSTALLATION & WIRING INSTRUCTIONS WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE. ALL WORK SHOULD BE PERFORMED TO LOCAL AND NATIONAL CODES AND ORDINANCES. USE 18 AWG SOLID COPPER, COLOR-CODED, MULTI-CONDUCTOR THERMOSTAT CABLE. Mount the panel housing in a suitable/convenient location. Mounting hardware is provided. Avoid locations that may become wet or produce condensation. Hot attics are OK. Use the knockouts on the panel housing as wire entryways. Strain relief fittings can be used if desired. Use care and do not damage the circuit board when removing the knockouts and making wire connections. NOTE: The 24vac power supply should be supplied by a separate transformer. DO NOT use the 24vac power supply from the HVAC system unless there is no other alternative. 2 zones and 2 dampers is the limit when stealing voltage from the HVAC system.
POWER WIRING
A single 24vac, 40va Line UL Listed transformer Voltage PROVIDE 24 VAC MEANS OF can power the DISCONNECT T’FORMER BMPlus3000 Main module with up to 7 R genuine ND or URD dampers. See page 9 C for more load and transformer data. TRANSFORMER R - Hot 24vac, 40 - 100va C - Common UL LISTED Figure 2 BMPlus 3000 Power wiring
Thermostat Wiring
HEAT PUMP THERMOSTATS
BMPlus 3000 Main Module
HEAT/COOL THERMOSTATS
TYPICAL HEAT PUMP THERMOSTAT 68
HEAT
ZONE1 T’STAT
C
E
C
W
B
O
Y
R
G
*
W/E O/B Y R G ONE ZONE
* Field jumper is necessary TYPICAL THERMOSTAT 68
HEAT
ZONE1 T’STAT
Figure 2c.
W
Y
R
G
C W/E O/B
The BMPlus will accept heat pump style thermostats in all zones. This allows you to energize 2nd stage heat thermostatically instead of through the W2 timer. Also, Emergency heat can be activated from any zone.
NOTE: The New BMPlus 3000 allows the user to install Heat Pump thermostats on all zones. This allows the user to turn off the W2 Timer and energize the auxiliary heat via thermostatic demand! You may still use regular Heat/Cool type thermostats with a Heat Pump system and use the W2 Timer to energize the auxiliary heat. Doing so may save more energy. This new design simplifies the thermostat selection process and allows the installer to easily adapt the BMPlus 3000 to any residential applications.
Y R G ONE ZONE
Figure 2a. Typical Battery or Power Robbing type Heat/Cool thermostat wiring in any Zone.
TYPICAL HEAT PUMP THERMOSTAT HEAT
TYPICAL THERMOSTAT 68
HEAT
ZONE2 T’STAT
C
W
Y
R
G
Y
R
G
W/E O/B
W/E O/B
Y
Y
R G
R G
4
W2/E O/B
C
C
Figure 2b.
C
ZONE2 T’STAT
68
* Typical Hard Wired Heat/Cool type thermostat wiring in any Zone.
Figure 2d.
Common wire may not be required on your thermostat.
Typical Heat Pump thermostat wiring in zone 2 or higher. Note that your thermostat may not have a common wire connection.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
THERMOSTAT WIRING CONTINUED WIRING FOR RADIANT FLOOR HEAT
WIRING FOR “ONE ZONE” MODE
ZONE THERMOSTAT 68
HEAT
ZONE2 T’STAT
C
Y
W2
RC RH
ZONE THERMOSTAT G
W1
68
HEAT
ZONE1 T’STAT
C W/E O/B
W
Y
R
G
C W/E O/B
Y R G
Y R G
SPST 24vac Isolation Relay
ONE ZONE
Optional ONE ZONE SWITCH
LED To Radiant floor / Baseboard heat zone valve or pump relay
Figure 3
Wiring for a Radiant floor loop as the first stage of heat via the isolation relay and 2nd stage Forced Air heat is controlled through the zone panel.
Figure 5
Wiring for manual activation of “One Zone” mode using a standard heat/cool thermostat in Zone1. An Optional, Illuminated One Zone Mode Switch, Part# “VAC” is required.
WIRING FOR “ONE ZONE” MODE
WIRING FOR RADIANT FLOOR HEAT
ZONE THERMOSTAT
ZONE2 T’STAT
C
Y
COMMERCIAL GRADE HEAT PUMP THERMOSTAT
68
HEAT
RC
G
RH
W
68
HEAT
ZONE1 T’STAT
C
C
W/E
O
Y
R
G
UNOCC/OCC
C
W/E O/B
W/E O/B
Y
Y
R G
R G ONE ZONE
To Radiant floor / Baseboard heat zone valve or pump relay
Figure 4
Figure 6
Wiring a split circuit thermostat to operate a Radiant floor heating or Baseboard heating Hydronic system. The BMPlus 3000 controls the cooling only, in this type of configuration.
Wiring for automatic activation of “One Zone” mode using a commercial grade thermostat in Zone 1. Program or wire the thermostat to Energize (close contact) the One Zone Terminal and setback the temperature when the building is Unoccupied....When the building is Occupied, the thermostat will de-energize (open contact) the One Zone Terminal.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
5
SYSTEM WIRING Single Transformer Gas or Electric Furnace & A/C 1 or 2 Stage Heat
Typical gas or Electric Furnace with A/C. Note the common “C” wire is connected to the SYSTEM terminal block of the BMPlus 3000.
