Transcript
MODELS BCG3 & ABCG3 COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER
• INSTALLATION • OPERATION • MAINTENANCE • LIMITED WARRANTY
ANSI/NSF-5 Thank you for buying this energy efficient water heater from American Water Heater Company. We appreciate your confidence in our product.
CAUTION
TE X T P R IN TE D OR OU TLIN E D IN R E D CO NTAI NS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE.
P.O. Box 1597, 500 Princeton Road Johnson City, TN 37605 PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. PRINTED 0609
1
197935-001
See Models Below
BCG370T120’s are approved for 5” (13 cm) venting using a 6” (15 cm) to 5” (13 cm) reducer.
FIGURE 1 BCG3-70T120-5_ THROUGH (A)BCG3-100T399-8_ - TABLE 1A MODEL BCG3 70T120’s BCG3 80T150’s BCG3 80T180’s BCG3 100T199’s BCG3 80T199’s (A)BCG3 100T200’s (A)BCG3 100T250’s (A)BCG3 65T250’s (A)BCG3 100T275’s (A)BCG3 65T300’s (A)BCG3 85T360’s (A)BCG3 100T390’s
INPUT APPROX. RATE BTU/ TANK CAP. HR. 120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kW/Hr 199,000 BTU/Hr 58 kW/Hr 199,000 BTU/Hr 58 kW/Hr 250,000 BTU/Hr 72 kW/Hr 251,000 BTU/Hr 73 kW/Hr 275,000 BTU/Hr 80 kW/Hr 305,000 BTU/Hr 89 kW/Hr 365,000 BTU/Hr 107 kW/Hr 390,000 BTU/Hr 114 kW/Hr
A
B
C
D
E
GAS INLET G
F
H
VENT DIA. I
J
TOP
CONNECTIONS INLET OUTLET FRONT BACK TOP FRONT BACK
APPROXIMATE SHIP WEIGHT STD. ASME
71 Gal 268 L
69.75” 4.25” 177 cm 11 cm
59.50” 151 cm
50.87” 129 cm
19.69” 19” 50 cm 48 cm
1/2” 1/2”
51.88” 6” 27.75” 132 cm 15 cm 71 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
400 Lbs 182 Kg
NA NA
81 Gal 307 L
73.00” 4.25” 185 cm 11 cm
66.50” 169 cm
57.87” 147 cm
19.69” 19” 50 cm 48 cm
1/2” 1/2”
59.00” 6” 27.75” 150 cm 15 cm 71 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
470 Lbs 213 Kg
NA NA
81Gal 307 L
67.50” 4.50” 171 cm 12 cm
62.00” 157 cm
53.62” 136 cm
20.50” 21” 52 cm 53 cm
1/2” 1/2”
54.62” 6” 27.75” 139 cm 15 cm 71 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
470 Lbs 213 Kg
NA NA
100 Gal 379 L
75.00” 4.50” 192 cm 12 cm
70.00” 178 cm
61.62” 157 cm
20.50” 21” 52 cm 53 cm
1/2” 1/2”
62.62” 6” 27.75” 159 cm 15 cm 71 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
603 Lbs 273 Kg
NA NA
81 Gal 307 L
67.50” 4.50” 171 cm 12 cm
62.00” 157 cm
53.62” 136 cm
20.50” 21” 52 cm 53 cm
1/2” 1/2”
54.62” 6” 27.75” 139 cm 15 cm 71 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
470 Lbs 213 Kg
NA NA
100 Gal 379 L
72.00” 4.50” 183 cm 12 cm
65.13” 165 cm
55.87” 142 cm
19.75” 23” 50 cm 58 cm
1/2” 1/2”
56.38” 6” 30.25” 143 cm 15 cm 77 cm
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
630 Lbs 725 Lbs 286 Kg 329 Kg
100 Gal 379 L
72.00” 4.50” 183 cm 12 cm
65.13” 165 cm
55.87” 142 cm
19.75” 23” 50 cm 58 cm
1/2” 1/2”
56.38” 8” 30.25” 143 cm 20 cm 77 cm
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
630 Lbs 725 Lbs 286 Kg 329 Kg
65 Gal 246 L
75.00” 4.50” 191 cm 12 cm
65.75” 167 cm
57.25” 145 cm
20.00” 51 cm
1/2” 1/2”
58.75 8” 27.75” 149 cm 20 cm 70 cm
NA NA
1.50” 1.50”
1.50” 1.50”
NA NA
1.50” 1.50”
1.50” 1.50”
750Lbs 341 Kg
100 Gal 379 L
72.00” 4.50” 183 cm 12 cm
65.13” 165 cm
55.87” 142 cm
19.75” 23” 50 cm 58 cm
1/2” 1/2”
56.38” 8” 30.25” 143 cm 20 cm 77 cm
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
630 Lbs 725 Lbs 286 Kg 329 Kg
65 Gal 246 L
75.00” 4.50” 191 cm 12 cm
65.75” 167 cm
57.25” 145 cm
20.00” 51 cm
1/2” 1/2”
58.75 8” 27.75” 149 cm 20 cm 70 cm
NA NA
1.50” 1.50”
1.50” 1.50”
NA NA
1.50” 1.50”
1.50” 1.50”
750 Lbs 862 Lbs 341 Kg 391 Kg
85 Gal 322 L
79.50” 4.50” 202 cm 12 cm
70.25” 178 cm
62.50” 159 cm
22.50” 23” 57 cm 58 cm
3/4” 3/4”
63.00 8” 27.75” 160 cm 20 cm 70 cm
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
1.50” 1.50”
725 Lbs 833 Lbs 329 Kg 379 Kg
100 Gal 379 L
75.50” 4.50” 192 cm 12 cm
67.50” 171 cm
58.25” 148 cm
26.75” 23” 68 cm 58 cm
3/4” 3/4”
59.00” 8” 30.25” 150 cm 20 cm 77 cm
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
1.50” 1.50”
2.00” 2.00”
2.00” 2.00”
760 Lbs 874 Lbs 345 Kg 396 Kg
NA NA
NA NA
862 Lbs 391 Kg
HEATER PERFORMANCE DATA (A)BCG3 MODELS - TABLE 1B MODEL
INPUT BTUH
APPROX. RATE CAP.
