Transcript
e
GE Power Controls
Uninterruptible Power Supplies
Uninterruptible Power Supplies 500 VA - 4 MVA
Uninterruptible Power Supplies
For more than a century, GE has led the way with innovative technologies and groundbreaking quality initiatives – literally helping to power the world. Along the way, through the development and delivery of state-of-the-art products and uncompromising service, GE has also built a legacy as a leading supplier of critical power solutions. To bridge the gap between the traditional utility grid and the needs of today’s business, GE offers a complete portfolio of critical power products and services, from desktop Uninterruptible Power Supply (UPS) units to engineered power systems, and from basic UPS and battery maintenance to comprehensive service contracts covering every aspect of your power quality and delivery system. At GE, our goal is simple – to never let power quality stand in the way of our customers’ success. That’s why GE is committed to developing and delivering: UPS
TECHNOLOGY
FOR
THE
D I G I TA L
WORLD
Uninterruptible Power Supplies
Introduction
UPS Topologies
1
RPA TM Redundant Parallel Architecture TM
2
IEM TM Intelligent Energy Management TM
3
Service for Mission Critical Power
4
g
UPS UPS Topologies A Brief Overview Off-Line
Introduction
The off-line system channels the incoming utility power, via a filter, directly to the load. As soon as the incoming power is outside tolerance, the UPS switches to battery operation. GE’s solution: none.
Utility
Switch
Filter
Load DC
AC
AC
DC Battery
Line Interactive
1
The line-interactive system channels the incoming utility power, via an AVR - Automatic Voltage Regulator, directly to the load. Compared to off-line, the system can handle much larger voltage variations before switching to battery operation. GE’s solution: Match lite, Match.
Utility
Filter
Switch
AVR
Load
DC
AC DC
AC Battery
On-Line (double conversion) Input and output are completely separated: the output converter (DC to AC) continuously supplies the critical load with a completely new, regulated and clean sine wave output. No switching takes place when the incoming utility power gets outside tolerances. A bypass switch automatically transfers the load to the utility when the output converter is unable to supply the load (e.g. due to overload or overtemperature). GE’s solution: NetPro, LanPro, SitePro
1.1
g
GE Industrial Systems
Static Switch Utility
DC
AC DC
Load AC
Battery
Notes
Introduction: UPS Topologies 1
1.2
g
x
UPS TM
RPA TM Redundant Parallel Architecture The Principle
Introduction
GE provides a unique technology called Redundant Parallel Architecture (RPA™) that can parallel Uninterruptible Power Supply (UPS) modules with true redundancy. With RPA™, there is no need for external electronics or switches to control the UPS modules in the parallel system. One of the UPS modules in the system arbitrarily takes a leadership role, while the other UPS modules have access to all control parameters. If one UPS fails to operate, the load is automatically redistributed among the others. If the lead UPS fails to operate then a different UPS automatically takes on the leadership role. The RPA systems are designed to have no single points of failure, ensuring the highest level of power protection for critical loads.
2
Utility
Load
A Unique Concept Many other so-called redundant UPS offerings have one critical shortfall, in that they have critical components that are not redundant. RPA technology provides complete redundancy of all critical components and there are no single points of failure. RPA technology allows UPS system expansion not only to increase capacity but also to improve the reliability of the power provided to critical loads. For mission critical applications, RPA technology provides true redundancy for the highest reliability.
Characteristics RPA Configuration provides complete redundancy of all critical components and allows paralleling of up to four units for increased load capacity. It ensures excellent dynamic behaviour based on output voltage load sharing. This provides the highest reliability and availability for mission-critical applications. Modular design allows for system upgrades to meet future power needs without any interruption to the critical load or transfer to bypass. Easy to install and maintain. Scaleable design allows for efficient use of capital. Peer-to-Peer architecture where any UPS can be the “logic leader” ensuring no single points of failure.
2.1
g
GE Industrial Systems
RPA A Comparative Overview TM
Introduction: RPA
Multiple UPS are configured in a system to support an increase in load capacity and/or to improve reliability. There are several configurations that include multiple UPS. These configurations all share a common shortfall: they all have critical components that are not redundant.
Parallel System with Automatic Transfer Switch
Utility
UPS #2
ATS Cititcal Load
The parallel system with an Automatic Transfer Switch (ATS) consists of one or more UPS modules with outputs connected by a switch that senses a loss in voltage and transfers the load to a different module or modules.
TM
UPS #1
Communication Link
If one of the UPS modules fails, another unit is available to provide power to the load. No load sharing.
2
Additional cost of the ATS. The ATS is a single point of failure: if it fails, the load will be interrupted even if utility power is available.
Parallel System with Paralleling Cabinet
Utility
UPS #1
Communication Link
The parallel cabinet configuration uses an external set of centralised electronics to distribute the load between the system’s UPS modules.
UPS #2
Paralelling Cabinet Cititcal Load
If one of the UPS modules fails, another unit is available to provide power to the load. Motor-operated breakers replace the function of the ATS. While less expensive than an ATS, they operate much more slowly. Failure or malfunction of the shared control electronics will result in a load interruption, which is possible even if the power is present. The shared electronics package is a single point of failure. Non-redundant communications links. System price is increased because of the additional cost of the shared control electronics and motor-operated breakers.
g
2.2
UPS TM
RPA A Comparative Overview Hot Standby Utility
Introduction
The cascade system or isolated redundant system uses the bypass static switch of the primary UPS to tie the output of a secondary (stand-by) UPS to the load.
Bypass Line
Bypass Line
Secundary UPS
Primary UPS
Output Critical Load
Inexpensive, since no additional components are added to the system. There are many single points of failure. No sharing of the load. If the primary unit fails, the secondary unit must be able to accept a 100% load increase in 10 milliseconds. Overload capacity is limited to the rating of the static switch of the primary module
2
System MTBF* is typically lower than the MTBF of a single module. * Mean Time Between Failures
Parallel System with Centralized Logic The parallel system with centralized logic is basically designed the same as the paralleling cabinet configuration. The difference is that they utilize the control electronics of one “lead” UPS module to control the distribution of the load between the system’s other modules.
Non-redundant data bus Utility
Lead UPS #1
UPS #2
UPS #3
Centralised control electronics
UPS #4
UPS #5
UPS #6
Critical Load
No ATS required. If the “lead” UPS module fails, the remaining units are uncontrolled. The system may go to bypass on all units, or may stop operation completely. If the communication link between the lead and other units fails, the load may be interrupted even without a utility power failure.
As stated before, these configurations all share a common shortfall: they all have critical components that are not redundant. GE´s RPA™ technology provides complete redundancy of all critical components and there are no single points of failure. RPA technology allows UPS system expansion not only to increase capacity but also to improve the reliability of the power provided to critical loads. For mission critical applications, RPA technology provides true redundancy for the highest reliability.
2.3
g
GE Industrial Systems
Notes
Introduction: RPA
TM
2
2.4
g
x
UPS TM
10%
15%
IEM TM Intelligent Energy Management
38%
GE offers the award-winning Intelligent Energy Management™ (IEM™) capability to optimise energy costs while maintaining the highest possible reliability for parallel redundant UPS systems.
37%
Introduction
Purchasing Direct operating cost Indirect operating cost Maintenance Typical life cycle cost of a large UPS.
Load
80%
20% 20% 00:0
0
07:0
0
18:0
0
Time 00:0
0
The life cycle cost of a UPS system is built up from different components. In general, approximately half of the total cost is operating cost as a result of energy losses - both direct heat losses in the UPS and indirect energy losses of the air conditioning system. UPS systems are engineered into applications taking into account the maximum load that needs to be supplied by the system. In practice the UPS will only supply a part of that load for most of the time. Many applications are shut down outside business hours. In addition very often a safety margin is included (over-dimensioning) for future expansion. As a result the system is not used at its nominal rating most of the time during operation. This reduces the efficiency of the system and increases the energy costs. For parallel UPS installations, secured with RPA™, IEM saves energy by dynamically utilising the UPS modules as required to supply the load without compromising on the power reliability.
In a typical application the actual load supplied is generally smaller than the nominal rating of the system.
3 The set-up of IEM™ is flexible, giving the end user the freedom of choice to select redundancy degrees in different time periods. IEM also rotates amongst the units that are switched off to get operating hours equally distributed over all units. Use of IEM resulted in incremental energy savings of up to $33,000 annually for a system of four 100kVA units secured by RPA™ operating at full load for 50 hours per week and partial load (10%) for the remaining time.
Benefits Reduced energy consumption Maintaining of power quality and reliability to the critical load Mains power quality monitoring User-definable protection levels Scheduled activation Automatic switch on of additional units in critical situations, increasing reliability Equal operating hours for each UPS in a parallel system
3.1
g
GE Industrial Systems
IEM compared to legacy parallel system TM
UPS2 100kVA
75%
UPS3 100kVA
75%
UPS4 100kVA
75%
Load = 100%
Time 18:00
07:00 Load 300 kVA
UPS1 100kVA
15%
UPS2 100kVA
15%
UPS3 100kVA
15%
UPS4 100kVA
15%
In full load condition the efficiency of a UPS is optimal. However, this condition only occurs typically 10 hours / day.
