Transcript
VRLA Rechargeable Battery
Measures
Technology
Values
Innovation
BC10-12 FEATURES Maintenance free(no water topping-up required) No free acid(Non-spillable battery) Can be used in any orientation(excluding used inverted) Absorbent Glass Mat technology for efficient gas recombination Its design life is up to 5 years in floating application
APPLICATION Laboratory
UPS
Equipment
SPECIFICATIONS Nominal Voltage Nominal Capacity
12V
CONTAINER MATERIAL
20 Hour Rate (500mA, 10.5V) 10 Hour Rate (950mA, 10.5V) 5 Hour Rate (1700mA, 10.5V) 1 Hour Rate (6000mA, 9.30V)
Approx. Weight
10.0 Ah 9.50 Ah 8.50 Ah 6.00 Ah
Standard: ABS( UL 94-HB) Model: BC10-12 (Dark gray color) Optional: ABS(UL 94-V0) Model: BC10-12FR (Light gray color)
3000g(6.61lbs.)
Terminals
T2 (Faston Tab 250) T1 is optional
Max. Discharge Current
150 A (5 sec.)
Max. Charge Current
3.00 A 0oC~40oC(32oF~104oF) -20oC~50oC(-4oF~122oF) -20oC~40oC(-4oF~104oF)
Charge
Operating Temperature Range
Discharge Storage
Self Discharge Internal Resistance
OUTER DIMENSIONS mm(inch)
UL
o
< 3% per month (25 C) 17m
IEC 61056-1
Width (W) 65±1.5(2.56±0.06)
JIS C 8702-1
GB/T 19639.1
(Fully Charged )
Length (L) 151±1.5(5.94±0.06)
CE
Container Height (H) 112±1.5(4.41±0.06)
Total Height (TH) 117±2.0(4.61±0.08)
TERMINAL TYPE Terminal T1
Terminal T2 3.4(0.13)
3.2(0.13) 4.75(0.19) 6.35(0.25)
0.8(0.03)
7.95(0.31) 0.8(0.03)
117 2(4.61 0.08)
112 1.5(4.41 0.06)
151 1.5(5.94 0.06)
65 1.5(2.56 0.06)
o
o
BC10-12 (BC10-12FR) discharge characteristics (25C /77F )
Battery Charging Characteristics (Typical example of the charge characteristics for the standby use)
13.0 0.21
15.0
0.18
14.0
140
10.0 0.6CA
9.0
8.0 2.5CA 2CA
7.0
1
2
3
5
10
1CA
20 30
0.15 0.12 0.09 0.06
120
Charge voltage vo lu m e
C ha rg e
13.0
100
1 Battery : BC10-12 2 Discharge 100 %(0.05CA x 20h) 50 %(0.05CA x 10h) 3 Constant voltage charging Charge voltage:2.275V/cell Charge current:0.1CA 4 Temperature:25 (77 )
12.0 11.0
80 60
10.0
40
0.03
60
2
3
5
10
20 Charge current
20 30
0
Hr
Min
Charge volume(%)
0.17CA 0.095CA 0.05CA 0.25CA
Charge voltage(V)
11.0
Charge current(CA)
Terminal Voltage(V)
12.0
0
0
5
10
15
20
0
25
Charge time (hr)
Discharge time
Effect Of Temperature On Long Term Float Life Charging Procedure
Charging method
Charging Temperature Max. charging compensation current Voltage coefficient of (CA) at 25OC voltage 100% 50% (V/cell) charging O (mV/C /cell) discharge discharge
Constant voltage & 2.25~2.30 Constant current charging For (with current cycle service restriction) 2.40~2.50
For standby power Source
-3
0.3
24
Life expectancy(year)
Application
Charging time O 0.1CA, 25 C (h)
Temp ( OC)
20 0~40 (32~104 OF)
-4
0.3
16
10 8 6 5 4 3
Charging voltage : 2.275V/cell
2 1 0.5 20 68
10
30 86
40 104
50°C 122°F
Battery temperature
Constant power discharge characteristics at 25 oC/77 oF Discharge Time
Unit: W
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
361.6
266.2
213.3
126.9
72.78
29.15
20.10
11.23
5.91
1.75V
418.5
288.4
223.1
131.7
74.96
29.73
20.40
11.40
6.00
1.70V
444.6
298.7
230.0
134.7
76.31
30.00
20.51
11.46
6.04
1.65V
464.6
305.9
235.3
136.6
77.23
30.21
20.58
11.49
6.05
1.60V
480.0
312.0
240.0
138.0
78.00
30.39
20.64
11.49
6.05
F.V. (V/cell)
Constant current discharge characteristics at 25 oC/77 oF Discharge Time
Unit: A
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
32.57
23.43
18.55
10.75
6.12
2.43
1.675
0.936
0.493
1.75V
38.39
25.38
19.40
11.16
6.30
2.48
1.700
0.950
0.500
1.70V
40.79
26.30
20.00
11.42
6.41
2.50
1.709
0.955
0.503
1.65V
42.62
26.93
20.46
11.58
6.49
2.52
1.715
0.958
0.504
1.60V
44.04
27.46
20.87
11.69
6.55
2.53
1.720
0.958
0.504
F.V. (V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/0
USA: B&B BATTERY(USA) INC. 6415 RANDOLPH ST.COMMERCE,CA,90040 U.S.A. TEL:1-323-278-1900.1-800-278-8599 FAX:1-323-278-1268 E-Mail:
[email protected] CHINA FACTORY: B.B. BATTERY CO., LTD. CHENG DONG TRIAL AREA,HUANG GANG, RAOPING, GUANG DONG,CHINA,515700 TEL:86-768-7601001-2 FAX:86-768-7601469 E-Mail:
[email protected]
Web Site: http://www.bb-battery.com
REV. Feb. 2013
EUROPE: B&B BATTERY(EUROPE) B.V. SUITE 8, HAAKSBERGWEG 33, 1101 BP AMSTERDAM,THE NETHERLANDS TEL: 31-30-320-0190 MOBILE: 852-9128-2711 E-Mail:
[email protected]
JAPAN: B&B BATTERY(JAPAN) CO., LTD. 1375-11 NARAHARA-MACHI,HACHIOJI, TOKYO 193-0803,JAPAN. TEL:81-426-25-6375 FAX:81-426-25-6375 E-Mail:
[email protected]
HONG KONG: B&B BATTERY(Hong Kong) Co. TEL:852-2311-4918 FAX:852-2739-1182 E-Mail:
[email protected]
TAIWAN: B.B. BATTERY(TAIWAN) CO., LTD. TEL:886-6-502-5150 FAX:886-6-589-8087 E-Mail:
[email protected]
Powered by