BCG370T120’s BCG380T150’s BCG380T180’s BCG3100T199’s BCG380T199’s (A)BCG3100T200’s (A)BCG3100T250’s (A)BCG365T250’s (A)BCG3100T275’s (A)BCG365T300’s (A)BCG385T360’s (A)BCG3100T390’s
120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kW/Hr 199,000 BTU/Hr 58 kW/Hr 199,000 BTU/Hr 58 kW/Hr 250,000 BTU/Hr 72 kW/Hr 251,000 BTU/Hr 73 kW/Hr 275,000 BTU/Hr 80 kW/Hr 305,000 BTU/Hr 89 kW/Hr 365,000 BTU/Hr 107 kW/Hr 390,000 BTU/Hr 114 kW/Hr
71 Gal 268 L 81 Gal 306 L 81 Gal 306 L 100 Gal 379 L 81 Gal 306 L 100 Gal 379 L 100 Gal 379 L 65 Gal 246 L 100 Gal 379 L 65 Gal 246 L 85 Gal 322 L 100 Gal 379 L
GAL% 80 80 80 80 80 80 80 80 80 80 80 80
EFF. (-)1°C 388 1469 498 1885 579 2192 643 2434 614 2324 643 2434 808 3059 811 3071 889 3365 986 3732 1180 4466 1293 4894
30°F 4°C 291 1102 373 1412 434 1643 482 1825 461 1745 482 1825 606 2294 608 2303 667 2524 739 2799 885 3349 970 3671
40°F 10°C 233 882 299 1132 347 1314 386 1461 368 1393 386 1461 485 1835 487 1843 533 2019 592 2239 708 2680 776 2936
RECOVERY RATING CAPACITIES (GPH AND LPH) 60°F 70°F 80°F 90°F 100°F 21°C 27°C 32°C 38°C 43°C 166 145 129 116 106 628 549 488 439 401 213 187 166 149 136 806 708 628 564 515 248 217 193 174 158 939 821 731 650 598 276 241 214 193 175 1045 912 810 731 662 263 230 205 184 167 996 871 776 697 632 276 241 214 193 175 1045 912 810 731 662 346 303 269 242 220 1311 1147 1020 918 834 348 304 270 243 221 1316 1152 1024 921 838 381 333 296 267 242 1442 1262 1122 1009 918 423 370 329 296 269 1599 1399 1244 1120 1018 506 442 393 354 322 1914 1675 1489 1340 1218 554 485 431 388 353 2097 1835 1631 1468 1335
50°F 15°C 194 734 249 943 289 1094 322 1219 307 1162 322 1219 404 1529 406 1536 444 1682 493 1866 590 2233 646 2447
2
110°F 49°C 97 367 124 469 145 549 161 609 154 583 161 609 202 765 203 768 222 841 246 933 295 1116 323 1224
120°F 54°C 90 341 115 435 134 507 148 560 142 538 148 560 186 706 187 709 205 776 228 861 272 1031 298 1129
130°F 60°C 83 314 107 405 124 469 132 500 132 500 132 500 173 655 174 658 190 721 211 800 253 957 277 1049
TABLE OF CONTENTS Page Grounding Instructions.........................................................15 Heater Wiring.......................................................................15 INSTALLATION DIAGRAMS...........................................15-21 MANIFOLDS.........................................................................22 MECHANICAL VENTING.....................................................23 Single Unit Installation..........................................................23 Vent Installation....................................................................23 Multiple Unit Installation.......................................................23 OPERATION.........................................................................24 General.................................................................................24 Filling....................................................................................24 Purging.................................................................................24 Lighting and Operating Labels........................................25-26 Water Temperature Control..................................................27 Testing Damper Control........................................................27 Checking Venting............................................................27-28 PREVENTIVE MAINTENANCE............................................28 Check The Pilot....................................................................28 Pilot Burner...........................................................................28 Main Burner.....................................................................28-29 Gas Valves...........................................................................29 Checking The Input..............................................................29 Venting System....................................................................30 Remote Storage Tank Temperature Control.........................30 Relief Valve...........................................................................3 0 Hot Water Odor....................................................................30 Anode Rod Inspection..........................................................30 Recommended Procedure For Periodic Removal of Lime Deposits From Tank Type Commercial Water Heaters.................................................................30-31 Deliming Solvents.................................................................31 Tank Cleanout Procedures..............................................31-32 Troubleshooting Ignition Module System.............................32 SERVICE..............................................................................32 Electrical Servicing...............................................................32 Replacement Parts...............................................................32 Effikal Flue Damper Troubleshooting Guide.........................33 Operational Checklist...........................................................34 Limited Warranty..................................................................35
ROUGH-IN-DIMENSIONS..................................................2-3 TABLE OF CONTENTS..........................................................4 FOREWORD..........................................................................4 GENERAL SAFETY INFORMATION......................................5 Chemical Vapor Corrosion......................................................5 Improper Combustion.............................................................5 Liquid Petroleum Models........................................................5 Extended Non-Use Periods....................................................5 Insulation Blankets..............................................................5-6 High Altitude Installation.........................................................6 FEATURES.............................................................................6 The Eliminator (Self-Cleaning System)..................................6 High Limit Switch (E.C.O.)...................................................6-7 Electronic Ignition Control......................................................7 Automatic Flue Damper Device..............................................7 Circulating Pump....................................................................7 Dishwashing Machine Requirement....................................7-8 INSTALLATION INSTRUCTIONS..........................................8 Uncrating................................................................................8 Locating The Heater...............................................................8 Levelling.................................................................................8 Clearances..........................................................................8-9 Installation on Combustible Flooring......................................9 Hard Water.............................................................................9 Air Requirements...............................................................9-10 Unconfined Space................................................................9 Confined Space..................................................................10 Vent Reducer........................................................................10 Venting.................................................................................10 Multiple Heater Manifold.......................................................10 Water Line Connections.......................................................10 Technical Data Venting....................................................11-12 Water (Potable) Heating and Space Heating.......................13 Thermometers (Not Supplied)..............................................13 Relief Valve...........................................................................13 Gas Piping.......................................................................13-14 Gas piping and Dirt Leg Installation................................14-15 Gas Pressure Regulator.......................................................15
FOREWORD These designs comply with ANSI Z21.10.3/CSA 4.3 as an automatic circulating or automatic storage tank type water heater.
natural gas and propane versions. MAKE SURE the gas on which the heater will operate is the same as that specified on the heater model and rating plate.
Heaters having an input of 305,000 (89 Kwh), 365,000 (107 Kwh) and 390,000 (117 Kwh) Btuh with a recovery rating of 277.3 gph (1049 Lph) or more also comply with ANSI Z21.10.3 as an automatic instantaneous type heater.
These heaters may be installed on combustible floors. In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
Detailed installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary. It is highly essential that all water, gas piping and wiring be installed as shown on the diagrams.
In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131. NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
Particular attention should be given to the installation of thermometers at the locations indicated on the diagrams as these are necessary for checking the proper functioning of the heater. This model water heater is designed and manufactured in both 3
GENERAL SAFETY INFORMATION
LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas (LPG) are different from natural gas models. A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas.
PRECAUTIONS
LP gas must be used with great caution. It is highly explosive and heavier than air. It collects first in the low areas making its odor difficult to detect at nose level. If LP gas is present or even suspected, do not attempt to find the cause yourself. Go to a neighbor’s house, leaving your doors open to ventilate the house, then call your gas supplier or service agent. Keep area clear until a service call has been made.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A QUALIFIED SERVICEMAN.
At times you may not be able to smell an LP gas leak. One cause is odor fade, which is a loss of the chemical odorant that gives LP gas its distinctive smell. Another cause can be your physical condition, such as having a cold or diminishing sense of smell with age. For these reasons, the use of a propane gas detector is recommended.
1. EXTERNAL FIRE. 2. DAMAGE. 3. FIRING WITHOUT WATER.
IF YOU EXPERIENCE AN OUT-OF-GAS SITUATION, DO NOT TRY TO RELIGHT APPLIANCES YOURSELF, Ask your LP delivery person to relight pilots for you. Only trained LP professionals should conduct the required safety checks in accordance with industry standards.
4. SOOTING
CHEMICAL VAPOR CORROSION
EXTENDED NON-USE PERIODS
WARNING
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the risk of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. Do not store products of this sort near the heater. Also, air which is brought in contact with a the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions.)
INSULATION BLANKETS
IMPROPER COMBUSTION
Insulation blankets available to the general public for external use on gas water heaters are not approved for use on your American water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your American water heater meets or exceeds the ANSI/ASHRAE/IESNA Standard 90.1 2004 with respect to insulation and standby loss requirement making an insulation blanket unnecessary.
WARNING
ATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE POISONING AND DEATH. OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE DRAFT IN THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY OR VENT PIPE.
WARNING
Should you choose to apply an insulation blanket to this heater, you should follow these instructions. Failure to follow these instructions can result in fire, asphyxiation , serious personal injury or death.
The venting of the water heater should be inspected by a qualified service technician at the time of installation and periodically thereafter to ensure a down-draft condition does not exist.
• Do not apply insulation to the top of the water heater, as this will interfere with safe operation of drafthood.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION.
• Do not cover the gas valve or temperature & pressure relief valve. 4
Upon completion of derating of the heater, adjustment to the gas pressure regulator may be required. See CHECKING THE INPUT section in this manual for inlet and manifold pressure requirements.
• Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. • Do not allow insulation to come within 2” (5 cm) of the burners, to prevent blockage of combustion air flow to the burners.
Also due to the input rating reduction required at high altitudes, the output rating of the appliance is reduced and should be compensated for in the sizing of the equipment for application.
• Do not allow insulation to come within 9” (23 cm) of floor, (within 2” (5 cm) of bottom cover) to prevent blockage of combustion air flow to the burners.
FEATURES
• Do inspect the insulation blanket frequently to make sure it does not sag, thereby obstructing combustion air flow.
(Self-Cleaning System)
• Do obtain new labels from American Water Heater for placement on the blanket directly over the existing labels.