Efficiency 4 UPS
Load %
TM
75%
Introduction: IEM
UPS1 100kVA
Legacy Parallel System Full-Load Condition
Load
Legacy Parallel System Partial-Load Condition
Load
Load = 20% Time 07:00
18:00 Load 60 kVA
In partial load condition (most of the time) the efficiency of the UPS is lower causing higher energy costs.
Efficiency 4 UPS
Load %
3 IEM Load
UPS1 100kVA
Load = 20% UPS2 100kVA
Time 07:00
18:00 Load 60 kVA
UPS3 100kVA
30%
UPS4 100kVA
30%
Efficiency 2 UPS
Intelligent Energy Management Partial Critical Load Condition (UPS Redundancy) With IEM installed 2 units will be switched off automatically. In this way the efficiency is improved, still maintaining a n+1 redundant system.
IEM UPS1 100kVA
Load = 20% 18:00
UPS4 100kVA
Time 07:00
Load 60 kVA
UPS3 100kVA
Efficiency 1 UPS
60%
TM
Load %
Load
UPS2 100kVA
TM
TM
Intelligent Energy Management Partial non-Critical Load Condition (Utility Redundancy)
TM
With IEM installed 3 units can be switched off. In this way the efficiency is improved even more. The bypass is still available and will supply the load in case of a failure.
Load %
g
3.2
UPS Service for Mission-Critical Power Whether you are a large corporation with multiple sites or a small business owner with a single location, GE will enable you to have a constant supply of clean and reliable power to keep your business up and running. GE offers a comprehensive portfolio of power quality services including:
Introduction
UPS installation and start-up, upgrades, spare parts and on-site services Battery installation, management and maintenance Power grounding Harmonic analysis Remote monitoring & diagnostics Global preventive and corrective services Training
Service Coverage GE has local offices in a number of countries around the globe and also a network of selected business partners, whose salespeople and service engineers combine expertise in our solutions with an in-depth knowledge of local market conditions. GE’s business partners, located in more than 80 countries around the world, use all that expertise and knowledge to adapt GE’s products and services precisely to their customers’ needs. Supported by highly trained people at our head offices, these business partners are able to provide advice, support and installation 24 hours a day.
4
4.1
g
GE Industrial Systems
Notes
Introduction: Service 4
4.2
g
x
Contents
Notes
g
GE Industrial Systems
x
Uninterruptible Power Supplies
A
NetPro and NetPro 19 inch
B
3 - 10 kVA
LanPro 11
C
5 - 10 kVA
LanPro 31T
D
LanPro 31
E
LanPro 33
F
SitePro
G
Connectivity Solutions: Protection and Management Software
H
0.6 - 4 kVA
3-1 phase
1-1 phase
Match and Match 19 inch
8 - 20 kVA
10 - 30 kVA 3-3 phase
Pluggable
0.5 - 3 kVA
Hard-wired
On-Line double conversion
Line-inter.
Uninterruptible Power Supplies
10 - 500 kVA
g
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies Match Applications
The line-interactive Match UPS is used in a wide range of IT, networking and telecommunications applications. It will protect servers, hubs, switches and routers, and may also be installed to protect PCs, workstations, cash registers, fax machines, modems and ISDN adaptors.
Characteristics A
Function Providing exceptional cost-critical protection for electrical equipment.
Standards/Marking Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2
The line-interactive Match UPS normally supplies the load through a bypass circuit. Filtering capabilities guard against surges, spikes and high frequency interferences. The utility also keeps the battery fully charged. The input voltage window is extremely wide: as long as the input voltage is within 165-275Vac (Match 500-1500VA) or even between 140-305Vac (Match 2200-3000) the Automatic Voltage Regulation (AVR) guarantees an output voltage that is between 190-254Vac and acceptable for every modern ICT device. In case of a mains failure the UPS switches to battery operation with a transfer time of 4 milliseconds, sufficiently short for computers which therefore will continue to operate without interruption.
Technical Specifications (general) Input voltage range 500-1500VA models, 70% load Input voltage range 2200-3000VA models, 70% load Input frequency Output voltage Output frequency Ambient operating temperature Relative humidity Audible noise Communication interface Protection degree
165-275 Vac 140-305Vac 50 or 60Hz ± 5% 230Vac ± 2% (battery operation) 50 or 60Hz, autosensing -10 to 40°C 95% non-condensing 35-45 dB(A) RS232; Plug and Play (except ML500); open collector alarm contacts (model dependent) IP 20
Runtime table (lite) 500
700
700L
1000
1000L
1500
2200
3000
minutes, at typical UPS load (75%)
7
12
40
13
28
16
7
7
Watts*
42 10 4 -
84 26 13 8 -
190 70 41 30 -
120 41 23 15 8 -
190 70 41 30 20 -
190 70 41 30 20 10 -
210 82 50 35 22 11 5 -
263 104 69 47 30 17 7 5
Match (lite) UPS model
60 180 300 420 600 900 1540 2100
* max. power factor: Match 500-1500: 0.6 Match 2200/3000: 0.7
A.1
g
GE Industrial Systems
Match - line-interactive Uninterruptible Power Supplies Match lite
Runtime (minutes) @ 100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Battery (V/Ah)
Number of IEC 320 outlets
Ref.No. see note†
500/300
4
150x102x300
7.4
12/7
2
(9)12320
4 8 8 10 5 5
144x155x350 144x155x350 225x180x360 225x180x360 225x187x485 225x187x485 225x187x485 225x187x485
7.2 10.0 16.5 20.8 18.0 21.3 20.1 26.5
12/7 24/7 36/7 36/12 36/14 48/14
3 3 4 4 7 7 -
(9)12321 (9)12322 (9)12324 (9)12326 (9)12328 (9)12330 (9)12329 (9)12331
Match lite LINE
BAT
ON/TEST
OFF
GE Digital Energy
Match 1000-3000 VA GE Digital Energy
Match on alarm avr progr. shutdown replace battery on battery
GE Digital Energy
Match
500/300 700/420 1000/600 1500/900 2200/1540 Batt. pack 3000/2100 Batt. pack
Line-Interactive: Match
Rating (VA/W)
on alarm avr
Match 2200 and 3000 require separate battery pack (not shown)
progr. shutdown replace battery on battery
500-700 VA
Match L built-in longer runtime
700/420 1000/600
30 20
225x180x360 225x180x360
20.8 20.8
36/12 36/12
4 4
(9)12323 (9)12325
700/420 1000/600 1500/900 2200/1540 3000/2100
8 8 10 5 5
3HUx19”x440mm 3HUx19”x440mm 3HUx19”x440mm 6HUx19”x440mm 6HUx19”x440mm
19.0 22.0 26.0 50.0 57.0
12/7 24/7 36/7 36/12 48/14
3 3 4 4 7
(9)12439 (9)12440 (9)12441 (9)15571 (9)15572
for 2000VA for 3000VA
15 15
3HUx19”x440mm 3HUx19”x440mm
26.0 30.0
36/14 48/14
-
(9)12453 (9)12454
-
-
53x130x204
0.8
-
-
(9)12349
A
12 9
3 6
GE Digital Energy
Match on alarm avr progr. shutdown replace battery on battery
Match 19 inch GE Digital Energy
Match on alarm avr progr. shutdown replace battery on battery
GE Digital Energy
Battery Pack
2200-3000 19”: 6HU
Battery Packs for Match 19 inch 12 9
3
GE Digital Energy
Battery Pack
6
to increase runtime
Options for Match and Match 19 inch Manual Service Bypass
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
A.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies NetPro® Applications
The on-line NetPro® UPS is designed for mission-critical applications. It is used in a wide range of IT networking and telecommunications applications: mission-critical servers, telecommunication equipment and local area networks.
Characteristics Function Providing exceptionally reliable protection for electrical equipment.
B
Standards/Marking Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2; EN 50081-1 + EN 50082-1; IEC 61000-4-5
The NetPro UPS is a true VFI (Voltage & Frequency Independent) online double conversion UPS. This technology allows the NetPro to eliminate any power reliability problem. The incoming AC mains power is continuously converted by the input converter to DC, which is used to charge the batteries and to supply the output converter. This output converter synthesizes a completely new AC sine wave output for the connected load. Any mains disturbance is blocked at the input. The 2000-4000VA models are equipped with a LCD information panel with status and alarm settings. The 3000-4000VA models have a programmable outlet that can be switched off for less critical loads, thus maximizing up-time of critical devices.