Conventional 1 stage Heat Pump with O or B Type Reversing Valve *
Typical heat pump system wiring with electric resistance backup heat. Wire up the reversing valve to either “O” or “W1/B”, depending on your type of system. Applies to air cooled or geothermal / ground source systems.
BMPlus 3000
OUTDOOR CONDENSING UNIT
GAS or Electric Furnace 1or2 STAGE
Y C
SYSTEM
G Y2
G Y
Y1 O
W1 W2
W1/B W2/E RH
R C
SYSTEM
G
G Y2
Y O/B
Y O/B
Y1 O
X/W R
W1 W2
C
R C
HEAT PUMP 1 STAGE
RC C
To make troubleshooting easier, connect the “C” Common from the Furnace to the BMPlus. If you don’t connect it, it’s OK.
BMPlus 3000 AIR HANDLER WITH 1 0R 2 STAGE ELECTRIC RESISTANCE BACKUP HEAT
*
W1/B W2/E RH RC C
RC/RH LINK
Figure 7 Single transformer HVAC system.
* Connect either the O or the W1/B. In a typical O type system, there will not be a connection to the W1/B terminal.
RC/RH LINK
Figure 9 Conventional Heat Pump System Wiring diagram for a typical oil burner, hydronic zone / Air handler with A/C. Cut the Rc / Rh link on the BMPlus Panel for systems requiring isolation.
Two Transformer Systems
TYPICAL FAN CENTER TERMINAL BLOCK OUTDOOR CONDENSING UNIT
Y C
*
ISOLATION TERMINALS OR WIRES
OR
BMPlus 3000
SYSTEM
G Y
Y1 O
W R C
W1/B W2/E RH
T
RC C
GAS/OIL Furnace 1or2 STAGE
SYSTEM
G
G Y2
Y O/B
Y O/B
Y1 O
X/W R
W1 W2
C
R C
W1/B W2/E RH
HEAT PUMP 1 STAGE
RC/RH LINK
T
RC C RC/RH LINK
T
Boiler Control OR Zone Valve Control OR Circulator Control
You may need to Cut the RC/RH Link
Figure 8 Two transformer Oil or Hydronic / A/C system. * Note: Your Air Handler may include a W terminal. That means it may have it’s own isolation circuit. If you can confirm this, simply connect the W1/B terminal to the W terminal on the air handler. Do not cut the Rc/ Rh jumper. Wire up your Oil Burner, Circulator relay, or Hydronic Zone valve to the isolation contacts or wires provided in the air handler. The fan is controlled via the time delay relay inside the air handler. Don’t worry if you accidentally cut the Rc/Rh link. Just install your own jumper across the Rc/Rh terminals!
6
Typical Heat Pump wiring with Gas or Oil Furnace backup heat. No dual fuel kit is required. Program the BMPlus to stage via the Adjustable Timer, Outside Air temperature or turn the Timer off and use Heat Pump Thermostats on all zones.
G Y2
T OIL BURNER PRIMARY CONTROL
BMPlus 3000
Dual Fuel Heat Pump with “O” Type Reversing Valve **
Figure 10 Single stage heat pump and 1or 2 stage furnace. **Note that a Conventional & Dual fuel heat pump wire up more or less the same. The difference is how 2nd stage heat operates. In a Conventional system, the indoor fan & the compressor continues to run when 2nd stage energizes. In a Dual Fuel system, the indoor fan & the compressor shuts down when 2nd stage energizes. The BMPlus 3000 will perform these functions automatically. All you have to do is set the dip switches to the correct settings. Select CONV or DF at dip switch #2. Install regular Heat/Cool thermostats and choose to activate 2nd stage heat by TIMER or by OUTSIDE AIR TEMPERATURE. (Optional Sensor required). Or you may choose to install Heat Pump Thermostats on all zones and turn the Onboard Timer OFF. When the thermostat 2nd stage heat demand is satisfied, the BMPlus 3000 will stage down, unless DF or OAS has been selected and the outdoor temperature is lower than the OAS changeover setting. In that case the system will continue in FUEL mode, until all current heating demands are satisfied.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
SYSTEM WIRING CONTINUED Single Transformer Gas & A/C 2 stage heat 2 stage cool
Typical 2 stage gas furnace with 2 stage A/C. Constant or variable speed systems can be connected and controlled. Choose Timer or Outside air to delay 2nd stage.
BMPlus 3000 2 STAGE OUTDOOR CONDENSING UNIT
2 STAGE GAS FURNACE
SYSTEM
Y2
G Y2
G Y2
Y1 R
Y1 W1
Y1 O
C
W2 R
W1/B W2/E RH
C
RC C NOTE: If desired, you can connect a “C” Common wire back to the “System” terminal block. Use it as a TEST point while troubleshooting. NOTE: The “R” wire connection to the condensing unit may not be required on your system.