These units include self-cleaning device (Self-Cleaning System) installed in the front water inlet. See figure 2. The Eliminator must be oriented correctly for proper function. There is a marked range on the pipe nipple portion of the Eliminator, that must be aligned with the top of the inlet spud. A label above the jacket hole has an arrow that will point to the marked portion of the pipe nipple if the orientation is correct. If the arrow does not point within the marked range on the pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied with the Eliminator to reduce the probability of misaligning the Eliminator accidentally while tightening the connection to the inlet water supply line. Improper orientation of the Eliminator can cause poor performance of the heater and can significantly reduce outlet water temperatures during heavy draws.
HIGH ALTITUDE INSTALLATIONS WARNING
INSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIRE REPLACEMENT OF THE BURNER ORIFICES IN ACCORDANCE WITH THE CURRENT EDITION OF NATIONAL FUEL GAS CODE (ANSI Z223.1). FAILURE TO REPLACE THE ORIFICES WILL RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE RESULTING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH. You should contact your gas supplier for any specific changes which may be required in your area. As elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply. Failure to make this reduction would result in an overfiring of the heater causing sooting, poor combustion and/or unsatisfactory heater performance.
NOTE: The inlet tube may have 1, 3 or 7 cross-tubes.
Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610 m). For elevations above 2000 feet (610), ratings must be reduced at the rate of 4% for each 1000 feet (305 m) above sea level. For example, if a heater is rated at 120,000 Btuh (35 Kwh) at sea level, to rate the heater at 4000 feet (1219 m), you subtract 4 (once for each thousand feet) x .04 (4% input reduction) x 120,000 (original rating) from the original rating. Therefore, to calculate the input rating at 4,000 feet (121.9 m): 4 x .04 x 120,000 =19,200 Btuh (5.6 Kwh), 120,000 (35 Kwh) - 19,200 (5.6 Kwh) = 100,800 Btuh (29.4 Kwh). At 6000 feet (1829 m) the correct input rating should be 91,200 Btuh (26.7 Kwh).
FIGURE 2 For proper function, The Eliminator must be oriented correctly. There is a marked range on the pipe nipple that must be aligned with the top of the inlet spud (check for label on the appliance) to assure proper orientation. Please check to confirm that the marked range is in alignment with the top of the spud. A pipe union is supplied with The Eliminator to help eliminate the possibility of changing the orientation by accidentally overtightening the inlet supply line. Improper orientation of The Eliminator may cause temperature build-up issues or spells of colder than usual water temperatures.
HIGH LIMIT SWITCH The input reduction is primarily achieved by reducing the size of the main burner orifices. To do this, the main burner orifices require replacement with orifices sized for the particular installation elevation. Correct orifice sizing and parts may be obtained from American Water Heater Company. When ordering, be sure to state the model number and the altitude of the location where the water heater is being installed.
The digital thermostat (Fig. 3) contains the high limit (energy cutoff) sensor. The high limit switch interrupts main burner gas flow should the water temperature reach 203°F (95°C). In the event of high limit switch operation, the appliance cannot be restarted unless the water temperature is reduced to approximately 120°F (49°C). The high limit reset button on the front of the control then needs to be depressed. 5
Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. The following is a possible reason for high limit switch operation:
Each automatic flue damper drive assembly is equipped with a “Service Switch”, as shown in figure 5.
• A malfunction in the thermostatic controls would allow the gas valve to remain open causing water temperature to exceed the thermostat setting. The water temperature would continue to rise until high limit switch operation. Contact your dealer or service agent if continued high limit switch operation occurs.
FIGURE 5 The “Service Switch” has 2 positions: AUTOMATIC OPERATION and HOLD OPEN DAMPER. For normal operation the switch should be in the AUTOMATIC OPERATION position. If there is a problem with the damper the “Service Switch” can be placed in the HOLD OPEN DAMPER position. When the switch is placed in the HOLD OPEN DAMPER position the damper disc will rotate to the open position and the heater may be used until vent assembly is repaired or replaced. DO NOT turn the damper disc manually; damage will occur to the drive assembly if operated manually. Refer to TESTING DAMPER OPERATION section of this manual for additional information.
DIGITAL THERMOSTAT FIGURE 3
ELECTRONIC IGNITION CONTROL Each heater is equipped with a Honeywell ignition module. The solid state ignition control, fig.4, ignites the pilot burner gas by creating a spark at the pilot assembly. Pilot gas is ignited and burns during each running cycle. The main burner and pilot gases are cut off during the OFF cycle. Pilot gas ignition is proven by the pilot sensor. Main burner ignition will not occur if the pilot sensor does not first sense pilot ignition.
CIRCULATING PUMP A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams in this manual for electrical hookup information and install in accordance with the current edition of the National Electrical Code NFPA 70. Only all bronze circulators should be used with commercial water heaters. Although circulating pumps are oiled and operated by the manufacturer some circulators must be oiled again before operating. Please refer to manufacturer’s instructions.
DISHWASHING MACHINE REQUIREMENT These appliances meet the NSF Standard 5 for sanitary installations when used with the following leg kits, Part No 9003425205. All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 psi (103 kPa and 173 kPa). Flow pressures above 25 psi (173 kPa), or below 15 psi (103 kPa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in 180°F (82°C) line to the dishwashing machine, and should be adjusted to deliver water between these limits.
HONEYWELL IGNITION MODULE S8600M Continuous Re-Try FIGURE 4
AUTOMATIC FLUE DAMPER DEVICE All units are equipped with an automatic flue damper that reduces heat loss during the OFF cycles. 6
The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine. Adjust flow by means of the plug cock in the circulating line.
NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER.
INSTALLATION INSTRUCTIONS
LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.
REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
When such locations cannot be avoided, it is recommended that a suitable metal drain pan, adequately drained, be installed under the appliance. Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
UNCRATING The heater is shipped with the flue damper already installed. The wiring conduit runs from the thermostat to the damper drive cover. Before turning unit on, check to make sure the wiring conduit is securely plugged into damper drive.
• Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.
LOCATING THE HEATER When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible.
• Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan. • Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IN SUCH AREAS IF THEY ARE INSTALLED 18” (.50 m). OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
• Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply. WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE METAL DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such pans should be fabricated with sides at least 2” (5 cm) deep, with length and width at least 2” (5 cm) greater than the diameter of the heater and must be piped to an adequate drain. The pan must not restrict combustion air flow.
LEVELING
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches (7.6 cm) in any direction. If the heater is installed in a carpeted alcove, the entire floor shall be covered by the panel. Also, see the DRAIN REQUIREMENTS.
If the unit is not level, insert the bolts which were used in crating into the legs to correct this condition.
CLEARANCES These heaters are approved for installation on combustible flooring in an alcove when the minimum clearance from any combustion construction are followed as indicated in figure 6 and Table 2.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
WARNING
The following units are approved for installation with side, rear and ceiling clearances as indicated below:
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST 7
ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE FIGURE 6
BCG370T120’s
A (RIGHT SIDE)
B (LEFT SIDE)
C (BACK)
D (CEILING)
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
BCG380T150’s
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
BCG380T180’s
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
BCG3100T199’s
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
BCG380T199’s
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
(A)BCG3100T200’s
1” (2.54 cm)
1” (2.54 cm)
1” (2.54 cm)
12” (30.48 cm)
(A)BCG3100T250’s
2” (5.08 cm)
2” (5.08 cm)
2” (5.08 cm)
12” (30.48 cm)
(A)BCG365T250’s
2” (5.08 cm)
2” (5.08 cm)
2” (5.08 cm)
12” (30.48 cm)
(A)BCG3100T275’s
2” (5.08 cm)
2” (5.08 cm)
2” (5.08 cm)
12” (30.48 cm)
(A)BCG365T300’s
2” (5.08 cm)
2” (5.08 cm)
2” (5.08 cm)
12” (30.48 cm)
(A)BCG385T360’s
3” (7.75 cm)
3” (7.75 cm)
3” (7.75 cm)
12” (30.48 cm)
(A)BCG3100T390’s
3” (7.75 cm)
3” (7.75 cm)
3” (7.75 cm)
12” (30.48 cm)
WARNING
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS AND LIQUIDS. DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR VENTILATING AIR.
WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION.
TABLE 2 In all installations the minimum combustible clearances from any draft hood surface or vent piping shall be 6” (16cm). Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints) and retain the 6” (16cm) clearance unless an approved reducing thimble is used.
Where an exhaust fan is supplied in the same room with a heater, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR EXPLOSION.
