Transcript
AutroSafe
Internal Communication Module - BSL-310
Features • • • •
Interface for internal communication between all I/O modules. Easily plugged onto each other or onto other I/O modules on a standard mounting rail. Automatic addressing of the I/O module. Designed to meet EN-54 and LPCB requirements and conforms to CE standards.
Application / Description The Communication Module BSL-310 serves as an interface for the common internal communication line between all the different I/O modules. The module provides the following: • RS-232 interface with hand-shake, all lines galvanically isolated to allow floating reference • built-in battery monitoring with control outputs for activ ation of charger/battery • monitoring of earth faults
Connections Front view when mounted on rail Cable 2 To Power Supply BSS-103A/02
Mounting The Communication Module is easily plugged onto a moun ting rail inside the Fire Alarm Control Panel (BS-310/320) or the Controller (BC-320). The Communication Module - as well as the Power Module (BSS-310) - is always delivered with the Fire Alarm Control Panel (BS-310/320) or the Controller (BC-320). Since the Communication Module provides the common external interface for all modules, the module must always be mounted on the rail directly on top of the Power Module BSS310, which is the first module placed at the bottom of the rail. The I/O module will automatically detect its own address, no Dip-switch or jumper settings are required.
Cabling Two small ribbon cables are used for the internal connections inside the cabinet (BS-310/320 or BC-320). One cable is used to interconnect the Communication Module and the Connection Module BSF-310A (indicated as cable 1). The other cable is used to interconnect the Communication Module and the Power Supply BSS-103 (indicated as cable 2). Refer to connection drawing / schematics on the other side of this data sheet.
P-BSL310/CE-Rev. B, 000315
Cable 1 To Connection Module BSF-310B
Connector on ribbon Cable 1 To Connection Module BSF-310B 1 2 3 4 5 6 7 8 9 10 Connector on ribbon Cable 2 To Power Module BSS-103A/02 1 2 3 4 5 6
Protecting environment, life and property...
Signal INT RS_GND TX RS_GND RS_GND RS_GND RX RS_GND CTS RS_GND Signal TEST N.C. N.C. MAINS_OK N.C. APPLY_LOAD
Communication Module, BSL-310
Technical Specifications Dimensions (mm)
Order Numbers 95x89x32
Weight (g)
81
Materials
Top and bottom: Zytel FR7200
Order number BSL-310
Description
Ship Weight metric/imperial
Communication Module
Snap-on mounting device: Zytel 7335S Electrical connection Mounting
Internal system: plug-in connection and ribbon cables.
Internal current consumption
24VREG: 15 mA
Current consumption, idle 24V REG
13mA
Current consumption, idle 5V REG
2mA
Current consumption, idle 24V BAT
18,5mA
Current consumption, 24V REG
21,5mA
Current consumption, 5V REG
2,7mA
RS-232 output RS-232 input RS-232 Baud Rate
Cable 1
BSF-310B Connection Module
BSL-310
BSS-103A/02 Power Supply Cable 2
Minimum 3K load resistance at +/-5V Minimum load resistance 3K 9600 Baud, 1 stop bit, no parity
Battery Voltage failure
Ubatt <22,6V +/-0,2V
Charger failure
Ubatt >28,5V +/-0,2V Ubatt <25,5V +/-0,2V
Earth failure
Battery + <52K +/-4K Battery - <10K +/-2K
Mains_OK
Installation Overview
Onto a standard mounting rail inside the Fire Alarm Control Panel or Controller.
12,5V