AWUF Series Wall-Mount Air Handler 1½ to 3 Tons Contents Nomenclature ..........................................2 Accessories ..............................................2 Product Specifications .............................3 Dimensions ..............................................6 Airflow Data .............................................8 Wiring Diagram ........................................9
Product Features • Equipped with a Check Flowrater for cooling-only and heat pump operation • Direct-drive, multi-speed motors allows air volume variation for heating/cooling –– Multi-speed ECM: AWUF19, 25, 31, 32, 37 –– Multi-speed PSC motor: AWUF18, 24, 30, 36 • Sequence-controlled, rust-resistant nickel chromium heating elements of 3, 5, 8, and 10 kW • Aluminum tubing coils on all models • Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193
• Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193 • Factory-installed pull-type disconnect • Thermoplastic drain pan with bottom primary and secondary drain connections • Built-in filter rack (filter included) • Large chassis (2½- and 3-ton units) – front return only • Small chassis (1½- and 2-ton units) – front or bottom return • Wall-hanging bracket provided • AHRI Certified; ETL Listed
* Complete warranty details available from your local dealer or at www.daikincomfort.com. To receive the 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
SS-DAWUF
www.daikincomfort.com
4/16 Supersedes 10/15
Nomenclature
A
1
W 2
U 3
F 4
24 5,6
05 7,8
Unit Tupe A -‐ Single-‐Piece Air Handler
1 9
6
10
AA
11,12
Engineering * Major/ Minor Revisions *Not used for inventory management
Unit Application W -‐ Wall-‐Mounted Unit
Refrigerant 6 = R-‐410A or R-‐22
Cabinet Finish U -‐ Unpainted
Electrical 1 -‐ 208/240 V, 1 Phase, 60 Hz
Expansion Device F -‐ Flowrater Nominal Capacity Range AWUF Units with PSC Motors 18 = 1½ Tons 24 = 2 Tons 30 = 2½ Tons 36 = 3 Tons
AWUF Units with ECM (X-‐13) Motors 19 = 1½ Tons 25 = 2 Tons 31, 32 = 2½ Tons 37 = 3 Tons
00 = No Heat 03 = 3 kW 05 = 5 kW
Heater Kit 06 = 6 kW 08 = 8 kW 10 = 10 kW
Accessories Model
2
Item #
Description
AWUF18 - AWUF19
Wad-1
Wall access door
AWUF24 - AWUF25
Wad-1
Wall access door
AWUF30 - AWUF37
Wad-2
Wall access door
www.daikincomfort.com
SS-DAWUF
Product Specifications
AWUF 180316B
AWUF 180516B
AWUF 180816B
AWUF 190316A
AWUF 190516A
AWUF 190816A
AWUF 240316B
AWUF 240516B
AWUF 240816B
AWUF 241016B
18,000
18,000
18,000
18,000
18,000
18,000
24,000
24,000
24,000
24,000
3
5
8
3
5
8
3
5
8
10
Diameter
9
9
9
10
10
10
10
10
10
10
Width
6
6
6
6
6
6
6
6
6
6
Liquid
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction
⅝"
⅝"
⅝"
⅝"
⅝"
⅝"
⅝"
⅝"
⅝"
⅝"
Coil Drain Connection (FPT)
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
Minimum Circuit Ampacity (230V)
17.3
26.6
39.6
18.9
28.3
41.3
17.3
26.6
39.6
52.7
Minimum Circuit Ampacity (208V)
15.1
23.3
34.6
16.8
24.9
36.2
15.1
23.3