A service clearance of 24” (61cm) should be maintained from serviceable parts, such as relief valves, flue baffles, flue damper devices, thermostats, cleanout openings or drain valves.
HARD WATER
UNCONFINED SPACE
Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.
In buildings of conventional frame, brick, or stone construction, unconfined spaces may provide adequate air for combustion, ventilation and draft hood dilution. If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood dilution must be obtained from outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
See MAINTENANCE section for details of tank cleanout procedure.
AIR REQUIREMENTS
REFER TO THE CURRENT EDITION OF THE “NATIONAL FUEL GAS CODE” ANSI Z223.1/NFPA 54. 8
CONFINED SPACE
This water heater must be vented in compliance with all local codes, the current edition of the National Fuel Gas Code (ANSIZ223.1) and with the Category I Venting Tables.
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2,225mm2/Kw) of the total input of all appliances in the enclosure, but not less than 100 square inches (645 square cm).
If any parts of the vent system are exposed to ambient temperatures below 35 degrees F (2 degrees C) they must be insulated to prevent condensation. • Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.
If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh (8,900mm2/Kw) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh (4,450mm2/Kw) of the total input of all appliances in the enclosure.
• Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe.
VENT REDUCER The BCG3100T2508N, BCG365T2508N, & BCG3100T2758N all models are shipped with an 8” to 6” diameter flue outlet adapter. Each adapter fits on top of the installed flue damper. Use only vent reducers supplied with the unit. The venting must comply with the NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54.
FIGURE 8
MULTIPLE HEATER MANIFOLD Figure 10 and table 3 should be used for horizontally manifolding two or more heaters. Also see MULTIPLE-UNIT INSTALLATIONS of MECHANICAL VENTING section for induced draft applications.
FIGURE 7
VENTING
FIGURE 9
WARNING
WATER LINE CONNECTIONS
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
This manual provides detailed installation diagrams (see pages 16-22 of this manual) for typical methods of application for the water heaters.
Heater must be protected from freezing downdrafts.
The water heater may be installed by itself, or with a separate storage tank, on both single and two-temperature systems. When used with a separate storage tank, the circulation may be either by gravity or by means of a circulating pump. When a circulating pump is used it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the heater.
Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is recommended with these heaters. See table 3 TECHNICAL DATA VENTING. 9
TECHNICAL DATA VENTING, TABLE 3
TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting mutiple tank type heaters using Type B vent pipe, follow the installation diagram (figure 8) and tables below which give sizing and data based upon NFPA 54/ANSI Z223.
FIGURE 10 MODEL BCG370T1205_ Input: 120,00Btuh Total Vent Height (Feet) Draft Hood: 5” 6 8 10 15 20 30 50 100 Input Btuh Rise V ent Connector Diameter (inches) 120,000 1 Ft. 7 7 7 6 6 6 6 6 120,000 2 Ft. 6 6 6 6 6 6 6 5 123,000 3 Ft. 6 6 6 6 6 5 5 5 Number Combined Input of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (In inches) 2 240 10 8 8 7 7 7 6 7 3 360 10 10 10 10 8 8 7 7 4 480 12 12 12 10 10 10 8 8 MODEL BCG380T1506_ Input: 154,000 Btuh Total Vent Height (Feet) Draft Hood: 6” 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter (in inches) 154,000 1 Ft. 8 8 7 7 7 7 7 7 154,000 2 Ft. 7 7 7 7 7 6 6 6 154,000 3 Ft. 7 7 7 6 6 6 6 6 Numbers Combined Input of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (in inches) 2 308 10 10 10 8 8 7 7 7 3 462 12 12 12 10 10 10 8 8 4 618 14 14 12 12 12 10 10 10 MODEL BCG380T1806_, BCG3100T1996_, BCG380T1996_, & (A)BCG3100T2006_ Input: 180,000, 199,000 Btuh T otal Vent Height (Feet) Draft Hood: 6” 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter (in inches) 180,000 1 Ft. 8 8 8 8 8 7 7 7 190,000 - 8 8 8 8 8 7 7 199,000 - - 8 8 8 8 8 7 180,000 2 Ft. 8 8 7 7 7 7 7 7 190,000 8 8 8 7 7 7 7 7 199,000 8 8 8 8 7 7 7 7 179,000 3 Ft. 7 7 7 7 7 7 6 6 190,000 8 7 7 7 7 7 6 6 197,000 8 7 7 7 7 7 7 6 199,000 8 8 7 7 7 7 7 6 Number of Combined Input Heaters in Thousands of Btuh Manifold & Common Vent Diameter 358 10 10 10 10 8 8 7 7 2 380 12 10 10 10 10 8 7 7 394/398 12 10 10 10 10 8 8 7 537 14 12 12 12 10 10 10 8 3 570 14 12 12 12 10 10 10 10 591/597 14 14 12 12 12 10 10 10 716 14 14 14 12 12 12 10 10 4 760 16 14 14 14 12 12 10 10 788/796 16 14 14 14 12 12 12 10 10
TECHNICAL DATA VENTING, TABLE 3 (Continued)
MODEL (A)BCG365T2508_, (A)BCG3100T2508_ Input: 250,000, 251,000 Total Vent Height (Feet) Draft Hood: 6” 6 8 10 15 20 30 50 100 Input Btuh Rise V ent Connector Diameter (in inches) 250/251,000 1 Ft. - - - - - - 8 8 250/251,000 - - - 8 8 8 8 8 250/251,000 3 Ft. - 8 8 8 - 8 7 7 Number Combined Input of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (In inches) 2 480 14 12 12 10 10 10 8 8 500/502 14 12 12 10 10 10 10 8 3 720 14 14 14 12 12 12 10 10 750/753 16 14 14 14 12 12 10 10 4 960/1000/1004 18 16 16 14 14 14 12 12 MODEL (A)BCG3100T2758_ Input: 275,000 Btuh Total Vent Height (Feet) Draft Hood: 6” 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter (in inches) 275,000 2 Ft. - - - - - 8 8 8 275,000 3 Ft. - - - 8 8 8 8 8 Numbers Combined Input of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (in inches) 2 550 - - - 12 10 10 10 10 3 825 - - - 14 14 12 12 12 4 1100 - - - 16 14 14 12 12 MODEL (A)BCG365T3008_ Input: 305,000 Btuh T otal Vent Height (Feet) Draft Hood: 8” 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter (in inches) 315,000 1 Ft. - - 10 10 10 10 10 10 305,000 2 Ft. 10 10 10 10 10 10 8 8 365,000 3 Ft. 10 10 10 10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold & Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL (A)BCG385T3608_, (A)BCG3100T3908_ Input: 365,000, 399,000 Total Vent Height (Feet) Draft Hood: 8” 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter (in inches) 365,000 1 Ft. - - - - - 10 10 10 400,000 - - - - - - 10 10 365,000 2 FT. 12 12 10 10 10 10 10 10 400,000 12 12 12 12 10 10 10 10 365,000 3 FT. 10 10 10 10 10 10 10 10 400,000 12 10 10 10 10 10 10 10 Number of Combined Input Heaters in Thousands of Btuh Manifold & Common Vent Diameter (inches) 2 730 14 14 14 12 12 12 10 10 800 16 14 14 14 12 12 10 10 3 1095 18 18 16 16 14 14 12 12 1200 18 18 18 16 16 14 14 12 4 1460 20 20 18 18 16 16 14 12 1600 22 20 20 18 18 16 14 14
11
If a water heater is installed in a closed water system, contact the water supplier or local plumbing inspector on how to control this situation.
installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s).
WATER (POTABLE) HEATING AND SPACE HEATING
T H E P U R P O S E O F R E L I E F VA LV E I S T O AV O I D EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.
WARNING
1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.
Your local code authority may have other specific relief valve requirements.
3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 15 through 20 in this manual for suggested piping arrangements.
CAUTION
As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.
See SERVICE INFORMATION section for procedure and precautions.
GAS PIPING Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.
A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank.
Size the main gas line in accordance with Table 4. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the current edition of the National Fuel Gas Code.
SYSTEM CONNECTIONS The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported.
TABLE 4 - GAS SUPPLY LINE SIZES (IN INCHES)* MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR
THERMOMETERS (Not Supplied)
NOMINAL IRON PIPE SIZES (INCHES)
LENGTH
Thermometers should be obtained and field installed as shown in the installation diagrams.
