Transcript
6OPzV600 2V 600AH OPzV - UzV
6OPzV600
Physical Specification
Awaiting Image
Part Number:
6OPzV600
Length:
145 ± 3 mm ( 5.17 inches )
Width:
206 ± 3 mm ( 8.11 inches )
Container Height:
646 ± 3 mm ( 25.4 inches )
Total Height (with terminal): 681 ± 3 mm ( 26.8 inches ) Approx 46.0 kg (101.4lbs)
Approx Weight:
Specifications
Terminal Type Container Material Rated Capacity
Nominal Voltage
2V
Nominal Capacity (10HR)
600.0AH
Standard Terminal
F11
Optional Terminal
-
Standard Option
ABS
Flame Retardant Option (FR)
ABS (UL94:VO)
738 AH/738A
(100 hr, 1.80V/cell, 20°C/68°F)
600 AH/60.0A
(10hr,1.80V/cell, 20°C / 68°F)
520 A H/104A
(5hr,1.75V/cell, 20°C / 68°F)
456 AH/152A
(3hr,1.75V/cell, 20°C / 68°F)
341 AH/341A
(1hr,1.60V/cell, 20°C / 68°F)
Max Discharge Current
4800A (5s)
Internal Resistance
Approx 0.62mΩ
Discharge Characteristics
Operating Temp. Range
Discharge: -20 ~ 55°C (-4 ~ 131°F) Charge:
0 ~ 40°C (32 ~ 104°F)
Storage: -20 ~ 50°C (-4 ~ 122°F) Nominal Operating Temp. Range
-
Cycle Use
Inital Charging Current less than 120.0A.Voltage 2.40V ~ 2.50V at 20°C (68°F) Temp. Coefficient -5mV/°C
Standby Use
No limit on Initial Charging Current Voltage 2.25V ~ 2.30V at 20°C (68°F) Temp. Coefficient -3mV/°C
Capacity affected by Temperature
Design Floating Life at 20°C
20 Years
Self Discharge
<2% pre month @ 20°C (68°F)
40°C (104°F)
103%
25°C (77°F)
100%
0°C (32°F)
86%
Dimensions F11 Terminal
1
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email:
[email protected]
www.ultracell.co.uk
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
ISO9001
Constant Current Discharge (Amperes) at 20 0C (68 0F ) F.V/Time
10min
15min
30min
1h
2h
3h
5h
8h
10h
1.85V/cell
409
389
335
267
177
137
94.2
65.8
56.2
1.80V/cell
503
470
390
301
195
149
102
70.5
60.0
1.75V/cell
595
526
416
313
200
152
104
71.7
60.9
1.70V/cell
668
574
440
325
205
156
105
72.6
61.6
1.65V/cell
717
607
458
335
209
158
107
73.5
62.3
1.60V/cell
750
628
469
341
212
160
108
74.1
62.7
8h
10h
Constant Power Discharge (Watts) at 20 0C (68 0F ) 15min
10min
F.V/Time
30min
1h
5h
3h
2h
1.85V/cell
761
730
640
517
344
268
185
130
112
1.80V/cell
919
871
738
578
376
290
199
139
119
1.75V/cell
1069
962
779
598
385
295
202
141
121
1.70V/cell
1178
1034
816
617
393
300
205
143
122
1.65V/cell
1243
1076
840
631
399
304
207
144
123
1.60V/cell
1276
1098
853
637
402
306
208
145
124
Charging Characteristics
Discharge Characteristics 2.50
25 Equ alin g cha rge v oltage for m ax. 1 6 hou rs
2.40
C harging time in hours
C harge voltage (V /cell)
2.45
2.35 2.30 2.25
Floa t voltage + /- 1%
2.20 2.15 2.10 -20
-10
30
20
10
0
A 10
B
A 0.2C
10
0
50
40
0
0.1C
20
B
10
0
50
Tempera ture ( C )
100
Depth of discharge in % of C
For continuous charging we recommend a voltage of 2.25 V. The charging voltage must be compensated to the curve for acontinuously different battery ambient temperature.
10
Charge voltage: A
2.25 V/cell
B
State of charge
2.40 V/cell
100 %
State
of charge 90 %
Effect of Temperature on Long Term Float Life
Temperature Effects in Relation to Battery Capacity
22
100
20
Life expectancy (year)
Available capacity( % )
110 105 95 90 85 80 75 70
C 10 C5 C3 C1
65 60 55 50 45
18
Charging voltage 2.25V/cell
16 14 12 10 5
40 35 30 -20
-15
-5
-10
5
0
10
15
20
Ambient temperatu re(
25
20 68
30
)
40 104
30 86
0
Ac c.t o IE C 8 96 -2 ( 20 C / 68 F)
80 70 60 50 40 30 20 3000
3500
4000
4500
5000
5500
6000
6500
Nu mb er of Cy cle s
2
Residu al averag e capacit y in % of C
120
90
Available capacity / %
E xtrac ted c apac ity in %
100
2500
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email:
[email protected]
www.ultracell.co.uk
C F
O
General Relation of Capacity VS. Storage Time 0
2000
0
Battery temperature
Cycle Life in Relation to Depth of Discharge
10 1500
50 122
10
100 80
10
60 30
40
40
20
20 0
5
10
15
20
25
St or ag e t im e ( mo nths )
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
ISO9001