RC/RH LINK
HVAC system with OEM Voltage Control Circuitry Some HVAC manufacturers are designing HVAC Systems with 5 - 18 vdc control circuits. Standard 24 vac thermostats will not work on these systems. These systems can only be controlled with their own thermostat. But the SYSTEM connections on a BMPlus 3000 are all dry contacts! Virtually any HVAC low voltage control circuit can be connected and controlled. All you have to do is ask the manufacturer which numbered terminal corresponds to the standard terminals. Theoretical diagram only shown below. OEM Geothermal Heat Pump
SYSTEM
5 4
G Y2
3 2
Y1 O
1
W1/B W2/E RH
Figure 11 Single transformer 2 Stage Heat & Cool system Warning: All of the wiring diagrams provided are general in nature and may not perfectly match your particular application, due to differences in HVAC Mfr’s design and terminal designations and functions! Variations on these diagrams and other System or Thermostat applications are available by contacting the EWC Technical Support Hotline.
BMPlus 3000
THEORETICAL DIAGRAM! CONTACT THE EQUIPMENT MANUFACTURER FOR TERMINAL DESIGNATIONS!
RC C RC/RH LINK
Figure 12 OEM system with 5 - 18 vdc control circuit.
ENHANCED FEATURES AND FUNCTIONS MODULE TO MODULE FACTORY POWER WIRING
SHORTED ZONE FEATURE FIRMWARE
The BMPlus 3000 includes Factory Power Wiring on all expanded systems. The 24 vac power to the expansion modules is fed through the bus cable. This simplifies your wiring and minimizes the chances of reversing polarity.
The BMPlus 3000 Zone Control System includes the Shorted Zone Feature. This feature allows the BMPlus to ignore demands from a zone thermostat that is putting out simultaneous demands for heat & cool. A condition most likely due to a short in the field wiring, incorrect wiring, or a defective thermostat. The BMPlus will honor any legitimate demands from any other zone(s), except the shorted zone. When the problem is identified and repaired, the BMPlus 3000 will automatically recognize that zone.
DUAL FUEL COMPATIBLE
The BMPlus 3000 is compatible with Dual Fuel Heat Pumps. Dual Fuel kits are not required. Select staging based on Adjustable Time Delay or an Optional Outside Air temperature Sensor. The intelligent firmware does the rest. * OFF, 7 TO 42 MINUTE 2ND STAGE TIME DELAY SETTINGS
*SECOND STAGE 50% ZONE RULE SAVES ENERGY
* 7 TO 42°F. OUTSIDE AIR CHANGEOVER
* STATUS LED’s ARE INCLUDED ON ALL MODULES
* HIGHEST LEVEL OF THERMOSTAT COMPATABILITY
*1 ZONE MODE COMPLIES WITH CALIFORNIA TITLE 24
* ADJUSTABLE DIFFERENTIAL LIMIT CONTROL
* SIMPLIFIED WIRING AND EASY SYSTEM SETUP
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
7
DAMPER WIRING AND CONFIGURATION Note: All zone dampers default to the "OPEN" position after a purge delay has occurred. Dampers also default “OPEN” during changeover & short cycle delays, and when all zone demands are satisfied, and no signals are detected from the thermostats.
All Models ESR Damper Wiring
MA-ESR
ZONE MOTOR Either one Not both
REFERENCE THESE DIAGRAMS PRIOR TO INSTALLATION AND POWER WIRING. DOING SO WILL SAVE TIME AND LABOR LATER ON.
{
M2 M1
NC NO C M M
ZONE MODULE DAMPER MOTOR TERMINAL BLOCK DESIGNATION & FUNCTION ZONE MOTOR
Terminal M6 Terminal M4 Terminal M2 Terminal M1
24vac to Close a damper(s) 24vac to Open a damper(s)
M6 M4
Constant 24vac HOT Common 24vac
M2 M1
.
Figure 13
Auxilary SPDT End Switch Dry Contacts Rated for 24vac only
A Spring Open Damper is wired to M1 & M6 . A Spring Close Damper is wired to M1 & M4 Figure 16
Multiple ND and/or URD Damper Wiring on a Single Zone PC
6
ZONE MOTOR
PC
6
PO 4 COM 1
COM 1
PC
M6 M4
M2 M1
6
PO 4 COM 1
M2 M1 PC
Figure 14
6
NOTE: Do not connect more than 4 motor actuators in a series configuration. That will decrease the chances of poor electrical connections and voltage drop issues.
PO 4 COM 1
All Models RSD Damper Wiring ZONE MOTOR MA-RSD
ZONE MOTOR
M6 M4
PO 4
All Models ND & URD Damper Wiring
M6 M4
M6 M4 M2 M1
TO THE NEXT MOTOR ACTUATOR
Figure 17
On all these dampers and most older style dampers, including competitor’s dampers, always wire up number to number or designation to designation.
Do not overload your transformer!