IN
FEET 1/2” 3/4”
Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.
RELIEF VALVE This water heater is equipped with a combination temperaturepressure relief valve that complies with the standard for relief valves for hot water supply system, ANSI Z21.22-CSA 4.4. FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED. ASME ratings cover pressure relief capacities. ANSI ratings cover release rate with temperature actuation. In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be 12
1” 1 1/4” 1 1/2” 2” 2 1/2”
3”
4”
10
175 360 680 1400 2100 3960 6300 11000 23000
20
120 250 465 950
1460 2750 4360 7700 15800
30
97
200 375 770
1180 2200 3520 6250 12800
40
82
170 320 660
990 1900 3000 5300 10900
50
73
151 285 580
900 1680 2650 4750 9700
60
66
138 260 530
810 1520 2400 4300 8800
70
61
125 240 490
750 1400 2250 3900 8100
80
57
118 220 460
690 1300 2050 3700 7500
90
53
110 205 430
650 1220 1950 3450 7200
100
50
103 195 400
620 1150 1850 3250 6700
125
44
93
175 360
550 1020 1650 2950 6000
150
40
84
160 325
500
950 1500 2650 5500
175
37
77
145 300
460
850 1370 2450 5000
200
35
72
135 280
430
800 1280 2280 4600
READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING C O N D I T I O N S . I N S TA L L I N A C C O R D A N C E W I T H RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE.
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 14.0” W.C.(3.5 kPa) (1/2 POUND PER SQUARE INCH GAGE- 3.5 kPa) SUPPLY GAS PRESSURE. EXPOSURE TO HIGHER SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS VALVE WHICH COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR DURING ICE STORMS.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
GAS PIPING AND DIRT LEG INSTALLATION
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION. IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE. TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 11). THE DIRT LEG MUST BE
FIGURE 11
FIGURE 12 13
The minimum gas supply pressure for input adjustment must not be less than 4.5” w.c. (1.12 kPa) for natural gas and 11.0” w.c. (2.74 kPa) for propane gas.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material acceptable for the purpose in locating the leaks. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
Do not subject the combination gas valve to inlet gas pressures of more than 14.0” W.C. (3.48 kPa) - natural gas, 14.0” W.C. (3.48 kPa)- propane gas. A service regulator is necessary if higher gas pressures are encountered.
DISCONNECT THE HEATER AND ITS MANUAL GAS SHUT-OFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.5 kPa). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1/2 PSIG (3.5 kPa) OR LESS. THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS Shut-off VALVE.
Gas pressure specified in Table 5, refer to flow pressure taken at pressure tap of automatic gas valve while heater is operating.
GROUNDING INSTRUCTIONS This water heater must be connected to a grounded metal, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater.
GAS METER SIZE — NATURAL GASES ONLY Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity.
HEATER WIRING All electrical work must be installed in accordance with the current edition of the National Electrical Code NFPA 70 and must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION (see FIGURE 12).
GAS PRESSURE REGULATOR The gas pressure regulator is built into the gas valve and is equipped to operate on the gas specified on model and rating plate. The regulator is factory adjusted to deliver gas to burner at correct water column pressure allowing for a nominal pressure drop through the controls.
If any of the original wire as supplied with the appliance must be replaced, use only type 105°C thermoplastic or equivalent. 250°C type F must be used for the flame sensor leads and the spark ignition cable must be high voltage 250°C.
INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGE GENERAL
installations in the state of North Carolina, due to the material of the tube (Polypropylene). Where such code restrictions exist, use only lower inlet tank connection. This may also require a heat trap - check local codes. The “Top Outlet” connection may still be used on these applications. Plug or cap all unused openings in the tank before filling with water.
The type, size and location of the relief valves must be in accordance with local codes. The locations of the relief valves shown in the installation diagrams are typical. The heater has a factory installed high temperature limit switch and temperature and pressure relief valve. Cold water lines to heater should be installed as shown in order to minimize gravity circulation of hot water to building cold water lines.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
A listed temperature and pressure relief valve of adequate capacity is installed on the heater. The locations shown in the installation diagrams on the following pages are typical. The discharge opening of the temperature and pressure relief valve, located in front of the heater must be piped to an open drain and should not be subject to freezing temperatures.
TUBE INLET INSTALLATION
Install in accordance with all local codes. Use of the top inlet water connection requires installation of an inlet dip tube (refer to figure 11). The tube is supplied in the heater. Follow caution labels if applying heat to this fitting. Do not allow pipe dope to contact the plastic tube during installation.
CODE RESTRICTIONS Use of the top inlet water connection is not permitted on
FIGURE 13 14
VERTICAL STORAGE TANK AND FORCED CIRCULATION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
HORIZONTAL STORAGE TANK AND FORCED CIRCULATION
15
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE WITH RECIRCULATION OF SANITIZING LOOP
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERATION AND OPEN (OFF) WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY. NOTE 2: I N S TA L L L I N E T E M P E R AT U R E C O N T R O L I N A N UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F (85°C).
INSET A
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK.
* TEMPERED WATER LOOP, IF USED, CONNECT TO POINT “A”. **PIPE RELIEF VALVE TO OPEN DRAIN. INSTALL IN ACCORDANCE WITH LOCAL CODES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.
16
INSTALLATION DIAGRAMS-SIDE INLET/OUTLET USAGE A listed temperature and pressure relief valve of adequate capacity is installed on the heater. The locations shown in the installation diagrams on the following pages are typical.
The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject to freezing conditions. DO NOT REDUCE, BLOCK OR PLUG THE DISCHARGE OPENING OF THE VALVE.
TWO TEMPERATURE - TWO HEATERS, ONE PRE-HEATER/ONE - BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
INSET A
CIRCULATING RETURN LINE CONNECTIONS - FROM FIXTURE LOOP, IF USED, CONNECT TO PREHEATER INLET. - FROM BOOSTED TEMPERATURE LOOP, IF USED CONNECT TO BOOSTER INLET. †AVALAIBLE FROM AMERICAN. *PIPE RELIEF VALVE TO OPEN DRAIN. INSTALL IN ACCORDANCE WITH LOCAL CODES.
17
ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE STORAGE WITH OR WITHOUT RECIRCULATION HEATER WITH OR WITHOUT MIXING VALVE
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
INSET A
HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE INSTALL IN ACCORDANCE WITH LOCAL RINSE OPERATION AND OPEN (OFF) WHEN CODES. DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY. CIRCULATING RETURN LINE CONNECTIONS.
* PIPE RELIEF VALVE TO OPEN DRAIN.
- T E M P E R E D W AT E R L O O P, I F U S E D , CONNECT TO POINT “R”. - STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO COLD WATER INLET.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.
18
NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F (85°C). NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK.
TWO TEMPERATURE - TWO PRE-HEATERS WITH MIXING VALVE OR BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION TWO PRE-HEATERS WITH MIXING VALVE
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
INSET A
TWO PRE-HEATERS WITH BOOSTER HEATER
19
MEDIUM TEMPERATURE - ONE HEATER WITH AUXILIARY STORAGE TANK FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION VERTICAL STORAGE TANK
* PIPE RELIEF VALVE TO OPEN DRAIN. ** WHEN USING AN AMERICAN T-140 -200, -350 OR -400 STORAGE TANK, USE LOWER 3/4” OPENING FOR TANK TEMPERATURE CONTROL.
IF BUILDING CIRCULATING LOOP IS USED, CONNECT TO AN OPENING NEAR THE BOTTOM OF THE TANK.
INSET A
HORIZONTAL STORAGE TANK
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED. *PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
20
TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN (ALL MODELS*) TYPE OF GAS NATURAL PROPANE 3.5 10.0
Gas pressure specified in Table 5, refer to flow pressure taken at pressure tap of automatic gas valve while heater is operating. TABLE 6 APPROXIMATE TIME REQUIRED TO CONSUME 1 CU. FT. OF GAS AT FULL CAPACITY INPUT RATE TYPE OF GAS (BTUH) 120,000 154,000 180,000 199,000 250,000 251,000 275,000 305,000 365,000 390,000
BTUH PER CU. FT.
NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE
1050 2500 1050 2500 1050 2500 1050 2500 1050 2500 1050 2500 1050 2500 1050 2500 1050 2500 1050 2500
TIME REQ’D TO CONSUME 1 CU. FT. OF GAS 31.5 SEC. 75.0 SEC. 24.5 SEC. 58.4 SEC. 21.1 SEC. 50.3 SEC. 19.0 SEC. 47.4 SEC. 15.1 SEC. 35.3 SEC. 15.06 SEC. 35.1 SEC. 13.75 SEC. 32.2 SEC. 12.4 SEC. 29.5 SEC. 10.4 SEC. 24.7 SEC. 9.5 SEC. 22.6 SEC.
Figures shown are valid for 0-2000 ft.(0-610m) installations. See “HIGH ALTITUDE INSTALLATIONS” for deration requirements over 2000 ft.(610m). TABLE 7 PILOT BURNER INFORMATION
MODEL ALL MODELS
TYPE OF GAS
PILOT BURNER PART NUMBER (WITH ORIFICE)
RATED ORIFICE SIZE
NATURAL
193314-004
0.018
PROPANE
193314-003
0.014
21
OPERATION
PURGING Gas line purging is required with new piping or systems in which air has entered.
IMPORTANT A qualified person must perform the initial firing of the heater. At this time the user should not hesitate to ask the individual any questions which they may have in regard to the operation and maintenance of the unit.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE. TO AVOID RISK OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED.
An Operational Checklist is included at the rear of this manual. By using this checklist the user may be able to make minor operational adjustments and avoid unnecessary service calls. However, the user should not attempt repairs which are not listed under the USER column.
WARNING
THE GAS VALVE MUST HAVE BEEN IN THE OFF POSITION FOR AT LEAST 5 MINUTES. This waiting period is an important safety step. Its purpose is to permit gas that may have accumulated in the combustion chamber to clear. IF YOU DETECT GAS ODOR AT THE END OF THIS PERIOD DO NOT PROCEED WITH LIGHTING. RECOGNIZE THAT GAS EVEN IF IT SEEMS WEAK, MAY INDICATE PRESENCE OF ACCUMULATED GAS SOMEPLACE IN THE AREA WITH RISK OF FIRE OR EXPLOSION. SEE THE FRONT PAGE FOR STEPS TO BE TAKEN. All gas and water lines leak tested and open.
GENERAL NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
With above conditions satisfied, light the unit in accordance with the instructions on the Operating label attached to the heater. If label instructions are not legible - determine which gas valve the appliance is equipped with and use the applicable OPERATING INSTRUCTIONS as follows:
CAUTION
Before proceeding with the operation of the unit make sure the water heater and system are filled with water and all air is expelled.
IF PILOT FLAME GOES OUT - Main burners will extinguish and pilot will attempt reignition.
FILLING
DAMPER MUST BE IN FULL OPEN POSITION FOR PILOT AND/ OR MAIN BURNER IGNITION TO OCCUR - See SEQUENCE OF OPERATION for complete description.
1. Close the heater drain valve by turning handle clockwise. 2. Open a nearby hot water faucet to permit the air in the system to escape.
Each heater is equipped with a Honeywell Ignition Module. This module will try to prove pilot for 90 seconds. If pilot is not proven within the 90 secs, the unit will retry after 5 minutes. This cycle will continue until pilot is proven.
3. Fully open the cold water inlet pipe valve allowing the heater and piping to be filled.
If pilot does not ignite when system calls for heat, check for pilot ignition spark at pilot assembly. Refer to OPERATIONAL CHECKLIST and EFFIKAL RVGP-KSF SERIES FLUE DAMPER TROUBLESHOOTING GUIDE.
4. Close the hot water faucet as water starts to flow. 5. The heater is ready to be operated.
22
FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
23
FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
24
ADJUSTMENTS
that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority.
ON INITIAL STARTUP SOME ADJUSTMENTS ARE NECESSARY.
The water temperature is controlled by a thermostat, Fig. 3, which has two sensing elements. One sensor is located near the top of the tank and the other is near the center. The thermostat is set in the lowest position before the heater leaves the factory.
1. CHECK MANIFOLD AND INLET GAS PRESSURES. 2. TO ADJUST PILOT FLAME - FOLLOW “PILOT BURNER” PROCEDURE UNDER “PREVENTIVE MAINTENANCE”.
The thermostat temperature dial, Fig. 3, is accessible by removing the control cover. The dial is adjustable and may be set for 120°F (49°C) to 180°F (82°C) water temperature, but 120°F (49°C) is the recommended starting point. It is suggested the dial be placed on the lowest setting which produces an acceptable hot water supply. This will always give the most energy efficient operation. The temperature control has a 4°F fixed differential.
WATER TEMPERATURE CONTROL
TESTING DAMPER OPERATION With the Service Switch in the AUTOMATIC OPERATION position, check the operation of the flue damper three (3) times with the water operating controls for proper operating sequence:
WARNING
• The damper disc must be open (in the vertical position) before the ignition and combustion process begins.
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/ OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.
• The damper disc must be in the open position when the main burner is firing. • The gas valve must close and the main burner must have ceased firing before the damper disc begins its return to the closed (horizontal) position. If during testing of the operation of the damper you find that there is a problem with the operation of the water heater when the Service Switch is in the AUTOMATIC OPERATION position: Reset the Service Switch to the HOLD OPEN DAMPER position and check operation again.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET TEMPERATURES. SETTING THE WATER HEATER TEMPERATURE AT 120°F WILL REDUCE THE RISK OF SCALDS. Some states or provinces require settings at specific lower temperatures.
If the water heater does operate when placed in the HOLD OPEN DAMPER position: • Refer to the EFFIKAL RVGP-FSF-SERIES TROUBLESHOOTING GUIDE at the end of this manual.
Below you will find listed the approximate time-of-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F (11°C).
CAUTION
If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards.
Do not force the damper disc manually or motor damage will occur.
TABLE 8
If the water heater does not operate with the Service Switch in either position:
Temperature Settings 180°F (82°C) 170°F (77°C) 160°F (71°C) 150°F (65°C) 140°F (60°C) 130°F (54°C) 120°F (49°C)
Time to Produce 2nd & 3rd Degree Burns on Adult Skin Nearly Instantaneous Nearly Instantaneous About 1/2 Second About 1 - 1/2 Seconds Less than 5 Seconds About 30 Seconds More than 5 Minutes
• Refer to the Troubleshooting Sections and Operational Checklist sections. CHECKING VENTING The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.
Valves for reducing point-of-use temperature by mixing cold and hot water are available. Also available are inexpensive devices
1. Seal any unused openings in the venting system. 25
• The pilot flame should envelop sensing device with 5/8” (1.6cm) flame, fig. 16. Remove pilot adjustment cover screw, fig. 15. Turn inner adjustment screw clockwise to decrease, or counterclockwise to increase pilot flame. Be sure to replace cover screw on gas valve after adjustment to prevent possible gas leakage.
2. Inspect the venting system for proper size and horizontal pitch, as required in the current edition of National Fuel Gas Code, ANSI Z223.1 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers.
2. Clogged pilot burner orifice.
•
Clean or replace orifice. A clogged orifice will restrict gas flow.
3. Incorrect orifice. • Replace. See Table 7, for correct orifice for type of gas used. Orifice size is stamped on the wrench flats.
4. Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so appliance shall operate continuously. 5. Test for draft hood spillage at the relief opening after 5 minutes of main burner operation. 6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use. 7. If improper venting is observed during any of the above tests, the venting system must be corrected.
WARNING
FIGURE 14
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.
Pilot sensing device must sense a flame before sparking will stop. Loose wires or a draft may cause intermittent or abnormal sparking. To eliminate this condition, first correct loose wiring condition, and then, if necessary, increase pilot flame.
• If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.
PILOT BURNER ASSEMBLY
PREVENTIVE MAINTENANCE CHECK THE PILOT At least once a year, check the pilot burner, fig. 15, and the main burner, fig. 16, for proper operation. Refer to the following pilot and main burner sections.
PILOT BURNER For access to pilot, unfasten two screws to burner cover and remove. Locate the burner with pilot and remove screw holding burner to manifold. Unfasten pilot tubing from valve and slide out burner and pilot.