Technical Specifications (general) 120-264 Vac 160-264 Vac 50 or 60Hz ± 10% 230Vac ± 2% 220/230/240Vac ± 1% 50 or 60Hz, front selectable -10 to 40°C 95% non-condensing 35-45 dB(A) RS232; Plug and Play; open collector alarm contacts IP 20
Input voltage range 600-2000VA models, 70% load Input voltage range 3000-4000VA models, 70% load Input frequency Output voltage 600-1500VA models Output voltage 2000-4000VA models Output frequency Ambient operating temperature Relative humidity Audible noise Communication interface Protection degree
Runtime table
B.1
g
NetPro UPS model
600
1000
1500
2000
3000
4000
at typical UPS load (75%)
12
12
10
12
12
10
Watts
53 30 14 9 -
90 49 25 15 8 -
120 71 36 24 12 7 -
190 117 60 38 21 13 9 -
270 165 95 63 35 22 15 11 9 -
310 185 105 72 40 25 18 13 10 7
60 120 240 360 600 900 1200 1500 1800 2400
GE Industrial Systems
On-Line double conversion: NetPro
NetPro - On-Line Uninterruptible Power Supplies NetPro
Rating (VA/W)
Runtime (minutes) @ 100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Battery (V/Ah)
600/360 1000/600 1500/900 2000/1200 3000/1800 4000/2400
9 8 7 9 9 7
225x185x430 225x185x430 225x185x430 293x220x557 293x220x557 293x220x557
13.0 15.5 18.0 29.0 38.0 42.0
24/7 36/7 48/7 72/7 108/7 120/7
2000-4000 VA GE Digital Energy
NetPro operation alarm
progr. shutdown weak mains
on line
9 mm 6 mm
ok
GE Digital Energy
NetPro on alarm on bypass progr. shutdown replace battery
Number of DC connector IEC 320 outlets (batt. ext.) 2 2 2 2 2+1* 2+1*
Ref.No. † see note
no yes no yes yes no
(9)12332 (9)12333 (9)12334 (9)12335 (9)12337 (9)12339
on battery
*= progr. output
600-1500 VA
NetPro ISO
2000/1200 3000/1800
9 9
293x220x557 293x220x557
40.0 50.0
72/7 108/7
2 2+1
yes yes
(9)12336 (9)12338
for NP 1000 for NP 1000
35 -
225x185x430mm 225x185x430mm
19.0 4.0
36/14 no batt.
-
yes yes
(9)12341 (9)12340
for NP 2000 for NP 2000 for NP 2000 for NP 2000
22 36 52 -
293x220x557mm 293x220x557mm 293x220x557mm 293x220x557mm
19.0 35.0 50.0 4.0
72/7 72/14 72/21 no batt.
-
yes yes yes yes
(9)12342 (9)12343 (9)12345 (9)12344
for NP 3000 for NP 3000 for NP 3000
22 37 -
293x220x557mm 293x220x557mm 293x220x557mm
27.0 50.0 4.0
108/7 108/14 no batt.
-
yes yes yes
(9)12346 (9)12348 (9)12347
600/360 1000/600 1500/900 2000/1200 3000/1800
9 8 7 9 9
3HUx19”x440mm 3HUx19”x440mm 3HUx19”x440mm 3HUx19”x440mm 6HUx19”x440mm
19.0 22.0 24.0 29.0 52.0
24/7 36/7 48/7 72/7 108/7
4 4 4 4 4
no no yes yes yes
(9)12444 (9)12445 (9)12446 (9)12447 (9)15573
for NP 1000 for NP 1000
35 70
3HUx19”x440mm 3HUx19”x440mm
28.0 42.5
36/14 36/28
-
yes yes
(9)12449 (9)12450
for NP 2000
36
3HUx19”x440mm
42.5
72/14
-
yes
(9)12451
for NP 3000
22
3HUx19”x440mm
35.0
108/7
-
yes
(9)12452
-
-
53x130x204
0.8
-
-
-
(9)12349
GE Digital Energy
NetPro operation alarm
progr. shutdown weak mains
on line
ok
Galvanic isolation
Battery Packs for NetPro (ISO) 12 GE Digital Energy
Battery Pack
9
3 6
to increase runtime
NetPro 19 inch GE Digital Energy
NetPro operation alarm
progr. shutdown weak mains
on line
ok
B
600-2000 19”: 3HU
Battery Packs for NetPro 19 inch 12 9
3 GE Digital Energy
6
Battery Pack
to increase runtime
Options for NetPro and NetPro 19 inch Manual Service Bypass
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
B.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies ® LanPro 11
Applications
® The on-line LanPro UPS is designed for a range of mission-critical applications. The LanPro is easy to install and service, optimised for the office environment. The robust design allows for more traditional industrial applications.
Characteristics Function Providing exceptionally reliable protection for electrical equipment.
Standards/Marking Safety: EN 50091-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2 Surge capability: IEC 61000-4-5 (6kV 1.2/50µs, 3kA 8/20µs)
C
The LanPro 11 UPS is a 1-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure, utilizing GE’s unique Redundant Parallel Architecture technology.
TM
TM (RPA )
Technical Specifications (general) 172-285 Vac
Input voltage range Input frequency range Output voltage Output frequency Environment Ambient operating temperature Relative humidity Audible noise Interfacing Standard features RPA Battery extension Backfeed protection Software compatibility
40-70 Hz 220/230/240 Vac ± 1% (user selectable) 50 or 60 Hz, front selectable IP 20 (IEC 60529) -10 to 40°C (14° to 104°F) 95% non-condensing 40-55 dB(A) (load and temperature dependent) std: RS232; optional: potential free contacts, SNMP ECO mode, SBM Superior Battery Management, boost charging optional optional for 5-10 kVA models, not available for 3 kVA optional for 3-6 kVA models, not available for 8-10 kVA TM TM TM TM PowerFLAG , PowerJUMP DataShield , PowerJUMP Manager , PowerJUMPin , IRIS
Runtime table 3-11
5-11
6-11
8-11
10-11
at typical UPS load (75%)
16
16
12
18
12
VA/Watts
30 15 10 -
60 40 18 10 -
60 40 18 10 8 -
120 60 40 22 17 11 -
120 60 40 22 17 11 8
LanPro UPS model
C.1
g
1000 / 800 2000 / 1600 3000 / 2400 5000 / 4000 6000 / 4800 8000 / 6400 10000 / 8000
GE Industrial Systems
On-Line double conversion: LanPro
LanPro 11 - Installable 1-1 phase On-Line UPS LanPro 11 single operation with batteries
LanPro 11 parallel operation with batteries
LanPro 11 single operation without batteries
LanPro 11 parallel operation without batteries
Rating (kVA)
Battery (V/Ah)
Runtime (minutes) 50/100% load
Dimensions (HxWxD, mm)
Net weight (kg)
DC connector (batt. ext.)
Ref.No. † see note
3 5 6 8 10
144/7 240/7 240/7 240/12 240/12
25/10 25/10 20/8 29/11 22/8
537x313x590 537x313x590 537x313x590 680x313x720 680x313x720
85 110 115 165 170
no* yes yes yes yes
(9)12354 (9)12362 (9)12374 (9)12386 (9)12398
3 5 6 8 10
144/7 240/7 240/7 240/12 240/12
25/10 25/10 20/8 29/11 22/8
537x313x590 537x313x590 537x313x590 680x313x720 680x313x720
85 110 115 165 170
no* yes yes yes yes
(9)12356 (9)12364 (9)12376 (9)12388 (9)12400
3 5 6 8 10
144/7 240/7 240/7 240/12 240/12
25/10 25/10 20/8 29/11 22/8
537x313x590 537x313x590 537x313x590 680x313x720 680x313x720
53 58 63 93 98
no* yes yes yes yes
(9)12353 (9)12361 (9)12373 (9)12385 (9)12397
3 5 6 8 10
144/7 240/7 240/7 240/12 240/12
25/10 25/10 20/8 29/11 22/8
537x313x590 537x313x590 537x313x590 680x313x720 680x313x720
53 58 63 93 98
no* yes yes yes yes
(9)12355 (9)12363 (9)12375 (9)12387 (9)12399
C
* For longer runtimes choose LanPro 5-11
Battery Packs including batteries
Battery Packs without batteries
Options for LanPro 11
for LP 5-11 for LP 5-11
240/7 240/14
53/25 83/45
537x313x590mm 537x313x590mm
70 120
-
(9)12433 (9)12436
for LP 6-11 for LP 6-11
240/7 240/14
44/21 69/35
537x313x590mm 537x313x590mm
70 120
-
(9)12433 (9)12436
for LP 8-11 for LP 8-11
240/7 240/14
45/22 64/33
537x313x590mm 537x313x590mm
70 120
-
(9)12433 (9)12436
for LP 10-11 for LP 10-11
240/7 240/14
36/16 51/25
537x313x590mm 537x313x590mm
70 120
-
(9)12433 (9)12436
for 5/6/8/10-11
-
-
537x313x590mm
20
-
(9)12435
RPA Redundant Parallel Architecture Kit (1 per unit) Backfeed Relay for LanPro 3/5/6-11 Connector and cable for 3rd party external battery
(9)12351 (9)15541 (9)12431
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
C.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies LanPro® 31T Applications
®
The on-line LanPro UPS is designed for a range of mission-critical applications. The LanPro is easy to install and service, optimised for the office environment. The robust design allows for more traditional industrial applications.
Characteristics Function
Standards/Marking
The LanPro 31T UPS is a 3-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure,
Safety: EN 50091-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2 Surge capability: IEC 61000-4-5 (6kV 1.2/50µs, 3kA 8/20µs)
utilizing GE’s unique Redundant Parallel ArchitectureTM (RPATM) technology. The LanPro 31T is a LanPro 11 equipped with a 3-1 phase conversion input transformer, galvanically separating the UPS from the incoming 3-phase mains.
Providing exceptionally reliable protection for electrical equipment.