Figure 15
8
A Spring Open Damper is wired to M1 & M6 A Spring Close Damper is wired to M1 & M4
Contact EWC Controls Technical Support when you are on the job site for assistance with damper wiring. Have a Multi-Meter, pocket screw driver and wire snips on hand.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
DAMPER WIRING CONTINUED If you need to connect numerous dampers to a single zone, or you are using dampers of unknown current draw such as Spring Types, Isolation relays and separate power supplies may be required. Parallel as many dampers as you want as long the total current load of the motor actuators does not exceed the VA rating of the transformer. Other factors should also be considered, such as the full load amp rating of the isolating relay contacts, voltage drops from long wire runs and feeder conductor sizing to junction points. NOTE: Some older style dampers and competitor’s dampers cannot be paralleled and must be isolated or wired in tandem. Contact EWC Controls Technical Support for assistance. Variations on this diagram and other damper solutions are available.
PC
6
ZONE MOTOR
TYPICAL JUNCTION POINT
PO 4
TYPICAL FEEDER CONDUCTOR 14 - 16 awg
NO
3
COM 1 C
M6 M4
1
TYPICAL JUNCTION POINT
COM 1
PC
NC TYPICAL FEEDER
PO 4
M2 M1
CONDUCTORS
6
TYPICAL LOADCONDUCTORS 18 awg T-stat Wire
PC
6
PO 4
2
COIL 24 vac One relay coil=One motor. Don’t overload your power transformer, by connecting too many relays.
R1 Isolation Relay SPDT action with 24 vac coil Relay is shown de-energized. All dampers are closed.
COM 1 H
TYPICAL JUNCTION POINT
PC
L1 To Line Voltage Provide over current protection
6
PO 4 TYPICAL LOADCONDUCTORS 18 awg T-stat Wire
COM 1
C
L2
TYPICAL FEEDER CONDUCTOR 14 - 16 awg
Separate 24vac 40va Transformer Multiple Damper Wiring on a Single Zone, using a Separate Transformer and an Isolating Relay. Maximum of 20 Genuine ND/URDdampers per 40va transformer.
Figure 18
BMPlus 3000, 5000, 7000, Revision “B” Recommended Power Solutions Number of Dampers Directly Connected
1-3
4-5
6-7
3 40va 40va 40va 5 40va 40va 40va 7 40va 40va 40va
Use Class 2 UL Listed 1585 Inherently current limiting transformers only!
Spring Types @ 6 - 10 va per damper
Number of Zones
Number of Zones
ND / URD’s @ 1.5 va per damper
Number of Dampers Directly Connected
1-3
4-5
6-7
3 40va 50va 75va 5 40va 60va 75va 7 50va 60va 100va
Non-inherently current limiting transformers must have field provided over-current protection on the secondary 24 vac output. The table values provided pertain to genuine ULTRAZONE Dampers and Competitors typical 24vac Spring loaded dampers. Included in these VA load ratings are the correct number of thermostats, the BMPlus Zone System, and a 5% field factor. Spring loaded dampers draw higher currents & require more power.
T E S T I N G D A M P E R MOTORS ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close. RDN / SMDL / BMDL Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminals 2 and 4. Damper should Open. Remove 24vac hot from terminal 4. Damper should Close. SR / ESR / RSD Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Close. Remove 24 vac hot. Damper should Open. SR / ESR / RSD Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Open. Remove 24vac hot. Damper should Close. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
9
LED’S BMPlus 3000 LED’s
The BMPlus is equipped with 11 LED’s which indicate system operation and status. Familiarize yourself with the LED’s definitions, in order to quickly & accurately determine the current system status and mode of operation.
RED
STATUS
The STATUS LED pulses as a steady heart beat to indicate proper Microprocessor system status.
RED
OAS
The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point. LED will blink rapidly to indicate a malfunctioning Outdoor Air Sensor.
RED
SAS
The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP LIMIT. LED will blink rapidly to indicate a malfunctioning Supply Air Sensor.
RED
ZONE 3
The ZONE 3 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
RED
ZONE 2
The ZONE 2 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
RED
ZONE 1
The ZONE 1 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
RED
FAN
The FAN LED will illuminate solid to indicate a demand for fan operation, during COOLING, HEATING, PURGE, or CONTINUOUS FAN.
RED
Y2
Y2 LED illuminates solid to indicate 2nd stage of COOLING is energized.
RED
Y1
The Y1 LED illuminates solid to indicate 1st stage of COOLING is energized in GAS/HYDRONIC or HEAT PUMP mode. The Y1 LED illuminates solid to indicate 1st stage HEATING in HEAT PUMP MODE.
RED
W1/B
The W1/B LED illuminates solid to indicate 1st stage of HEATING is energized in Gas/Hydronic mode. The W1/B LED illuminates solid to indicate ‘B’ reversing valve is energized in HEAT PUMP operation.
RED
W2/E
The W2/E LED illuminates solid to indicate 2nd stage of HEATING is energized in GAS/HYDRONIC or HEAT PUMP mode. The W2/E LED illuminates solid to indicate EMERGENCY HEAT is energized in HEAT PUMP mode.
The BMPlus Zone Control System is not compatible with 2 speed / 2 stage compressor Heat Pumps. (3 stage heat pumps).