FIGURE 15
MAIN BURNER
Servicing of the pilot burner includes keeping pilot free of lint, cleaning the burner head, the primary air opening and the orifice of the pilot burner.
The main burner, fig. 16, should display the following characteristics:
Pilot burner flame is affected by:
• Cause rapid ignition and carry over of flame across entire burner.
1. Low gas pressure.
• Give reasonably quiet operation during ignition, burning and extinction.
• Adjust pilot flame by means of the pilot gas adjustment located on the gas valve. See fig. 17.
• Cause no excessive lifting of flame from burner ports. 26
TYPICAL PILOT AND MAIN BURNER FLAMES
If the gas valve becomes defective, repairs should not be attempted. A new valve should be installed in place of the defective one.
CHECKING THE INPUT For appliance installation locations with elevations above 2000 feet (610 m), refer to HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure.
FIGURE 16 If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or other foreign material that restricts or blocks the air openings to the burner or heater.
1. Attach a pressure gauge or a manometer to the gauge port and refer to Table 5, for correct manifold pressure. 2. Use this formula to “clock” the meter. Be sure that other gas consuming appliances are not operating during this interval.
NOTE: Cleaning of main burners. 1. Remove main burners from unit.
3600 X H = Btuh T
T = Time in seconds to burn one cubic foot of gas.
H = Btu’s per cubic foot of gas.
4. Reinstall burners in unit. Make sure front and rear of burners are installed correctly in burner support brackets.
Btuh = Actual heater input.
Also check for good flow of combustion and ventilating air to the unit. Maintain a clear area around the heater at all times.
Example: (Using BTRC-199 heater) T = 15.8 seconds
GAS VALVES
H = 1050 Btu
Btuh = ?
19.0 X 1050 = 199,000 Btuh (70.3 Kwh) (Compare with 15.9 heater model and rating)
2. Check that burner venturi and ports are free of foreign matter. 3. Clean burners with bristle brush and/or vacuum cleaner — DO NOT distort burner ports or pilot location.
Figure 17 shows the two types of combination gas control valves used on these heaters.
Should it be necessary to adjust the gas pressure to the burners to obtain the full input rate, the steps below should be followed: 3. Remove the regulator adjustment sealing cap, fig. 17, and adjust the pressure by turning the adjusting screw with a screwdriver. Clockwise to increase gas pressure and input rate.
LP VALVE
Counterclockwise to decrease gas pressure and input rate.
4. “Clock” the meter as in step 2 above. 5. Repeat steps 3 and 4 until the specified input rate is achieved. 6. Turn the gas control knob to PILOT. Remove the pressure gauge and replace the sealing cap and the allen wrench set screw in the pressure tap opening.
WARNING
UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT EXCEED THE INPUT SHOWN ON THE HEATER MODEL AND RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE OR SOOTING OF THE HEATER.
NATURAL VALVE
When the heater is operating at full capacity, or full gas input, it should consume 1 cu. ft. of gas in time indicated on Table 6.
FIGURE 17 27
VENTING SYSTEM
the factory installed magnesium anodes with aluminum anodes may correct the condition.
Examine the venting system every six months for obstructions and/or deterioration of the vent piping.
Occasionally water softener companies recommend removal of heater anodes for odor reasons.
Remove all soot or other obstructions from chimney which will retard free draft.
CAUTION
Unauthorized removal of the anode(s) will void the warranty. For further information contact your dealer.
REMOTE STORAGE TANK TEMPERATURE CONTROL
ANODE ROD INSPECTION
The water temperature in the storage tank (if used) is controlled by the storage tank temperature control. The sensing element is mounted in the hot water storage tank, see page 16.
The heater tank is equipped with anode rods to provide corrosion control. At least once a year the anode rods should be checked to determine if replacement is necessary. Initially the anode rods are approximately 7/8” (22mm) in diameter with a 1/8” (3mm) diameter steel core wire running down the center of the anode material. THE ANODES SHOULD BE REPLACED when the 1/8” (3mm) diameter core wire is visible as this means that the anode material has been expended in the control of corrosion.
A change in water temperature in the storage tank lower than the tank temperature control setting will cause the sensor to activate the circulating pump. The pump then circulates the water through the heater where the thermostat senses the drop in water temperature and activates main burner operation of the appliance. If the storage tank temperature control is out of calibration, replace with new control.
For models with top inlet and outlet, it is recommended that, before removing the inner cover for cleaning, inspection or removal of inner parts, you obtain two new nipple collars, part no. 74060. The nipple collars on the heater will usually be damaged when removed. New pipe collars will insure that the seal is such as to prevent leakage of flue products when properly installed.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
RELIEF VALVE
NOTE: Anode rod inspection may need to be made more frequently in areas subject to acid rain that obtains their water supply from surface water as the low pH will accelerate anode consumption.
At least once a year, the temperature and pressure relief valve should be checked to ensure that it is in operating condition. Lift the lever at the top of the valve several times until the valve seats properly and operates freely.
CAUTION: Close cold water inlet valve serving heater and open nearby hot water faucet to relieve the pressure in the heater before attempting to remove anode(s) for inspection.
If the appliance installation includes other relief valves, such as in “remote” storage tanks etc., check their relief valve operation with the same frequency.
WARNING
RECOMMENDED PROCEDURE FOR PERIODIC REMOVAL OF LIME DEPOSITS FROM TANK TYPE COMMERCIAL WATER HEATERS
THE WATER PASSING OUT OF THE VALVE DURING THIS CHECKING OPERATION MAY BE EXTREMELY HOT. AVOID CONTACT AND DISCHARGE SAFELY TO PREVENT WATER DAMAGE. If the temperature and pressure relief valve on the heater discharges periodically or continuously, a problem exists. This may be due to unusually high water temperatures or pressures in the system, or to a faulty relief valve. Contact your dealer or a qualified service technician to find the cause of the problem and to correct it. This may also be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.
The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the heater and increases fuel consumption. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
HOT WATER ODOR
The time between cleaning will vary from weeks to months depending upon water conditions and usage.
On occasion, hot water may develop a strong odor. If this occurs drain the heater completely, flush thoroughly, and refill. If the problem persists, chlorination of the heater and replacement of
Refer to American booklet, Form No. 4800, entitled “Why? When and How” for detailed description on tank inspection and 28
TROUBLESHOOTING IGNITION MODULE SYSTEM
cleanout. UN•LIME® and the booklet may be obtained through your American dealer or distributor.
Before calling your service agent, the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing. — Check that “main manual gas shut-off valve” is fully open and that gas service has not been interrupted. — Check that after following the appliance OPERATING INSTRUCTIONS, the “Top Knob” of the appliance gas valve is in “ON” position. — Check electrical supply to the appliance for possible blown (or tripped) fusing or power interruption. — Is the water temperature in tank below the thermostat dial setting on the appliance thermostat (calling for heat)? — It is possible that the high limit (E.C.O.) has functioned to shut off the appliance. See FEATURES — Water Temperature Control for reset procedure. Contact your serviceman if limit continues to function to shut off appliance.
FIGURE 18 CAUTION Observe handling instructions on label of product being used.
TANK CLEANOUT PROCEDURE
SERVICE
The following practices will ensure longer life and enable the unit to operate at its designed efficiency:
The installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER, it is recommended that only qualified servicemen, using appropriate test equipment, be allowed to service the heater.
1. Once a month the heater should be flushed. Open the drain valve and allow two gallons of water to drain from the heater. Inlet water valve should remain open to maintain pressure in tank.
As preliminary step, check wiring against diagram, check for grounded, broken or loose wires. Check all wire ends to be sure that they are making good contact.
2. A cleanout opening is provided for periodic cleaning of the tank. Gas must be shut off and heater drained before opening cleanout.
ELECTRICAL SERVICING
To clean heater through cleanout opening, proceed as follows: 1. Drain heater.
CAUTION
2. Remove outer cover plate from lower side of heater jacket.
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
3. Remove six (6) hex head screws securing tank cleanout plate and remove plate.
VERIFY PROPER OPERATION AFTER SERVICING.
4. Remove lime, scale, or sediment using care not to damage the glass lining.
REPLACEMENT PARTS
5. Inspect cleanout plate gasket, if new gasket is required, replace with American Water Heater Company part no. 99038.
Replacement parts may be ordered through American Water Heater Company. When ordering parts be sure to state the quantity, part number and description of the item(s) including the complete model and serial number as it appears on the product. Refer to the part’s list for more information.