34.6
45.9
Max. Overcurrent Device (240V)
20
30
40
20
30
45
20
30
40
60
Max. Overcurrent Device (208V)
20
25
35
20
25
40
20
25
35
50
Minimum VAC
197
197
197
197
197
197
197
197
197
197
Maximum VAC
253
253
253
253
253
253
253
253
253
253
Full Load Amps (FLA)
1.3
1.3
1.3
2.6
2.6
2.6
1.3
1.3
1.3
1.3
Horsepower (HP)
1/5
1/5
1/5
1/3
1/3
1/3
1/5
1/5
1/5
1/5
Ship Weight (lbs)
84
84
84
84
84
84
84
84
84
84
Nominal Ratings Cooling (BTU/h) Electric Heat (kW) Blower
Coil Connections
Electrical Data Voltage
Blower Motor
SS-DAWUF
www.daikincomfort.com
3
Product Specifications
AWUF 250316B
AWUF 250516B
AWUF 250816B
AWUF 251016B
AWUF 300316B
AWUF 300516B
AWUF 300816B
AWUF AWUF AWUF 301016B 310516A* 310816A*
24,000
24,000
24,000
24,000
30,000
30,000
30,000
30,000
30,000
30,000
3
5
8
10
3
5
8
10
5
8
Diameter
10
10
10
10
9
9
9
9
10
10
Width
6
6
6
6
8
8
8
8
8
8
Liquid
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction
⅝"
⅝"
⅝"
⅝"
¾"
¾"
¾"
¾"
¾"
¾"
Coil Drain Connection (FPT)
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
230/208
Minimum Circuit Ampacity (230V)
18.9
28.3
41.3
54.3
17.6
27.0
40.0
53.0
30.1
43.1
Minimum Circuit Ampacity (208V)
16.8
24.9
36.2
47.5
15.5
23.6
34.9
46.2
26.8
38.1
Max. Overcurrent Device (240V)
20
30
45
60
20
30
40
60
35
45
Max. Overcurrent Device (208V)
20
25
40
50
20
25
35
50
30
40
Minimum VAC
197
197
197
197
197
197
197
197
197
197
Maximum VAC
253
253
253
253
253
253
253
253
253
253
Full Load Amps (FLA)
2.6
2.6
2.6
2.6
1.58
1.58
1.58
1.58
4.1
4.1
Horsepower (HP)
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/2
1/2
Ship Weight (lbs)
84
84
84
84
93
109
109
109
109
109
Nominal Ratings Cooling (BTU/h) Electric Heat (kW) Blower
Coil Connections
Electrical Data Voltage
Blower Motor
4
www.daikincomfort.com
SS-DAWUF
Product Specifications
AWUF 321016A*
AWUF 360516B
AWUF 360816B
AWUF 361016B
AWUF 370516B
AWUF 370816B
AWUF 371016B
30,000
36,000
36,000
36,000
36,000
36,000
36,000
10
5
8
10
5
8
10
Diameter
10
9
9
9
10
10
10
Width
8
8
8
8
8
8
8
Liquid
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction
¾"
¾"
¾"
¾"
¾"
¾"
¾"
Coil Drain Connection (FPT)
¾"
¾"
¾"
¾"
¾"
¾"
¾"
230/208
230/208
230/208
230/208
230/208
230/208
230/208
Minimum Circuit Ampacity (230V)
56.2
27.0
40.0
53.0
30.1
43.1
56.2
Minimum Circuit Ampacity (208V)
49.4
23.6
34.9
46.2
26.8
38.1
49.4
Max. Overcurrent Device (240V)
60
30
40
60
35
45
60
Max. Overcurrent Device (208V)
50
25
35
50
30
40
50
Minimum VAC
197
197
197
197
197
197
197
Maximum VAC
253
253
253
253
253
253
253
Full Load Amps (FLA)
4.1
1.58
1.58
1.58
4.1
4.1
4.1
Horsepower (HP)
1/2
1/3
1/3
1/3
1/2
1/2
1/2
Ship Weight (lbs)
109
96
96
96
96
96
96
Nominal Ratings Cooling (BTU/h) Electric Heat (kW) Blower
Coil Connections
Electrical Data Voltage
Blower Motor
SS-DAWUF
www.daikincomfort.com
5
Dimensions Note - Once installed, top of unit must be level or slightly tilted back to ensure proper condensate drainage.