NOTES:
10
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
BMPlus3000 3 Zone Main Module
Rugged 10 pin Expansion Header Protective header cap not shown for clarity
User Friendly Adjustable Potentiometers
J1
CONTROL SYSTEM Rugged Damper Motor Terminal Blocks
Dual Function Reset Button
21
14
ZONE3 MOTOR
M6 M4 M2 M1
OFF TIMER
R2
Isolated Common terminal. Useful when HVAC troubleshooting
26
D10 D11 D12 D13
33 40
R 36 R 37 R 38 R 39 R 41
47
2 ND STAGE HEAT R4
C7 C8
C15
SAS
R 43
U3
R14
SAS
R 42
DIFFERENTIAL
D 21
OAS
R 40 R 82
OAS
R 81 R44
U2
U1
R45
K2
M6 M4 M2 M1
C10
RESET
C W/E O/B Y R G
R 47 R 48
R13
R 49
K3
C12 R 50
M6 M4 M2 M1
R 51
U9
F1
D4
C13
D3
+
+
C1
C2
C14
Y1
R 52 R 53
U5
R 79
ZONE3 T STAT
SW 3
R D5
C
K5
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
W1 B W2 E RH RC C
EWC Figure 19
R 55
LED 1
R 22
K 6 R 23
LED 2
R 58 R 59 R 60
STATUS
R 35
D7
K7
R 26 R 27
D8
K8
R 30
LED 4
ZONE 3
LED 5
ZONE 2
LED 6
ZONE 1
LED 7
FAN
LED 8
Y2
R 31 R 32 R 33
D9
U7
R 63 R 71 R 64 R 65 R 68
C W/E O/B Y R G
Multi Functional Zone 1 Thermostat Terminal Block
ONE ZONE
R 67
U8
R 69
EM
R 70
LED 9
Y1
LED 10
W1
B
LED 11
W2
EM
R 34
ZONE1 T STAT
R 62
SAS
R 28 R 29
R 61
OAS
LED 3
R 24 R 25
R 57
U6
R 21 D6
R 56
C9
Z1
R 19 R 20
G Y2 Y1 O
R 54
R 66
Rugged Thermostat Terminal Blocks
C W/E O/B Y R G
R 78
K4
Outdoor Air Sensor Connections
ZONE3 T STAT
R 46
U4
C11 D2
RC RH LINK
On-Board CUTTABLE Rc/Rh Link
R3
R15 R16
D1
SYSTEM
Isolated HVAC System Terminal Block
19
HIGH TEMP LIMIT C5
K1
24 VAC T’FORMER Polarized Power Input Terminals
OAS
150
160 12 170 5
110
LOW TEMP LIMIT
R1
140
130
52
2 ND STAGE
ZONE1 MOTOR
Easy Setup 8 switch Bank
34
42
46
49 120
35 37
7
ZONE2 MOTOR
Thermal Circuit Breaker
43
40
28
Supply Air Sensor Connections
R 73 R 72 R 77
NORM
R 76
BMPlus3000B System Status LED’s
SW 4
On-Board Emergency Switch
The BMPlus 3000 Zone Control System includes Module to Module Factory Wiring. We power up the Expansion Modules for you. The XM2 Expansion module includes a Status LED and Damper Status LED’s. See page 11 and 12 for drawing representations of a 5 and 7 zone system and appropriate dip switch settings. All you have to do is: 1. Set the dip switches to your specific application. 2. Connect your thermostats, dampers and system wiring. 3. Power up the Main Module 4. Check System Operation. 5. Enjoy. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]
11
Setting the XM2 Expansion Panel DIP Switches Each expansion module has a 2 position DIP switch. Factory set to insure the main module recognizes each expansion module in the proper sequence.
BMPlus5000 C1
STATUS
U1
U4
C W/E T S O/B T Y A R T G
R 19 R 21 K1
D M P R
D M P R
+ R1
M6 M4 M2 M1
R2
D3
R 40 R 39
R4
A 0<>1 A 0<>2
R5
K2
M6 M4 M2 M1
C3 U3
R3
R 13
R 10 D6
R 15 D7 R 36 R 16 R 37 R 22
Y1
Z1
R 17
R 26
R 29
R 25
R 28 D4
R 27 D5
D8
R 34
EWC
J1
R 23
C T W/E S O/B T A Y T R G
R 20
R 30
U2
R6
FACTORY SUPPLIED POWER & DATA POLARIZED BUS CABLE
R 14
R 11
R 38
U5
D2 D1
R 12
R 35
R 24
R 18
DIP switch settings for 1st Expansion panel. Zones 4 & 5
J1
CONTROL SYSTEM
Protective header caps not shown for clarity
21
14
ZONE3 MOTOR
M6 M4 M2 M1
43
40
28
46
49 120
35 37
7 OFF
42
34
52
2 ND STAGE
TIMER
OAS R2
19
26
R3
40