6. Install cleanout plate. Be sure to draw plate up tight by tightening screws securely. 7. Replace outer jacket cover plate. 29
EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE Do not turn damper open manually or motor damage will result, use the service switch. All readings are taken from harness receptacle. Do not push meter leads into harness receptacle. This opens the pins and will create connection problems.
Effikal Pinouts Adapter wire & wire colors Function colors in* 1. Brown 24 VAC HOT Black 2. Orange Signal In Yellow 3. Yellow Signal Out Red 4. Black 24 VAC Common White *See Connection Diagram, Figure 14.
PIN END VIEW Note: Damper disc shown in open position.
24 V.A.C.
NORMAL SEQUENCE OF OPERATION
A. FLUE DAMPER OPEN OR OPENING (Unit is calling for heat and damper disc should be in vertical position) WARNING VOLTAGE ACROSS: Do not negate the action 4 & 1 All Times that High Limit is closed of any existing safety 4 & 2 Calling for Heat Open or Opening or operational controls. 4 & 3 During Combustion Damper Open+ B. FLUE DAMPER CLOSED (Unit is not calling for heat and damper disc should be in horizontal position) NOTE: POSITION 4 IS COMMON AND POSITION 3 IS HOT 24VAC VOLTAGE ACROSS: 4 & 1 All Times that High Limit is closed NO VOLTAGE ACROSS: 4 & 3 or 4 & 2 1.Thermostat not calling for heat.
ABNORMAL OPERATION
A. NOTHING WORKING NO VOLTAGE ACROSS: 4 & 1 1. High Limit has tripped and is OPEN. Determine reason for tripping of high limit 2. Bad Transformer 3. Loose or broken connections 4. Blown fuse or circuit breaker 5. Disconnect switch off 6. Harness not plugged into appliance receptacle B. DAMPER HAS OPENED, NO COMBUSTION VOLTAGE ACROSS: 4 & 1; 4 & 2; 4 & 3: 1. Check for power at ignition module terminals. If 24VAC power is present damper is working properly. 2. Defective component in appliance after the flue damper. 3. If 24 VAC is not present at the ignition module, look for loose or broken connections between damper and ignition module. 4. If the connections from damper to ignition module seem proper, replace damper assembly. If a damper assembly is not available, place the service switch in the hold open position. This should keep the damper in the open position and allow the customer to have automatic heat, until a replacement damper can be installed. C. DAMPER ROTATES CONTINUOUSLY Change the entire damper assembly D. DAMPER STICKS 1. Make sure no screws obstruct the damper blade. 2. Make sure damper pipe assembly is not egg shaped. 3. Make sure damper rod is not rubbing on pipe assembly. See figure on front page of this insert sheet IMPORTANT: DAMPER MUST BE OPEN BEFORE COMBUSTION TAKES PLACE. If all steps have been tried and damper problems persists call Product Service and Support 800-456-9805. 30
OPERATIONAL CHECKLIST This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper piping and wiring can result in unsatisfactory system performance, it is suggested that the installation by examined before using the checklist. Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.
REMEDY COMPLAINT CAUSE USER SERVICE AGENT *Water not hot enough. Thermostat set too low. Set thermostat dial to a higher temperature. Thermostat out of calibration. Call service agent. Recalibrate thermostat. If thermostat cannot be recalibrated, replace. *Insufficient hot water Thermostat set too low. Set thermostat dial to a *See WATER TEMPERATURE higher temperature. WARNING (on page 27) Thermostat out of calibration. Call service agent. Recalibrate thermostat. If thermostat cannot be recalibrated, replace. Main manual gas shutoff Open main manual gas valve partially closed. shutoff valve to fullest extent. Heater too small for demand. Space usage to give heater time to restore water temperature. Thermostat differential is Call service agent. Replace dual bulb controller if too wide. differential is greater than 4°F. Heater recovery is slower. Call service agent. Check gas input. If incorrect, adjust gas pressure or replace main burner orifice. Draft hood not installed or Call service agent. Install draft hood or baffles as one or more flue baffles. furnished with unit. Water temperature too hot. Thermostat set too high. Set thermostat to a lower setting. Heater makes sounds: sizzling. Condensation on outside of tank - normal. Rumbling. Sediment accumulation on Drain a quantity of water bottom of tank. through drain valve. If Delime heater. rumbling persists, call a service agent. Ticking or metallic sounds. Expansion and contraction- normal. Pounding. Air chambers in piping have Drain piping system and become waterlogged. refill. Heater must be off while this is being done. Combustion noises. Too much primary air. Adjust shutters. Overfired heater. Incorrect burners or orifice for types Call serviceman. Check and correct as necessary. of gas used. Water leaks. Drain valve not closed tightly. If drain valve cannot be closed tightly, replace. If leakage source cannot be Shut off gas supply to heater Repair or in case of suspected corrected or identified, call and close cold water inlet tank leakage, be certain to confirm service agent. valve to heater. before replacing heater. Gas odors. Heater is overfired. Shut off gas supply to Check for sooted flue passage. heater and call service agent. Check for obstructed vent line. Check backdraft or lack of draft. Draft hood may be improperly installed or not sized properly. Possible gas leaks. Shut off gas supply to heater and call gas company at once. 31
Model BCG3 & ABCG Limited Warranty
American Water Heater Company, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.
1. THE TANK
If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water therein, during the first THREE years after initial installation, the warrantor will supply a complete new American water heater of equivalent size and current model. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, American Water Heater Company will provide a model which complies with the regulations of your area, in which case the consumer will be charged the difference in price between the like replacement and the energy efficient model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty.
2. ALL OTHER PARTS
If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor will repair or replace such part or portion at its option.
3. CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by A.G.A./CGA and approved by the American Society of Mechanical Engineers, must have been installed. a. This warranty shall apply only when the heater is: (1) used at temperatures not exceeding the maximum calibrated setting of its thermostat; (2) used at water pressure not exceeding the working pressure shown on the heater; (3) filled with potable water, free to circulate at all times and with the tank free of damaging water sediment or scale deposits; (4) used in a non-corrosive and non-contaminated atmosphere; (5) used with factory approved anode(s) installed; (6) in its original installation location; (7) in the United States, its territories or possessions, and Canada; (8) sized in accordance with proper sizing techniques for commercial and/or residential water heaters; (9) bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor; (10) used in an open system or in a closed system with properly sized and installed thermal expansion tank; (11) operated with properly installed dirt leg; (12) fired with the fuel for which it was factory built; (13) fired at the factory rated input; (14) operated with the inner and outer combustion chamber doors in place. b. Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, any use of insulation blankets, or any attempt to repair tank leaks will void this warranty. c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relief valve installed on the heater is not an acceptable method.
4. SERVICE AND REPAIR EXPENSES
Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs. Such costs may include but are not limited to: a. Labor charges for service removal, repair or reinstallation of the water heater or any component part; b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor. c. All cost necessary or incidental for any material and/or permits required for installation of the replacement heater or part.
5. LIMITATIONS ON IMPLIED WARRANTIES
Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state or provincial law are limited to one (1) year duration for the heater or any of its parts. Some states and provinces do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
6. CLAIM PROCEDURE
Any claim under the warranty should be initiated with the dealer who sold the heater, or with any other dealer handling the warrantor’s products. If this is not practicable, the owner should contact: U.S. Customers American Water Heater Company PO Box 1597, 500 Princeton Road Johnson City, TN 37605 a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor. b. Dealer replacements are made subject to in-warranty validation by warrantor.
7. DISCLAIMERS
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE HEATER. THE WARRANTOR SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT. a. Some states or provinces do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not apply to you. b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heater’s rating plate. Model No._ _________________________________ Serial No._________________________________ Date Installed_______________________ Dealer’s Name__________________________________________________________________________________________________________ Dealer’s Address___________________________________________________________________ Phone No.____________________________ City and State/Province_______________________________________________________________Zip/PostalCode________________________ KEEP THIS WARRANTY POSTED ADJACENT TO THE HEATER FOR FUTURE REFERENCE 32
NOTES
33
NOTES
34
NOTES
35
P.O. Box 1597, 500 Princeton Road Johnson City, TN 37605 36