D
Technical Specifications (general) 340-470 Vac
Input voltage range Input frequency range Output voltage Output frequency Environment Ambient operating temperature Relative humidity Audible noise Interfacing Standard features RPA Battery extension Backfeed protection Software compatibility
40-70 Hz 220/230/240 Vac ± 1% (user selectable) 50 or 60 Hz, front selectable IP 20 (IEC 60529) -10 to 40°C (14° to 104°F) 95% non-condensing 40-55 dB(A) (load and temperature dependent) std: RS232; optional: potential free contacts, SNMP ECO mode, SBM Superior Battery Management, boost charging optional optional standard available PowerFLAGTM, PowerJUMP DataShieldTM, PowerJUMP ManagerTM, PowerJUMPinTM, IRIS
Runtime table LanPro UPS model
D.1
g
5-31T
6-31T
8-31T
10-31T
at typical UPS load (75%)
16
12
18
12
VA/Watts
60 40 18 10 -
60 40 18 10 8 -
120 60 40 22 17 11 -
120 60 40 22 17 11 8
1000 / 800 2000 / 1600 3000 / 2400 5000 / 4000 6000 / 4800 8000 / 6400 10000 / 8000
GE Industrial Systems
On-Line double conversion: LanPro
LanPro 31T - Installable 3-1 phase On-Line UPS LanPro 31T single operation with batteries
LanPro 31T par. operation with batteries
LanPro 31T single operation without batteries
LanPro 31T par. operation without batteries
Battery Packs including batteries
Battery Packs without batteries
Options for LanPro 31T
Rating (kVA)
Battery (V/Ah)
Runtime (minutes) 50/100% load
Dimensions (HxWxD, mm)
Net weight (kg)
DC connector (batt. ext.)
Ref.No. † see note
5 6 8 10
240/7 240/7 240/12 240/12
25/10 20/8 29/11 22/8
855x313x590 855x313x590 995x313x720 995x313x720
180 185 270 275
yes yes yes yes
(9)12408 (9)12414 (9)12420 (9)12426
5 6 8 10
240/7 240/7 240/12 240/12
25/10 20/8 29/11 22/8
855x313x590 855x313x590 995x313x720 995x313x720
180 185 270 275
yes yes yes yes
(9)12410 (9)12416 (9)12422 (9)12428
5 6 8 10
240/7 240/7 240/12 240/12
25/10 20/8 29/11 22/8
855x313x590 855x313x590 995x313x720 995x313x720
128 133 198 203
yes yes yes yes
(9)12407 (9)12413 (9)12419 (9)12425
5 6 8 10
240/7 240/7 240/12 240/12
25/10 20/8 29/11 22/8
855x313x590 855x313x590 995x313x720 995x313x720
128 133 198 203
yes yes yes yes
(9)12409 (9)12415 (9)12421 (9)12427
for LP 5-31T for LP 5-31T
240/7 240/14
53/25 83/45
537x313x590mm 537x313x590mm
70 120
no yes
(9)12433 (9)12436
for LP 6-31T for LP 6-31T
240/7 240/14
44/21 69/35
537x313x590mm 537x313x590mm
70 120
no yes
(9)12433 (9)12436
for LP 8-31T for LP 8-31T
240/7 240/14
45/22 64/33
537x313x590mm 537x313x590mm
70 120
no yes
(9)12433 (9)12436
for LP 10-31T for LP 10-31T
240/7 240/14
36/16 51/25
537x313x590mm 537x313x590mm
70 120
no yes
(9)12433 (9)12436
for 5-10 kVA
-
-
537x313x590mm
20
-
(9)12435
RPA Redundant Parallel Architecture Kit (1 per unit) Connector and cable for 3rd party external battery
D
(9)12351 (9)12431
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
D.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies LanPro® 31 Applications
®
The on-line LanPro UPS is designed for a range of mission-critical applications. The LanPro is easy to install and service, optimised for the office environment. The robust design allows for more traditional industrial applications.
Characteristics Function Providing exceptionally reliable protection for electrical equipment.
Standards/Marking Safety: EN 50091-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2
The LanPro 31 UPS is a 3-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The transformerless design provides a high efficiency. In the ECO Mode the efficiency can be even further increased. The batteries are easy to replace by acces via the front. Superior Battery Management optimizes the lifespan of the batteries and keeps you from surprises.
Technical Specifications (general) 300-470 Vac
Input voltage range Input frequency range Output voltage Output frequency Environment Ambient operating temperature Relative humidity Audible noise Interfacing Standard features Battery extension Backfeed protection Software compatibility
E
45-65 Hz 220/230/240 Vac ± 1% (user selectable) 50 or 60 Hz, front selectable IP 20 (IEC60529) 0 to 40°C (32° to 104°F) 95% non-condensing 40-55 dB(A), load and temperature dependent std: RS232; potential free contacts, SNMP ECO mode, SBM Superior Battery Management optional standard available TM TM TM TM PowerFLAG , PowerJUMP DataShield , PowerJUMP Manager , PowerJUMPin , IRIS
Runtime table LanPro UPS model
8-31*
10-31*
15-31**
20-31**
at typical UPS load (75%)
22
16
23
13
VA/Watts
35 24 14 -
35 24 14 10 -
75 56 28 24 13 -
75 56 28 24 13 10
4000 / 3200 5000 / 4000 8000 / 6400 10000 / 8000 15000 / 12000 20000 / 16000
*7Ah batt.
E.1
g
GE Industrial Systems
**14Ah batt.
On-Line double conversion: LanPro
LanPro 31 - Installable 3-1 phase On-Line UPS LanPro 8-31
Battery capacity (V/Ah)
Runtime (minutes) 50/100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
240/7 240/14 240/7+14 240/14+14 240/7+28 240/14+28
7/14 52/36 78/58 168/80 210/101 250/125
1190x410x890 925x410x890 925x410x890 925x410x890 (2x) 925x410x890 (2x)
135 250 355 250+300 355+300 250+600 355+600
(9)11787 (9)11561 (9)11562 (9)11563 (9)11564 (9)11565 (9)11567
240/7 240/14 240/7+14 240/14+14 240/7+28 240/14+28
27/10 63/25 98/40 130/58 170/78 205/96
1190x410x890 925x410x890 925x410x890 925x410x890 (2x) 925x410x890 (2x)
135 250 355 250+300 355+300 250+600 355+600
(9)11789 (9)11561 (9)11562 (9)11563 (9)11564 (9)11565 (9)11567
UPS 15 kVA without battery 14Ah battery in UPS cabinet 28Ah battery, 1 extra cabinet 42Ah battery, 2 extra cabinets
240/14 240/14+14 240/14+28
40/13 86/33 132/55
1190x410x890 925x410x890 925x410x890 (2x)
150 365 365+300 365+600
(9)11791 (9)11562 (9)11564 (9)11567
UPS 20 kVA without battery 14Ah battery in UPS cabinet 28Ah battery, 1 extra cabinet 42Ah battery, 2 extra cabinets
240/14 240/14+14 240/14+28
27/10 60/25 100/41
1190x410x890 925x410x890 925x410x890 (2x)
150 365 365+300 365+600
(9)11793 (9)11562 (9)11564 (9)11567
925x410x890 925x410x890
85 300
(9)11566 (9)11568
-
-
(9)11000
UPS 8 kVA without battery* 7Ah battery in UPS cabinet* 14Ah battery in UPS cabinet* 21Ah battery, 1 extra cabinet** 28Ah battery, 1 extra cabinet** 35Ah battery, 2 extra cabinets** 42Ah battery, 2 extra cabinets** charger: * 2.1A std., ** 4.2A included
LanPro 10-31
UPS 10 kVA without battery* 7Ah battery in UPS cabinet* 14Ah battery in UPS cabinet* 21Ah battery, 1 extra cabinet** 28Ah battery, 1 extra cabinet** 35Ah battery, 2 extra cabinets** 42Ah battery, 2 extra cabinets** charger: * 2.1A std., ** 4.2A included
LanPro 15-31
LanPro 20-31
Options Battery Cabinets and -Charger
Battery cabinet without batteries Battery cabinet with batt. 240/14Ah Battery charger 4.2A, necessary for battery capacity over 14Ah on LP8-31 and LP10-31 ordered without batteries
E
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
E.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies LanPro® 33 Applications
®
The on-line LanPro UPS is designed for a range of mission-critical applications. The LanPro is easy to install and service, optimised for the office environment. The robust design allows for more traditional industrial applications.
Characteristics Function Providing exceptionally reliable protection for electrical equipment.
Standards/Marking Safety: EN 50091-1; EN 60950; IEC 60950; IEC 62040; EMC: EN 50091-2 (level A)
The LanPro 33 UPS is a 3-phase in / 3-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure, utilizing GE’s unique Redundant Parallel ArchitectureTM (RPATM) technology.
