Transcript
GB.BCSA455.050101
Instructions for the BASIC BCSA Damper, Sizes 004–055
1. General The BCSA Air intake damper has counter-rotating, torsionally rigid damper blades made of aluminium-zinc-plated, doubleskin sheet steel, to environment class M3. The damper blades are journalled in nylon bearings and are available with or without insulation. The damper conforms to the provisions of tightness class 3 to Swedish Standard VVS-AMA 98 (equivalent to a type 4 damper to VVS-AMA 83). The damper is available in three variants: mounted on end wall, mounted in a casing including the set of slip clamps for connection to ducting and mounted in a casing for installation between functional sections.
1.1 Specification
The version, sizes, etc. are specified in the delivery documents
BCSA, fitted in a casing incl. slip clamps
2. Installation The BCSA damper section must be installed with the damper shafts horizontal. The damper section can be connected as illustrated below. Connection to the ducting. Slip clamp a) by means of slip clamps
Connection accessories for the inlet
Seal
BCXZ-1-aaa-17 Flexible connection
Self-tapping screw or pop rivet
End connection wall BCXZ-1-aaa-17 Flexible connection, large BCXZ-1-aaa-25 Set of slip clamps, large
b) to a flanged duct
Seal
Specifications are subject to alteration without notice.
www.swegon.se
1
GB.BCSA455.050101
3. Technical data
Torque, Nm
3.1 Torque
Static pressure differential**, Pa
**Pressure differential across closed damper(s). * The size 035–055 damper sections have two dampers. Two actuators are required on these sizes. The torque has been calculated for one damper.
3.2 Dimensions 3.2.1 BCSA, externally fitted on end wall, sizes 004–027
160
A
100 ø15
22 C
2
www.swegon.se
BCSA
A
C
Weight
004
600
300
15
006
800
300
19
009
800
500
25
014
1000
500
32
020
1200
600
43
027
1400
800
57
Specifications are subject to alteration without notice.
GB.BCSA455.050101
3.2.2 BCSA, mounted in a casing incl. set of slip clamps, sizes 004–027
B 30
A
E
279
75
F 22
ø15
C
BCSA
B
H
A
C
E
F
004
1039
546
600
006
1259
656
800
300
220
123
35
43
300
230
178
42
52
009
1459
756
014
1759
906
800
500
330
128
52
63
1000
500
380
203
63
78
020
1946
1026
027
2306
1206
1200
600
373
213
77
93
1400
800
453
203
96
117
H
Wgt., Std. Wgt., EI 30
BCSA, mounted in a casing incl. set of slip clamps, sizes 035–055
279
B
A
E
30
F
ø15
22
BCSA
C
B
H
A
035
2706
1206
2300
055
3206
1656
2500
C
E
F
800
203
303
127
154
1100
353
278
169
203
Specifications are subject to alteration without notice.
H
Wgt., Std. Wgt., EI 30
www.swegon.se
3
GB.BCSA455.050101
3.2.3 BCSA, mounted in a casing between functional sections, sizes 004–027
75
B
253
E
A
F
ø15 C
BCSA
B
H
A
C
E
F
004
1039
546
600
300
220
123
26
31
006
1259
656
009
1459
756
800
300
230
178
32
38
800
500
330
128
38
014
1759
44
906
1000
500
380
203
49
57
020 027
1946
1026
1200
600
373
213
61
69
2306
1206
1400
800
453
203
74
84
H
Wgt., Std. Wgt., EI 30
BCSA, mounted in a casing between functional sections, sizes 035–055
253
B E
A
F
ø15
C H
BCSA
4
B
H
A
035
2706
1206
2300
055
3206
1656
2500
www.swegon.se
C
E
F
Wgt., Std. Wgt. EI 30
800
203
303
93
105
1100
353
278
123
137
Specifications are subject to alteration without notice.