R 36 R 37 R 38 R 39 R 41
47
R4
C15
SAS
R 43
U3
R14
SAS
R 42
DIFFERENTIAL
C7 C8
R15 R16
D10 D11 D12 D13
33
2 ND STAGE HEAT
HIGH TEMP LIMIT C5
K1
150
160 12 170 5
110
LOW TEMP LIMIT
R1
140
130
D 21
OAS
R 40 R 82
OAS
R 81
ZONE2 MOTOR
D1
R44
U2
U1
R45
K2
M6 M4 M2 M1
C10
RESET
C W/E O/B Y R G
R 46
U4
R 47
C11 D2
ZONE3 T STAT
R 48
R13
R 49
K3
C12 R 50
ZONE1 MOTOR
Provide Over-Current Protection To Line Voltage
M6 M4 M2 M1
U9
F1
D4
D3
+
+
C1
C2
R 52 R 53 R 79
ZONE3 T STAT
C W/E O/B Y R G
R 78
24 VAC T’FORMER
SW 3
K4
D5
C
K5
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
LED 1
SYSTEM
G Y2 Y1 O W1 B W2 E RH RC C
R 55 R 66
D6
R 22
K 6 R 23
LED 2
D7
K7
R 26 R 27
R 58 R 59 R 60 R 35
D8
K8
R 30
ZONE 3
R 32 R 33 D9
U7
LED 5
ZONE 2
LED 6
ZONE 1
LED 7
FAN
LED 8
Y2
LED 9
Y1
R 63 R 71 R 64 R 65 R 68
C W/E O/B Y R G ONE ZONE
R 67
U8
R 69
EM
R 70 R 73
LED 10
W1
B
LED 11
W2
EM
R 34
ZONE1 T STAT
R 62
SAS
R 31
R 61
OAS
LED 3
R 28 R 29
R 57
U6
STATUS
LED 4
R 24 R 25
R 56
C9
R 21
RC RH LINK
EWC
R 54
Z1
R 19 R 20
24 vac transformer
C14
Y1 U5
R
12
R 51 C13
R 72 R 77
NORM
R 76
BMPlus3000B
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
SW 4
Figure 20
E-Mail-
[email protected]
BMPlus7000
Setting the XM2 Expansion Panel DIP Switches
C1
STATUS
U1
U4
R 19
Each expansion panel has a 2 position DIP switch. Factory set to insure the main module recognizes each expansion module in the proper sequence.
K1
D M P R
D M P R
+
R 14
R 11
R 13
R 10 D6
R 15 D7
R1
M6 M4 M2 M1
R2
D3
A 0<>1 A 0<>2
R4 R5
K2
M6 M4 M2 M1
C3 U3
R 40 R 39
R3
R 36 R 16 R 37 R 22
R 38
U5
Y1
Z1
D2 D1
R 17
R 26
R 29
R 25
R 28 D4
R 27 D5
D8
R 34
EWC
J1
C1
STATUS
U1
R 35
R 24
FACTORY SUPPLIED POWER & DATA POLARIZED BUS CABLE Protective header caps not shown for clarity
D M P R
D M P R
+ R2
D3
R5
M6 M4 M2 M1
U3
R 15 D7 R 36 R 16 R 37 R 22
Y1
U2
R6
Z1
D2 D1
R 13
R 10 D6
R 38
U5
R 17
R 30
R 26
R 29
R 25 R 27 D5
R 34
R 24
D8
C W/E O/B Y R G
R 23
DIP switch settings for 2nd Expansion panel. Zones 6 & 7
R 35
T S T A T
C T W/E S O/B T A Y T R G
R 20
R 28 D4
EWC
J1
R 18
R 21
R 11
A 0<>1 A 0<>2
R4 K2
C3
R 40 R 39
R3
C T W/E S O/B T A Y T R G
R 14
R 12 R1
M6 M4 M2 M1
T S T A T
U4
R 19 K1
R 23
R 20
R 30
U2
R6
C W/E O/B Y R G
R 21
R 12
R 18
DIP switch settings for 1st Expansion panel. Zones 4 & 5
J1
CONTROL SYSTEM 14
ZONE3 MOTOR
M6 M4 M2 M1
21
43
40
28
34
42
OFF
52
2 ND STAGE TIMER OAS R2
19
26
R3
40
R 36 R 37 R 38 R 39 R 41
47
R4
C15
SAS
R 43
U3
R14
SAS
R 42
DIFFERENTIAL
C7 C8
R15 R16
D10 D11 D12 D13
33
2 ND STAGE HEAT
HIGH TEMP LIMIT C5
K1
150
160 12 170 5
110
LOW TEMP LIMIT
R1
140
130
49 120
35 37
7
46
D 21
OAS
R 40 R 82
OAS
R 81
ZONE2 MOTOR
D1
R44
U2
U1
R45
K2
M6 M4 M2 M1
C10
RESET
U4
C W/E O/B Y R G
R 47
C11 D2
ZONE3 T STAT
R 46
R 48
R13
R 49
K3
C12 R 50
ZONE1 MOTOR
Provide Over-Current Protection To Line Voltage
M6 M4 M2 M1
U9
F1
D4
D3
+
+
C1
C2
R 51 C13
R 52 R 53
U5
R 79
ZONE3 T STAT
C W/E O/B Y R G
R 78
24 VAC T’FORMER
SW 3
K4
R D5
C
K5
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
LED 1
SYSTEM
G Y2 Y1 O W1 B W2 E RH RC C
R 55 R 66 C9
D6
R 22
K 6 R 23
LED 2
D7
K7
R 26 R 27
R 59 R 60 R 35
D8
K8
R 30
ZONE 3
R 32 R 33 D9
U7
LED 5
ZONE 2
LED 6
ZONE 1
LED 7
FAN
LED 8
Y2
LED 9
Y1
R 63 R 71 R 64 R 65 R 68
C W/E O/B Y R G ONE ZONE