Technical Specifications (general) 324-478 Vac
Input voltage range
45-65 Hz 380/400/415 Vac ± 1% (user selectable) 50 or 60 Hz, front selectable IP 20 (IEC60529) 0 to 40°C (32° to 104°F) 95% non-condensing 40-55 dB(A), load and temperature dependent std: RS232, potential free contacts, SNMP SBM Superior Battery Management optional standard available TM TM TM PowerJUMP DataShield , PowerJUMP Manager , PowerJUMPin , IRIS
Input frequency range Output voltage Output frequency Environment Ambient operating temperature Relative humidity Audible noise Interfacing Standard features Battery extension Backfeed protection Software compatibility
F
Runtime table LanPro UPS model battery
F.1
g
10-33 7Ah
20-33 14Ah
30-33 21Ah
at typical UPS load (75%)
11
11
11
VA/Watts
35 17 10 7 -
70 43 24 17 11 7 -
110 59 40 31 18 13 7
3000 / 2400 5000 / 4000 8000 / 6400 10000 / 8000 15000 / 12000 20000 / 16000 30000 / 24000
GE Industrial Systems
On-Line double conversion: LanPro
LanPro 33 - Installable 3-3 phase On-Line UPS LanPro 10-33
LanPro 20-33
LanPro 30-33
Options RPA Options Battery Cabinets and -Charger
Options Special
Battery capacity (V/Ah)
Runtime (minutes) 50/100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
UPS 10 kVA without battery, single input UPS 10 kVA without battery, dual input 7Ah battery in UPS cabinet 14Ah battery in UPS cabinet 21Ah battery, 1 extra cabinet 28Ah battery, 1 extra cabinet 35Ah battery, 1 extra cabinet 42Ah battery, 1 extra cabinet
240/7 240/14 240/21 240/28 240/35 240/42
18/7 44/18 76/33 105/45 135/60 175/77
1280x500x780 1280x500x780 1050x760x780 1050x760x780 1050x760x780 1050x760x780
113 113 247 345 450 570 690 810
(9)11600 (9)11616 (9)11584 (9)11585 (9)11591 (9)11592 (9)11593 (9)11594
UPS 20 kVA without battery, single input UPS 20 kVA without battery, dual input 14Ah battery in UPS cabinet 21Ah battery, 1 extra cabinet 28Ah battery, 1 extra cabinet 35Ah battery, 1 extra cabinet 42Ah battery, 1 extra cabinet
240/14 240/21 240/28 240/35 240/42
18/7 32/12 44/18 60/25 75/33
1280x500x780 1280x500x780 1050x760x780 1050x760x780 1050x760x780 1050x760x780
140 140 372 450 570 690 810
(9)11602 (9)11617 (9)11585 (9)11591 (9)11592 (9)11593 (9)11594
UPS 30 kVA without battery, single input UPS 30 kVA without battery, dual input 21Ah battery in UPS cabinet 28Ah battery, 1 extra cabinet 35Ah battery, 1 extra cabinet 42Ah battery, 1 extra cabinet
240/21 240/28 240/35 240/42
18/7 27/11 37/14 44/18
1280x660x780 1280x660x780 1280x500x780 1050x760x780 1050x760x780 1050x760x780
140 140 520 570 690 810
(9)11604 (9)11618 (9)11586 (9)11592 (9)11593 (9)11594
-
-
(9)11615 (9)11587
1050x760x780 -
90 -
(9)11595 (9)11588 (9)11589 (9)11590 (9)11596 (9)11597 (9)11598 (9)11599
-
-
(9)11001
-
-
(9)11002
-
-
(9)15660 (9)15661 (9)15662
RPA Redundant Parallel Architecture kit factory installed RPA Redundant Parallel Architecture kit field installed, 1 per unit
Battery cabinet without batteries, incl. cables (5m) and batt. temp. measurement Mounting set for 7Ah battery in UPS cabinet (40 blocks) without battery Mounting set for 2x7Ah battery in UPS cabinet (80 blocks) without battery Mounting set for 3x7Ah battery in UPS cabinet (120 blocks) without battery Mounting set for each 7Ah battery in battery cab. (40 blocks) without battery, incl. fuses Battery fuse box (with fuses) LP10-33 Battery fuse box (with fuses) LP20-33 Battery fuse box (with fuses) LP30-33 Battery charger 2.8A, necessary for battery capacity over 14Ah on LP10-33 ordered without batteries Battery charger 4.2A, necessary for battery capacity over 28Ah on LP10-33 and LP20-33 ordered without batteries Note: UPS and battery cabinets without batteries are also without battery mounting sets. To mount locally purchased batteries, order the mounting set.
Wooden crate (per cabinet) mandatory for sea and air freights 10-20 kVA Wooden crate (per cabinet) mandatory for sea and air freights 30 kVA Wooden crate (per cabinet) mandatory for sea and air freights Battery Cabinets
F
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
F.2
UPS Uninterruptible Power Supplies
Uninterruptible Power Supplies SitePro 10-500 kVA Applications
The on-line SitePro UPS is an extremely reliable UPS providing critical power protection for a wide range of demanding mission-critical applications such as computer and data centers, medical facilities, broadcasting and sattelite transmission systems, manufacturing and process control units, security systems, financial institutions, transportation infrastructure etc. etc.
Function
Characteristics
Providing exceptionally reliable protection for electrical equipment.
The SitePro family of 3-phase in / 3-phase out high-performance UPS systems operates in a double conversion mode (providing true on-line operation), thus providing the highest levels of power reliability. Each UPS is fully compliant with international standards regarding Voltage and Frequency Independent (VFI) operation. True VFI makes the GE SitePro an extremely reliable UPS for data security and other demanding critical applications, even under the toughest conditions.
Standards/Marking Safety: EN 50091; IEC 62040-0; EMC: EN 50091-2; IEC 62040-2
The SitePro UPS is available in models from 10 kVA up to 500 kVA. For high-power redundant applications, the GE SitePro can be installed with up to eight units in parallel achieving power protection up to 4 MVA. The systems are controlled in a true peer-to-peer configuration with redundancy in all critical elements and functions, utilizing GE’s unique Redundant Parallel ArchitectureTM (RPATM) technology. This advanced technology provides the highest possible system reliability for mission critical applications with no single points of failure.
G
The SitePro 400-500. Paralelling 8 units of 500 kVA each results in a 4 MVA Parallel System!
G.1
g
GE Industrial Systems
UPS On-Line double conversion: SitePro
Technical Specifications (model dependent) 10
Output power rating (kVA)
1 Output power factor 10 Output power rating (kW) Dimensions HxWxD (mm) Weight (without batteries) kg 240 Noise level (DIN45630) dB(A) 48
15
20
30
1 1 1 15 20 30 1450x680x800 290 290 320 50 50 55
40
60
0.9 54 1450x750x800 475 350 60 60 1 40
80
100
120
0.9 0.9 0.9 90 108 72 1450x1100x800 670 745 750 63 63 63
150
200
0.9 0.9 135 180 1800x1100x800 930 1000 65 65
250
300
400
500
0.9 0.9 0.9 0.9 225 270 360 450 1800x1550x800 1800x2600x800 1450 1550 2725 2950 68 68 70 70
Technical Specifications (general) 320-460 Vac 45-66 Hz 3x380/400/415 Vac +N ± 1% (user selectable) 50 or 60 Hz, front selectable < 2% < 3% > 3:1 125% 10 min., 150% 1 min. (400-500 kVA 30 sec.)
Input voltage range Input frequency range Output voltage Output frequency Output distortion at linear load Output distortion at non-linear load Crest factor Overload capability on inverter Output voltage regulation static dynamic Overall efficiency at 100% load (double conversion mode) Environment Ambient operating temperature Relative humidity Interfacing Standard features Battery extension Backfeed protection Software compatibility
± 1% ± 3% up to 94.5% IP 20 (IEC60529) 0 to 40°C (32° to 104°F) 95% non-condensing std: RS232, potential free contacts, programmable relays SBM Superior Battery Management optional standard available TM TM TM PowerJUMP DataShield , PowerJUMP Manager , PowerJUMPin , IRIS
Runtime table 10-60 kVA* SitePro UPS model
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
60 kVA
8 15 30 43 50 100 120
10 15 24 30 60 70
6 10 16 20 40 50
6 10 12 25 30
6 7 17 20
10 12
Capacity of battery set (V/Ah) 360 / 10 360 / 17 360 / 24 360 / 33 360 / 38 360 / 65 360 / 76
*For the full SitePro range (10-500 kVA) runtimes are possible from 5 minutes up to 4 hours. Contact your dealer for customized battery solutions not mentioned in this catalog.
