Transcript
Bussmann®
Disconnect Switch
BDF60 and BDF100
Fusible, 60-100A, 600V
BDF60J6
BDF100JT6 Components:
Catalog Symbols*: BDF60J6, BDF100JT6 Ampere Rating: 60 to 100 Amperes Voltage Rating: 600 Volts Agency Approvals: UL Listed, Guide WPZX, File E155129 CSA Certified, File 58077M9 IEC 947-1 General Information: Bussmann fused disconnect switches are UL 98/CSA 22.2 No. 4 devices. This makes them suitable for use on service equipment, panel boards, switchboards, industrial control equipment, motor control centers, etc.
Handles
Style
NEMA Type
Color
Pistol Pistol Pistol
1, 12 1, 3R, 12 4, 4X
Blk Blk Blk
Grip Length (Inches)
Marking
Padlock- Defeatable able
Catalog Number
60-100A ( 0.24˝ x 0.24˝) 3.15 2.36 2.36
Off/On Off/On Off/On
Yes Yes Yes
Yes Yes No
BDH20 BDH50 BDH57
Terminal Lug Kits - Kit Includes 6 Lugs Amp Rating
Wire Size
Wire Type
Kit Catalog Number
100 200 400 600 & 800
#14 - 2/0 #6 - 300 kcmil #2 - 600 kcmil (2) #2 - 600 kcmil
Cu/Al Cu/Al Cu/Al Cu/Al
BDTL24 BDTL25 BDTL26 BDTL27
E T C T E E N L
*Catalog symbol is for switch only. Handles and shafts are ordered separately.
Shafts
Fuse Maximum Horsepower Rating Type 200V 208V 240V 480V 600V BDF60J6 J 15 15 15 30 40 BDF100JT6 J† 25 25 30 40 50 †Class J fuses are standard. If 600V Class T fuses are desired, us BDTA1 adapters.
Mounting Depth**
Shaft Length
Catalog Number
60 - 100 Amps ( 0.24˝ x 0.24˝)
5.50 8.00 11.00 13.75 16.54
-
8.50 11.00 14.00 16.75 19.69
5.90 8.26 11.41 14.17 16.93
BDS150 BDS210 BDS290 BDS360 BDS430
N G O O C L S A B I T O W D CA S E E N H E C E T S I SW
O S
CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information.
**Mounting depth is measured from outside panel door to mounting plate of disconnect. Shaft can be cut to desired length.
Accessories: Fuse Covers and Terminal Shrouds (line-side) Switch Type
Amp Rating
Fuse Type
60 100
J J or T
Voltage
Fuse Covers Catalog Number
Terminal Shrouds Catalog Number
600V 600V
BDFC60J BDFC100
Not Required BDTSF1
Auxiliary Contacts - F60 through F100 Switch Aux. Contact Amp Rating Amp Rating 60 100
12-17-98 SB98107
Rev. A
6 6
Voltage 250 250
1 N.O. & 1 N.C. 2 N.O. & 2 N.C. Catalog Number Catalog Number BDAUX7 BDAUX7
BDAUX8 BDAUX8
Form No. BDF Page 1 of 2 BIF Doc #1121
Bussmann®
Disconnect Switch
BDF60 and BDF100
Fusible, 60-100A, 600V Dimensional Data
00.00 00.00 Inches Inches 00.0 00.00Millimeters Millimeters
60 Amps
0.23
0.27 Dia.
5.9
7.1
74.1
4.74 3.70 120.3
2.36
2.92
60.0
1.18
94.0
30.0
3.19 80.9
.80
1.54
20.2
39.1
1.46
4.85
37.0
123.1
5.57 141.4
E T C T E E N L
6.85 ( 3 POLE ) 8.31 ( 4 POLE ) 174.0
2.13
44.4
54.1
0.26 Dia.
N G O O C L S A B I O W D CAT S E E N H E C E T S I SW
O S 6.5
M6 X 1.0
0.27 Dia. 6.9
1.18 30.0
140.0 ... 219.0
50.8
100 Amps 1.75
5.50 ... 8.63
2.00
211.0
3.58
0.23 6.0
4.76
121.0
6.80 5.61 172.5
91.0
2.36
142.5
60.0
3.90 99.2
2.15 54.6
.79
20.0
5.15
7.70
130.8
195.5
8.39
213.0
2.01
5.50...8.62
51.0
139.7....219.0
1.14 30.0
8.78
223.0
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-17-98 SB98107
Rev. A
Form No. BDF Page 2 of 2 BIF Doc #1121