R 67
U8
R 69
EM
R 70 R 73
LED 10
W1
B
LED 11
W2
EM
R 34
ZONE1 T STAT
R 62
SAS
R 31
R 61
OAS
LED 3
R 28 R 29
R 57 R 58
STATUS
LED 4
R 24 R 25
R 56
U6
R 21
RC RH LINK
EWC
R 54
Z1
R 19 R 20
24 vac transformer
C14
Y1
R 72 R 77
NORM
R 76
BMPlus3000 rev.B
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
SW 4
Figure 21
E-Mail-
[email protected]
13
PC
6
PO 4 COM 1
6
ND / URD DAMPERS PC PO 4
6
COM 1
PC PO 4 COM 1
To Line Voltage. Provide Over-Current Protection. 24 vac transformer 40va
2 STAGE GAS FURNACE
Y O/B W1 W2
Y O/B
G
X/W R
R C
OUTDOOR HEAT PUMP
C
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
J1
ZONE3 MOTOR
ZONE2 MOTOR
ZONE1 MOTOR
SYSTEM
24 VAC T’FORMER
R C G Y2 Y1 O W1 B W2 E RH RC C RC RH LINK
EWC
7
14
28
Dual Fuel Heat Pump
43 46 130
R14
C7 C8
HIGH TEMP LIMIT
140 26 33 40
19
160 12 170
D 21
R 73
R 70
R 77
R 72
R 35
R 66 C9
C14
C10
C15
47
R4
U8
U7
U6
U5
U4
U3
2 ND STAGE HEAT DIFFERENTIAL
5
150
CONTROL SYSTEM
R3
110
49 120 52
C5 R15 R16
U2
C11
SAS
OAS
B
D10 D11 D12 D13
2nd Stage Heat Activates via Outdoor air Temperature or Heat Pump Thermostat 2nd Stage Input
40
LOW TEMP LIMIT
U1
Y1
RESET R13 C12
C13
Z1
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
LED 3
LED 2
ZONE 3
STATUS
LED 4
ZONE 2
LED 1
LED 5
ZONE 1 FAN
LED 6 LED 7
W1
Y1
Y2 LED 9
EM
LED 8
LED 10
W2 LED 11
R 41 R 42 R 43
R 51
R 49
R 47
R 46
R45
R 81
R 40 R 82
R 48
R 50
R 52 R 53
R 78
R 79
R 54
R 56
R 55
R 57
R 63
R 62
R 61
R 59
R 58
R 60
R 71 R 64 R 65
R 67
R 68
R 69
SAS
SAS OAS OAS
SUPPLY AIR SENSOR
C W/E O/B Y R G C W/E O/B Y R G C W/E O/B Y R G ONE ZONE
EM
NORM
R 36 R 37 R 38 R 39
ZONE3 T STAT
ZONE3 T STAT
ZONE1 T STAT
SW 4
OUTDOOR AIR SENSOR
E-Mail-
[email protected]
All wiring should be done to local and national codes and ordinances. Use color-coded, multi-conductor wire. Wire number to number or letter to letter on each control.
R 76
R44
BMPlus 3000 Wiring Diagram
21
R2
K1
K2
U9
SW 3
R 34
R 33
R 32
R 31
R 30
R 29
R 28
R 27
R 26
R 25
R 23 R 24
R 22
R 21
R 20
R 19
34
35 37 42
D1
D2
K3
+
D3
+ C2
D4
2 ND STAGE TIMER OAS
OFF R1
F1
C1
K4
D5
K5
K6
D6
D7
K7
D8
K8
D9
BMPlus3000 rev.B WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
HEAT
W2/E O/B
68
Y
R
G
ZONE 3 THERMOSTAT
C
HEAT
W2/E O/B
68
Y
R
G
ZONE 2 THERMOSTAT
C
HEAT
W2/E O/B
68
Y
R
G
ZONE 1 THERMOSTAT
C
6
6
OUTDOOR CONDENSING UNIT
24 vac transformer 40 va
W2 R
C
C
Y1 W1
Y1 R
G Y2
2 STAGE GAS FURNACE
COM 1
PO 4
PC
COM 1
To Line Voltage. Provide Over-Current Protection.
Y2
6
PO 4
PC
ND / URD DAMPERS
COM 1
PO 4
PC
R
SYSTEM
F1
R1
21
C2
C1
U9
U1
R 19
R 22
R 21
D9
K8
D8
K7
D7
R 24
R 34
R 33
R 32
R 31
R 30
R 29
R 28
R 27
R 26
R 25
43 130
C13 Y1
C11
U2
R4
LED 11
LED 10
LED 9
LED 8
LED 7
W2
W1
Y1
Y2
FAN
EM
B
ZONE 1
ZONE 2
LED 5 LED 6
ZONE 3
SAS
OAS
STATUS
U8
U7
U6
U5
U4
U3
R 73
R 70
D 21
D10 D11 D12 D13
R 52
R 51
R 49
R 47
R 46
R45
R 65
R 63
R 62
R 61
R 59
R 57
SW 4
ZONE1 T STAT
ZONE3 T STAT
ZONE3 T STAT
EM
ONE ZONE
C W/E O/B Y R G
C W/E O/B Y R G
C W/E O/B Y R G
OAS
OAS
SAS
SAS
NORM
R 36 R 37 R 38 R 39
SUPPLY AIR SENSOR
E-Mail-
[email protected]
All wiring should be done to local and national codes and ordinances. Use color-coded, multi-conductor wire. Wire number to number or letter to letter on each control.