G
g
G.2
Uninterruptible Power Supplies
UPS SitePro 10
SitePro 15
SitePro 20
G
SitePro 10-500 - Installable 3-3 phase On-Line UPS Battery capacity (V/Ah)
Runtime (minutes) 100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
UPS 10 kVA without battery, 6-pulse rectifier RPA kit installed in factory 10Ah battery in UPS cabinet 17Ah battery in UPS cabinet 24Ah battery in UPS cabinet 33Ah battery in UPS cabinet 10Ah battery in separate cabinet 17Ah battery in separate cabinet 24Ah battery in separate cabinet 38Ah battery in separate cabinet 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuses for cabinet 500mm Battery fuses for cabinet 750/1100mm Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer in UPS cabinet batt. cavity Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/10 360/17 360/24 360/33 360/10 360/17 360/24 360/38 360/65 360/76 -
8 15 30 43 8 15 30 50 100 120 -
1450x680x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800
240 140 230 290 400 230 290 370 530 790 1030 -
(9)11715 (9)11786 (9)11256 (9)11257 (9)11258 (9)11283 (9)11517 (9)11518 (9)11521 (9)11524 (9)11527 (9)11530 (9)11254 (9)11255 (9)11237 (9)11280 (9)11292 (9)11727 (9)12202 (9)11536 (9)11541 (9)11546
UPS 15 kVA without battery, 6-pulse rectifier RPA kit installed in factory 17Ah battery in UPS cabinet 24Ah battery in UPS cabinet 33Ah battery in UPS cabinet 17Ah battery in separate cabinet 24Ah battery in separate cabinet 38Ah battery in separate cabinet 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuses for cabinet 500mm Battery fuses for cabinet 750/1100mm Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer in UPS cabinet batt. cavity Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/17 360/24 360/33 360/17 360/24 360/38 360/65 360/76 -
10 15 24 10 15 30 60 70 -
1450x680x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800
290 230 290 400 290 370 530 790 1030 -
(9)11716 (9)11786 (9)11257 (9)11258 (9)11283 (9)11519 (9)11522 (9)11525 (9)11528 (9)11531 (9)11252 (9)11253 (9)11238 (9)11281 (9)11293 (9)11728 (9)12203 (9)11537 (9)11542 (9)11547
UPS 20 kVA without battery, 6-pulse rectifier RPA kit installed in factory 17Ah battery in UPS cabinet 24Ah battery in UPS cabinet 33Ah battery in UPS cabinet 17Ah battery in separate cabinet 24Ah battery in separate cabinet 38Ah battery in separate cabinet 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuses for cabinet 500mm Battery fuses for cabinet 750/1100mm Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer in UPS cabinet batt. cavity Distortion Control Unit in separate cabinet, for 50Hz Distortion Control Unit in separate cabinet, for 60Hz Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/17 360/24 360/33 360/17 360/24 360/38 360/65 360/76 -
6 10 16 6 10 20 40 50 -
1450x680x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800
290 230 290 400 290 370 530 790 1030 -
(9)11717 (9)11786 (9)11257 (9)11258 (9)11283 (9)11519 (9)11522 (9)11525 (9)11528 (9)11531 (9)11252 (9)11253 (9)11238 (9)11281 (9)11294 (9)11772 (9)12206 (9)11729 (9)12204 (9)11538 (9)11543 (9)11548
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
G.3
g
GE Industrial Systems
On-Line double conversion: SitePro
SitePro 10-500 - Installable 3-3 phase On-Line UPS SitePro 30
SitePro 40
SitePro 60
Battery capacity (V/Ah)
Runtime (minutes) 100% load
Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
UPS 30 kVA without battery, 6-pulse rectifier RPA kit installed in factory 24Ah battery in UPS cabinet 33Ah battery in UPS cabinet 24Ah battery in separate cabinet 38Ah battery in separate cabinet 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuses for cabinet 500mm Battery fuses for cabinet 750/1100mm Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer in UPS cabinet batt. cavity Distortion Control Unit in separate cabinet, for 50Hz Distortion Control Unit in separate cabinet, for 60Hz Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/24 360/33 360/24 360/38 360/65 360/76 -
6 10 6 12 25 30 -
1450x680x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800
320 290 400 370 530 790 1030 -
(9)11718 (9)11786 (9)11258 (9)11283 (9)11523 (9)11526 (9)11529 (9)11532 (9)11250 (9)11251 (9)11239 (9)11281 (9)11295 (9)11773 (9)12207 (9)11730 (9)12205 (9)11539 (9)11544 (9)11549
UPS 40 kVA without battery, 6-pulse rectifier UPS 40 kVA without battery, prepared for 12-p. rectifier RPA kit installed in factory 33Ah battery in UPS cabinet 38Ah battery in separate cabinet 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Battery fuses for cabinet 750/1100mm Input isolation transformer in UPS cabinet batt. cavity Input isolation transformer in separate cabinet 12-p rectifier without galv. separation, in separate cab. 12-p rectifier with galv. separation, in separate cab. Distortion Control Unit in separate cabinet, for 50Hz Distortion Control Unit in separate cabinet, for 60Hz Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/33 360/38 360/65 360/76 -
6 7 17 20 -
1450x680x800 1450x680x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800
350 350 400 530 790 1030 -
(9)11719 (9)11560 (9)11786 (9)11283 (9)11526 (9)11529 (9)11532 (9)11239 (9)11281 (9)11241 (9)11374 on request (9)11721 (9)11720 (9)11774 (9)12208 (9)11722 (9)12201 (9)11540 (9)11545 (9)11550
UPS 60 kVA without battery, 6-pulse rectifier UPS 60 kVA without battery, prepared for 12-p. rectifier RPA kit installed in factory 65Ah battery in separate cabinet 2x38Ah battery in separate cabinet Battery fuse box (with fuses) Battery fuses for cabinet 750/1100mm Input isolation transformer in separate cabinet 12-p rectifier without galv. separation, in separate cab. 12-p rectifier with galv. separation, in separate cab. Distortion Control Unit in separate cabinet, for 50Hz Distortion Control Unit in separate cabinet, for 60Hz Input filter 5th harmonic w/ pf. correction, for 50Hz Input filter 5th harmonic w/ pf. correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
360/65 360/76 -
10 12 -
1450x750x800 1450x750x800 1450x750x800 1450x1100x800 400x300x200 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x1100x800 1450x1100x800
475 475 790 1030 -
(9)11622 (9)11815 (9)11786 (9)11636 (9)11637 (9)11240 (9)11242 (9)11651 (9)11647 (9)11643 (9)11775 (9)12209 (9)11732 (9)12193 (9)11633 (9)11634 (9)11635
G
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
G.4
Uninterruptible Power Supplies
UPS SitePro 80
SitePro 10-500 - Installable 3-3 phase On-Line UPS Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
UPS 80 kVA without battery, 6-pulse rectifier UPS 80 kVA without battery, prepared for 12-pulse rectifier RPA kit installed in factory Input isolation transformer in separate cabinet 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1450x1100x800 1450x1100x800 1450x500x800 1450x500x800 1450x500x800 600x400x200 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 1450x1100x800
620 620 -
(9)11623 (9)11816 (9)11786 (9)11652 (9)11648 (9)11644 (9)11243 (9)11776 (9)12210 (9)11733 (9)12194 (9)11665 (9)16666 (9)11667
UPS 100 kVA without battery, 6-pulse rectifier UPS 100 kVA without battery, prepared for 12-pulse rectifier RPA kit installed in factory Input isolation transformer in separate cabinet 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1450x1100x800 1450x1100x800 1450x500x800 1450x500x800 1450x500x800 600x400x200 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 1450x1100x800
675 675 -
(9)11624 (9)11817 (9)11786 (9)11653 (9)11649 (9)11645 (9)11244 (9)11777 (9)12211 (9)11734 (9)12195 (9)11668 (9)16669 (9)11670
UPS 120 kVA without battery, 6-pulse rectifier UPS 120 kVA without battery, prepared for 12-pulse rectifier RPA kit installed in factory Input isolation transformer in separate cabinet 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1450x1100x800 1450x1100x800 1450x500x800 1450x500x800 1450x500x800 600x400x200 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 1450x1100x800
813 675 -
(9)11625 (9)11818 (9)11786 (9)11654 (9)11650 (9)11646 (9)11245 (9)11778 (9)15653 (9)11735 (9)12196 (9)11671 (9)16672 (9)11673
UPS 150 kVA without battery, 6-pulse rectifier UPS 150 kVA without battery, prepared for 12-pulse rectifier with galvanic separation UPS 150 kVA without battery, prepared for 12-pulse rectifier without galvanic separation RPA kit installed in factory Input isolation transformer in separate cabinet 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit in separate cabinet, for 50Hz, if with iso-trafo T6/T12 Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x1100x800 1800x1100x800 1800x1100x800 1800x680x800 1800x680x800 1800x680x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1100x800 1800x1550x800
925 925 925 -
(9)11676 (9)11819 (9)15721 (9)11786 (9)11684 (9)11690 (9)11686 (9)11223 (9)11704 (9)11703 (9)12197 (9)11450 (9)12192 (9)12016 (9)12009 on request
SitePro 100
SitePro 120
SitePro 150
G
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
G.5
g
GE Industrial Systems
On-Line double conversion: SitePro
SitePro 10-500 - Installable 3-3 phase On-Line UPS SitePro 200
SitePro 250
SitePro 300
SitePro 400
SitePro 500
Dimensions (HxWxD, mm)
Net weight (kg)
Ref.No. † see note
UPS 200 kVA without battery, 6-pulse rectifier UPS 200 kVA without battery, prepared for 12-pulse rectifier with galvanic separation UPS 200 kVA without battery, prepared for 12-pulse rectifier without galvanic separation RPA kit installed in factory Input isolation transformer in separate cabinet 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics in separate cabinet, for 60Hz Distortion Control Unit in separate cabinet, for 50Hz, if with iso-trafo T6/T12 Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x1100x800 1800x1100x800 1800x1100x800 1800x680x800 1800x680x800 1800x680x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1100x800 1800x1550x800
995 995 995 -
(9)11677 (9)11820 (9)15723 (9)11786 (9)11685 (9)11691 (9)11687 (9)11224 (9)11707 (9)12199 (9)11705 (9)11706 (9)12198 (9)12100 (9)12122 on request