L OW V OL T P OWE R S UP P LY ( L A R G E C H AS S I S O N L Y )
S UC TION LINE OFFS E T HANG ING B R AC K E T
LIQUID LINE
P U L L O U T DI S C O N N E C T
R E M O V AB L E S E R V I C E DO O R
LOW V OLT P OWE R S UP P LY E L E C T R I C AL P OWE R S UP P LY
F R O N T AC C E S S P AN E L S M AL L C H AS S I S
S T U D AT T A C H M E N T HOLE S
FR ONT R E TUR N FILTE R L AR G E C H AS S I S
B O T T O M P R I M AR Y AN D S E C O N DAR Y DR AI N S C AN B E AC C E S S E D T H R O U G H T H E B O T T O M O F T H E U N I T . ( 3 /4 " N P T F E M AL E C ONNE C TION) N O T E : H AN D T I G H T E N O N L Y
Small Chassis (AWUF18-25)
6
Large Chassis (AWUF30-37)
A
36"
A
36"
B
203/16"
B
24"
C
16⅛"
C
21"
D
16"
D
19⅞"
E
11"
E
15⅞"
Filter
14" x 18" x 1"
Filter (30, 36,31,32,37)
18" x 20" x 1"
www.daikincomfort.com
SS-DAWUF
Dimensions 9
8
7
6
5
4
D 36.000
B
F 4.127
.109
5
1.026
E C
E 20.115
K
I
H A
10.057
J
G F
TOP 45 VIEW TYP.
D
1.026
Fresh Air Openings
2.031
C .750 4.0"
Front 2X 88 BEND SECTION B-B
3.0"
B
3.0"
Bottom DETAIL C BOTH SIDE SCALE 0.250
L
A
M
BOTTOM VIEW
N
COMPONENTS AND MATERIALS SPECIFIED HEREIN WILL ALSO CONFORM TO THE APPLICABLE SECTION OF GOODMAN MSP 824.01 WORKMANSHIP STANDARD.
SPECIAL CHARACTERISTICS: = 6SIGMA
CC
= CRITICAL CHARACTERISTIC
9
SC
= SIGNIFICANT CHARACTERISTIC
8
CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO OTHE PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAND, ON COMPLETION OF ORDER, OR OTHER P
7
6
5
4
A
B
C
D
E
F
G
H
I
J
K
L
M
N
AWUF 18-25
36"
20¼"
16⅛"
16"
11"
1¾"
1½"
2¼"
⅞"
1⅛"
1¾"
4"
6"
10"
AWUF 30-37
36"
24"
21"
19⅞"
16"
4⅛"
1½"
1¾"
2"
1¼"
2⅜"
4"
8"
12"
SS-DAWUF
www.daikincomfort.com
7
Airlfow Data
Model
AWUF18XX16B*
AWUF19XX16A*
AWUF24XX16B*
AWUF25XX16A*
AWUF30XX16B*
AWUF310516XX
AWUF310816XX AWUF321016XX
AWUF36XX16B*
AWUF37XX16B*
8
CFM Delivered Against External Static Pressure
Motor Speed
0.1"
0.2"
0.3"
0.4"
0.5"
High
755
715
670
615
545
Low
740
700
655
595
535
T5
899
870
853
824
800
T4
635
604
580
546
520
T3
799
775
747
727
702
T2
635
604
580
546
520
T1
635
604
580
546
520
High
900
870
835
795
760
Low
865
835
800
765
725
T5
899
870
853
824
800
T4
635
604
580
546
520
T3
799
775
747
727
702
T2
635
604
580
546
520
T1
635
604
580
546
520
High
1255
1120
1100
1020
950
Low
1115
1010
990
900
820
T5
875
865
830
805
765
T4
1005
975
945
920
890
T3
840
795
785
745
700
T2
645
615
550
500
445
T1
645
615
550
500
445
T5
1090
1065
1040
1015
985
T4
1005
975
945
920
890
T3
840
795
785
745
700
T2
645
615
550
500
445
T1
645
615
550
500
445
High
1215
1145
1070
985
890
Low
1120
1065
1000
915
820
T5
1315
1290
1260
1230
1200
T4
1240
1205
1175
1145
1115
T3
1175
1140
1105
1075
1045
T2
1060
1020
990
955
925
T1
1060
1025
995
960
925