R 69
R 67
R 68
R 71 R 64
R 60
R 58
R 56
R 55
R 54
R 78
R 79
R 53
R 50
R 48
R44
R 81
R 40 R 82
R 43
R 42
R 41
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
R 76
R 77
R 72
R 35
C9
R 66
C14
C10
C15
47
40
33
2 ND STAGE HEAT
LED 4
LED 3
LED 2
LED 1
Z1
26
DIFFERENTIAL
19
160 12 170 5
150
HP < SYSTEM > GAS DF < HP > CONV HC < TSTATS > HP O < RV > B OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC
C12
R13
R14
C7 C8
HIGH TEMP LIMIT
140
RESET
R3
110
R15 R16
C5
52
49 120
46
BMPlus3000 rev.B
LOW TEMP LIMIT
K 6 R 23
D6
K5
D5
K4
+
D3
R 20
K2
K1
R2
34
K3
D2
D1
42
SW 3
40
35 37
28
+
D4
2 ND STAGE TIMER OAS
OFF
7
14
CONTROL SYSTEM
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE.
EWC
RC RH LINK
W1 B W2 E RH RC C
G Y2 Y1 O
C
ZONE1 MOTOR
ZONE2 MOTOR
24 VAC T’FORMER
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
ZONE3 MOTOR
J1
2nd Stage Heat & 2nd Stage Cool Activates via The Adjustable Timer.
2 STAGE GAS HEAT WITH 2 STAGE A/C
BMPlus 3000 Wiring Diagram
W
Y
68 R
G
W
Y
68 R
G
C
HEAT
W
Y
68 R
G
ZONE 3 THERMOSTAT
C
HEAT
ZONE 2 THERMOSTAT
C
HEAT
ZONE 3 THERMOSTAT
T R O U B L E S H O O T I NG SYMPTOM
SOLUTIONS
LED’S are responding properly but HVAC system is malfunctioning.
Check HVAC system wiring for proper connections. Check HVAC system wiring for shorts/miswiring. Check HVAC System. Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
LED’s are not responding properly and HVAC system is malfunctioning.
Check HVAC system wiring for shorts/miswiring. Check HVAC system wiring for proper connections. Check HVAC thermostat for proper connections. Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
LED’s illuminate and HVAC system functions normally but dampers do not respond.
Check damper motor wiring for proper connections. Check damper motor 24vac transformer voltage/fuse/BMPlus circuit breaker. Check damper motor wiring for shorts/miswiring. Refer to Technical Bulletin for correct Setup/Wiring. REFER TO THE DAMPER MOTOR TESTING PAGE 8
LED’s do not illuminate and HVAC system does not respond.
Check HVAC & BMPlus system transformer supply voltage. Check HVAC & BMPlus system 24vac transformer voltage, fuse & the BMPlusB circuit breaker. Check HVAC & BMPlus system wiring for shorts/miswiring.
CHECK YOUR WIRING DETECTING 24vac SHORTS
SYMPTOMS: Module(s) appear to be dead!
HVAC system not responding and BMPLUS 3000 LED’s are off. Dampers not responding and THE BMPLUS 3000 LED’s are off.
If 24vac short has occurred, 24vac will be present at the BMPlus 3000 Module Input terminals R & C; but 24vac will not be present at the Thermostat R&C.
ISOLATING 24vac SHORTS
Disconnect the wire(s) from the ‘R’ terminals on the BMPlus 3000 thermostat terminal blocks , and the “M2/M4/M6’’ terminals on the BMPlus 3000 damper motor terminal blocks. Restore power. If the short is no longer present, Ohm out the thermostat and damper field wiring for shorts/misconnections. Replace or repair wires as necessary. Restore power. Module(s) will resume operation.
F1 circuit breaker protects the BMPlus 3000 and reacts to a short in the damper motor or thermostat component and field wiring.
SOLUTIONS: Remove 24vac power from BMPlus 3000 and allow circuit breaker to cool! Find and repair short(s) in damper and/or thermostat field wiring. Restore 24 vac power.
TESTING THERMOSTATS Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires separation of these circuits. Use the (C) Common terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats. You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is connected there. Make sure that you wire and configure your thermostats for the correct application. Most thermostats built today can be field configured to operate as regular Heat/ Cool type or as Heat Pump type. Remember that you can use regular Heat/Cool thermostats on the BMPlus 3000 for Heat Pump applications.
TECHNICAL SUPPORT EWC Controls provides superior toll free Troubleshooting Support for the BMPlus 3000 when you are on the job site! Call 1-800-446-3110 Monday - Friday 8am to 5pm EST Otherwise call 1-732-446-3110 for information on the BMPlus 3000 and other ULTRA-ZONE products.. When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy.
16
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
E-Mail-
[email protected]