UPS 250 kVA without battery, 6-pulse rectifier UPS 250 kVA without battery, prepared for 12-pulse rectifier with galvanic separation UPS 250 kVA without battery, prepared for 12-pulse rectifier without galvanic separation RPA kit installed in factory 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Distortion Control Unit in separate cabinet, for 50Hz, if with iso-trafo T6/T12 Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x1550x800 1800x1550x800 1800x1550x800 1800x680x800 1800x1100x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1550x800 1800x1780x800
1450 1450 1450 -
(9)11678 (9)15503 (9)15725 (9)11786 (9)11692 (9)11688 (9)11225 (9)11393 (9)15514 (9)11394 (9)11440 (9)15515 (9)12057 (9)11986 on request
UPS 300 kVA without battery, 6-pulse rectifier UPS 300 kVA without battery, prepared for 12-pulse rectifier with galvanic separation UPS 300 kVA without battery, prepared for 12-pulse rectifier without galvanic separation RPA kit installed in factory 12-pulse rectifier without galvanic separation, in separate cabinet 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Distortion Control Unit in separate cabinet, for 50Hz, if with iso-trafo T6/T12 Input filter 5th harmonic with power factor correction, for 50Hz Input filter 5th harmonic with power factor correction, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x1550x800 1800x1550x800 1800x1550x800 1800x680x800 1800x1100x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1550x800 1800x1780x800
1550 1550 1550 -
(9)11679 (9)15504 (9)15727 (9)11786 (9)11689 (9)11693 (9)11226 (9)11702 (9)15518 (9)11708 (9)11451 (9)15516 (9)12103 (9)12123 on request
UPS 400 kVA without battery, 12-pulse rectifier without galvanic separation UPS 400 kVA without battery, prepared for 12-pulse rectifier with galvanic separation RPA kit installed in factory 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x2600x800 1800x2600x800 1800x680x800 1000x600x260 1800x1100x800 1800x1100x800 1800x1550x800 1800x1780x800 1800x1780x800
2700 2700 -
(9)11659 (9)15566 (9)11786 (9)11699 (9)11233 (9)11697 (9)15517 (9)12121 (9)12014 on request
UPS 500 kVA without battery, 12-pulse rectifier without galvanic separation UPS 500 kVA without battery, prepared for 12-pulse rectifier with galvanic separation RPA kit kit installed in factory 12-pulse rectifier with galvanic separation, in separate cabinet Battery fuse box (with fuses) Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Distortion Control Unit, filter for 5,7,11,13 harmonics, in separate cabinet, for 60Hz Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x2600x800 1800x2600x800 1800x1100x800 1000x600x260 1800x1100x800 1800x1100x800 1800x1550x800 1800x2200x800 1800x2200x800
2900 2900 -
(9)11657 (9)15507 (9)11786 (9)11675 (9)11229 (9)12069 (9)15519 (9)12085 (9)12101 on request
G
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy
g
G.6
Uninterruptible Power Supplies
UPS SitePro 10-500 - Installable 3-3 phase On-Line UPS Options Miscellaneous
Kit to convert single to RPA (Redundant Parallel Architecture) operation Kit to mount Chinese Display Top cable entry box (for 10-120 kVA) Remote signalling panel (incl. 24Vdc Power Supply for 10-40 kVA) Remote signalling panel (incl. 24Vdc Power Supply for 60-500 kVA) Remote monitoring system (on request) Auxiliary Power Supply 24Vdc (for 10-500 kVA) factory mounted only Additional customer Interface card (for 10-500 kVA) Mounting set for battery 10/17/24 Ah in 10-30 kVA UPS cabinet Mounting set for 33Ah battery 10-40 kVA UPS cabinet
Dimensions (HxWxD, mm)
Ref.No. † see note
-
(9)11626 (9)11780 (9)11632 (9)11785 (9)11698 on request (9)11696 (9)(10)06691†† (9)11279 (9)11284
1450x500x800 1450x750x800 1450x1100x800 -
(9)11516 (9)11655 (9)11656 (9)11631
1800x680x800 1800x1100x800 1800x1550x800 -
(9)11700 (9)11694 (9)11695 (9)11674
1450x500x800 1450x750x800 1450x1100x800 1800x680x800 1800x1100x800 1800x1550x800
(9)(10)07839 †† (9)(10)07840 †† (9)(10)07841 †† (9)(10)07843 (9)11814 (9)(10)07844††
Note: UPS without batteries are also without battery mounting set. To mount the purchased batteries, order the mounting set.
Options Battery Cabinets
Battery cabinet 500mm with 4 shelves (3 mobile) + 1 x side panel (10-40 kVA) Battery cabinet 750mm with 4 shelves (3 mobile) + 1 x side panel (10-120 kVA) Battery cabinet 1100mm with 4 shelves (3 mobile) + 1 x side panel (10-120 kVA) 2 bottom side grids + 1 x side panel for cabinet (10-120kVA) Note: Battery cabinets are normally mounted next to the UPS. For remote placement, order bottom grids and side panel. Battery cabinet 680mm with 4 shelves (3 mobile) with + 1 x side panel (150-500 kVA) Battery cabinet 1100mm with 4 shelves (3 mobile) with + 1 x side panel (150-500 kVA) Battery cabinet 1550mm with 4 shelves (3 mobile) with + 1 x side panel (150-500 kVA) 2 bottom side grids + 1 x side panel for cabinet (150-500 kVA) Note: For all batteries installed on racks, installation of a battery fuse is recommended Note: for battery cabinets that are placed more than 3 meters from the UPS, installation of a battery fuse box (wall-mounted) or battery fuse+holder (inside UPS cabinet) is recommended. Empty cabinet 500mm with 2 x sides and 2 x bottom grills (10-120 kVA) Empty cabinet 750mm with 2 x sides and 2 x bottom grills (10-120 kVA) Empty cabinet 1100mm with 2 x sides and 2 x bottom grills (10-120 kVA) Empty cabinet 680mm with 2 x sides and 2 x bottom grills (150-500 kVA) Empty cabinet 1100mm with 2 x sides and 2 x bottom grills (150-500 kVA) Empty cabinet 1550mm with 2 x sides and 2 x bottom grills (150-500 kVA)
††
Note: empty cabinets are battery cabinets without battery shelves
Options Cabinet Colour
Non-standard colour (per cabinet) (10-40 kVA) Non-standard colour (per cabinet) (60-120 kVA) Non-standard colour (per cabinet) (150-500 kVA)
-
(9)(10)09555†† (9)(10)09557†† (9)(10)09556††
G
G.7
g
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy †† = 6-digit number starting with 9 = GE Power Controls 7-digit number starting with 10 = GE Digital Energy
GE Industrial Systems
On-Line double conversion: SitePro
Notes
G.8
g
x
G
UPS
Connectivity Solutions
Connectivity Solutions
PowerJUMP DataShield™
PowerJUMP DataShield™ ® PowerJUMP Manager Power JUMPin™ IRIS - Internet Remote Information System UPS Service Tools Applications
PowerJUMP Manager™
In today’s business environment, a power failure causes loss of crucial data, expensive down time and damaged computers or industrial equipment. With the use of appropriate monitoring and management software, the UPS becomes a comprehensive power quality solution. The software is an indispensable and fully integrated element, increasing system availability and process protection.
Function
Characteristics
Turning the UPS into a comprehensive power quality solution, thus providing increased system availability and process protection.
During a power failure, the software takes a number of actions: users are alerted, processes are managed into defined statuses, open files and communication links are closed and unattended systems are shut down in a controlled way. When the mains power returns, the system is automatically started up and begins operating.
Protection Software The main function of the GE protection software is data and operating system protection. PowerJUMP DataShield™ diminishes the risk of lost data or system crashes. The software provides events handling and computer shutdown for all major operating systems, protecting the security of precious data. Multi-vendor and multi-platform environments, as well as client-server structures, are managed using SNMP-based network communication protocols.
Management Software
H
H.1
The GE UPS management software provides direct access to remote UPS, and active management of each UPS in multi-unit configurations, to ensure efficient and predictable power quality. A network manager or facilities engineer can use PowerJUMP Manager™ to monitor and control the local or remote UPS, and the equipment and processes it protects. Typically, an SNMP client/agent structure, direct serial link or modem connection is used for this purpose. The PowerJUMPin™ software allows easy integration into all leading Network Management Systems. The UPS can also be monitored on the Internet using the GE IRIS system.
g
GE Industrial Systems
IRIS - Internet Remote Information System
UPS Connectivity Solutions Code Reference Table
Code cs cp i
UPS Interface / Functionality
IMV-C or VIC-25 Contact shutdown adapter IMV-I or VIC-23
Contact / power failure, battery low & shutdown Contact / power failure, battery low & shutdown Intelligent / features depend on UPS type
Connectivity Solutions
Network Protection Software on CD-ROM
Related Cable
This free software on CD-ROM and an intelligent communication cable are shipped with each UPS (except SitePro UPS). Prices for additional copies of this software and special media are listed below (all software is without cabling). Medium
Operating System
CD-ROM
Microsoft Windows (all) Novell Netware 3.1+ IBM OS/2 3.0+ Linux AT&T Intel 2.03.00+, 3.00.00+ COMPAQ Tru64 Unix DEC UNIX AXP Alpha V3.2+ DEC Ultrix RISC V4.3+ DEC OpenVMS VAX/AXP V6.2 up to V7.2 HP-UX 700/800 R9.0+/R10.0+ IBM AIX RISC/60x V3 R2+ NEC-UX 700/800 R9.0+/R10.0+ UNIXWARE INTEL V2 R3.2/4.1+ SCO INTEL V2 R3.2+ Siemens SINIX RM V5.41+ Silicon Graphics IRIX/IRIS 6.2+ SUN OS SPARC V3 R4.1.3+ SUN SOLARIS SPARC V2 R5.4+ SUN SOLARIS Intel x86pc V2 R5.4+ All OS supporting JAVA 1.2+
Code
Ref.No. † see note
cp,i cs,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i i
(9)(10)09227
-
(9)12317 (9)12318 (9)12319
Code
Ref.No. † see note
††
The CD-ROM contains: 1) UPS Protection and Management Program, incl. SNMP Agent and Client 2) Unix: PowerVIEW graphical UPS manager, requires X/Motif 3) Unix: VMS works only when the following is installed: Open VMS 6.2, UCX 4.1 and POSIX 2.0, patch level eco 3.0 4) Manuals in PDF format
Network Protection Software on other media
QIC-24 tape DAT/DDS tape TK 50 tape
All Unix, tar format All Unix, tar format All Unix, tar format
Stand Alone Protection Software
Operating Sys.