www.daikincomfort.com
SS-DAWUF
SS-DAWUF
www.daikincomfort.com
BR
WH
RD
BL
RD
DISC
RD
BK
BK
BK
RD
RD BL
RD
G
L2
L1
BL
BR
K1
K1
RD
NO
RD
BK
RD
RD
BK
BK
NC M2
COM
HC
T2
T1
RD
WH
BL
EBTDR
M1
EBTDR
R XFMR-R XFMR-C C
GR
RD
EVAPORATOR MOTOR LEADS PU COMMON BK HIGH RD LOW
DISC
L1
BR
FC
BR
EM
RD PU BK
RD
SEE NOTE 5
RD
BK
*
5
3
BK
BK
TL2*
TL2
RD
4
1 TR
RD
HTR2*
* HTR1 TL1
TL1
2
*
HC
DISC EM EBTDR
WH BK RD YL BL
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
⚠
Warning
HI
TL1
* TL1
4
EBTDR
EBTDR
GREEN PURPLE BROWN
DISCONNECT SWITCH EVAPORATOR MOTOR ELECTRONIC BLOWER TIME DELAY RELAY HEATER CONTACTOR
R FC TL TR HTR
RELAY FAN CAPACITOR THERMAL LIMIT TRANSFORMER HEATER ELEMENT
FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE
WH BR
COMPONENT CODE
GR PU BR
L2
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
5) EBTDR HAS A 7 SECOND ON DELAY WHEN "G" IS ENERGIZED AND A 65 SECOND OFF DELAY WHEN "G" IS DE-ENERGIZED.
3) SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE WIRING CONNECTIONS. 4) ASTERISK (*) INDICATES THAT HEATING ELEMENT , THERMAL LIMIT, AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.
NO
0140A00282-B
GR
G
DISC
NOTE 3
R1
COM
HC
WIRING CODE
M2
NC
T2
BL
C
TL2
* TL2
N.E.C. CLASS 2 WIRE
24 VOLT 5
3
LO
HTR 1
* HTR 2
SEE NOTE 1 1 2
EM
COLOR CODE
TR
T1
WHITE BLACK RED YELLOW BLUE
RD
R
EBTDR
FC
HC
208/230 VOLTS
1) RED WIRE TO BE ON TRANSFORMER TERMINAL 3 FOR 230 VOLTS AND ON TERMINAL 2 FOR 208 VOLTS. 2) TO PLACE AIRHANDLER IN HIGH SPEED, REMOVE RED MOTOR LEAD FROM ELECTRONIC BLOWER TIME DELAY RELAY (EBTDR) COM TERMINAL AND REPLACE WITH BLACK MOTOR LEAD. ALL UNITS WILL BE FACTORY CONNECTED AT LOW SPEED.
NOTES:
RD
RD
L1
DISC
CONTROLS SHOWN WITH UTILITIES IN "ON" POSITION AND THERMOSTAT IN "OFF" POSITION. IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE 105°C. WIRE SIZE TO CONFORM TO THE NATIONAL ELECTRIC CODE.
COPPER POWER SUPPLY (SEE RATING PLATE) USE MIN. 75°C FIELD WIRE N.E.C. CLASS 2 WIRE
GR RD
SEE NOTE 3
EQUIPMENT GROUND
L2
AWUF18/24/30/36 Wiring Diagram
9
10
www.daikincomfort.com 18000 24000
PURPLE PINK
⚠
C
L1
L2
WH
Warning
TABLE-1
BK
RD
BK
RD
BTUh
BK
BK
RD
RD
BK
FIELD CONNECTIONS SEE NOTE 2 USE N.E.C CLASS 2 WIRE
WIRE COLOR
BK
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
7. FOR UNITS USING 3KW AND 5KW HEATERS, WHITE WIRE WILL BE CONNECTED TO TERMINAL 4.
6. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER
5. WIRING CODE: FACTORY WIRING: HIGH VOLTAGE LOW VOLTAGE FIELD WIRING: HIGH VOLTAGE
4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW PK - PINK
3. ASTERISK (*) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.
2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO "Y" FROM THERMOSTAT/CONDENSER (SEE TABLE-1).
1. RED WIRE TO BE ON TRANSFORMER TERMINAL "3" FOR 230 VOLTS AND ON TERMINAL "2" FOR 208 VOLTS.
NOTES:
BR
BK BK
BR
PK
PU
BL BK
RD
CL GN
EM
1 2 3 4 5
PU GR PK WH
GR/YL
BK
BL
SEE NOTE 7
BL
5
24V
4
3
1
2
RD
BK
BK
BK
HTR 2*
HTR 1
TL2*
TL1
RD
SEE NOTE 1
F
SEE NOTE # 3
⚡
240V TR
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
T1
RD
WH
GR
T2
RD
WH
BL
MOTOR CONNECTIONS ONLY ONE WILL BE CONNECTED (SEE NOTE 2)
UNUSED WIRES MUST HAVE THEIR ENDS TAPED OR CAPPED
OPTIONAL CONNECTION
0140A00314-A
RD
RD
AWUF19/25 Wiring Diagram
SS-DAWUF
SS-DAWUF
www.daikincomfort.com WH BR
T1
T2
600 800 950
PK
PU
YL
BL BK
RD
CL GN
EM
1 2 3 4 5
PU YL GR PK WH
GR/YL
BK
MOTOR CONNECTIONS ONLY ONE WILL BE CONNECTED (SEE NOTE 2)
BL
UNUSED WIRES MUST HAVE THEIR ENDS TAPED OR CAPPED OPTIONAL CONNECTION
BL
5
24V
4
3
1
2
RD
BK
BK
BK
TL2*
TL1
⚡
RD
F
SEE NOTE # 3
HTR 2*
HTR 1
SEE NOTE 1
240V TR
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
BK
BR
BK
RD
WH
GR
RD
RD
WH
BL
BL
NOMINAL CFM
C
L1
L2
BL
RD
Warning
TABLE-1
18000 24000 30000
⚠
BK
RD
BK
RD
PURPLE PINK YELLOW
BK
BK
RD
BTUh
DISC
RD
BK
FIELD CONNECTIONS SEE NOTE 2 USE N.E.C CLASS 2 WIRE
WIRE COLOR
BK
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
6. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER
5. WIRING CODE: FACTORY WIRING: HIGH VOLTAGE LOW VOLTAGE FIELD WIRING: HIGH VOLTAGE
4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW
3. ASTERISK (*) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.
2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO "Y" FROM THERMOSTAT/CONDENSER (SEE TABLE-1).
1. RED WIRE TO BE ON TRANSFORMER TERMINAL "3" FOR 230 VOLTS AND ON TERMINAL "2" FOR 208 VOLTS.
NOTES:
0140A00276-A
RD
RD
AWUF31/32 Wiring Diagram
11
12
www.daikincomfort.com
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
7. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER
6. WIRING CODE: FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE SEE NOTE 3
5. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW
4. ASTERISK (*) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.
3. SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE WIRING CONNECTIONS.
2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO TERMINAL "4" ON RELAY.
NOTES: 1. RED WIRE TO BE ON TRANSFORMER TERMINAL "3" FOR 230 VOLTS AND ON TERMINAL "2" FOR 208 VOLTS.
⚠
BK
RD
RD
RD
RD BK
RD
L1
L2
C
Warning
BK
DISC
RD
BK
FIELD CONNECTIONS SEE NOTE 3 USE N.E.C CLASS 2 WIRE
BR BL
WH
BL
T1
T2
RD
BK
BR
BK
RD
WH
BL
BL
WH YL OR BR
PU
BL BK
RD
CL GN
EM
1 2 3 4 5
OR BR YL
WH
3
6
9
B
GR/YL
1
4
7
A
WH
RD
GR
BL
PU
YL
BL
5
24V
RD
4
3
1
2
RD
BK
BK
BK
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
WH
BL
BK
BL
RD GR
SPEED TAPS FROM MOTOR SEE NOTE 2
⚡
240V TR
SEE NOTE 1
RD
SEE NOTE 4
HTR 2*
HTR 1
F
TL2*
TL1
0140A00321-A
RD
RD
AWUF37 Wiring Diagram
Our continuing commitment to quality products may mean a change in specifications without notice. ©2016 • Houston, Texas • Printed in the USA.
SS-DAWUF