Product
Cabling to be used with built-in UPS Protection Software.
Windows NT IBM OS/400
IMV-C Cable Kit for built-in UPS driver IBM AS400 Cable Kit for built-in UPS driver
cs c
(9)12470 †† (9)(10)09230
Stand Alone Prot. Software AS/400
IBM OS/400 / RISC
PowerFLAG/400 RISC 1/4” Tape PowerFLAG/400 RISC 8mm Tape PowerFLAG/400 RISC CD-ROM PowerFLAG/400 CISC 1/4” Tape PowerFLAG/400 CISC 8mm Tape
c c c c c
(9)12461 (9)12462 (9)12463 (9)12464 (9)12465
i
(9)12473
IBM OS/400 / CISC
Incl. 2 special cables for 9 and 15 pin AS/400 system, with surge suppression
Service Software
Windows all (Intel)
PowerFLAG SerVICe on CD-ROM
H † = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy †† = 6-digit number starting with 9 = GE Power Controls 7-digit number starting with 10 = GE Digital Energy
g
H.2
UPS Code Reference Table
Code
Connectivity Solutions
cs cp i
JUMP Manager
Related Cable
UPS Interface / Functionality
IMV-C or VIC-25 Contact shutdown adapter IMV-I or VIC-23
Contact / power failure, battery low & shutdown Contact / power failure, battery low & shutdown Intelligent / features depend on UPS type
Product
Code
Check for availability. JUMP Manager on CD-ROM
i
Ref.No. † see note (9)(10)09227
††
Free for use with max. 2 single UPSs or 2 complete parallel configurations no limitation of managed power
ARGUS Management Software for SitePro
IRIS
License for more than 2 UPS systems and max. 100 kVA managed power License for more than 2 UPS systems and max. 1000 kVA managed power License for more than 2 UPS systems and unlimited managed power SSL security internet communication module
(9)11162 (9)11163 (9)11164 (9)12316
ARGUS Software Package 30 days full featured license
(9)11382
Note: No license required for 1 UPS License for 2 to 10 single UPSs License for more than 10 single UPSs License for more than 1 parallel UPS system License for unlimited number of single & parallel UPS systems Intelligent Energy Management (IEM), only for parallel units
(9)11003 (9)15655 (9)11004 (9)15656 (9)11005
Starter Kit (incl. 1st year fee) IRIS starter kit for LanPro 11/31 IRIS starter kit for SitePro Single/Parallel 10-40 kVA IRIS starter kit for SitePro Single/Parallel 60-120 kVA IRIS starter kit for SitePro Single/Parallel 150-500 kVA
(9)11176 (9)11177 (9)11178 (9)11179
Including InterLinc box. Prices per system. After 1st year IRIS yearly fee after 1st year for LanPro 11/31 IRIS yearly fee after 1st year for SitePro Single/Parallel 10-40 kVA IRIS yearly fee after 1st year for SitePro Single/Parallel 60-120 kVA IRIS yearly fee after 1st year for SitePro Single/Parallel 150-500 kVA
(9)11167 (9)11168 (9)11169 (9)11170
Not including InterLinc box. Additional IRIS fee IRIS end user license per year, incl. 1 password, 1 Email, fax or SMS address IRIS additional SMS, fax or Email address, per message for each individual address IRIS manual refresh UPS status (per refresh/per UPS)
(9)11180 (9)11165 (9)15654
H
H.3
g
† = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy †† = 6-digit number starting with 9 = GE Power Controls 7-digit number starting with 10 = GE Digital Energy
GE Industrial Systems
UPS Connectivity Solutions Code Reference Table
Code cs cp i
Related Cable
UPS Interface / Functionality
IMV-C or VIC-25 Contact shutdown adapter IMV-I or VIC-23
Contact / power failure, battery low & shutdown Contact / power failure, battery low & shutdown Intelligent / features depend on UPS type
Connectivity Solutions
Accessories Hardware Interfaces Product Contact UPS Relay Box Contact UPS Splitter Box 2-Way Contact UPS Splitter Box 4-Way Contact UPS Alarm Box Contact UPS Shutdown Adapter UPS Service Box* SNMP/ Web Interface Card UTP/BNC for Match (19”)**, NetPro (19”), LanPro 11/31(T) Advanced SNMP/ Web Interface Card UTP/BNC for LanPro 33 and SitePro Series 6 SNMP/ Web Interface Box Ethernet UTP/BNC* for Match (19”)**, NetPro (19”), LanPro 11/31(T), with Linc-box also valid for SitePro Series 5 Relay Card for Match 700L-1500*** and Match 19” 1000-1500*** Relay Card for Match (19”) 2200-3000, NetPro (19”) and LanPro 11/31(T) Multi-Serial Board (8 x RS232)* Modem* (Only valid for European market) Converter RS485-RS232, RS232-RS422* 1) 2)
Code
Ref.No. † see note
c cs cs c cs cs,i i i
(9)12466 (9)12467 †† (9)(10)09226 (9)12214 (9)12460 (9)12468 (9)(10)09224†† (9)11701
cs,i
i i
(9)(10)09223†† (9)12459 (9)12458 (9)(10)01145†† (9)(10)01673†† (9)11277
i
(9)11249 (9)11483
i i cs i i c,cs,i
(9)11469 (9)(10)09231 (9)12470 (9)12471 (9)12472 (9)(10)09225
1) Not needed if ESI is installed 2) Only if distance is more than 15m * These products are delivered including cable(s) ** Not for Match 500-700 and Match 19” 700; alternative: SNMP Box, Ref. no. (9)(10)09223 *** Not for Match 500-700 and Match 19” 700; alternative: Relay Box, Ref. no. (9)12466
Accessories
External Signal Interface (ESI)
Hardware Interfaces for SitePro Linc Box: CP4 Protocol Converter* * These products are delivered including cable(s)
Accessories
IMV-I Cable Intelligent UPS for LanPro and SitePro
Cable Kits - Adapters VIC-23 Cable Intelligent UPS for Match and NetPro IMV-C Cable Kit Contact UPS VIC-32 Cable UPS to modem for Match and NetPro IMV-M Cable UPS to modem for LanPro and SitePro series 6 Adapter 9p male -> 25p female subd Note: Length of all cables is 2 meters.
H † = 6-digit number (9)12349 = GE Power Controls 5-digit number = GE Digital Energy †† = 6-digit number starting with 9 = GE Power Controls 7-digit number starting with 10 = GE Digital Energy
g
H.4
Connectivity Solutions
Notes
H
H.5
g
GE Industrial Systems
x
Notes
x
g
e
We bring good things to life.
GE Industrial Systems UPS Product Technology GE is a leader in the field of critical power protection. It’s UPS Product Technology business designs,manufactures and delivers premium power quality products and related software products that ensure organisations all over the world enjoy a safe and managed power supply. Protect your critical power application with a GE UPS – ranging from 500VA to 4MVA. Using state of the art technology GE has developed different UPS with high reliability and maximum application flexibility. With a GE power solution in place, your mission-critical equipment is protected from any fluctuation in your power source, enabling you to concentrate on your core activities. Leave your critical power needs with GE, a reliable power quality supplier for more than 100 years.
Ref. UPSTECH-GB-03/2003
GE Power Controls GE Power Controls Axxes Business Park Guldensporenpark 30 B-9820 Merelbeke Tel. +32 (0)9 210 38 11 Fax +32 (0)9 210 39 90
[email protected] www.gepowercontrols.com
GE Power Controls France 7, Rue Nicolas Robert BP32 - ZI La Garenne F-93601 Aulnay Sous Bois Cedex Tel. +33 (0)1 48 19 41 50 Fax +33 (0)1 48 19 41 51 www.gepowercontrols.com
Region Paris, France N-E Tel. +33 (0)1 48 19 41 02 Fax +33 (0)1 48 19 41 80
[email protected] Region France West Tel. +33 (0)2 28 03 03 70 Fax +33 (0)2 40 92 28 81
[email protected] Region France South Tel. +33 (0)4 78 89 13 13 Fax +33 (0)4 72 43 96 42
[email protected]